Professional Documents
Culture Documents
FXDQ Pdve
FXDQ Pdve
201710
Engineering Data
FXDQ-PDVE(T)
FXDQ-NDVE(T)
50 / 60 Hz
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
FXDQ-PDVE(T) / FXDQ-NDVE(T)
Slim Ceiling Mounted Duct Type
(Standard Series)
50 / 60 Hz
1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
2.1 FXDQ-PDVE(T).................................................................................3
2.2 FXDQ-NDVE(T).................................................................................7
3. Dimensions................................................................................................11
3.1 FXDQ-PDVE(T)...............................................................................11
3.2 FXDQ-NDVE(T)...............................................................................13
4. Piping Diagrams........................................................................................17
5. Wiring Diagrams........................................................................................18
6. Electric Characteristics..............................................................................19
7. Safety Devices Setting..............................................................................20
8. Capacity Tables.........................................................................................21
8.1 Cooling Capacity for Te: Auto..........................................................21
8.2 Cooling Capacity for Te: 6°C...........................................................21
8.3 Cooling Capacity for Te: 9°C...........................................................22
8.4 Heating Capacity..............................................................................22
9. Fan Performances.....................................................................................23
9.1 FXDQ-PDVE(T)...............................................................................23
9.2 FXDQ-NDVE(T)...............................................................................25
10.Sound Levels.............................................................................................28
10.1 FXDQ-PDVE(T)...............................................................................28
10.2 FXDQ-NDVE(T)...............................................................................30
11.Centre of Gravity.......................................................................................32
11.1 FXDQ-PDVE(T)...............................................................................32
11.2 FXDQ-NDVE(T)...............................................................................33
12.Accessories...............................................................................................35
12.1 Optional Accessories (for Unit)........................................................35
12.2 Optional Accessories (for Controls).................................................35
13.Installation Manual....................................................................................36
1
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
1. Lineup
Note:
FXDQ has following 2 series, as shown below.
FXDQ-PDVE, NDVE, PDV2S, NDV2S, PDVE4, NDVE4: with a Drain Pump
FXDQ-PDVET, NDVET, PDVTS, NDVTS, PDVT4, NDVT4: without a Drain Pump
2
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
2. Specifications
2.1 FXDQ-PDVE(T)
With a drain pump
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.
3
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
Model FXDQ32PDVE
Power supply 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 3,100
1 3 Cooling capacity Btu/h 12,300
kW 3.6
kcal/h 3,400
2 3 Heating capacity Btu/h 13,600
kW 4.0
50 Hz kW 0.089
Cooling
60 Hz kW 0.095
Power input
50 Hz kW 0.070
Heating
60 Hz kW 0.076
Casing / Colour Galvanized steel plate
Dimensions: (H×W×D) mm 200×700×620
Model —
Type Sirocco fan
Motor output × W 62×1
Number of units
Fan m³/min 8.0/7.2/6.4
Airflow rate l/s 133/120/106
(HH/H/L)
cfm 282/254/226
4 External static pressure Pa 30-10
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene
Air filter Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection)
Piping
connections Gas pipes mm φ12.7 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20)
Mass kg 23
5 Sound pressure level (HH/H/L) dB(A) 28/26/24
Sound power level (HH/H/L) dB(A) 56/54/52
Safety devices Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve
Operation manual, Installation manual, Drain hose, Sealing pads, Clamps, Washers, Insulation
Standard accessories for fitting, Clamp metal, Washer fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B
Drawing No.
Sound level C: 4D112291
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.
4
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.
