Professional Documents
Culture Documents
Ata-36 Pneumatic: Training Manual Boeing 747-400
Ata-36 Pneumatic: Training Manual Boeing 747-400
Training E & M
Boeing 747-400
Training manual
ATA-36 PNEUMATIC
Config: ALL
k engineering & maintenance
Training E & M
Boeing 747-400
Training manual
NOTES:
Config: ALL
k engineering & maintenance
Training E & M
PNEUMATIC
Introduction
Boeing 747-400
Aircraft and Powerplant
PNEUMATIC SYSTEM SOURCES AND USES ............................ 2 PNEUMATIC MANIFOLD ISOLATION VALVES ........................... 18
PNEUMATIC SYSTEM SOURCES ................................................ 4 MANIFOLD ISOLATION VALVE CIRCUIT .................................... 20
PNEUMATIC SYSTEM DISTRIBUTION ........................................ 6 ISOLATION VALVE EICAS MESSAGES ....................................... 22
AIRPLANE PNEUMATIC MANIFOLD ............................................ 8 APU BLEED AND ISOLATION VALVE CONTROLS ..................... 24
AIR SUPPLY CONTROL TEST UNIT ............................................ 10 APU ISOLATION VALVE CIRCUIT ................................................ 26
AIR SUPPLY CONTROL TEST UNIT-SCHEMATIC ...................... 12 AIR SUPPLY CONTROL TEST UNIT MAINTENANCE
AIR SUPPLY CONTROL TEST UNIT EICAS MESSAGES ........... 14 COMPUTER MESSAGES ......................................................... 28
ENGINE AIR SUPPLY VALVES OPERATION .............................. 16 PNEUMATIC GROUND CONNECTORS ....................................... 30
The air supply for the airplane systems is obtained from the four
engines, an Auxiliary Power Unit (APU) and ground carts. The air
temperature and pressure are regulated prior to delivery to the
various airplane systems. Electrical power is used for the controls
and indications.
- Air conditioning
- Pressurization
- Wing anti-icing
- Nacelle anti-icing
- Leading edge flap drives
- Hydraulic pumps
- Engine starting
- Water tank pressurization
- Hydraulic reservoir pressurization
- Cargo compartment heating
- Total air temperature probe and rain repellent aspiration
- Cargo smoke detection
- Thrust Reverser
The primary sources of air are intermediate pressure (8th) stage and
high pressure (14th) stage engine bleeds.
The APU isolation valve is located in the APU manifold and operates
in conjunctionwith the APU. Two ground connectors are in the
crossover manifold. Air is supplied from the manifold to the various
systems.
The air supply control test unit (ASCTU), M7957 is located in the
main equipment center on rack E2-4. The module is a line
replaceable unit.
Location
Control Indication
The ASCTU receives inputs from M7328 bleed air control moduleon
P5, processes the information, and outputs the appropriate
commands to the engine mounted air supply components. The
ASCTU monitors the individual switches and sensors on the engine
air supply components and distribution system. This information is
processed and transmitted to the flight deck annunciators, EFIS/
EICAS interface units and to the central maintenance computer.
The data is transmitted by ARINC 429 data buses.
The air supply control test unit messages are shown on the auxiliary
EICAS display:
The isolation valves provide a means for controlling the air flow in
the pneumatic manifold. Three isolation valves are in the pneumatic
system. Two isolation valves are located in the air conditioning bay
and the APU isolation valve is located in the aft left wheel well. The
APU isolation valve will operate only when the APU is operating.
The isolation valve is a motor driven 7 inch diameter butterfly type
valve that operates on 115 volts ac power. If a malfunction occurs in
either the left or right pneumatic system, the system can be isolated
by selecting the appropriate isolation valve to off.
The manifold isolation valves and the APU isolation valve are
identical.
The isolation valve messages are shown on the main and auxiliary
EICAS displays.
The APU bleed and isolation valves controls are located in module
M7328 BLEED AIR CONTROL on P5.
The isolation valve opens, when selected on, and the APU is
operating above 95% RPM. If the isolation valve is open and the fire
switch is pulled, the valve closes.
Whenever the valve position and the isolation valve switch position
are in disagreement, an amber VALVE light illuminates. If the valve
and switch remain in disagreement for 10 seconds or longer, an
EICAS message will be displayed.
Display
Messages
<GROUND TESTS
<36 PNEUMATIC
<BLEED SYS ELEC
<BLEED SYS APU
<BLEED SYS ENG
Air supply to the pneumatic system from ground carts is through two
ground connectors.
The two connectors, with check valves, are located in the left air
conditioning bay connected to the crossover manifold. The ground
connectors can be accessed through a hinged panel located aft of
the left air conditioning bay.
NOTES:
The engine bleed system automatically selects either high or The intermediate stage check valve prevents reverse flow of high
intermediate stage air from the engine compressor and delivers pressure air into the intermediate stage compressor. The PRSOV
pressure regulated and temperature limited air to the pneumatic provides reverse flow control from the distribution system to the
manifold. engine and allows reverse flow during engine start.
The bleed source control components are the high pressure shutoff
valve and the high pressure shutoff valve controller. The controller
automatically selects 14th or 8th stage bleed.
Temperature Control
Temperature control is provided by the fan air valve, fan air valve
sensor, and precooler. The pressure regulator and shutoff valve
(PRSOV) also regulates air temperature. An overheat switch
provides system protection during an overheat condition.
The engine air supply components are located on the engine, in the
engine strut, and in the wing leading edge. These components are
attached to the engine manifold and together form the engine
manifold system.
On the left side of the engine are the fan air valve and precooler. On
the upper left side are the high pressure shutoff valve (HPSOV)
controller and pressure regulator valve (PRV) controller. In the
engine strut are the overheat switch and temperature sensor.
NOTES:
The engine bleed air system controls are located in module M7328,
BLEED AIR control on P5.
The valves are enabled by pushing and releasing the switchlight and
the ON indicator will be displayed. The valves are closed by
pushing and releasing the switchlight. The ON indicator will retract,
and the OFF light will illuminate when the PRSOV is closed.
The engine air supply system is enabled by placing the engine bleed The PRSOV regulates the pressure of the air entering the
air switchlight, on M7328 bleed air control to ON. This enables the distribution manifold to 45 psig. With the PRSOV closed, an input to
PRSOV, PRV controller and the HPSOV controller. With engine the ASCTU through the PRSOV closed limit switch causes the OFF
bleed pressure available the HPSOV, PRV and PRSOV will open. light to illuminate. Also, with the PRSOV closed and the respective
engine operating, the OFF light illuminates and information from the
The engine supplies air from the intermediate (8th) or high (14th) ASCTU is provided to EICAS through the EFIS/EICAS interface
stage bleed ports. At low power settings, air is supplied from the units.
