You are on page 1of 4

SOC ­ Selected Optimized Coordination

IEC Coordination tables for motor protection

Data exported from SOC tool on: 2023/10/19


Important notice
2023/10/19

This book is the result of a web search made from Selected Optimized Coordination ­ Coordination tables for motor protection
(/soc) made on 19 Oct 2023.
Please always refer to /soc for the lastest updated information.

Guarantee
The information contained in SOC – Selected Optimized Coordination – reflects the current state of our knowledge and aims to present our products for motor
coordination and their possible applications as defined with the applicable International standards. The product data, ratings and utilization conditions are
indicated in SOC coordination tables; thus, the information does not guarantee special utilizations or combination of characteristics that have not been defined or
tested according to normalized values or test conditions defined with the standards and does not guarantee the fit for any specific purpose. The devices shall be
used in accordance with the user manual.
This SOC tool is made available “as is” and with no express warranty. ABB further disclaims all other statutory and implied warranties, including, but not limited
to, any warranty of fitness for particular purpose or merchantability. The user and user’s company agree that in no event will ABB be liable to the user or user’s
company for any claims, liabilities, or damages even if caused by the negligence of ABB, and under no circumstances will ABB be liable for any indirect, special,
incidental or consequential damages.

Liability
The devices in coordination tables do not endanger safety when they are selected, mounted, commissioned, used, maintained and disassembled with the
applicable rules and standards and in accordance with the user manual. The devices shall be used by experts and well­trained people.
The results generated by the SOC tool must be reviewed and approved by the user.

Additional information
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed
particulars will take precedence. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.

Used filters:
Standard: IEC
Motor Efficiency Class ­ Design: Any
Index
Data exported from SOC tool on: 2023/10/19

Molded case circuit­breaker, Star­Delta Normal Start, 400 V AC, 36kA, IEC Type 2, Thermal overload relay, IE3/IE4 NE/HE............................. 4
Table ID: 3998
Starter Type : Star­Delta starter Starting type : Normal start Motor Efficiency Class ­ Design : IE3/IE4 NE/HE
Rated voltage : 400 / 415 V AC Rated short­circuit current : 36 kA Coordination type : IEC Type 2
Protection Device : Molded case circuit­breaker Overload protection : Thermal overload relay Table version : Tmax XT + AF + TF ­ IE3
Table status: Active Created on date : 3/3/2016 3:22:31 PM Edited on date : 6/25/2020 11:43:45 AM

Motor Molded case circuit­breaker Contactor type Overload protection


Motor rated power Rated Current Type Inst.Trip.Current Line Delta Star Type Trip Class Current range Max allowed load current Status
1 0.55 kW 1.5 A XT2N 160 MF In 2 28 A AF09 AF09 AF09 TF42­1.0 10 0.74 ­ 1.00 A 1.5 A Active
2 0.75 kW 1.9 A XT2N 160 MF In 2 28 A AF09 AF09 AF09 TF42­1.3 10 1.00 ­ 1.30 A 1.9 A Active
3 1.1 kW 2.7 A XT2N 160 MF In 4 56 A AF09 AF09 AF09 EF19­2.7 10E 0.80 ­ 2.70 A 2.7 A Active
4 1.5 kW 3.6 A XT2N 160 MF In 4 56 A AF16 AF16 AF16 EF19­6.3 10E 1.90 ­ 6.30 A 3.6 A Active
5 2.2 kW 4.9 A XT2N 160 MF In 8.5 120 A AF38 AF38 AF16 EF19­6.3 10E 1.90 ­ 6.30 A 4.9 A Active
6 3 kW 6.5 A XT2N 160 MF In 8.5 120 A AF38 AF38 AF16 EF19­6.3 10E 1.90 ­ 6.30 A 6.5 A Active
7 4 kW 8.5 A XT2N 160 MF In 12.5 175 A AF38 AF38 AF16 EF19­6.3 10E 1.90 ­ 6.30 A 8.5 A Active
8 5.5 kW 11.5 A XT2N 160 MF In 12.5 175 A AF38 AF38 AF16 EF19­18.9 10E 5.70 ­ 18.90 A 11.5 A Active
9 7.5 kW 15.5 A XT2N 160 MA In 20 240 A AF38 AF38 AF16 EF19­18.9 10E 5.70 ­ 18.90 A 15.5 A Active
10 9 kW 18.6 A XT2N 160 MA In 20 280 A AF40 AF40 AF40 EF19­18.9 1) 10E 5.70 ­ 18.90 A 18.6 A Active
11 11 kW 22 A XT2N 160 MA In 32 320 A AF40 AF40 AF40 EF19­18.9 1) 10E 5.70 ­ 18.90 A 22 A Active
12 15 kW 29 A XT2N 160 MA In 32 448 A AF40 AF40 AF40 EF19­18.9 1) 10E 5.70 ­ 18.90 A 29 A Active
13 18.5 kW 35 A XT2N 160 MA In 52 520 A AF40 AF40 AF40 EF65­56 1) 10E 20.00 ­ 56.00 A 35 A Active
14 22 kW 41 A XT2N 160 MA In 52 624 A AF52 AF52 AF40 TF65­28 10 22.00 ­ 28.00 A 41 A Active
15 25 kW 46.6 A XT2N 160 MA In 52 728 A AF52 AF52 AF40 TF65­33 10 25.00 ­ 33.00 A 46.6 A Active
16 30 kW 55 A XT2N 160 MA In 80 800 A AF65 AF65 AF40 TF65­40 10 30.00 ­ 40.00 A 55 A Active
17 37 kW 66 A XT2N 160 MA In 80 960 A AF80 AF80 AF40 EF96­100 10E 36.00 ­ 100.00 A 66 A Active
18 45 kW 80 A XT2N 160 MA In 100 1200 A AF96 AF96 AF40 TF96­51 10 40.00 ­ 51.00 A 80 A Active
19 55 kW 97 A XT4N 250 Ekip I In 250 1600 A AF116 AF116 AF116 EF146­150 10E 54.00 ­ 150.00 A 97 A Active
20 75 kW 132 A XT4N 250 Ekip I In 250 1920 A AF116 AF116 AF116 EF146­150 10E 54.00 ­ 150.00 A 132 A Active
21 90 kW 160 A XT4N 250 Ekip I In 250 2250 A AF116 AF116 AF116 EF146­150 10E 54.00 ­ 150.00 A 160 A Active
22 110 kW 195 A T4N 320 PR221DS­I In 320 2720 A AF190 AF190 AF190 TA200DU­150 10A 110.00 ­ 150.00 A 200 A Legacy

Comments :
Valid also for 415V.
1) DB19EF mounting kit is needed.