5
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
Model FXDQ32PDVET
Power supply 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 3,100
1 3 Cooling capacity Btu/h 12,300
kW 3.6
kcal/h 3,400
2 3 Heating capacity Btu/h 13,600
kW 4.0
50 Hz kW 0.070
Cooling
60 Hz kW 0.076
Power input
50 Hz kW 0.070
Heating
60 Hz kW 0.076
Casing / Colour Galvanized steel plate
Dimensions: (H×W×D) mm 200×700×620
Model —
Type Sirocco fan
Motor output × W 62×1
Number of units
Fan m³/min 8.0/7.2/6.4
Airflow rate l/s 133/120/106
(HH/H/L)
cfm 282/254/226
4 External static pressure Pa 30-10
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene
Air filter Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection)
Piping
connections Gas pipes mm φ12.7 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20)
Mass kg 23
5 Sound pressure level (HH/H/L) dB(A) 28/26/24
Sound power level (HH/H/L) dB(A) 56/54/52
Safety devices Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve
Operation manual, Installation manual, Drain hose, Sealing pads, Clamps, Washers, Insulation
Standard accessories for fitting, Clamp metal, Washer fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B
Drawing No.
Sound level C: 4D112291
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.
6
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
2.2 FXDQ-NDVE(T)
With a drain pump
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.
7
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
Model FXDQ63NDVE
Power supply 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 6,100
1 3 Cooling capacity Btu/h 24,200
kW 7.1
kcal/h 6,900
2 3 Heating capacity Btu/h 27,300
kW 8.0
50 Hz kW 0.181
Cooling
60 Hz kW 0.192
Power input
50 Hz kW 0.168
Heating
60 Hz kW 0.179
Casing / Colour Galvanized steel plate
Dimensions: (H×W×D) mm 200×1,100×620
Model —
Type Sirocco fan
Motor output × W 130×1
Number of units
Fan m³/min 16.5/14.5/13.0
Airflow rate l/s 275/241/216
(HH/H/L)
cfm 583/512/459
4 External static pressure Pa 44-15
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene
Air filter Removal / Washable / Mildew proof
Liquid pipes mm φ9.5 (Flare connection)
Piping
connections Gas pipes mm φ15.9 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20)
Mass kg 31
5 Sound pressure level (HH/H/L) dB(A) 33/31/29
Sound power level (HH/H/L) dB(A) 61/59/57
Safety devices Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve
Operation manual, Installation manual, Drain hose, Sealing pads, Clamps, Washers, Insulation
Standard accessories for fitting, Clamp metal, Washer fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B
Drawing No.
Sound level C: 4D112295
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.
8
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.
9
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
Model FXDQ63NDVET
Power supply 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 6,100
1 3 Cooling capacity Btu/h 24,200
kW 7.1
kcal/h 6,900
2 3 Heating capacity Btu/h 27,300
kW 8.0
50 Hz kW 0.168
Cooling
60 Hz kW 0.179
Power input
50 Hz kW 0.168
Heating
60 Hz kW 0.179
Casing / Colour Galvanized steel plate
Dimensions: (H×W×D) mm 200×1,100×620
Model —
Type Sirocco fan
Motor output × W 130×1
Number of units
Fan m³/min 16.5/14.5/13.0
Airflow rate l/s 275/241/216
(HH/H/L)
cfm 583/512/459
4 External static pressure Pa 44-15
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene
Air filter Removal / Washable / Mildew proof
Liquid pipes mm φ9.5 (Flare connection)
Piping
connections Gas pipes mm φ15.9 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20)
Mass kg 31
5 Sound pressure level (HH/H/L) dB(A) 33/31/29
Sound power level (HH/H/L) dB(A) 61/59/57
Safety devices Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve
Operation manual, Installation manual, Drain hose, Sealing pads, Clamps, Washers, Insulation
Standard accessories for fitting, Clamp metal, Washer fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B
Drawing No.
Sound level C: 4D112295
Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.