14th stage. The HPSOV controller automatically switches from 14th
to 8th stage when the pressure in 14th stage reaches approximately The ASCTU has redundant BIT logic that continuously monitors the
105 psig. The ASCTU monitors the HPSOV through the closed limit air supply components but does not provide any inputs for the
switch of the valve. operation or control of the system.
The PRV controller causes the PRV to modulate to maintain engine The pressure and temperature are monitored through ASCTU and
manifold pressure at 97 psig. When engine manifold pressure information is sent to EICAS CMC maintenance page.
reaches 110 psig, the overpressure switch operates and supplies an
input to the ASCTU.
The fan air valve and fan air temperature sensor operate together to
maintain bleed air temperature at 350°F (177°C). When the
temperature rises to 470°F (243°C) the overheat switch operates
and supplies an input to the ASCTU. With overpressure,
overtemperature, or a malfunction of the PRV or HPSOV, he ASCTU
activates the SYS FAULT light and provides information to EICAS
through EFIS/EICAS interface units.
The 8th stage check valve is located on the upper right side of the
engine in the eighth stage bleed duct upstream of the IP-HP
junction. The 8th stage check valve prevents reverse flow into the
eighth stage compressor when the HPSOV is open or whenever
upstream pressure is greater than eighth stage pressure. Access to
the check valve is by opening the thrust reverser on the right side of
the engine.
The HPSOV is located on the right side of the engine. The controller
is remotely mounted on the upper left side of the engine. The
controller is mounted in this position to avoid harmful temperatures
and vibration from the high stage compressors. Both HPSOV
controller and the HPSOV can be accessed by opening the fan cowl
and the thrust reversers.
The high pressure shutoff valve controller opens and closes the high
pressure shutoff valve (HPSOV) in response to pneumatic servo
pressure. The servo pressure is controlled by the open/close
latching, solenoid-operated valve. The high pressure shutoff valve
controller provides intermediate pressure-high pressure switching by
controlling the HPSOV position. The HPSOV controller senses high
stage pressure and altitude pressure. The switchover pressure is
105 psig. Below 105 psig the pneumatic system operates on high
stage pressure (14th stage) and above 105 psig on intermediate
pressure (8th stage). An aneroid changes the switchover pressure
linearly from 105 psig at 27,000 feet to 71 psig at 45,000 feet.
The HPSOV controller has four BITE pressure switches. Two of the
switches, PL and PH, are monitored by the air supply control test
unit (ASCTU) BITE logic to verify proper operation of the HPSOV
controller.
The HPSOV has two plunger type valve position switches. Both
switches provide BITE information. The close switch provides
information to the air supply control test unit (ASCTU) for valve
position indication.
A valve position indicator and a locking pin are on the valve for
manually deactivating the valve in the closed position.
The HPSOV controller has four BITE pressure switches. Two of the
switches, PL and PH, are monitored by the air supply control test
unit (ASTCU) BITE logic to verify proper operation of the HPSOV
controller.
The high pressure shutoff valve messages are shown on the main
and auxiliary EICAS display.
The high pressure shutoff valve (HPSOV) and the pressure regulator
valve (PRV) are identical and interchangeable. The controllers
determine whether the valve operates as a regulator or a shutoff
valve. The deactivation procedures for each valve is the same.
The PRV has two plunger type valve position switches. Both
switches provide BITE information. The PRV close switch provides
information to the air supply control test unit (ASCTU) for valve
position indication.
A valve position indicator and locking pin are on the valve for
manually deactivating the valve in the closed position.
The pressure regulator valve controller consists of an open and A 5 second time delay is provided for the overheat switch to prevent
close latching solenoids which are energized momentarily. In the transient operation of the close solenoid.
event of electrical failure, the latching open-close solenoid remains
in its last position. With the ENGINE BLEED switchlight in the off position, the operation
of the open solenoid by the nacelle anti-icing switch is inhibited until
The open solenoid is energized momentarily by pushing the the high pressure shutoff valve (HPSOV) is fully closed.
ENGINE BLEED switchlight on P5 to the ON position. This provides
a signal to the pulse generator to energize the open solenoid for 0.5 During engine start, with the start valve in the open position, the
seconds. close solenoid is momentarily energized. A 15 second time delay
prevents operation of the open solenoid after the start valve closes.
The close solenoid is energized momentarily by pushing the
ENGINE BLEED switchlight on P5 to the off position, operation of
the engine fire switch on P5 or actuation of the 470°F (243°C)
overheat switch downstream of the precooler. This provides a signal
to the pulse generator to energize the close solenoid for 0.5
seconds.
The pressure regulator valve messages are shown on the main and
auxiliary EICAS displays.
The bleed air precooler system reduces and maintains the engine
manifold bleed air temperature to approximately 350°F (177°C). The
system uses fan air as a heat sink to remove excessive heat from
the air in the engine manifold. The components of the bleed air
precooler system consist of a fan air valve, fan air temperature
sensor and a precooler (heat exchanger).
The fan air valve is located on the upper left side of the engine and
is mounted at the cooling air inlet to the precooler in the fan air duct.
The valve can be accessed by opening the left core cowl panel. The
fan air temperature sensor is located in the strut, and mounted in the
bleed air supply duct downstream of the precooler. Access to the
temperature sensor is through a panel on the left side of the engine
strut.
General
The fan air temperature sensor controls the fan air valve position.
The temperature sensor is installed in the bleed air supply duct
downstream of the precooler. Pneumatic signals from the sensor
modulate the position of the fan air valve when the bleed air
temperature is in the range of 320°-380°F (160°-193°C).
The fan air valve is pneumatically operated, modulating, The fan air valve can be deactivated by removing the locking pin
spring-loaded valve. The valve consists of a half-area actuator from its stowed position. The locking crank is moved over the
spring-loaded to the open position. It is located at the cooling air locking pin slot and locking pin inserted. The locking pin, when
inlet to the precooler in the fan air duct. The valve is controlled by installed in the locking crank, locks the valve 48 degrees from the
the fan air temperature sensor. Located on the valve are a manual valve closedposition and vents the supply pressure. To unlock,
locking crank and position switches. The valve is internally cooled. reverse the above procedures. It is very important to insure the
locking pin is properly reinstalled in the stowed position. If it is not
The precooler outlet servo pressure is used to operate the valve. installed completely, the valve will not operate correctly because the
When the valve receives a pneumatic signal from the fan air actuator pressure will be vented to ambient around the pin.
temperature sensor, it moves towards the closed position and
modulates to maintain air temperature downstream of the precooler
to 320°F -380°F (160°C - 193°C).
