Professional Documents
Culture Documents
2.Connections between beams and columns are not shown. Details needed on bolt
sizes, plate sizes, weld specifications.
3.he material specifications for the structural elements like beams and columns are
not clearly mentioned. It will be good to include the grade of concrete and type of
steel to be used.
9.No connection/joint details for pillars, beams and walls. Proper joints are
important for stability during construction as well resisting seismic forces.
11.provide information about the operating conditions of the internal floating roof
system, such as the temperature and pressure ranges. This information would help to
ensure that the steel sections and connections are selected appropriately.
13how to ensure tank has a proper venting system to prevent the accumulation of
vapors inside the tank.?
14.how to ensure foundation of the tank are strong enough to support the weight of
the tank and its contents, including the floating roof system.
15.kindly check and clarify The thickness for leg support in Drawing is 2mm but in
staad considered as 4mm.