10
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
3. Dimensions
3.1 FXDQ-PDVE(T)
FXDQ20PDVE / FXDQ25PDVE / FXDQ32PDVE (with a drain pump)
Unit: mm
3D049799D
11
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
3D050732C
12
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
3.2 FXDQ-NDVE(T)
FXDQ40NDVE / FXDQ50NDVE (with a drain pump)
Unit: mm
3D045494E
13
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
3D045496F
14
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
3D049701D
15
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
3D049702D
16
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
4. Piping Diagrams
4D104913
17
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
5. Wiring Diagrams
3D103337
18
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
6. Electric Characteristics
3D112184
19
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
20
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
8. Capacity Tables
8.1 Cooling Capacity for Te: Auto
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
21
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXDQ20PDVE 20 1.0 1.0 1.2 1.2 1.6 1.5 1.7 1.6 1.8 1.6 1.9 1.4 2.0 1.5
FXDQ20PDVET
FXDQ25PDVE 25 1.3 1.2 1.6 1.6 2.0 1.8 2.2 1.8 2.2 1.8 2.4 1.8 2.6 1.7
FXDQ25PDVET
FXDQ32PDVE 32 1.7 1.5 2.0 1.8 2.6 2.0 2.8 2.2 2.8 2.0 3.0 2.1 3.2 2.1
FXDQ32PDVET
FXDQ40NDVE 40 2.0 2.0 2.5 2.3 3.2 2.7 3.5 2.8 3.7 2.7 3.9 2.6 4.1 2.8
FXDQ40NDVET
FXDQ50NDVE 50 2.6 2.4 3.1 2.9 3.9 3.3 4.4 3.4 4.6 3.3 4.8 3.4 5.1 3.1
FXDQ50NDVET
FXDQ63NDVE 63 3.2 2.9 4.0 3.5 5.1 4.1 5.6 4.2 5.8 4.0 6.2 4.1 6.5 4.1
FXDQ63NDVET
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.
22
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
9. Fan Performances
9.1 FXDQ-PDVE(T)
FXDQ20PDVE / FXDQ25PDVE
FXDQ20PDVET / FXDQ25PDVET
3D052156E
23
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
FXDQ32PDVE
FXDQ32PDVET
3D052157E
24
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
9.2 FXDQ-NDVE(T)
FXDQ40NDVE
FXDQ40NDVET
3D046299G
25
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
FXDQ50NDVE
FXDQ50NDVET
3D046300G
26
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
FXDQ63NDVE
FXDQ63NDVET
3D046301G
27
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
10.Sound Levels
10.1 FXDQ-PDVE(T)
FXDQ20PDVE
FXDQ20PDVET
4D112287
FXDQ25PDVE
FXDQ25PDVET
4D112290
28
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
FXDQ32PDVE
FXDQ32PDVET
4D112291
29
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
10.2 FXDQ-NDVE(T)
FXDQ40NDVE
FXDQ40NDVET
4D112292
FXDQ50NDVE
FXDQ50NDVET
4D112294
30
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
FXDQ63NDVE
FXDQ63NDVET
4D112295
31
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
11.Centre of Gravity
11.1 FXDQ-PDVE(T)
FXDQ20PDVE / FXDQ25PDVE / FXDQ32PDVE
FXDQ20PDVET / FXDQ25PDVET / FXDQ32PDVET
Unit: mm
4D049300M
32
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
11.2 FXDQ-NDVE(T)
FXDQ40NDVE / FXDQ50NDVE
FXDQ40NDVET / FXDQ50NDVET
Unit: mm
4D043886R
33
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
FXDQ63NDVE
FXDQ63NDVET
Unit: mm
4D043887Q
34
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
12.Accessories
12.1 Optional Accessories (for Unit)
Model
Item FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE
FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET
Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63
C: 3D112270A
Model
Item FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE
FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET
Cooling Only BRC4C66 (Note 4)
Remote Wireless
Heat Pump BRC4C65 (Note 4)
controller
Wired BRC1C62 (Note 4)
Navigation remote controller BRC1E62 (Note 4)
(Wired remote controller)
Simplified remote controller BRC2C51
Remote controller for hotel use BRC3A61
Adaptor for wiring KRP1B56
Wiring adaptor for electrical KRP2A53
appendices (1)
Wiring adaptor for electrical KRP4A54
appendices (2)
Remote sensor KRCS01-1B
Installation box for adaptor printed KRP1BA101(Note 2, 3)
circuit board
External control adaptor for outdoor
unit (must be installed on indoor DTA104A53
units)
C: 3D112270A
Notes:
1. Installation box (KRP1BA101) is necessary for each adaptor marked .
2. Up to 2 installation boxes can be installed for each indoor unit.
3. Installation (KRP1BA101) is necessary for each adaptor.
4. Wireless remote controller does not have AUTO fan mode.
Use wired remote controller to select AUTO fan mode.