The fan air valve is monitored by the ASCTU through the valve
position switches. Valve failure is indicated on EICAS.
The bleed air precooler is mounted on top of the engine and is part
of the engine bleed air temperature control system. The precooler
uses engine fan air as a heat sink to reduce bleed air temperature.
The precooler is a heat exchanger of the crossflow type. It receives
pressure regulated bleed air through the PRV and fan air through
the fan air modulating valve. The air flows at right angles to each
other and remains separated by the fin-plate arrangement. As fan
air passes through the precooler, it absorbs the heat of the engine
bleed air. The fan air is then exhausted out of the engine area
through a port on the left side of the engine. Access to the precooler
is by opening the core cowl panels.
The fan air modulating valve messages are shown on the auxiliary
EICAS display.
The pressure regulator and shutoff valve is a pneumatically operated Electrical control of the valve is by a latching solenoid. Valve
and electrically controlled valve that is spring loaded to the closed operation is monitored through position switches that provide
position. The PRSOV is a 6 inch diameter modulating valve. The information to the air supply control test unit. The filter is shop
PRSOV provides six basic functions: replaceable only.
The PRSOV controls the bleed air pressure downstream of the valve
to 45 psi. The valve requires 10 psi to operate and is fully open at
30 psig. The PRSOV contains a temperature sensor that provides a
temperature limiting feature that starts closing the valve at a bleed
air temperature of 405°F (207°C). At 450°F (232°C), the valve is
fully closed and the amber OFF light illuminates. The temperature
limiting feature overrides the pressure regulating function and is not
operational during reverse flow operation.
NOTES:
Using the engine start switch on P5, the reverse flow solenoid is
energized. The pressure regulator and shutoff valve opens allowing
airflow from the pneumatic manifold to the engine starter.
Termination of the engine start sequence deenergizes the reverse
flow solenoid and the valve closes.
The reverse flow solenoid can be energized by the GND SVC switch
on the right side of the engine fancase. The pressure regulator and
shutoff valve opens allowing airflow from the pneumatic manifold to
the thrust reverser.
The pneumatic system control consists of the air supply control test
unit (ASCTU), switchlights and indications on the P5 panel,
controllers and valves on the engine and protection system in the
engine manifold.
NOTES:
Indication
Monitoring
NOTES:
The bleed air flow indication system measures the system mass air
flow and processes the signal for display on EICAS.
The system uses four sensors and a signal conditioner.
The sensors are located in the wing pneumatic ducts. The channel
1 and channel 4 sensors (outboard sensors) are positioned
upstream of engines 2 and 3 pneumatic duct inlets. The outboard
sensors are accessible with the leading edge flaps extended.
General Description
The bleed air flow indication system measures mass air flow from The outboard sensor measures the mass flow from the outboard
each engine and displays this information on EICAS. The system engine. The inboard sensor measures the mass flow from the
consists of four sensors, a four channel bleed air flow signal inboard and outboard engines and the ASCTU provides the
conditioner, the air supply control and test unit (ASCTU), and the resolution to indicate the inboard mass flow.
EIU’s for display. The bleed air flow indicating system can be checked on the ground
by INPUT MONITORING.
System Operation
The bleed air flow sensor has two flow sensor elements. One
element measures the ambient duct temperature. The secnd
element is heated to a set temperature above the ambient duct air
temperature with the power supplied by the bleed air flow signal
conditioner. The air mass flow rate is proportional to the rate at
which heat is being removed by the cooler air stream which flows
past the self-heated element of the flow sensor.
The left and right pneumatic duct pressures are displayed on the
main EICAS display and on a ECS maintenance page.
The ECS data block is displayed on the main EICAS display when
the secondary engine indications or the ECS synoptic or ECS
maintenance page has been selected. The data block contains
pneumatic duct pressure and pressurization parameters. The ECS
data block will automatically blank when any other EICAS selection
is made.
The ECS synoptic page displays the status of the pneumatic system.
The pressure regulating and shutoff valves, APU isolation valve and
the left and right isolation valves are shown in the open or closed
positions. The pneumatic manifold duct pressure is displayed for the
left and right sides.
The EXT AIR indication will be shown whenever the external air
supply is used by the air conditioning system or for engine starting.
The air for the pneumatic system is obtained from the external
source, auxiliary power unit (APU) or the low pressure, high
pressure and fan stages of the engine. A series of valves and a
precooler control the pressure and temperature of the air supplied by
the engine, prior to entering the pneumatic manifold. Protection is
provided against excessive air temperature and pressure in the
engine pneumatic manifold. Located in the pneumatic manifold are
isolation valves and pressure transmitters.
NOTES:
CIRCUIT .............................................................................. 8
BLEED AIR INDICATIONS ..................................................... 10
ECS EICAS SYNOPTIC .......................................................... 12
The bleed air flow indication system measures the system mass air
flow and processes the signal for display on EICAS.
The system uses four sensors and a signal conditioner.
The sensors are located in the wing pneumatic ducts. The channel
1 and channel 4 sensors (outboard sensors) are positioned
upstream of engines 2 and 3 pneumatic duct inlets. The outboard
sensors are accessible with the leading edge flaps extended.
36.22.0504 -001
36.22.0004 -001
General Description
The bleed air flow indication system measures mass air flow from The outboard sensor measures the mass flow from the outboard
each engine and displays this information on EICAS. The system engine. The inboard sensor measures the mass flow from the
consists of four sensors, a four channel bleed air flow signal inboard and outboard engines and the ASCTU provides the
conditioner, the air supply control and test unit (ASCTU), and the resolution to indicate the inboard mass flow.
EIU’s for display. The bleed air flow indicating system can be checked on the ground
by INPUT MONITORING.
System Operation
The bleed air flow sensor has two flow sensor elements. One
element measures the ambient duct temperature. The secnd
element is heated to a set temperature above the ambient duct air
temperature with the power supplied by the bleed air flow signal
conditioner. The air mass flow rate is proportional to the rate at
which heat is being removed by the cooler air stream which flows
past the self-heated element of the flow sensor.
36.22.0005 -001
36.21.0504 -001
36.21.0004 -001
36.21.0507 -001
36.21.0007 -001
The left and right pneumatic duct pressures are displayed on the
main EICAS display and on a ECS maintenance page.
The ECS data block is displayed on the main EICAS display when
the secondary engine indications or the ECS synoptic or ECS
maintenance page has been selected. The data block contains
pneumatic duct pressure and pressurization parameters. The ECS
data block will automatically blank when any other EICAS selection
is made.
36.21.0505 -007
36.21.0005 -007
The ECS synoptic page displays the status of the pneumatic system.
The pressure regulating and shutoff valves, APU isolation valve and
the left and right isolation valves are shown in the open or closed
positions. The pneumatic manifold duct pressure is displayed for the
left and right sides.
The EXT AIR indication will be shown whenever the external air
supply is used by the air conditioning system or for engine starting.
36.21.0508 -002
36.21.0008 -002
NOTES:
Config: ALL
k engineering & maintenance
Training E & M
Boeing 747-400
Training manual
NOTES:
Config: ALL
k engineering & maintenance
Training E & M
ICE AND RAIN PROTECTION Boeing 747-400
Avionics
ICE DETECTOR EICAS MESSAGES .................................... 14 OVERHEAT AND PRESSURE SWITCHES ........................... 48
ICE DETECTOR CENTRAL MAINTENANCE NACELLE ANTI-ICING CONTROLS ........................................ 50
COMPUTER MESSAGES .................................................. 16 NACELLE ANTI-ICING CIRCUIT .............................................. 52
WING ANTI-ICING CONTROLS .............................................. 24 NACELLE ANTI-ICING DUCT LEAK EICAS MESSAGES ....... 58
WING ANTI-ICING VALVE CIRCUIT ......................................... 26 NACELLE ANTI-ICING/ENGINE SPEED INDICATION ............. 60
WING ANTI-ICING VALVE INDICATION CIRCUIT .................... 28 PROBES AND SENSORS ANTI-ICING ................................... 62
The ice and rain protection systems are used to protect the airplane
and aid the pilots when operating in adverse weather conditions.
- Engine nacelles
30.00.0501 -002
30.00.0001 -002
The anti-ice and rain removal controls are located on the M7321
ANTI-ICE RAIN REMOVAL on P5.
30.00.0502 -002
30.00.0002 -002
30.81.0501 -001
30.81.0001 -001
NOTES:
General
This process is repeated as long as icing conditions exist.
Two ice detection systems provide flight deck indication of icing
conditions and automatic activation of wing and nacelle anti-icing The ice detector system measures the probe heater ON time and
systems. Each ice detector contains a magnetostrictive (vibrating) counts the number of consecutive icing/de-icing cycles. Probe
probe, which changes frequency with ice buildup. The probe has an heater failure is based on probe heater ON time greater than 25
internal heating element which melts the accumulated ice off of the seconds.
probe after it has been detected. The detectors provide separate
outputs to activate the wing and nacelle anti-icing systems. If the time between icing/de-icing cycles is greater than three
minutes, the consecutive icing/de-icing counter is reset to zero.
Operation When the airplane is on the ground, the ice detector heater is
disabled. The icing/de-icing count is held at zero, preventing
The ice detector consists of a frequency detector, probe heater and automatic operation of the anti-icing system. The system is
control, interval timer and resettable counter. monitored through the central maintenance computer.
30.81.0502A-001
Nacelle Anti-Icing
Wing Anti-Icing
30.81.0502B-001
30.81.0002 -001
The ice detector EICAS messages are shown on the main and
auxiliary displays.
30.81.0503 -001
30.81.0003 -001
Display
The ice detector messages are displayed on the control display unit
(CDU).
Messages
ICE DETECTOR L
ICE DETECTOR R
30.81.0504 -001
30.81.0004 -001
WING ANTI-ICING
30.10.0501 -002
30.10.0001 -002
The pneumatic system supplies air for the wing anti-icing system.
The air supply is connected to the wing leading edges through two
valves in the leading edge flap cavities near the outboard engines.
The valve is connected to a Y-type coupling, which is connected to
two elbows. Each elbow is connected to an anti-icing duct (made
from titanium) and located inboard and outboard inside the leading
edge. Thermal expansion of the ducts is provided for by use of teflon
impregnated cushioned clamps which permit the duct to slide in a
direction opposite the elbow during expansion and towards the
elbow during contraction. The forward surface of the duct has spray
holes through which air is discharged onto the interior of the wing
leading edge. The air is exhausted overboard through slots under
the leading edge.
30.10.0502 -001
30.10.0002 -001
Two wing anti-icing valves allow air from the pneumatic manifold to
be supplied to the spray ducts in the leading edges.
The valve is accessible through the leading edge flap segments No.
6 on the left wing and No. 21 on the right wing.
30.11.0501 -001
30.11.0001 -001
30.11.0502 -002
30.11.0002 -002
The left and right wing anti-icing valves are operated electrically by
one switch.
Placing the switch to the AUTO position and if ice is detected, relays
R7788 and R7536 energize and 115 volts ac power is supplied to
open the valve.
The valve operation is inhibited when the leading edge flaps are not
fully up.
30.11.0503 -002
30.11.0003 -002
Operation
When the valve is closed, relay R7534 is energized and the valve
position signal to EICAS is not present. During valve opening, relay
R7536 is energized and relay R7534 is deenergized, allowing valve
position signal to EICAS. When the valve is open, relay R7535 and
R7534 are energized, and the valve position signal to EICAS is not
present.
Display
30.11.0004 -002
30.11.0505 -002
30.11.0005 -002
Operation Display
The left and right wing anti-icing valves are operated electrically by When valve position is in disagreement with the switch position, the
one switch. relays R7534 and R7535 provide this information to EICAS through
the EFIS/EICAS interface units.
On the ground relay R227 is energized and the valve remains
closed. In flight, placing the switch to the ON position energizes relay
R7536 and 115 volts ac power is supplied to open the valve. Test
Placing the switch to the AUTO position and if ice is detected, relays The wing anti-icing valve operation can be checked on the ground
R7788 and R7536 energize and 115 volts ac power is supplied to by the central maintenance computer with the valve switch in the
open the valve. OFF position and flaps retracted. The CMC is enabled by energizing
relay R8087 by the GRD TESTS switch on P461. During test, relays
The valve operation is inhibited when the leading edge flaps are not R7788 and R7536 are energized. The valves open and, after a time
fully up. delay of seven seconds, relay R7776 energizes and relay R7536
deenergizes and the valves close. The test results are observed on
the CDU.
30.11.0506 -002
Indication
When the valve is closed, relay R7534 is energized and the valve
position signal to EICAS is not present. During valve opening, relay
R7536 is energized and relay R7534 is deenergized, allowing valve
position signal to EICAS. When the valve is open, relayR7535 and
R7534 are energized, and the valve position signal to EICAS is not
present.
30.11.0006 -002
The wing anti-icing system EICAS messages are shown on the main
and auxiliary displays.
30.11.0507 -002
30.11.0007 -002
30.11.0009 -001
Display
Prior to performing the test, the wing anti-icing switch must be OFF,
flaps retracted and the GND TESTS switch on P461 in the ENABLE
position.