35
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
13.Installation Manual
English 1
3P432203-7B
36
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
2 English
3P432203-7B
37
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
Large (5) Are the indoor and outdoor The units may drop, vibrate
Shape for liquid pipe (3)
unit fixed firmly? or make noise.
It may result in insufficient
Is the gas leak test finished?
for gas pipe (4) mid. (6) cooling.
Is the unit fully insulated? Condensate may drip.
Does drainage flow
Screws for Washer for Washer Condensate may drip.
Name duct flanges hanging Clamp fixing plate smoothly?
(7) bracket (8) (11) Does the power supply
The unit may malfunction or
Quantity 1 set 8 pcs. 1 set 4 pcs. voltage correspond to that
the components burn out.
shown on the name plate?
Are wiring and piping The unit may malfunction or
correct? the components burn out.
Large (9)
8 pcs. Imcomplete grounding may
Shape Is the unit safely grounded?
result in electric shocks.
26 pcs. Is wiring size according to The unit may malfunction or
small (10) specifications? the components burn out.
4 pcs.
Is something blocking the air
It may result in insufficient
outlet or inlet of either the
cooling.
indoor or outdoor units?
Sealing
Name Air filter (13) Are refrigerant piping length
material (12) The refrigerant charge in the
(Other) and additional refrigerant
Quantity 2 pcs. 1 pc. system is not clear.
• Operation manual charge noted down?
• Installation manual
(this manual) Also review the “SAFETY PRECAUTIONS”.
Shape
b. Items to be checked at time of delivery
Items to be checked Check
Did you explain about operations while showing the
operation manual to your customer?
2-3 OPTIONAL ACCESSORIES
Did you hand the operation manual and warranty over to
• These are two types of remote controllers: wired and your customer?
wireless. Select a remote controller according to customer
Did you explain about the way of maintaining and cleaning
request and install in an appropriate place.
local procurements (air filter, grille (both air outlet and
suction grille), etc.) to your customer?
Table 1
Remote controller Did you hand manuals of local procurements (in case
equipped) over to your customer?
Wired type
Heat pump type c. Points for explanation about operations
Wireless type
Cooling only type
The items with WARNING and CAUTION marks in
the operation manual are the items pertaining to
NOTE
possibilities for bodily injury and material damage in
• If you wish to use a remote controller that is not listed in addition to the general usage of the product. Accordingly, it
Table 1, select a suitable remote controller after consulting is necessary that you make a full explanation about the
catalogs and technical materials. described contents and also ask your customers to read the
operation manual.
English 3
3P432203-7B
38
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
3. SELECTING INSTALLATION SITE (2) Use suspension bolts for installation. Check whether
the ceiling is strong enough to support the weight of
CAUTION the unit or not. If there is a risk, reinforce the ceiling
• When moving the unit during or after unpacking, make sure before installing the unit.
to lift it by holding its lifting lugs. Do not exert any pressure on (Installation pitch is marked on the carton box for installation.
other parts, especially the refrigerant piping, drain piping and Refer to it to check for points requiring reinforcing.)
flange parts.
• If you think the humidity inside the ceiling might exceed 4. PREPARATIONS BEFORE INSTALLATION
30°C and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that (1) Confirm the positional relationship between the unit
it is no thicker than 10 mm and fits inside the ceiling and suspension bolts. (Refer to Fig. 2)
opening. • Install the inspection opening on the control box side where
maintenance and inspection of the control box and drain
(1) Select an installation site where the following conditions pump are easy. Install the inspection opening also in the
are fulfilled and that meets with your customer’s approval. lower part of the unit.
• Where optimum air distribution can be ensured. 620
• Where nothing blocks air passage. 500
• Where condensate can be properly drained.
• Where the ceiling is strong enough to bear the indoor unit Suspension (length : mm)
bolt pitch
weight.
• Where the false ceiling is not noticeably on an incline.
B
A
possible within the allowable limit. (Refer to the installation
Drain pump Control box
manual for the outdoor unit.)
450×450
(Inspection
*300
300 opening size)
or
more Control box or more
Maintenance Maintenance
space space
2500 or more 240 or more
Ceiling
200
*H1=
〈SERVICE SPACE〉
*H2=20 or more 620
Ceiling
4 English
3P432203-7B
39
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
Chamber lid
Protection net
Air discharge
Air inlet
Fig. 4
English 5
3P432203-7B
40
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
0
36.3±3.6 13.0±0.2 R0.4-0.8
45 2
Vinyl tube (3/8”)
0
2
0
0
90
φ 12.7
A
(4) Tighten the upper nut. (1/2”)
54.9±5.4 16.4±0.2
φ 15.9
68.6±6.8 19.5±0.2
(5/8”)
6. REFRIGERANT PIPING WORK
• For the outdoor unit refrigerant piping, refer to the installation CAUTION
manual attached to the outdoor unit. Overtightening may damage the flare and cause leaks.
• Carry out insulation of both gas and liquid refrigerant piping Be careful for oil not to adhere to any portions other
than a flare part. If oil adhere to resin parts etc., there is
securely. If not insulated, it may cause water leakage. For a possibility of damaging by deterioration.
gas piping, use insulation material of which heat resistant
temperature is not less than 120°C.
• Refer to Table 2 if no torque wrench is available.
For use under high humidity, strengthen the insulation
Using a wrench to tighten flare nuts causes the tightening
material for refrigerant piping. If not strengthened, the
torque to suddenly grow much tighter after a certain point.
surface of insulation material may sweat.
From there, tighten the nut further by the appropriate angle
• Before installation work, make sure that the refrigerant is
listed in Table 2.
R410A. (Unless the refrigerant is R410A, the normal
operation cannot be expected.) (1) After the work is finished, make sure to check that
CAUTION there is no gas leak.
This air conditioner is a dedicated model for new refrigerant (2) After checking for gas leaks, be sure to insulate the
R410A. Make sure to meet the requirements shown below pipe connections referring to Fig. 8.
and carry out installation work. • Insulate using the insulation for fitting (3) (4) included with
• Use dedicated piping cutters and flaring tools for R410A. the liquid and gas pipes. Besides, make sure the
• When making a flare connection, coat the flared inner insulation for fitting (3) (4) on the liquid and gas piping
surface only with ether oil or ester oil. has its seams facing up.
• Use only the flare nuts attached to the air conditioner. If (Tighten both edges with clamp (9).)
other flare nuts are used, it may cause refrigerant • For the gas piping, wrap the mid. sealing pad (6) over the
leakage. insulation for fitting (4) (flare nut part).
• To prevent contamination or moisture from getting into
the piping, take measures such as pinching or taping the Liquid Piping Insulation Procedure
pipings.
Insulation for fitting (3)
Do not mix substance other than the specified refrigerant Piping insulation material (accessory)
such as air into the refrigeration circuit. (main unit)
If the refrigerant leaks during the work, ventilate the room. Flare nut connection
Attach to base Turn seams up
• The refrigerant is pre-charged in the outdoor unit. Main unit
• When connecting the pipings to the air conditioner, make Clamp (9) (accessory) Piping insulation material
sure to use a spanner and a torque wrench as shown in (Field supply)
Fig. 6.
• For the dimension of flared part and the tightening torque,
refer to the Table 1. Liquid pipe
• When making a flare connection, coat the flared inner
surface only with ether oil or ester oil.