Messages
30.11.0508 -002
30.11.0008 -002
30.20.0501 -002
30.20.0001 -002
The engine bleed system supplies air for the nacelle anti-icing
system. When the valve is open, bleed air flows to the nacelle
leading edge through the spray duct and exhausts overboard at the
bottom of the nacelle.
30.21.0501 -001
30.21.0001 -001
30.21.0002 -001
The nacelle anti-icing valve allows air from the engine bleed duct to
be supplied to the spray duct in the nacelle leading edge.
The valve is accessible through the access panel on the left side of
the strut.The filter is shop replaceable only.
The valve can be manually operated and locked in either full open or
closed positions. Before the valve can be locked in position, the
valve must be in the desired position. The position indicator is hex
shaped to allow a 7/16 inch wrench to manually move the valve disk
to the desired position. The lockout knob has three detented
positions: NORMAL, LOCKED OPEN, and LOCKED CLOSED. The
knob is positioned in a detent by pulling and rotating.
30.21.0503 -001
30.21.0003 -001
The overheat switch is located on the fan cowl support beam at the
top of the nacelle behind the spray duct. When air is leaking from the
duct, the switch will sense increasing air temperature in the nacelle.
At 250°F (121°C), the switch closes the nacelle anti-icing valve.
30.21.0504 -001
30.21.0004 -001
30.21.0505 -002
30.21.0005 -002
Operation
Each nacelle anti-icing valve is controlled electrically by a switch. The valve can be opened by placing the switch momentarily to the
OFF position. The switch ON and AUTO positions also enable
The valve is energized to open by placing the switch to the ON or continuous engine ignition and pressure regulating valve (PRV).
AUTO position. In the ON position, relay R8004 is energized. In the
AUTO position, when ice is detected, relays R8279 and R8284 During reverse thrust operation, the nacelle anti-icing valve closes.
energize allowing relays R8000 and R8004 to energize. If the thrust
reverser is not operated, 28 volts dc power is supplied to the valve When the airplane is on the ground, the ice detectors are disabled
solenoid. When the valve is open, relay R8008 is energized and the preventing automatic operation of the anti-icing system.
valve position signal to EICAS is not present.
During overheat condition, the overheat switch closes at 250°F Valve open position provides information for NA1 display on the N1
(121°C), relay R7570 is energized and the valve closes. When the EICAS indication.
temperature decreases, the overheat switch opens,but relay R7570
30.21.0506 -006
remains energized and the valve remains closed.
30.21.0006 -006
30.21.0507 -001
30.21.0007 -001
30.21.0508 -002
30.21.0008 -002
The nacelle anti-icing duct leak EICAS messages are shown on the
auxiliary display.
30.21.0509 -001
30.21.0009 -001
When the wing anti-ice valve opens a green WAI (wing anti-icing)
message is displayed on the EICAS between the N1 indications.
30.21.0510 -002
30.21.0010 -002
30.30.0501 -002
30.30.0001 -002
PITOT-STATIC PROBE
Four (two main and two auxiliary) pitot static-probes provide air data
information to various airplane systems. The probes are mounted
externally to the airplane skin on the left and right sides of the
forward fuselage.
The probe consists of a small tube with one inlet port at the tip
sensing total pressure and two inlet ports at the side sensing static
pressure.
30.31.0501 -001
30.31.0001 -001
Operation Test
Each main pitot-static probe is anti-iced by two electric heaters. The heater operation can be checked on the ground by the central
maintenance computer. During test, relays R7421 and R7423 are
On the ground, with engines not operating, the probe heaters are not energized. The head and strut of the probe are supplied with 115
powered. With any engine operating, relays R7423 and R7425 are volts ac power. The test results are observed on the CDU.
energized. The strut of the probe is supplied with 115 volts ac
30.31.0502 -001
power. Reduced power is supplied to the head of the probe.
Display
30.31.0002 -001
30.31.0503 -001
30.31.0003 -001
Operation Test
Each auxiliary pitot-static probe is anti-iced by two electric heaters. The heater operation can be checked on the ground by the central
maintenance computer. During test, relays R7421 and R7423 are
On the ground, with engines not operating, the probe heaters are not energized. The head and strut of the probe are supplied with 115
powered. With any engine operating, at 50% RPM, relays R7423 volts ac power. The test results are observed on the CDU.
and R7425 are energized. The strut of the probe is supplied with 115
30.31.0504 -001
volts ac power. Reduced power is supplied to the head of the probe.
Display
30.31.0004 -001
30.31.0005 -001
The probe consists of a small strut with inlet and outlet ports. It
senses the temperature of the air passing through cavities within the
strut by means of temperature sensitive elements. Air enters an inlet
port at the top of the strut and exits through several outlet ports on
the side and aft surfaces of the strut.
30.31.0506 -001
30.31.0006 -001
Operation
Display
Test
30.31.0507 -001
30.31.0007 -001
The total air temperature probe heater EICAS messages are shown
on the main and auxiliary displays.
30.31.0508 -001
30.31.0008 -001
30.31.0509 -001
30.31.0009 -001
Operation
On the ground, with engines not operating, the sensor heater is not
powered. With any engine operating, relay R7423 is energized. The
sensor heater is supplied with 115 volts ac power.
Display
Test
30.31.0010 -001
30.31.0511 -001
30.31.0011 -001
Display
Messages
30.31.0519 -001
30.31.0019 -001
WINDOW HEATING
30.41.0501 -001
30.41.0001 -001
30.41.0502 -002
30.41.0002 -002
Two temperature sensors (control and spare) are laminated into the
window adjacent to the heating element. Wires from the bus bars
and temperature sensors extend through the window laminations to
the terminals on the inner face.
30.41.0503 -001
30.41.0003 -001
The two window heat control units are located in the main equipment
center. M73, left control unit is located on the E1-4 and M273, right
control unit is located on the E2-3.
30.41.0504 -001
30.41.0004 -001
The heat is applied by pushing and releasing the switchlight and the
ON position is indicated. The heat is removed by pushing and
releasing the switchlight and the ON position is cancelled.
30.41.0505 -002
30.41.0005 -002
Operation Display
Each (left and right) forward window 1 are electrically heated by 115 If a fault occurs (overheat, heating element failure, temperature
volts ac power and controlled by 28 volts dc power. sensor failure) the amber INOP light illuminates and the BITE circuit
provides this information to EICAS through the EFIS/EICAS interface
The heating power is supplied to the window by pushing and units.
releasing the switch light. The ON light is illuminated and the heat
control and fault detector supplies power gradually to the heating
element. The window temperature is sensed by a temperature Test
sensor. When the window temperature reaches the operating
temperature, the power supply is modulated to maintain a constant The window heat operation can be checked on the ground by the
window temperature. A spare sensor is provided in case of primary central maintenance computer. The relay R8055 enables the ground
sensor failure. test. The test is inhibited in flight. During test, the BITE circuit checks
the window heating system and the test results are observed on the
In case of temperature sensor failure a spare sensor in provided CDU. The INOP light will illuminate momentarily during test. Relay
which can be connected into the circuit at rear of control unit. R330 ensures that test operation is on ground only.