(Refer to Fig. 7)
Gas pipe
Then, turn the flare nut 3 to 4 times with your hand and screw
in the nut. Gas Piping Insulation Procedure
6 English
3P432203-7B
41
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
English 7
3P432203-7B
42
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
Large sealing 1. Remove the control box lid. Connect the remote controller
Metal clamp (1) pad (5) and power supply (single-phase, 50 Hz 220-240 V or
(accessory) (accessory) single-phase, 60Hz 220V) respectively to the terminal block
Metal clamp (1) and securely connect the earth also (as shown in the figure
(accessory) below).
Tape Drain hose (2) ≤4 mm CAUTION
(accessory)
Securely clamp the cables with the clamps (9)(10) offered
Fig. 11 Fig. 12 as accessories as shown in Fig. 17 so that tension will not
be applied on the cable connection areas.
〈 PRECAUTIONS FOR DRAIN RAISING PIPE 〉
• Make sure the drain raising pipe height is no higher than 2. Confirm that the control box lid is closed before turning on
600 mm. the power.
• Place the drain raising pipe vertically and make sure it is no 3. Remove the inspection lid.
further than 300 mm from the unit. (Refer to Fig. 13) 4. Gradually pour approximately 1L of water from the
inspection window into the drain pan to check drainage.
Ceiling slab CAUTION
300 mm or less 1 – 1.5m Hanging bracket Be sure to prevent an external force from being exerted on
the float switch.
(This may cause breakage.)
5. Attach the inspection lid.
Adjustable range 6. Perform the following operation using the remote controller,
(600mm or less) and check drainage.
Metal clamp (1) (accessory)
• Select the inspection/test operation button “ TEST ” using
Drain raising pipe the remote controller. The unit will engage the test
Drain hose (2) (accessory)
(Field supply) operation. Press the operation selector button “ ”, and
select FAN OPERATION “ ”.
Drain hose (2) (accessory) • Press the ON/OFF button “ ”. (The indoor fan and
drain pump will operate.)
Horizontal or CAUTION
upward slope
The fan will turn also at the same time. Take due care.
Do not touch the drain pump to prevent electric shock.
Locate the drain hose horizontally
or with a little upward gradient. Drain outlet Inspection window
If there is an air bank, noise may be generated Portable pump
as a result of a water backflow when the drain
Inspection lid
pump comes to a stop.
Refrigerant pipes
Fig. 13 Bucket
Service drain hole L N
the indoor unit through the drain piping and corrode the heat
CNTRL WIRING OFF
CNTRL WIRING OFF
L N
Single phase,
exchanger. 60Hz, 220 V
• Do not twist or bend the drain hose (2), so that excessive Power terminal
force is not applied to it. Remote controller connection
terminal connection method
(This type of treatment may cause leaking.) method Terminal block Terminal block
• If you are using central drain piping, follow the procedure
outlined in the figure 10. 7. Make sure to use the remote controller in finishing the
• Select central drain piping of proper size according to the operation.
capacity of the connected unit.
(2) After piping work is finished, check drainage flows
smoothly, with manner described below. In case of PDVET, NDVET type (without drain pump)
CAUTION CAUTION
• The electric wiring work shall be performed by qualified • The connection opening on the drain piping may vary
electricians. depending on the model, so check the model name and use
• If workers not having the electrician qualification have the right method for that model.
performed the electric wiring work, the steps 3 to 7 shall be • Make sure all water is out before making the duct connection.
performed after the TEST RUN.
8 English
3P432203-7B
43
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
English 9
3P432203-7B
44
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
10 English
3P432203-7B
45
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
∗Transmission wiring Power supply wiring Indoor PC board (ASSY) Power supply wiring
∗Remote controller wiring Earth wire Earth wire
∗ Do not connect power
supply wiring here. Clamp (for fixing in place) P1P2 F1F2T1 T2
Wiring through hole
REMOTE TRANSMISSION FORCED
CAUTION
• When clamping the wiring, use the included clamp material
(9) and (10) as shown in the Fig.17 to prevent outside pres-
sure being exerted on the wiring connections and clamp
firmly.