30.41.0506 -002
Operating Temperature
30.41.0006 -002
The window 1 heat EICAS messages are shown on the main and
auxiliary displays.
30.41.0510 -001
30.41.0010 -001
Display
Messages
30.41.0513 -001
30.41.0013 -001
30.41.0507 -001
30.41.0007 -001
30.41.0508 -001
30.41.0008 -001
Operation
Relay R7568 and the current sensor are normally energized, and
relay R7343 is energized or deenergized depending upon the
position of the control thermostat.
Display
30.41.0509 -001
30.41.0009 -001
30.41.0511 -001
30.41.0011 -001
WINDSHIELD WIPERS
The windshield wipers are provided for window 1, left and right. The
system consists of two motor/converters, two wiper assemblies and
controls.
30.42.0501 -001
30.42.0001 -001
General
Each windshield wiper system consists of an electrically operated WARNING: BEFORE PERFORMING MAINTENANCE ON
motor/converter unit located inside the fuselage. The wiper arm WINDSHIELD WIPER SYSTEM, OPEN WINDOW HEAT
attachment to the shaft of the motor/converter consists of a washer, POWER L1 AND R1 CIRCUIT BREAKERS ON P6 AND
adjustable bushing, and hub. Attached to the arm is a blade WINDOW HEAT CONTROL L1 AND R1 CIRCUIT
restrainer and the wiper assembly. The arm applies approximately a BREAKERS ON P180. IF CIRCUIT BREAKERS ARE
10 pound pressure to the blade at center of the stroke and a 5 NOT OPEN DURING MAINTENANCE, PERSONNEL
pound pressure at parked position. Wiper arm tension is not MAY RECEIVE AN ELECTRICAL SHOCK WHEN
adjustable and arm replacement is necessary if pressure does not WINDSHIELD IS TOUCHED.
meet requirements.
CAUTION: DO NOT OPERATE WINDSHIELD WIPERS ON DRY
WINDSHIELD AS WINDSHIELDS MAY BE DAMAGED.
Operation
30.42.0502 -001
The wiper blades can be operated at low or high speed and clear a
path 22 inches wide through an arc of approximately 70 degrees. At
low speed the wipers operate at 160 strokes per minute and at high
speed at 250 strokes per minute.
30.42.0002 -001
30.42.0503 -001
30.42.0003 -001
When the wipers are turned on, friction of the wiper blade on the
windshield moves the blade from its parked position parallel to the
wiper arm to the wiping position at 20° to the arm. As the wiping
position is reached, a spring-loaded unlatch mechanism on the arm
locks to fix the blade in the wiping position.
When the switch is placed in the OFF position, the blade moves
towards the parked position. The blade moves down from the
window onto the rub strip. The lever strikes an actuating pin causing
the plunger to disengage from the blade attachment. A stop rotates
the blade attachment to the parked position. The blade restrainer,
attached to the supporting arm, prevents lifting of the blade in flight
when the wipers are not used.
30.42.0504 -001
30.42.0004 -001
30.42.0505 -002
30.42.0005 -002
The power supply for the windshield motor is 28 volts dc. Placing the
windshield wiper switch to the LO position enables the motor to
operate at low speed of 160 strokes per minute. The HI position
enables the motor to operate at high speed of 250 strokes per
minute.
The wipers can operate during towing with relay R8353 energized
and ground handling bus supplying operating power to wipers.
30.42.0506 -002
30.42.0006 -002
WINDSHIELD WASHER
The windshield washer system is provided for the window 1, left and
right. The system consists of fluid container, pump, two valves and
nozzles, and associated plumbing. The controls are located in the
flight deck.
30.44.0501 -001
30.44.0001 -001
30.44.0502 -001
30.44.0002 -001
The two windshield washer nozzles are also used in the rain
repellent system and are located below the window 1, left and right
inboard of the windshield wipers. Each nozzle has four spray holes,
the three lower holes are for the rain repellent fluid and the fourth
hole is for the windshield washer fluid. The two supply lines are
concentric within the nozzle and are separated by O-rings. A
seepage control valve is installed at the base of the nozzle fitting.
The valve prevents fluid in the supply line from seeping through the
spray hole and smearing the windows in flight.
The spray from the nozzle can be altered using 3 adjustment screws
under the nozzle fairing.
30.44.0503 -001
30.44.0003 -001
30.44.0004 -001
The pump supplies the washer fluid from the container through two
valves to the uppermost spray hole in the nozzle.
30.44.0505 -001
30.44.0005 -001
30.44.0506 -001
30.44.0006 -001
The water and drain line heaters are provided to prevent ice
formation in the water and drain systems in unheated areas of the
airplane. Electric power is used for heating. The heaters are
provided for the toilet service panel, drain masts, water distribution
and drain lines.
30.70.0501 -001
30.70.0001 -001
Tape heaters are on the water supply and drain lines to prevent ice
formation. The heaters are located in the forward, mid and aft
fuselage.
Electrically heated tapes are wrapped around the lines and electric
current to the tapes is controlled by temperature switches.
30.71.0501 -001
30.71.0001 -001
The forward, mid and aft potable water hose heaters are powered
automatically whenever 115 volts ac power is available.
30.71.0502 -001
30.71.0002 -001
The forward and aft drain lines tape heaters are powered
automatically whenever 115 volts ac power is available.
30.71.0503 -001
30.71.0003 -001
IN-LINE HEATER
In-line heaters are in the water supply lines to prevent ice formation.
The heaters are located in the forward, mid and aft fuselage.
Electrically heated elements are inside the water lines and are
controlled by temperature controllers.
30.71.0504 -001
30.71.0004 -001
The forward, mid and aft water supply in-line heaters are powered
automatically whenever 115 volts ac power is available.
30.71.0505 -001
30.71.0005 -001
DRAIN MASTS
The three drain masts are for drainage of waste water from the
lavatories. Two drain lines are connected to the forward and center
masts and single line is connected to the aft mast.
The masts are located on the underside of the fuselage and have
integral electrically heated elements to prevent ice formation.
30.71.0506 -001
30.71.0006 -001
General
Ground Operation
With the ground handling bus powered, relay R8277 is relaxed, relay
R731 is energized and the heaters are supplied with 42.5 volts ac
from the drain mast heater transformer.
Air Operation
In flight, the ground handling bus is not powered, relays R8277 and
R731 are relaxed. The heaters are supplied with 115 volts ac from
the ground service transfer bus.
30.71.0507 -001
30.71.0007 -001
The waste tank service panel is for emptying and rinsing of the toilet
waste tanks. The panel is located on the underside of the fuselage
and has one drain fitting and four rinse fittings.
30.71.0508 -001
30.71.0008 -001
30.71.0509 -001
30.71.0009 -001
The ice and rain protection systems are used to protect the airplane
and aid the pilots when operating in adverse weather conditions.
- Engine nacelles
30.00.0503 -002
30.00.0503-002
NOTES:
ATA- 35 OXYGEN
Config: ALL
k engineering & maintenance
Training E & M
Boeing 747-400
Training manual
NOTES:
Config: ALL
k engineering & maintenance
Training E & M
OXYGEN Boeing 747-400
Aircraft and Powerplant
OXYGEN SYSTEMS
35.00.0501 -002
- Mask/regulator assemblies
- flight deck
- Crew and passenger oxygen cylinders
- forward cargo compartment
- Passenger oxygen modules
- overhead, throughout main and upper deck passenger cabins
- Attendant oxygen modules
- attendant station and crew rest area
- Lavatory oxygen module
- lavatories
- Portable oxygen equipment throughout main and upper deck
passenger cabins
35.00.0001 -002
35.10.0001 -001
35.11.0501 -001
35.11.0001 -001
General
Maintenance Practices
35.11.0502 -001
35.11.0002 -001
PRESSURE TRANSDUCER
35.11.0503 -001
35.11.0003 -001
PRESSURE REDUCER
35.11.0504 -001
35.11.0004 -001
One discharge port and indicator serves the crew and passenger
oxygen systems. The port is in the fuselage skin aft of the forward
cargo door. A green plastic indicator disc seals the port to prevent
entry of dirt and moisture. A snap ring retains the disc. If oxygen
pressure becomes excessive and ruptures the frangible disc at the
cylinder, the indicator disc will be blown out of the fuselage port,
providing visual evidence of the overboard discharge.
35.11.0505 -001
35.11.0005 -001
PRESSURE REGULATOR
35.11.0506 -001
35.11.0006 -001
Oxygen masks are stowed in boxes within easy reach of the flight
crew station. The stowage box includes a door-operated shutoff
valve, a sliding RESET-TEST lever and an oxygen flow indicator
(blinker).
When the mask is withdrawn from the stowage box, opening the
doors actuates the shutoff valve and supplies oxygen to the mask.
Subsequent closing of the stowage box doors displays an OXY-ON
flag. The flag is a reminder that the shutoff valve will remain open
until reset with the RESET-TEST lever. An alternate function of the
RESET-TEST lever allows in-place preflight checkout of the stowage
box and mask assembly without removing the mask from the box.
The flow indicator displays a yellow cross when oxygen flow exists.
The cross increases in size as flow increases. During no-flow
condition the indicator is black.
35.11.0507 -001
35.11.0007 -001
NOTES:
MASK/REGULATOR ASSEMBLY
General
Each crew station is equipped with an oxygen mask/regulator The oxygen mask/regulator provides oxygen to the flight crew in a
stowed in a box on the sidewall. When the mask/regulator is stowed diluted state or 100% oxygen.The oxygen dilution control for normal
and box doors are closed, oxygen flow to the mask is prevented by a or 100% oxygen is on the front of the regulator and is marked N
shutoff valve inside the box. With the doors closed, the 100% PUSH. 100% oxygen is obtained by pushing in on the end of
RESET-TEST lever on the left door holds this valve closed. the control marked 100% PUSH.
The pneumatic harness that holds the mask to the face is deflated The EMERGENCY control knob changes the flow from diluter
when stowed. The harness fits all head sizes. demand to steady flow if it is rotated to the EMERGENCY setting.
35.11.0508A-002
Operation
When the mask/regulator is removed from the box, the box doors
open, thus opening the shutoff valve in the box. With the harness
inflation control depressed, the harness inflates. Releasing the
inflation control deflates the harness and holds the mask around the
head.
Mask Stowage
Restowing the mask involves coiling the supply line in the stowage
box, correctly positioning the mask and folded harness inside the
box and then closing the doors. The pin on the left door engages the
hole in the mask regulator. Engagement of the pin is prevented by
the OXY-ON flag. The shutoff valve in the stowage box must be
turned off by operating the RESET-TEST control with the left door
closed. When the shutoff valve is properly reset, the OXY-ON flag
will disappear. After restowing the mask, an in-situ check is
performed to verify proper functioning.
35.11.0508B-002
35.11.0008 -002
General
Operation
35.10.0502 -001
35.10.0002 -001
35.10.0503 -001
35.10.0003 -001
35.10.0506 -001
35.10.0006 -001
35.10.0504 -001
35.10.0004 -001
The oxygen system manual control and indications are located in the
flight deck.
35.20.0501 -001
35.20.0001 -001
The passenger oxygen system provides supplemental oxygen for System servicing is by replacement of the depleted cylinders. An
the passenger cabins, crew rest areas, lavatories, and attendant access panel is provided inside the cargo compartment.
stations. Maintenance personnel are cautioned to follow the maintenance
manual procedure for opening, closing and safety wiring the cylinder
Three high pressure oxygen cylinders in the forward cargo shutoff valves.
compartment supply oxygen to masks stowed in overhead oxygen
modules. WARNING: VALVES MUST BE OPENED SLOWLY OR
EXCESSIVE TEMPERATURES MAY RESULT.
Each cylinder has an integral shutoff valve, pressure gauge and
35.21.0501 -001
frangible disc. A coupling with an integral thermal compensator
connects each cylinder to a pressure transducer and pressure
reducer. These components are similar to the ones in the crew
system. Capped fittings at the aft cylinder permit connection of test
equipment.
The oxygen system manual control and indications are located in the
flight deck.
35.21.0001 -001
Three continuous flow control units connected in parallel regulate The three flow control units are similar in appearance but have
the flow of oxygen to the oxygen mask modules. The flow control different internal features. The two electropneumatic units have
units are mounted in the right sidewall of the forward cargo solenoids which permit electric actuation from the flight deck. The
compartment, behind the passenger oxygen cylinder access panel. center electropneumatic unit has a pressure switch actuated by
outlet pressure. The switch closes at approximately 7 psig to
With the flow control unit turned off (RESET) no oxygen flows activate system operating indications. The center and lower units
through the unit. If cabin altitude increases to approximately 13,250 have the initial pressure surge delivery feature which ativates the
to 14,500 feet, an internal aneroid automatically actuates the unit. oxygen modules.