• Be sure to attach power supply wiring and earth wire to the
control box with the clamp.
• When doing the wiring, make sure the wiring is neat and
does not cause the control box lid to stick up, then close the
cover firmly. When attaching the control box lid, make sure
you do not pinch any wires.
• Outside the air conditioners, separate the weak wiring (remote
controller and transmission wiring) and strong wiring (earth
wire and power supply wiring) at least 50 mm so that they do
not pass through the same place together. Proximity may
cause electrical interference, malfunctions, and breakage.
English 11
3P432203-7B
46
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
[ WIRING EXAMPLE ]
CAUTION FOR WIRING
• For connection to the terminal block, use ring type crimp style No. 1 system When using 1 remote controller for
terminals with insulation sleeve or insulate the wirings 1 indoor unit
properly. Power supply
single phase
Wiring 50Hz 220-240V
Insulation sleeve or
single phase
60Hz 220V Outdoor unit
Ring type crimp
L N
style terminal IN/D OUT/D
F1 F2 F1 F2
Fig. 19
L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2
P1 P2 P1 P2 P1 P2
Fig. 21
Use wires the same in size
(if the air conditioner is in No. 2 system For group control or use with 2 remote
simultaneous multi operation)
controllers
Fig. 20
Power supply
single phase
(Abnormal heating may occur if the wirings are not tightened
50Hz 220-240V
securely.) or
• Use the required wirings, connect them securely and fix single phase
these wirings securely so that external force may not apply to 60Hz 220V Outdoor unit Note) There is not need to set the indoor unit
the terminals. L N
IN/D OUT/D
address when using group control.
• Use a proper screw driver for tightening the terminal screws.
F1 F2 F1 F2 (It is automatically set when the power
is turned on.)
If an improper screw driver is used, it may damage the screw
head and a proper tightening cannot be carried out.
• If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of Most down-
terminals. L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 stream
Table 3 indoor unit
Indoor Indoor unit B
WARNING
• When wiring, form the wirings orderly so that the control box
lid can be securely fastened. If the control box lid is not in
place, the wirings may come out or be sandwiched by the box
and the lid and cause electric shocks or a fire.
12 English
3P432203-7B
47
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
No. 3 system When including BS unit (4) Add remote controller 2 (SUB) to the terminal block for
remote controller (P1, P2) in the control box.
Power supply
single phase (There is no polarity.)
50Hz 220-240V
or P1 P2 F1 F2 T1 T2
REMOTE TRANSMISSION FORCED
Remote Remote
controller 1 controller 2
(MAIN) (SUB)
[ PRECAUTIONS ]
LN P1 P2 F1 F2 T1 T2 • Crossover wiring is needed when using group control and
2 remote controllers at the same time.
Indoor unit A • Connect the indoor unit at the end of the crossover wire
(P1, P2) to remote controller 2 (SUB).
Max. No. of
P1 P2
Indoor unit 1 Indoor unit 2 indoor units
Remote controller
(option)
Fig. 23
Crossover wire (P1.P2)
10-2 CONTROL BY 2 REMOTE CONTROLLERS
Remote controller 1 Remote controller 2
(Controlling 1 indoor unit by 2 remote controllers) (MAIN) (SUB)
• When using 2 remote controllers, one must be set to “MAIN”
and the other to “SUB”.
MAIN/SUB CHANGEOVER
10-3 REMOTE CONTROL (FORCED OFF AND ON/
OFF OPERATION)
(1) Insert a screwdriver into the recess between the
• Connect input lines from the outside to the terminals T1
upper and lower part of remote controller and, working
and T2 on the terminal block (6P) for remote controller to
from the 2 positions, pry off the upper part (2 locations).
achieve remote control.
The remote controller PC board is attached to the upper • See the “11. FIELD SETTING AND TEST RUN” for
part of remote controller. details on operation.
Upper part of
remote controller
P1 P2 F1 F2 T1 T2
REMOTE TRANSMISSION FORCED
CONTRL WIRING OFF
Input A
English 13
3P432203-7B
48
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
11. FIELD SETTING AND TEST RUN 11-3 SETTING THE FILTER SIGN DISPLAY INTERVAL
• Explain the following to the customer if the filter dirt settings
〈Field settings may have to be performed using the
have been changed.
remote controller, depending on the type of installation.〉
• The filter sign display time is set to 2500 hours
(1) Make sure the control box lids are closed on the indoor (equivalent to 1 year’s use) when shipped.
and outdoor units. • The settings can be changed to not display.
(2) Depending on the type of installation, make the field • When installing the unit in a place with much dusts, set the
settings from the remote controller after the power is filter sign display time to shorter intervals (1,250 hours).
turned on, following the “Field Settings” manual which • Explain it to the customer that the filter needs to be cleaned
came with the remote controller. regularly to prevent clogging and also the time that is set.
• The settings can select “Mode No.”, “FIRST CODE NO.”
SECOND
and “SECOND CODE NO.”. CODE NO.
Mode No. FIRST CODE NO.
• The “Field Settings” included with the remote controller
01 02
lists the order of the settings and method of operation.
0 Filter dirt low high
Displayed time 2500/ 10000/
SECOND 1 (low/high)
10 (20) (units: hours) 1250 5000
CODE NO. Mode No. Filter sign
3 ON OFF
FIRST display
CODE NO.
SETTING
FIELD SET 11-4 SETTINGS FOR SEPARATELY SOLD
MODE ACCESSORIES
• See the instruction manuals included with separately sold
• Lastly, make sure the customer keeps the “Field Settings” accessories for the necessary settings.
manual, along with the operating manual, in a safe place. 〈 When using a wireless remote controller 〉
• A wireless remote controller address needs to be set when
11-1 SETTING THE STATIC PRESSURE SELECTION
using a wireless remote controller. See the installation
• Select the SECOND CODE NO. for the resistance of the con- manual included with the wireless remote controller for
nected duct. details on how to make the settings.
(The SECOND CODE NO. is set to “01” when shipped.)
• See the technical documentation for details. 11-5 SWITCHING TIME OF THE DRY OPERATION AT
External static FIRST SECOND VRTsmart control SETTING.
Mode No. • If you change the operation mode to “Dry” when VRTsmart
pressure CODE NO. CODE NO.
control is in effect, the operation mode is change to “Cooling”
Standard (10Pa) 01 after certain period of time.
High static pres- 13(23) 5 If you want to continue dry operation longer, please change
02 the setting position as mentioned in the table below.
sure setting (30Pa) (Setting position of factory setting is “0”.)
11-2 REMOTE CONTROL SETTING ※ If you keep dry operation longer, energy saving
performance decrease.
• Forced off and ON/OFF operation should be selected by
Mode Setting switch Setting position
selecting the SECOND CODE NO. as shown in the table Dry operation
number number number
below.
30 min 01
(The SECOND CODE NO. is set to “01” when shipped.)
60 min 02
FIRST SECOND
External ON/OFF input Mode No.
CODE NO. CODE NO. 90 min
10 10
03
Forced off 01 Continuous (Not return 04
12(22) 1 to Cooling)
ON/OFF operation 02
• Input A of forced off and ON/OFF operation work as shown in ※ At the time of Group control setting, Dry operation time for the
indoor units in the same group shall be the same setting value.
the table below.
Forced off ON/OFF operation NOTE
Input A “on” to force a stop Unit operated by changing input A from For VRTsmart control function it is necessary to connect
(remote controller reception prohibited) “off” to “on” with an outdoor unit with a compatible function.
Unit stopped by changing input A from “on”
Input A “off” to allow remote controller
to “off”
14 English
3P432203-7B
49
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749
CAUTION
• Always stop the test run using the remote controller to stop
operation.
English 15
3P432203-7B
50
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.
●Specifications, designs and other content appearing in this brochure are current as of October 2017 but subject to change without notice.