Oxygen is metered into the low pressure distribution manifold. An
initial pressure surge (50 - 115 psig) unlatches the oxygen module A test port is provided on each unit to allow connection of a vacuum
doors and purges air from the distribution manifold. A relief valve in source. Automatic actuation and outlet pressure regulation may be
the flow control unit opens if outlet pressure reaches 140 psig. tested.
35.21.0502 -001
Within 20 seconds of actuation, the pressure surge decays. Outlet
pressure is then regulated according to cabin altitude. Approximate
outlet pressure range is 2 psig (at 14,000 feet cabin altitude) to 43
psig (at 40,000 feet cabin altitude).
35.21.0002 -001
General
The reset solenoid permits resetting the flow control units from a
switch on the flight deck. The solenoid is mounted on a bracket
immediately below the flow control units. When the solenoid is
energized, the switch bar operates the reset levers. The levers
simultaneously depress the reset plungers on the three flow control
units. Deenergizing the solenoid returns the linkage to its original
position.
Maintenance Practices
35.21.0503 -001
35.21.0003 -001
TEST ADAPTER
35.21.0504 -001
35.21.0004 -001
Low pressure oxygen from the flow control units is supplied to five
main feeder manifolds; one on each side of the fuselage, one down
the center of the fuselage and two in the upper deck passenger
compartment. Short distribution lines off the main feeder manifolds
supply oxygen to the lavatories. Flexible tubing attached to
connections along each manifold delivers oxygen to each oxygen
mask module.
35.21.0505 -006
35.21.0005 -006
The couplings consist of a male and female end fitting swaged to the
tubing ends. An o-ring seal is installed on the male fitting. A
clamshell closure holds the assembly together. The closure locks
automatically when the hinged halves are snapped together. To
unlock the closure, the three latch pawls must be lifted
simultaneously.
35.21.0506 -001
35.21.0006 -001
General
Operation
Maintenance Practices
35.21.0007 -001
General
The automatic vent valve is located above the aft right entry door.
Access is by lowering the aft attendants service unit or removing the
adjacent ceiling panel.
Operation
35.21.0008 -001
General
The oxygen module includes a mask stowage box, unitized valve Masks are to be cleaned and disinfected after each use prior to
assembly and oxygen masks. The unitized valve assembly consists repacking. Quick-disconnect hose fittings permit removal and
of a manifold and a pressure actuated door latch coupled to a installation. Access for repacking is through the oxygen module
shutoff valve. The manifold has two oxygen mask outlets, each with door.
a mask valve and bayonet-type quick-disconnect fitting. A removable
actuating pin tethered to the mask holds the mask valve closed. WARNING: ENSURE THAT HOSE AND ACTUATING PIN OF
Attendant-type oxygen modules are installed at the attendant EACH MASK ARE CONNECTED TO THE SAME
stations, crew rest area and lavatories. VALVE. ENSURE THAT VALVES ARE CLOSED.
35.21.0009 -003
A transparent cover secured to the top of the mask stowage box with
velcro permits inspection and mask repacking.
35.21.0510 -001
35.21.0010 -001
35.21.0511 -002
35.21.0011 -002
Passenger oxygen is stored in high pressure cylinders. Each Within several seconds of actuation, the pressure surge decays,
cylinder is equipped with a pressure gauge, shutoff valve and allowing the bleed valves to close. While oxygen continues to flow to
frangible disc. The frangible disc provides over-pressure relief the masks, pressure in the manifold is sufficient to hold the
through an overboard discharge port and manifold common to the automatic vent valve closed.
crew system. A coupling with an integral thermal compensator
connects the cylinder to a pressure transducer and pressure When oxygen is no longer required, the flow control units are reset
reducer. A medium pressure manifold carries oxygen from the by the flight crew, stopping the flow of oxygen to the distribution
pressure reducers to the flow control units. manifold. Residual pressure in the manifold is depleted through the
masks allowing the automatic vent valve to open.
In the off (RESET) condition, the flow control units prevent oxygen
flow into the low pressure distribution manifold. Any small amount of Test fittings allow connection of an external pressure source and
oxygen leakage through the flow control units is discharged by the gauge for system testing.
automatic vent valve to prevent unscheduled mask deployment.
35.20.0502 -001
When the flow control units are actuated, the resulting pressure
surge unlatches the oxygen module doors, causing the masks to
deploy. The surge also closes the automatic vent valve and opens
the bleed valves. Air is purged from the distribution manifold through
the bleed valves, allowing immediate delivery of oxygen to the
oxygen modules.
35.20.0002 -001
With the control switch in NORM position, the flow control unit
actuating solenoids are de-energized and no oxygen flows through
the units.
35.20.0503 -001
35.20.0003 -001
The voltage averaging unit receives inputs from the oxygen cylinders
pressure transducers, and provides an output of average pressure
to the indicating system. The unit is located in the ceiling of the
forward cargo compartment above the crew oxygen cylinder.
35.20.0506 -001
35.20.0006 -001
35.20.0504 -001
35.20.0004 -001
35.20.0507 -001
35.20.0007 -001
35.20.0505 -001
35.20.0005 -001
35.30.0501 -001
35.30.0001 -001
The portable oxygen cylinders are mounted on the walls, floor and
inside stowage units in the passenger cabin. The cylinders are
secured in place by quick release mounting clamp.
The floor cylinders are inside a shroud located under the passenger
seats near attendants station and are accessible by releasing a latch
on the shroud. The pressure gauges on the cylinders are visible
through the shroud window. The cylinders in the stowage units are
accessible through a door at the side of the unit.
35.31.0502 -001
35.31.0002 -001
The portable oxygen cylinder assembly includes a storage cylinder, The cylinder date of manufacture or the last hydrostatic test date is
pressure regulator and mask. The cylinder capacity is 11 cubic feet stamped near the threaded opening. Cylinders must be re-tested at
at 1800 psig and 70°F. A pressure gauge indicates cylinder specified intervals.
pressure. A shutoff valve controls the flow of oxygen from the
35.31.0501 -001
cylinder to the regulator. The regulator reduces the high pressure of
the cylinder to a value suitable for use. The outlet fittings include a
flow metering device and a check valve. The check valve opens to
allow oxygen flow to the mask when the mask plug-in adapter is
inserted. A charging valve is provided for refilling the cylinder.
Over-pressure protection is provided by a frangible safety plug.
35.31.0001 -001
Summary
Maintenance Practices
The oxygen systems are for emergency use for breathing purposes
and must be hygienically clean. Characteristics of compressed
oxygen create significant safety hazards.
35.00.0502 -002
35.00.0002 -002
NOTES: