You are on page 1of 56

EDFMT391749

201710

Engineering Data

FXDQ-PDVE(T)
FXDQ-NDVE(T)
50 / 60 Hz
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ-PDVE(T) / FXDQ-NDVE(T)
Slim Ceiling Mounted Duct Type
(Standard Series)
50 / 60 Hz
1. Lineup..........................................................................................................2
2. Specifications..............................................................................................3
2.1 FXDQ-PDVE(T).................................................................................3
2.2 FXDQ-NDVE(T).................................................................................7
3. Dimensions................................................................................................11
3.1 FXDQ-PDVE(T)...............................................................................11
3.2 FXDQ-NDVE(T)...............................................................................13
4. Piping Diagrams........................................................................................17
5. Wiring Diagrams........................................................................................18
6. Electric Characteristics..............................................................................19
7. Safety Devices Setting..............................................................................20
8. Capacity Tables.........................................................................................21
8.1 Cooling Capacity for Te: Auto..........................................................21
8.2 Cooling Capacity for Te: 6°C...........................................................21
8.3 Cooling Capacity for Te: 9°C...........................................................22
8.4 Heating Capacity..............................................................................22
9. Fan Performances.....................................................................................23
9.1 FXDQ-PDVE(T)...............................................................................23
9.2 FXDQ-NDVE(T)...............................................................................25
10.Sound Levels.............................................................................................28
10.1 FXDQ-PDVE(T)...............................................................................28
10.2 FXDQ-NDVE(T)...............................................................................30
11.Centre of Gravity.......................................................................................32
11.1 FXDQ-PDVE(T)...............................................................................32
11.2 FXDQ-NDVE(T)...............................................................................33
12.Accessories...............................................................................................35
12.1 Optional Accessories (for Unit)........................................................35
12.2 Optional Accessories (for Controls).................................................35
13.Installation Manual....................................................................................36

1
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

1. Lineup

2.2 kW 2.8 kW 3.6 kW 4.5 kW 5.6 kW 7.1 kW


Capacity range
0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP 2.5 HP
Capacity index 20 25 31.25 40 50 62.5

20PDVE 25PDVE 32PDVE — — —

20PDVET 25PDVET 32PDVET — — —


FXDQ
— — — 40NDVE 50NDVE 63NDVE

— — — 40NDVET 50NDVET 63NDVET

20PDV2S 25PDV2S 32PDV2S — — —

20PDVTS 25PDVTS 32PDVTS — — —


FXDQ
(for Thailand)
— — — 40NDV2S 50NDV2S 63NDV2S

— — — 40NDVTS 50NDVTS 63NDVTS

20PDVE4 25PDVE4 32PDVE4 — — —

20PDVT4 25PDVT4 32PDVT4 — — —


FXDQ
(for Indonesia)
— — — 40NDVE4 50NDVE4 63NDVE4

— — — 40NDVT4 50NDVT4 63NDVT4

Note:
FXDQ has following 2 series, as shown below.
FXDQ-PDVE, NDVE, PDV2S, NDV2S, PDVE4, NDVE4: with a Drain Pump
FXDQ-PDVET, NDVET, PDVTS, NDVTS, PDVT4, NDVT4: without a Drain Pump

VE : 1 phase, 220-240/220 V, 50/60 Hz


VET : 1 phase, 220-240/220 V, 50/60 Hz
V2S : 1 phase, 220 V, 50 Hz (for Thailand)
VTS : 1 phase, 220 V, 50 Hz (for Thailand)
VE4 : 1 phase, 220-240/220 V, 50/60 Hz (for Indonesia)
VT4 : 1 phase, 220-240/220 V, 50/60 Hz (for Indonesia)

2
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

2. Specifications
2.1 FXDQ-PDVE(T)
With a drain pump

Model FXDQ20PDVE FXDQ25PDVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 1,900 2,400
1 3 Cooling capacity Btu/h 7,500 9,600
kW 2.2 2.8
kcal/h 2,200 2,800
2 3 Heating capacity Btu/h 8,500 10,900
kW 2.5 3.2
50 Hz kW 0.086 0.086
Cooling
60 Hz kW 0.092 0.092
Power input
50 Hz kW 0.067 0.067
Heating
60 Hz kW 0.073 0.073
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 200×700×620 200×700×620
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 62×1 62×1
Number of units
Fan m³/min 8.0/7.2/6.4 8.0/7.2/6.4
Airflow rate l/s 133/120/106 133/120/106
(HH/H/L)
cfm 282/254/226 282/254/226
4 External static pressure Pa 30-10 30-10
Drive Direct drive Direct drive
Microprocessor thermostat for cooling and Microprocessor thermostat for cooling and
Temperature control heating heating
Sound absorbing thermal insulation material Foamed polyethylene Foamed polyethylene
Air filter Removal / Washable / Mildew proof Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping
connections Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20) VP20 (External dia. 26, Internal dia. 20)
Mass kg 23 23
5 Sound pressure level (HH/H/L) dB(A) 28/26/23 28/26/23
Sound power level (HH/H/L) dB(A) 56/54/51 56/54/51
Safety devices Fuse, Thermal protector for fan motor Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers, hose, Sealing pads, Clamps, Washers,
Standard accessories Insulation for fitting, Clamp metal, Washer Insulation for fitting, Clamp metal, Washer
fixing plate, Screws for duct flanges, Air filter fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B C: 3D109082B
Drawing No.
Sound level C: 4D112287 C: 4D112290

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.

3
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

With a drain pump

Model FXDQ32PDVE
Power supply 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 3,100
1 3 Cooling capacity Btu/h 12,300
kW 3.6
kcal/h 3,400
2 3 Heating capacity Btu/h 13,600
kW 4.0
50 Hz kW 0.089
Cooling
60 Hz kW 0.095
Power input
50 Hz kW 0.070
Heating
60 Hz kW 0.076
Casing / Colour Galvanized steel plate
Dimensions: (H×W×D) mm 200×700×620
Model —
Type Sirocco fan
Motor output × W 62×1
Number of units
Fan m³/min 8.0/7.2/6.4
Airflow rate l/s 133/120/106
(HH/H/L)
cfm 282/254/226
4 External static pressure Pa 30-10
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene
Air filter Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection)
Piping
connections Gas pipes mm φ12.7 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20)
Mass kg 23
5 Sound pressure level (HH/H/L) dB(A) 28/26/24
Sound power level (HH/H/L) dB(A) 56/54/52
Safety devices Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve
Operation manual, Installation manual, Drain hose, Sealing pads, Clamps, Washers, Insulation
Standard accessories for fitting, Clamp metal, Washer fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B
Drawing No.
Sound level C: 4D112291

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.

4
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

Without a drain pump

Model FXDQ20PDVET FXDQ25PDVET


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 1,900 2,400
1 3 Cooling capacity Btu/h 7,500 9,600
kW 2.2 2.8
kcal/h 2,200 2,800
2 3 Heating capacity Btu/h 8,500 10,900
kW 2.5 3.2
50 Hz kW 0.067 0.067
Cooling
60 Hz kW 0.073 0.073
Power input
50 Hz kW 0.067 0.067
Heating
60 Hz kW 0.073 0.073
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 200×700×620 200×700×620
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 62×1 62×1
Number of units
Fan m³/min 8.0/7.2/6.4 8.0/7.2/6.4
Airflow rate l/s 133/120/106 133/120/106
(HH/H/L)
cfm 282/254/226 282/254/226
4 External static pressure Pa 30-10 30-10
Drive Direct drive Direct drive
Microprocessor thermostat for cooling and Microprocessor thermostat for cooling and
Temperature control heating heating
Sound absorbing thermal insulation material Foamed polyethylene Foamed polyethylene
Air filter Removal / Washable / Mildew proof Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping
connections Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20) VP20 (External dia. 26, Internal dia. 20)
Mass kg 23 23
5 Sound pressure level (HH/H/L) dB(A) 28/26/23 28/26/23
Sound power level (HH/H/L) dB(A) 56/54/51 56/54/51
Safety devices Fuse, Thermal protector for fan motor Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers, hose, Sealing pads, Clamps, Washers,
Standard accessories Insulation for fitting, Clamp metal, Washer Insulation for fitting, Clamp metal, Washer
fixing plate, Screws for duct flanges, Air filter fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B C: 3D109082B
Drawing No.
Sound level C: 4D112287 C: 4D112290

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.

5
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

Without a drain pump

Model FXDQ32PDVET
Power supply 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 3,100
1 3 Cooling capacity Btu/h 12,300
kW 3.6
kcal/h 3,400
2 3 Heating capacity Btu/h 13,600
kW 4.0
50 Hz kW 0.070
Cooling
60 Hz kW 0.076
Power input
50 Hz kW 0.070
Heating
60 Hz kW 0.076
Casing / Colour Galvanized steel plate
Dimensions: (H×W×D) mm 200×700×620
Model —
Type Sirocco fan
Motor output × W 62×1
Number of units
Fan m³/min 8.0/7.2/6.4
Airflow rate l/s 133/120/106
(HH/H/L)
cfm 282/254/226
4 External static pressure Pa 30-10
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene
Air filter Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection)
Piping
connections Gas pipes mm φ12.7 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20)
Mass kg 23
5 Sound pressure level (HH/H/L) dB(A) 28/26/24
Sound power level (HH/H/L) dB(A) 56/54/52
Safety devices Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve
Operation manual, Installation manual, Drain hose, Sealing pads, Clamps, Washers, Insulation
Standard accessories for fitting, Clamp metal, Washer fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B
Drawing No.
Sound level C: 4D112291

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.

6
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

2.2 FXDQ-NDVE(T)
With a drain pump

Model FXDQ40NDVE FXDQ50NDVE


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 3,900 4,800
1 3 Cooling capacity Btu/h 15,400 19,100
kW 4.5 5.6
kcal/h 4,300 5,400
2 3 Heating capacity Btu/h 17,100 21,500
kW 5.0 6.3
50 Hz kW 0.160 0.165
Cooling
60 Hz kW 0.182 0.185
Power input
50 Hz kW 0.147 0.152
Heating
60 Hz kW 0.168 0.170
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 200×900×620 200×900×620
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 62×1 130×1
Number of units
Fan m³/min 10.5/9.5/8.5 12.5/11.0/10.0
Airflow rate l/s 175/158/141 208/183/166
(HH/H/L)
cfm 371/335/300 441/388/353
4 External static pressure Pa 44-15 44-15
Drive Direct drive Direct drive
Microprocessor thermostat for cooling and Microprocessor thermostat for cooling and
Temperature control heating heating
Sound absorbing thermal insulation material Foamed polyethylene Foamed polyethylene
Air filter Removal / Washable / Mildew proof Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping
connections Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20) VP20 (External dia. 26, Internal dia. 20)
Mass kg 27 28
5 Sound pressure level (HH/H/L) dB(A) 30/28/26 33/30/27
Sound power level (HH/H/L) dB(A) 58/56/54 61/58/55
Safety devices Fuse, Thermal protector for fan motor Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers, hose, Sealing pads, Clamps, Washers,
Standard accessories Insulation for fitting, Clamp metal, Washer Insulation for fitting, Clamp metal, Washer
fixing plate, Screws for duct flanges, Air filter fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B C: 3D109082B
Drawing No.
Sound level C: 4D112292 C: 4D112294

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.

7
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

With a drain pump

Model FXDQ63NDVE
Power supply 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 6,100
1 3 Cooling capacity Btu/h 24,200
kW 7.1
kcal/h 6,900
2 3 Heating capacity Btu/h 27,300
kW 8.0
50 Hz kW 0.181
Cooling
60 Hz kW 0.192
Power input
50 Hz kW 0.168
Heating
60 Hz kW 0.179
Casing / Colour Galvanized steel plate
Dimensions: (H×W×D) mm 200×1,100×620
Model —
Type Sirocco fan
Motor output × W 130×1
Number of units
Fan m³/min 16.5/14.5/13.0
Airflow rate l/s 275/241/216
(HH/H/L)
cfm 583/512/459
4 External static pressure Pa 44-15
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene
Air filter Removal / Washable / Mildew proof
Liquid pipes mm φ9.5 (Flare connection)
Piping
connections Gas pipes mm φ15.9 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20)
Mass kg 31
5 Sound pressure level (HH/H/L) dB(A) 33/31/29
Sound power level (HH/H/L) dB(A) 61/59/57
Safety devices Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve
Operation manual, Installation manual, Drain hose, Sealing pads, Clamps, Washers, Insulation
Standard accessories for fitting, Clamp metal, Washer fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B
Drawing No.
Sound level C: 4D112295

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.

8
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

Without a drain pump

Model FXDQ40NDVET FXDQ50NDVET


Power supply 1 phase, 220-240/220 V, 50/60 Hz 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 3,900 4,800
1 3 Cooling capacity Btu/h 15,400 19,100
kW 4.5 5.6
kcal/h 4,300 5,400
2 3 Heating capacity Btu/h 17,100 21,500
kW 5.0 6.3
50 Hz kW 0.147 0.152
Cooling
60 Hz kW 0.168 0.170
Power input
50 Hz kW 0.147 0.152
Heating
60 Hz kW 0.168 0.170
Casing / Colour Galvanized steel plate Galvanized steel plate
Dimensions: (H×W×D) mm 200×900×620 200×900×620
Model — —
Type Sirocco fan Sirocco fan
Motor output × W 62×1 130×1
Number of units
Fan m³/min 10.5/9.5/8.5 12.5/11.0/10.0
Airflow rate l/s 175/158/141 208/183/166
(HH/H/L)
cfm 371/335/300 441/388/353
4 External static pressure Pa 44-15 44-15
Drive Direct drive Direct drive
Microprocessor thermostat for cooling and Microprocessor thermostat for cooling and
Temperature control heating heating
Sound absorbing thermal insulation material Foamed polyethylene Foamed polyethylene
Air filter Removal / Washable / Mildew proof Removal / Washable / Mildew proof
Liquid pipes mm φ6.4 (Flare connection) φ6.4 (Flare connection)
Piping
connections Gas pipes mm φ12.7 (Flare connection) φ12.7 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20) VP20 (External dia. 26, Internal dia. 20)
Mass kg 27 28
5 Sound pressure level (HH/H/L) dB(A) 30/28/26 33/30/27
Sound power level (HH/H/L) dB(A) 58/56/54 61/58/55
Safety devices Fuse, Thermal protector for fan motor Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve Electronic expansion valve
Operation manual, Installation manual, Drain Operation manual, Installation manual, Drain
hose, Sealing pads, Clamps, Washers, hose, Sealing pads, Clamps, Washers,
Standard accessories Insulation for fitting, Clamp metal, Washer Insulation for fitting, Clamp metal, Washer
fixing plate, Screws for duct flanges, Air filter fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B C: 3D109082B
Drawing No.
Sound level C: 4D112292 C: 4D112294

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.

9
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

Without a drain pump

Model FXDQ63NDVET
Power supply 1 phase, 220-240/220 V, 50/60 Hz
kcal/h 6,100
1 3 Cooling capacity Btu/h 24,200
kW 7.1
kcal/h 6,900
2 3 Heating capacity Btu/h 27,300
kW 8.0
50 Hz kW 0.168
Cooling
60 Hz kW 0.179
Power input
50 Hz kW 0.168
Heating
60 Hz kW 0.179
Casing / Colour Galvanized steel plate
Dimensions: (H×W×D) mm 200×1,100×620
Model —
Type Sirocco fan
Motor output × W 130×1
Number of units
Fan m³/min 16.5/14.5/13.0
Airflow rate l/s 275/241/216
(HH/H/L)
cfm 583/512/459
4 External static pressure Pa 44-15
Drive Direct drive
Temperature control Microprocessor thermostat for cooling and heating
Sound absorbing thermal insulation material Foamed polyethylene
Air filter Removal / Washable / Mildew proof
Liquid pipes mm φ9.5 (Flare connection)
Piping
connections Gas pipes mm φ15.9 (Flare connection)
Drain pipe mm VP20 (External dia. 26, Internal dia. 20)
Mass kg 31
5 Sound pressure level (HH/H/L) dB(A) 33/31/29
Sound power level (HH/H/L) dB(A) 61/59/57
Safety devices Fuse, Thermal protector for fan motor
Refrigerant control Electronic expansion valve
Operation manual, Installation manual, Drain hose, Sealing pads, Clamps, Washers, Insulation
Standard accessories for fitting, Clamp metal, Washer fixing plate, Screws for duct flanges, Air filter
Specifications C: 3D109082B
Drawing No.
Sound level C: 4D112295

Notes:
+1. Indoor temp.: 27°CDB, 19°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5 m, level difference: 0 m. Conversion formulae
+2. Indoor temp.: 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5 m, level difference: 0 m. kcal/h=kW×860
+3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. Btu/h=kW×3412
+4. External static pressure is changeable to set by the remote controller. This pressure means “High static cfm=m³/min×35.3
pressure - Standard static pressure”. (Factory setting is 10 Pa for FXDQ-PD models and 15 Pa for FXDQ-ND l/s=m³/min×1000/60
models.)
+5. The operation sound levels are the conversion values in anechoic chamber.
In practice, the sound tend to be larger than the specified values due to ambient noise or reflections.
When the place of suction is changed to the bottom suction, the sound level will increase by approx, 5dBA.

10
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

3. Dimensions
3.1 FXDQ-PDVE(T)
FXDQ20PDVE / FXDQ25PDVE / FXDQ32PDVE (with a drain pump)
Unit: mm

3D049799D

11
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ20PDVET / FXDQ25PDVET / FXDQ32PDVET (without a drain pump)


Unit: mm

3D050732C

12
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

3.2 FXDQ-NDVE(T)
FXDQ40NDVE / FXDQ50NDVE (with a drain pump)
Unit: mm

3D045494E

13
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ63NDVE (with a drain pump)


Unit: mm

3D045496F

14
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ40NDVET / FXDQ50NDVET (without a drain pump)


Unit: mm

3D049701D

15
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ63NDVET (without a drain pump)


Unit: mm

3D049702D

16
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

4. Piping Diagrams

FXDQ20PDVE / FXDQ25PDVE / FXDQ32PDVE / FXDQ40NDVE / FXDQ50NDVE / FXDQ63NDVE


FXDQ20PDVET / FXDQ25PDVET / FXDQ32PDVET / FXDQ40NDVET / FXDQ50NDVET /
FXDQ63NDVET

4D104913

„„ Refrigerant pipe connection port diameters


Unit: mm
Model Gas Liquid
FXDQ20PDVE / FXDQ25PDVE / FXDQ32PDVE / FXDQ40NDVE / FXDQ50NDVE
FXDQ20PDVET / FXDQ25PDVET / FXDQ32PDVET / FXDQ40NDVET / FXDQ50NDVET φ12.7 φ6.4
FXDQ63NDVE
FXDQ63NDVET φ15.9 φ9.5

17
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

5. Wiring Diagrams

FXDQ20PDVE / FXDQ25PDVE / FXDQ32PDVE / FXDQ40NDVE / FXDQ50NDVE / FXDQ63NDVE


FXDQ20PDVET / FXDQ25PDVET / FXDQ32PDVET / FXDQ40NDVET / FXDQ50NDVET /
FXDQ63NDVET

3D103337

18
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

6. Electric Characteristics

FXDQ20PDVE / FXDQ25PDVE / FXDQ32PDVE / FXDQ40NDVE / FXDQ50NDVE / FXDQ63NDVE


FXDQ20PDVET / FXDQ25PDVET / FXDQ32PDVET / FXDQ40NDVET / FXDQ50NDVET /
FXDQ63NDVET

3D112184

19
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

7. Safety Devices Setting

Model FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE


Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
OFF: 130±5 OFF: 130±5 OFF: 130±5
Fan motor thermal protector °C ON: 83±15 ON: 83±15 ON: 83±15
Drain pump thermal fuse °C 145 145 145

Model FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET


Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
OFF: 130±5 OFF: 130±5 OFF: 130±5
Fan motor thermal protector °C ON: 83±15 ON: 83±15 ON: 83±15
Drain pump thermal fuse °C — — —

Model FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE


Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
OFF: 130±5 OFF: 130±5 OFF: 130±5
Fan motor thermal protector °C ON: 83±15 ON: 83±15 ON: 83±15
Drain pump thermal fuse °C 145 145 145

Model FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET


Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A
OFF: 130±5 OFF: 130±5 OFF: 130±5
Fan motor thermal protector °C ON: 83±15 ON: 83±15 ON: 83±15
Drain pump thermal fuse °C — — —
3D104897

20
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

8. Capacity Tables
8.1 Cooling Capacity for Te: Auto

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXDQ20PDVE 20 1.9 1.8 2.1 1.9 2.2 1.9 2.2 1.9 2.2 1.8 2.3 1.6 2.3 1.7
FXDQ20PDVET
FXDQ25PDVE 25 2.5 2.1 2.6 2.2 2.8 2.3 2.8 2.1 2.8 2.1 2.9 2.0 3.0 1.9
FXDQ25PDVET
FXDQ32PDVE 32 3.2 2.4 3.4 2.6 3.5 2.6 3.6 2.6 3.6 2.4 3.7 2.4 3.8 2.4
FXDQ32PDVET
FXDQ40NDVE 40 4.0 3.0 4.2 3.3 4.4 3.4 4.5 3.3 4.6 3.1 4.7 3.0 4.8 3.1
FXDQ40NDVET
FXDQ50NDVE 50 4.9 3.7 5.3 4.0 5.5 4.2 5.6 4.0 5.7 3.9 5.8 3.8 5.9 3.5
FXDQ50NDVET
FXDQ63NDVE 63 6.3 4.8 6.7 5.1 7.0 5.3 7.1 4.9 7.2 4.6 7.3 4.6 7.5 4.6
FXDQ63NDVET

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.2 Cooling Capacity for Te: 6°C

Indoor air temp.


Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXDQ20PDVE 20 1.5 1.4 1.8 1.6 2.1 1.8 2.2 1.9 2.2 1.8 2.3 1.6 2.3 1.7
FXDQ20PDVET
FXDQ25PDVE 25 1.9 1.6 2.3 1.9 2.6 2.1 2.8 2.1 2.8 2.1 2.9 2.0 3.0 1.9
FXDQ25PDVET
FXDQ32PDVE 32 2.4 1.9 2.9 2.2 3.4 2.4 3.6 2.6 3.6 2.4 3.7 2.4 3.8 2.4
FXDQ32PDVET
FXDQ40NDVE 40 3.0 2.5 3.6 2.8 4.2 3.2 4.5 3.3 4.6 3.1 4.7 3.0 4.8 3.1
FXDQ40NDVET
FXDQ50NDVE 50 3.8 3.1 4.5 3.5 5.2 3.9 5.6 4.0 5.7 3.9 5.8 3.8 5.9 3.5
FXDQ50NDVET
FXDQ63NDVE 63 4.8 3.8 5.7 4.3 6.6 4.8 7.1 4.9 7.2 4.6 7.4 4.6 7.5 4.6
FXDQ63NDVET

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

21
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

8.3 Cooling Capacity for Te: 9°C

For VRV indoor units only at Te: 9°C / mixed combination of VRV and residential indoor units
Indoor air temp.
Capacity 14°CWB 16°CWB 18°CWB 19°CWB 20°CWB 22°CWB 24°CWB
Model indication 20°CDB 23°CDB 26°CDB 27°CDB 28°CDB 30°CDB 32°CDB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
FXDQ20PDVE 20 1.0 1.0 1.2 1.2 1.6 1.5 1.7 1.6 1.8 1.6 1.9 1.4 2.0 1.5
FXDQ20PDVET
FXDQ25PDVE 25 1.3 1.2 1.6 1.6 2.0 1.8 2.2 1.8 2.2 1.8 2.4 1.8 2.6 1.7
FXDQ25PDVET
FXDQ32PDVE 32 1.7 1.5 2.0 1.8 2.6 2.0 2.8 2.2 2.8 2.0 3.0 2.1 3.2 2.1
FXDQ32PDVET
FXDQ40NDVE 40 2.0 2.0 2.5 2.3 3.2 2.7 3.5 2.8 3.7 2.7 3.9 2.6 4.1 2.8
FXDQ40NDVET
FXDQ50NDVE 50 2.6 2.4 3.1 2.9 3.9 3.3 4.4 3.4 4.6 3.3 4.8 3.4 5.1 3.1
FXDQ50NDVET
FXDQ63NDVE 63 3.2 2.9 4.0 3.5 5.1 4.1 5.6 4.2 5.8 4.0 6.2 4.1 6.5 4.1
FXDQ63NDVET

TC: Total capacity: kW


SHC: Sensible heat capacity: kW

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

8.4 Heating Capacity

Indoor air temp.


Capacity
Model 16°CDB 18°CDB 20°CDB 21°CDB 22°CDB 24°CDB
indication
kW kW kW kW kW kW
FXDQ20PDVE 20 2.6 2.6 2.5 2.4 2.3 2.2
FXDQ20PDVET
FXDQ25PDVE 25 3.4 3.4 3.2 3.1 3.0 2.8
FXDQ25PDVET
FXDQ32PDVE 32 4.2 4.2 4.0 3.9 3.7 3.5
FXDQ32PDVET
FXDQ40NDVE 40 5.2 5.2 5.0 4.8 4.7 4.4
FXDQ40NDVET
FXDQ50NDVE 50 6.6 6.6 6.3 6.1 5.9 5.5
FXDQ50NDVET
FXDQ63NDVE 63 8.4 8.4 8.0 7.7 7.5 7.0
FXDQ63NDVET

Notes:
1. These capacity tables are for use when selecting a VRV indoor unit. The actual capacity of the VRV system depends on factors such as the
selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the VRV system
satisfies the required heat load.
2. shows rated condition.

22
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

9. Fan Performances
9.1 FXDQ-PDVE(T)
FXDQ20PDVE / FXDQ25PDVE
FXDQ20PDVET / FXDQ25PDVET

3D052156E

23
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ32PDVE
FXDQ32PDVET

3D052157E

24
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

9.2 FXDQ-NDVE(T)
FXDQ40NDVE
FXDQ40NDVET

3D046299G

25
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ50NDVE
FXDQ50NDVET

3D046300G

26
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ63NDVE
FXDQ63NDVET

3D046301G

27
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

10.Sound Levels
10.1 FXDQ-PDVE(T)
FXDQ20PDVE
FXDQ20PDVET

4D112287
FXDQ25PDVE
FXDQ25PDVET

4D112290

28
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ32PDVE
FXDQ32PDVET

4D112291

29
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

10.2 FXDQ-NDVE(T)
FXDQ40NDVE
FXDQ40NDVET

4D112292
FXDQ50NDVE
FXDQ50NDVET

4D112294

30
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ63NDVE
FXDQ63NDVET

4D112295

31
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

11.Centre of Gravity
11.1 FXDQ-PDVE(T)
FXDQ20PDVE / FXDQ25PDVE / FXDQ32PDVE
FXDQ20PDVET / FXDQ25PDVET / FXDQ32PDVET

Unit: mm

4D049300M

32
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

11.2 FXDQ-NDVE(T)
FXDQ40NDVE / FXDQ50NDVE
FXDQ40NDVET / FXDQ50NDVET

Unit: mm

4D043886R

33
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

FXDQ63NDVE
FXDQ63NDVET

Unit: mm

4D043887Q

34
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

12.Accessories
12.1 Optional Accessories (for Unit)

Model
Item FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE
FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET
Insulation kit for high humidity KDT25N32 KDT25N50 KDT25N63
C: 3D112270A

12.2 Optional Accessories (for Controls)

Model
Item FXDQ20PDVE FXDQ25PDVE FXDQ32PDVE FXDQ40NDVE FXDQ50NDVE FXDQ63NDVE
FXDQ20PDVET FXDQ25PDVET FXDQ32PDVET FXDQ40NDVET FXDQ50NDVET FXDQ63NDVET
Cooling Only BRC4C66 (Note 4)
Remote Wireless
Heat Pump BRC4C65 (Note 4)
controller
Wired BRC1C62 (Note 4)
Navigation remote controller BRC1E62 (Note 4)
(Wired remote controller)
Simplified remote controller BRC2C51
Remote controller for hotel use BRC3A61
Adaptor for wiring  KRP1B56
Wiring adaptor for electrical  KRP2A53
appendices (1)
Wiring adaptor for electrical  KRP4A54
appendices (2)
Remote sensor KRCS01-1B
Installation box for adaptor printed KRP1BA101(Note 2, 3)
circuit board
External control adaptor for outdoor
unit (must be installed on indoor  DTA104A53
units)
C: 3D112270A
Notes:
1. Installation box (KRP1BA101) is necessary for each adaptor marked .
2. Up to 2 installation boxes can be installed for each indoor unit.
3. Installation (KRP1BA101) is necessary for each adaptor.
4. Wireless remote controller does not have AUTO fan mode.
Use wired remote controller to select AUTO fan mode.

35
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

13.Installation Manual

VRV SYSTEM Air Conditioners Installation manual

necessary to take proper measures so that the amount of


CONTENTS any leaked refrigerant does not exceed the concentration
1. SAFETY PRECAUTIONS................................................ 1 limit in the event of a leakage.
2. BEFORE INSTALLATION ................................................ 2 Otherwise, this may lead to an accident due to oxygen
3. SELECTING INSTALLATION SITE ................................. 4 deficiency.
4. PREPARATIONS BEFORE INSTALLATION.................... 4 • Be sure to use only the specified parts and accessories for
5. INDOOR UNIT INSTALLATION ....................................... 5 installation work.
6. REFRIGERANT PIPING WORK ..................................... 6 Failure to use the specified parts may result in the air condi-
7. DRAIN PIPING WORK .................................................... 7 tioner falling down, water leakage, electric shocks, a fire, etc.
• Install the air conditioner on a foundation that can withstand
8. INSTALLING THE DUCT................................................. 9
its mass.
9. ELECTRIC WIRING WORK .......................................... 10
Insufficient strength may result in the air conditioner falling
10. WIRING EXAMPLE ....................................................... 11 down and causing injury.
11. FIELD SETTING AND TEST RUN ................................ 14 In addition, it may lead to vibration of indoor units and cause
12. WEIGHT AND DIMENSION .......................................... 15 unpleasant chattering noise.
The original instructions are written in English. All other • Carry out the specified installation work in consideration of
languages are translations of the original instructions. strong winds, typhoons, or earthquakes. Improper installation
may result in an accident such as air conditioner falling.
• Make certain that all electrical work is carried out by qualified
1. SAFETY PRECAUTIONS personnel according to the applicable legislation (note 1) and
Please read the these “SAFETY CONSIDERATIONS” carefully this installation manual, using a separate circuit.
before installing air conditioning unit and be sure to install it In addition, even if the wiring is short, make sure to use a
correctly. After completing the installation, make sure that the wiring that has sufficient length and never connect additional
unit operates properly during the start-up operation. wiring to make the length sufficient.
Please instruct the customer on how to operate the unit and Insufficient capacity of the power supply circuit or improper
keep it maintained. electrical construction may lead to electric shocks or a fire.
Also, inform customers that they should store this installation (note 1) applicable legislation means “All international,
manual along with the operation manual for future reference. national and local directives, laws, regulations and/
This product comes under the term “appliances not accessible or codes which are relevant and applicable for a
to the general public”. certain product or domain”.
This is a class A product. In a domestic environment this
• Make sure that all wiring is secure, using the specified wiring
product may cause radio interference in which case the user
and ensuring that external forces do not act on the terminal
may be required to take adequate measures.
connections or wiring.
This manual classifies the precautions into WARNINGS and Incomplete connection or fixing may cause an overheat or a
CAUTIONS. fire.
Be sure to follow all the precautions below: They are all • When wiring the remote controller wiring and transmission
important for ensuring safety. wiring, and wiring the power supply, form the wiring orderly
so that the control box cover can be securely fastened.
WARNING ............. Indicates a potentially hazardous If the control box cover is not in place, overheat of the
situation which, if not avoided, could terminals, electric shocks or a fire may be caused.
result in death or serious injury. • If refrigerant gas leaks during installation work, ventilate the
CAUTION .............. Indicates a potentially hazardous area immediately.
situation which, if not avoided, may Toxic gas may be produced if refrigerant gas comes into
result in minor or moderate injury. contact with a fire.
It may also be used to alert against • After completing the installation work, check to make sure
unsafe practices. that there is no leakage of refrigerant gas.
• After the installation is completed, test the air conditioner and Toxic gas may be produced if refrigerant gas leaks into the
check if the air conditioner operates properly. Give the user room and comes into contact with a source of a fire, such as
adequate instructions concerning the use and cleaning of the a fan heater, stove or cooker.
indoor unit according to the Operation Manual. Ask the user • Disconnect the power supply before touching the electric
to keep this manual and the Operation Manual together in a components.
handy place for future reference. If you touch the live part, you may get an electric shocks.
• Never directly touch any accidental leaking refrigerant. This
WARNING could result in severe wounds caused by frostbite.
• Ask your local dealer or qualified personnel to carry out • Earth the air conditioner.
installation work. Do not connect the earth wiring to gas or water piping,
Improper installation may result in water leakage, electric lightning conductor or telephone earth wiring.
shocks or a fire. Incomplete earthing may cause electric shocks or a fire.
• Perform installation work in accordance with this installation A high surge current from lightning or other sources may
manual. cause damage to the air conditioner.
Improper installation may result in water leakage, electric • Be sure to install an earth leakage circuit breaker.
shocks or a fire. Failure to do so may cause electric shocks and a fire.
• Consult your local dealer regarding what to do in case of • Do not allow children to climb on the outdoor unit and avoid
refrigerant leakage. placing objects on the unit.
When the air conditioner is installed in a small room, it is Injury may result if the unit becomes loose and falls.

English 1

3P432203-7B

36
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

(If the system is charged with refrigerant in its gaseous state,


CAUTION
due to composition change, the system will not function
• Install drain piping according to this installation manual to normally). The indoor unit is designed for R410A use.
ensure good drainage, and insulate the piping to prevent See the catalogue for indoor unit models that can be
condensation. connected. (Normal operation is not possible when
Improper drain piping may cause water leakage, make the connecting units that are originally designed for other
furniture get wet. refrigerants.)
• Install the air conditioner, power supply wiring, remote • Do not touch the heat exchanger fins.
controller wiring and transmission wiring at least 1 meter Improper handling may result in injury.
away from televisions or radios to prevent image interference • Be very careful about product transportation.
or noise. Some products use PP bands for packaging. Do not use any
(Depending on the radio waves, a distance of 1 meter may PP bands for a means of transportation. It is dangerous.
not be sufficient to eliminate the noise.) • Safely dispose of the packing materials.
• Install the indoor unit as far as possible from fluorescent Packing materials, such as nails and other metal or wooden
lamps. parts, may cause stabs or other injuries.
If a wireless remote controller kit is installed, the transmission Tear apart and throw away plastic packaging bags so that
distance may be shorter in a room where an electronic children will not play with them. If children play with a plastic
lighting type (inverter or rapid start type) fluorescent lamp is bag which was not torn apart, they face the risk of suffocation.
installed. • Do not turn off the power immediately after stopping operation.
• Do not install the air conditioner in places such as the Always wait at least 5 minutes before turning off the power.
following: Otherwise, water leakage and trouble may occur.
1. Where there is mist of oil, oil spray or vapour for • In a domestic environment this product may cause radio
example a kitchen. interference in which case the user may be required to take
Resin parts may deteriorate, and cause them to fall out adequate measures.
or water to leak.
2. Where corrosive gas, such as sulfurous acid gas, is
Follow national standards for installation work.
produced.
Corrosion of copper pipings or brazed parts may cause
the refrigerant to leak.
3. Where there is machinery which emits electromagnetic
2. BEFORE INSTALLATION
waves. The accessories needed for installation must be retained in
Electromagnetic waves may disturb the control system, your custody until the installation work is completed. Do
and cause malfunction of the equipment. not discard them!
4. Where flammable gases may leak, where carbon fibre 1. Decide upon a line of transport.
or ignitable dust is suspended in the air or where volatile
flammables, such as thinner or gasoline, are handled. 2. Leave the unit inside its packaging while moving, until
If the gas should leak and remained around the air reaching the installation site. Where unpacking is
conditioner, it may cause ignition. unavoidable, use a sling of soft material or protective plates
• Make sure to provide for adequate measures in order to together with a rope when lifting, to avoid damage or
prevent that the outdoor unit be used as a shelter by small scratches to the unit.
animals. When moving the unit at or after opening, hold the unit by
• Small animals making contact with electrical parts can cause the hanger brackets. Do not apply force to the refrigerant
malfunctions, smoke or fire. Please instruct the customer to piping, drain piping or flange parts.
keep the area around the unit clean. Be sure to check the type of R410A refrigerant to be used
• Install in a machine room that is free of moisture. The unit is before installing the unit.
designed for indoor use. (Using an incorrect refrigerant will prevent normal
• Disposal requirements operation of the unit.)
Dismantling of the unit, treatment of the refrigerant, of oil
and of other parts must be done in accordance with relevant For the installation of an outdoor unit, refer to the installation
local and national legislation. manual attached to the outdoor unit.

SPECIAL NOTICE PRODUCT 2-1 PRECAUTIONS


• [Refrigerant] • Be sure to instruct customers how to properly operate the
• The refrigerant R410A requires that strict precautions be unit (operating different functions, and adjusting the
observed for keeping the system clean, dry and tightly sealed. temperature) by having them carry out operations themselves
A. Clean and dry while looking at the operation manual.
Strict measures must be taken to keep impurities • Do not install in locations where the air contains high levels of
(including SUNISO oil and other mineral oils as well as salt such as that near the ocean and where voltage fluctuates
moisture) out of the system. greatly such as that in factories, or in vehicles or vessels.
B. Tightly sealed
R410A contains no chlorine, does not destroy the ozone
layer and so does not reduce the earth's protection
against harmful ultraviolet radiation. R410A will contribute
only slightly to the greenhouse effect if released into the
atmosphere.
• Since design pressure is 4.0 MPa or 40 bar (for R407C
units: 3.3 MPa or 33 bar), the thickness of pipes must be
greater than previously. Since R410A is a mixed refrigerant,
the required additional refrigerant must be charged in its
liquid state.

2 English

3P432203-7B

37
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

2-2 ACCESSORIES FOR THE FOLLOWING ITEMS, TAKE SPECIAL


Check the following accessories are included with your unit. CARE DURING CONSTRUCTION AND CHECK
AFTER INSTALLATION IS FINISHED.
Metal Drain Insulation Sealing pad
Name
clamp (1) hose (2) for fitting
a. Items to be checked after completion of work
Quantity 1 pc. 1 pc. 1 each 1 each
If not properly done, what is
Items to be checked Check
likely to occur

Large (5) Are the indoor and outdoor The units may drop, vibrate
Shape for liquid pipe (3)
unit fixed firmly? or make noise.
It may result in insufficient
Is the gas leak test finished?
for gas pipe (4) mid. (6) cooling.
Is the unit fully insulated? Condensate may drip.
Does drainage flow
Screws for Washer for Washer Condensate may drip.
Name duct flanges hanging Clamp fixing plate smoothly?
(7) bracket (8) (11) Does the power supply
The unit may malfunction or
Quantity 1 set 8 pcs. 1 set 4 pcs. voltage correspond to that
the components burn out.
shown on the name plate?
Are wiring and piping The unit may malfunction or
correct? the components burn out.
Large (9)
8 pcs. Imcomplete grounding may
Shape Is the unit safely grounded?
result in electric shocks.
26 pcs. Is wiring size according to The unit may malfunction or
small (10) specifications? the components burn out.
4 pcs.
Is something blocking the air
It may result in insufficient
outlet or inlet of either the
cooling.
indoor or outdoor units?
Sealing
Name Air filter (13) Are refrigerant piping length
material (12) The refrigerant charge in the
(Other) and additional refrigerant
Quantity 2 pcs. 1 pc. system is not clear.
• Operation manual charge noted down?
• Installation manual
(this manual) Also review the “SAFETY PRECAUTIONS”.
Shape
b. Items to be checked at time of delivery
Items to be checked Check
Did you explain about operations while showing the
operation manual to your customer?
2-3 OPTIONAL ACCESSORIES
Did you hand the operation manual and warranty over to
• These are two types of remote controllers: wired and your customer?
wireless. Select a remote controller according to customer
Did you explain about the way of maintaining and cleaning
request and install in an appropriate place.
local procurements (air filter, grille (both air outlet and
suction grille), etc.) to your customer?
Table 1
Remote controller Did you hand manuals of local procurements (in case
equipped) over to your customer?
Wired type
Heat pump type c. Points for explanation about operations
Wireless type
Cooling only type
The items with WARNING and CAUTION marks in
the operation manual are the items pertaining to
NOTE
possibilities for bodily injury and material damage in
• If you wish to use a remote controller that is not listed in addition to the general usage of the product. Accordingly, it
Table 1, select a suitable remote controller after consulting is necessary that you make a full explanation about the
catalogs and technical materials. described contents and also ask your customers to read the
operation manual.

English 3

3P432203-7B

38
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

3. SELECTING INSTALLATION SITE (2) Use suspension bolts for installation. Check whether
the ceiling is strong enough to support the weight of
CAUTION the unit or not. If there is a risk, reinforce the ceiling
• When moving the unit during or after unpacking, make sure before installing the unit.
to lift it by holding its lifting lugs. Do not exert any pressure on (Installation pitch is marked on the carton box for installation.
other parts, especially the refrigerant piping, drain piping and Refer to it to check for points requiring reinforcing.)
flange parts.
• If you think the humidity inside the ceiling might exceed 4. PREPARATIONS BEFORE INSTALLATION
30°C and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that (1) Confirm the positional relationship between the unit
it is no thicker than 10 mm and fits inside the ceiling and suspension bolts. (Refer to Fig. 2)
opening. • Install the inspection opening on the control box side where
maintenance and inspection of the control box and drain
(1) Select an installation site where the following conditions pump are easy. Install the inspection opening also in the
are fulfilled and that meets with your customer’s approval. lower part of the unit.
• Where optimum air distribution can be ensured. 620
• Where nothing blocks air passage. 500
• Where condensate can be properly drained.
• Where the ceiling is strong enough to bear the indoor unit Suspension (length : mm)
bolt pitch
weight.
• Where the false ceiling is not noticeably on an incline.

(Suspension bolt pitch )


• Where there is no risk of flammable gas leakage.
• Where sufficient clearance for maintenance and service
Air outlet Air inlet
can be ensured. (Refer to Fig. 1)
• Where piping between indoor and outdoor units is

B
A
possible within the allowable limit. (Refer to the installation
Drain pump Control box
manual for the outdoor unit.)

450×450
(Inspection
*300
300 opening size)
or
more Control box or more
Maintenance Maintenance
space space
2500 or more 240 or more

Ceiling
200

*H1=

〈SERVICE SPACE〉
*H2=20 or more 620

Ceiling

Fig. 1 Floor surface


(length : mm)
A

• *H1 dimension means the minimum height of the unit.


• Select the *H1, *H2 dimension such that a downward
slope of at least 1/100 is ensured as indicated in
“7. DRAIN PIPING WORK”.
• The maintenance space marked with “ * ” is required when Allow view
the installation box for adaptor PC board (KRP1BA101) Inspection door
(Ceiling opening) Fig. 2
sold separately is used.
(length: mm)
[ PRECAUTION ]
• Install the indoor and outdoor units, power supply wiring Model A B
and connecting wires at least 1 m away from televisions or 20 · 25 · 32 type 700 740
radios in order to prevent image interference or noise. 40 · 50 type 900 940
(Depending on the radio waves, a distance of 1 m may not 63 type 1100 1140
be sufficient enough to eliminate the noise.)
• If installing the wireless kit in a room with electronic (2) Make sure the range of the unit’s external static
fluorescent lighting (inverter or rapid start type), the pressure is not exceeded.
remote controller’s transmission distance may be (See the technical documentation for the range of the
shortened. Indoor units should be installed as far away external static pressure setting.)
from fluorescent lighting as possible.

4 English

3P432203-7B

39
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

(3) Open the installation hole. (Pre-set ceilings) (3)


• Once the installation hole is opened in the ceiling where Main unit
the unit is to be installed, pass refrigerant piping, drain
piping, transmission wiring, and remote controller wiring Force
Attach the filter to the
(It is not necessary if using a wireless remote controller) main unit while pushing
to the unit’s piping and wiring holes. down on the bends.
See “6. REFRIGERANT PIPING WORK”, “7. DRAIN Filter
PIPING WORK”, and “10. WIRING EXAMPLE”. Force
• After opening the ceiling hole, make sure ceiling is level if
needed. It might be necessary to reinforce the ceiling
frame to prevent shaking.
Consult an architect or carpenter for details.
(4) Install the suspension bolts.
(Use W3/8 to M10 suspension bolts.)
Use a hole-in-anchor for existing ceilings, and a sunken
insert, sunken anchor or other part to be procured in the
field to reinforce the ceiling to bearing the weight of the unit
for new ceiling. (Refer to Fig. 3)
In case of bottom side In case of back side
Ceiling slab
Anchor bolt
Long nut or turn-buckle 5. INDOOR UNIT INSTALLATION
Suspension bolt
〈〈As for the parts to be used for installation work, be sure to
use the provided accessories and specified parts
Indoor unit
designated by our company.〉〉
Note: All the above parts are field supplied. (1) Install the indoor unit temporarily.
Fig. 3
• Attach the hanger bracket to the suspension bolt. Be sure
to fix it securely by using a nut and washer from the upper
(5) For bottom intake, replace the chamber lid and and lower sides of the hanger bracket. (Refer to Fig. 5)
protection net in the procedure listed in Fig. 4.
[ Securing the hanger bracket ] [ How to secure washers ]
(1) Remove the protection net.
(6 locations)···PDVE(T) type only Part to be procured
Remove the chamber lid. (7 locations) in the field
(2) Reattached the removed chamber lid in the orientation Washer for
shown in Fig. 4. (7 locations) hanging bracket (8)
Reattached the removed protection net in the
orientation shown in Fig. 4. (accessory)
(6 locations)···PDVE(T) type only Hanger
(3) Attach the air filter (accessory) in the manner shown in bracket Insert below washer
the diagram. Tighten
The four holes which cannot be covered by the air filter (double nut) Washer fixing plate (11)
should be covered with commercially available tape.
Fig. 5 (accessory)
Protection net
(1)
[ PRECAUTION ]
Air inlet Since the unit uses a plastic drain pan, prevent welding
spatter and other foreign substances from the air outlet
during installation.

(2) Adjust the height of the unit.

(3) Check the unit is horizontally level.


Chamber lid
CAUTION
Air discharge • Make sure the unit is installed level using a level or a
plastic tube filled with water. In using a plastic tube
instead of a level, adjust the top surface of the unit to the
surface of the water at both ends of the plastic tube and
adjust the unit horizontally. (One thing to watch out for in
(2) particular is if the unit is installed so that the slope is not
in the direction of the drain piping, this might cause
leaking.)

Chamber lid
Protection net

Air discharge
Air inlet
Fig. 4

English 5

3P432203-7B

40
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

• Refer to Table 1 for tightening torque.


Table 1
Pipe Tightening torque Flare dimen-
Flare shape
size (N·m) sion A (mm)
φ 6.4
15.7±1.5 8.9±0.2
(1/4”)
Level φ 9.5

0
36.3±3.6 13.0±0.2 R0.4-0.8

45 2
Vinyl tube (3/8”)

0
2
0
0
90
φ 12.7

A
(4) Tighten the upper nut. (1/2”)
54.9±5.4 16.4±0.2

φ 15.9
68.6±6.8 19.5±0.2
(5/8”)
6. REFRIGERANT PIPING WORK
• For the outdoor unit refrigerant piping, refer to the installation CAUTION
manual attached to the outdoor unit. Overtightening may damage the flare and cause leaks.
• Carry out insulation of both gas and liquid refrigerant piping Be careful for oil not to adhere to any portions other
than a flare part. If oil adhere to resin parts etc., there is
securely. If not insulated, it may cause water leakage. For a possibility of damaging by deterioration.
gas piping, use insulation material of which heat resistant
temperature is not less than 120°C.
• Refer to Table 2 if no torque wrench is available.
For use under high humidity, strengthen the insulation
Using a wrench to tighten flare nuts causes the tightening
material for refrigerant piping. If not strengthened, the
torque to suddenly grow much tighter after a certain point.
surface of insulation material may sweat.
From there, tighten the nut further by the appropriate angle
• Before installation work, make sure that the refrigerant is
listed in Table 2.
R410A. (Unless the refrigerant is R410A, the normal
operation cannot be expected.) (1) After the work is finished, make sure to check that
CAUTION there is no gas leak.
This air conditioner is a dedicated model for new refrigerant (2) After checking for gas leaks, be sure to insulate the
R410A. Make sure to meet the requirements shown below pipe connections referring to Fig. 8.
and carry out installation work. • Insulate using the insulation for fitting (3) (4) included with
• Use dedicated piping cutters and flaring tools for R410A. the liquid and gas pipes. Besides, make sure the
• When making a flare connection, coat the flared inner insulation for fitting (3) (4) on the liquid and gas piping
surface only with ether oil or ester oil. has its seams facing up.
• Use only the flare nuts attached to the air conditioner. If (Tighten both edges with clamp (9).)
other flare nuts are used, it may cause refrigerant • For the gas piping, wrap the mid. sealing pad (6) over the
leakage. insulation for fitting (4) (flare nut part).
• To prevent contamination or moisture from getting into
the piping, take measures such as pinching or taping the Liquid Piping Insulation Procedure
pipings.
Insulation for fitting (3)
Do not mix substance other than the specified refrigerant Piping insulation material (accessory)
such as air into the refrigeration circuit. (main unit)
If the refrigerant leaks during the work, ventilate the room. Flare nut connection
Attach to base Turn seams up
• The refrigerant is pre-charged in the outdoor unit. Main unit
• When connecting the pipings to the air conditioner, make Clamp (9) (accessory) Piping insulation material
sure to use a spanner and a torque wrench as shown in (Field supply)
Fig. 6.
• For the dimension of flared part and the tightening torque,
refer to the Table 1. Liquid pipe
• When making a flare connection, coat the flared inner
surface only with ether oil or ester oil.
(Refer to Fig. 7)
Gas pipe
Then, turn the flare nut 3 to 4 times with your hand and screw
in the nut. Gas Piping Insulation Procedure

Piping insulation Insulation for fitting (4)


Torque wrench Coat the flared inner
surface only with ether material (main unit) (accessory)
Mid. sealing pad (6)
oil or ester oil. Flare nut connection
Attach to base (accessory)
Turn seams up
Spanner Main unit
Flare nut Clamp (9)
Piping insulation material Wrap over the top of
Piping union (accessory)
(Field supply) the flare nut connection.

Fig. 6 Fig. 7 Fig. 8

6 English

3P432203-7B

41
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

CAUTION 7. DRAIN PIPING WORK


Be sure to insulate any field piping all the way to the piping
connection inside the unit. Any exposed piping may cause In case of PDVE, NDVE type (with drain pump)
condensation or burns if touched.
• When brazing the refrigerant piping, perform nitrogen CAUTION
replacement first, or perform the brazing (CAUTION 2) while • The connection opening on the drain piping may vary
feeding nitrogen into the refrigerant piping (CAUTION 1), and depending on the model, so check the model name and use
finally connect the indoor unit using the flare connections. the right method for that model.
(Refer to Fig. 9) • Make sure all water is out before making the duct connection.

CAUTION (1) Install the drain piping.


1. When brazing a pipe while feeding nitrogen inside the
pipe, make sure to set the nitrogen pressure to 0.02 MPa Drain socket
2
(0.2 kg/cm ) using the pressure reducing valve. (This
pressure is such that breeze is blown to your cheek.)
2. Do not use a flux when brazing the refrigerant pipe joints.
Use phosphor copper brazer (BCuP-2: JIS Z 3264/B-
Cu93P-710/795: ISO 3677) which does not require flux.
(Using a flux containing chlorine may cause the piping to
Refrigerant pipes
corrode. Using a welding flux containing fluorine may
cause the refrigerant lubricant to deteriorate, and affect Service drain hole
adversely the refrigerant piping system.) (with rubber cap)

Pressure-reducing valve • Make sure the drain works properly.


• The diameter of the drain piping should be greater than or
Part to be brazed Taping equal to the diameter of the connecting pipe (vinyl tube; pipe
size: 20 mm; outer dimension: 26 mm).
Nitrogen (not including the riser)
hands
valve • Keep the drain piping short and sloping downwards at a
Refrigerant piping Nitrogen
gradient of at least 1/100 to prevent air pockets from forming.
Fig. 9
(Refer to Fig. 10)

Not recommendable but in case of emergency


You must use a torque wrench but if you are obliged to install the
unit without a torque wrench, you may follow the installation
method mentioned below.
After the work is finished, make sure to check that there is Central drain piping
(with a slope of at least 1/100)
no gas leak.
When you keep on tightening the flare nut with a spanner, there
600mm
or less

is a point where the tightening torque suddenly increases. From


that position, further tighten the flare nut the angle shown below:
Table 2
Recommended arm
Pipe size Further tightening angle Fig. 10
length of tool
φ 6.4 (1/4”) 60 to 90 degrees Approx. 150 mm
CAUTION
φ 9.5 (3/8”) 60 to 90 degrees Approx. 200 mm
Water accumulating in the drain piping can cause the
φ 12.7 (1/2”) 30 to 60 degrees Approx. 250 mm
drain to clog.
φ 15.9 (5/8”) 30 to 60 degrees Approx. 300 mm
• To keep the drain piping from sagging, space hanging
bracket every 1 to 1.5 m.
• Use the drain hose (2) and the metal clamp (1). Insert the
drain hose (2) fully into the drain socket and firmly tighten the
metal clamp (1) with the upper part of the tape on the hose
end. Tighten the metal clamp (1) until the screw head is less
than 4 mm from the hose. (Refer to Fig. 11, 12)
• The two areas below should be insulated because
condensation may form there causing water to leak.
• Drain piping passing indoors
• Drain socket
Referring the figure below, insulate the metal clamp (1) and
drain hose (2) using the included large sealing pad (5).
(Refer to Fig. 12)

English 7

3P432203-7B

42
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

Large sealing 1. Remove the control box lid. Connect the remote controller
Metal clamp (1) pad (5) and power supply (single-phase, 50 Hz 220-240 V or
(accessory) (accessory) single-phase, 60Hz 220V) respectively to the terminal block
Metal clamp (1) and securely connect the earth also (as shown in the figure
(accessory) below).
Tape Drain hose (2) ≤4 mm CAUTION
(accessory)
Securely clamp the cables with the clamps (9)(10) offered
Fig. 11 Fig. 12 as accessories as shown in Fig. 17 so that tension will not
be applied on the cable connection areas.
〈 PRECAUTIONS FOR DRAIN RAISING PIPE 〉
• Make sure the drain raising pipe height is no higher than 2. Confirm that the control box lid is closed before turning on
600 mm. the power.
• Place the drain raising pipe vertically and make sure it is no 3. Remove the inspection lid.
further than 300 mm from the unit. (Refer to Fig. 13) 4. Gradually pour approximately 1L of water from the
inspection window into the drain pan to check drainage.
Ceiling slab CAUTION
300 mm or less 1 – 1.5m Hanging bracket Be sure to prevent an external force from being exerted on
the float switch.
(This may cause breakage.)
5. Attach the inspection lid.
Adjustable range 6. Perform the following operation using the remote controller,
(600mm or less) and check drainage.
Metal clamp (1) (accessory)
• Select the inspection/test operation button “ TEST ” using
Drain raising pipe the remote controller. The unit will engage the test
Drain hose (2) (accessory)
(Field supply) operation. Press the operation selector button “ ”, and
select FAN OPERATION “ ”.
Drain hose (2) (accessory) • Press the ON/OFF button “ ”. (The indoor fan and
drain pump will operate.)
Horizontal or CAUTION
upward slope
The fan will turn also at the same time. Take due care.
Do not touch the drain pump to prevent electric shock.
Locate the drain hose horizontally
or with a little upward gradient. Drain outlet Inspection window
If there is an air bank, noise may be generated Portable pump
as a result of a water backflow when the drain
Inspection lid
pump comes to a stop.
Refrigerant pipes
Fig. 13 Bucket
Service drain hole L N

(with rubber cap)


〈 PRECAUTIONS 〉
Drain piping connections Indoor PC board L N
(ASSY) Power supply:
• Do not connect the drain piping directly to sewage pipes that Single phase,
smell of ammonia. The ammonia in the sewage might enter P1 P2 F1 F2 T1 T2
P1 P2 F1 F2 T1 T2
50 Hz, 220 V~
240V
REMOTE TRANSMISSION FORCED REMOTE TRANSMISSION FORCED

the indoor unit through the drain piping and corrode the heat
CNTRL WIRING OFF
CNTRL WIRING OFF
L N

Single phase,
exchanger. 60Hz, 220 V
• Do not twist or bend the drain hose (2), so that excessive Power terminal
force is not applied to it. Remote controller connection
terminal connection method
(This type of treatment may cause leaking.) method Terminal block Terminal block
• If you are using central drain piping, follow the procedure
outlined in the figure 10. 7. Make sure to use the remote controller in finishing the
• Select central drain piping of proper size according to the operation.
capacity of the connected unit.
(2) After piping work is finished, check drainage flows
smoothly, with manner described below. In case of PDVET, NDVET type (without drain pump)

CAUTION CAUTION
• The electric wiring work shall be performed by qualified • The connection opening on the drain piping may vary
electricians. depending on the model, so check the model name and use
• If workers not having the electrician qualification have the right method for that model.
performed the electric wiring work, the steps 3 to 7 shall be • Make sure all water is out before making the duct connection.
performed after the TEST RUN.

8 English

3P432203-7B

43
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

(1) Install the drain piping. 〈 PRECAUTIONS 〉


Drain piping connections
Drain socket • Do not connect the drain piping directly to sewage pipes that
smell of ammonia. The ammonia in the sewage might enter
the indoor unit through the drain piping and corrode the heat
exchanger.
• Do not twist or bend the drain hose (2), so that excessive
force is not applied to it.
Refrigerant pipes (This type of treatment may cause leaking.)
• If you are using central drain piping, follow the procedure
Connect the drain pipe after removing the rubber cap and outlined in the figure 14.
insulation tubing attached to the connection hole.
• Select central drain piping of proper size according to the
• Make sure the drain works properly. capacity of the connected unit.
• The diameter of the drain piping should be greater than or (2) After piping work is finished, check drainage flows
equal to the diameter of the connecting pipe (vinyl tube; pipe smoothly, with manner described below.
size: 20 mm; outer dimension: 26 mm).
Air outlet
(not including the riser)
• Keep the drain piping short and sloping downwards at a Portable pump
gradient of at least 1/100 to prevent air pockets from forming.
(Refer to Fig. 14) Refrigerant
Bucket pipes
Drain outlet

• Gradually pour approximately 1L of water from the outlet hole


into the drain pan to check drainage.
• Check the drainage.

8. INSTALLING THE DUCT


or more
100mm

Connect the duct supplied in the field.


Air inlet side
Central drain piping • Attach the duct and intake-side flange (field supply).
Fig. 14 (with a slope of at least 1/100) • Connect the flange to the main unit with accessory screws
(7).
CAUTION Class 20 · 25 · 32 40 · 50 63
Water accumulating in the drain piping can cause the Number of
16 22 26
drain to clog. positions
• Wrap the intake-side flange and duct connection area with
• To keep the drain piping from sagging, space hanging aluminum tape or something similar to prevent air escaping.
bracket every 1 to 1.5 m.
• Use the drain hose (2) and the metal clamp (1). Insert the CAUTION
drain hose (2) fully into the drain socket and firmly tighten the When attaching a duct to the intake side, be sure to attach an air
metal clamp (1) with the upper part of the tape on the hose filter inside the air passage on the intake side. (Use an air filter
end. Tighten the metal clamp (1) until the screw head is less whose dust collecting efficiency is at least 50% in a gravimetric
than 4 mm from the hose. (Refer to Fig. 15, 16) technique.)
• The two areas below should be insulated because The included filter is not used when the intake duct is attached.
condensation may form there causing water to leak.
• Drain piping passing indoors
Flange
• Drain socket (Field supply)
Referring the figure below, insulate the metal clamp (1) and Insulation
drain hose (2) using the included large sealing pad (5). Connection screw (7) Flange material
Main unit
(Field supply)
(Refer to Fig. 16) (accessory)

Large sealing Aluminum tape


Metal clamp (1) pad (5) (Field supply)
(accessory) (accessory)
Metal clamp (1) Aluminum tape
(accessory) (Field supply)
Tape Drain hose (2) Air inlet side Air outlet side
≤4mm
(accessory)
Air outlet side
Fig. 15 Fig. 16
• Connect the duct according to the air inside of the outlet-side
flange.
• Wrap the outlet-side flange and the duct connection area
with aluminum tape or something similar to prevent air
escaping.

English 9

3P432203-7B

44
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

9-2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES


CAUTION
AND WIRE
• Be sure to insulate the duct to prevent condensation from
forming. (Material: glass wool or polyethylene foam, 25 mm Power-related
thick) Power supply wiring (including earth wire)
• Use electric insulation between the duct and the wall when Field
Model Number
using metal ducts to pass metal laths of the net or fence fuses Wire Size
of units
shape or metal plating into wooden buildings.
• Be sure to explain about the way of maintaining and cleaning 20 · 25 · 32 type
local procurements (air filter, grille (both air outlet and suction
40 · 50 type H05VV-U3G 2.5 mm2
grille), etc.) to your customer. 1 16A
(NOTE 1) (NOTE 3)
63 type

9. ELECTRIC WIRING WORK Transmission wiring


Model Remote controller wiring
9-1 GENERAL INSTRUCTIONS Wire Size (mm2)
• Shut off the power before doing any work.
20 · 25 · 32 type
• All field supplied parts and materials, electric works must Sheathed vinyl cord
conform to local codes. 40 · 50 type 0.75 - 1.25
or cable (2 wires) (NOTE 2)
• Use copper wire only. 63 type
• See also the “Wiring Diagram plate” attached to the control
box lid when laying electrical wiring. NOTES
• For details on hooking up the remote controller, refer to the 1. Shows only in case of protected pipes. Use H07RN-F in
“REMOTE CONTROLLER INSTALLATION MANUAL”. case of no protection. (Do not lighter than 60245 IEC 57.)
• All wiring must be performed by an authorized electrician. 2. Insulated thickness : 1mm or more.
• This system consists of multiple indoor units. Mark each 3. This size is based on IEC 60335-1 (Table 11), and this size
must comply with local codes.
indoor unit as unit A, unit B . . . , and be sure the terminal board
4. If the wiring is in a place where people it can be easily
wiring to the outdoor unit and BS unit are properly matched. If
touched by people, install an earth leakage breaker to
wiring and piping between the outdoor unit and an indoor unit
prevent electric shock.
are mismatched, the system may cause a malfunction.
5. When using an earth leakage breaker, make sure to select
• A circuit breaker capable of shutting down power supply to
one useful also to protection against overcurrent and short-
the entire system must be installed.
circuit.
• Refer to the installation manual attached to the outdoor unit
When using an earth leakage breaker only for earth device,
for the size of power supply wiring connected to the outdoor
make sure to use a wiring interrupter together.
unit, the capacity of the circuit breaker and switch, and wiring
instructions. • The length of the transmission wiring and remote controller
• Be sure to ground the air conditioner. wiring are as follows.
• Do not the earth wire should come in contact with gas pipes, Length of the transmission wiring and remote controller wiring
water pipes, lightning rods, or telephone earth wires. Max. 1000 m
• Gas pipes: gas leaks can cause explosions and fire. Outdoor unit – Indoor unit
(Total wiring length: 2000 m)
• Water pipes: they cannot be grounded if hard vinyl pipes Indoor unit – Remote controller Max. 500 m
are used.
• Telephone earth wire and lightning rods: the ground 9-3 ELECTRICAL CHARACTERISTICS
potential when struck by lightning gets extremely high.
Units Power supply Fan motor
• To avoid short circuiting the power supply wire, be sure to use
insulated terminals. Model Voltage
Hz Volts MCA MFA KW FLA
range
• Do not turn on the power supply (circuit breaker or earth
leakage breaker) until all other work is done. 20 · 25 · 32 PDVE 0.8 0.062 0.6
20 · 25 · 32 PDVET Min. 0.7 0.062 0.6
220- 198
40 NDVE(T) 50 1.0 16 0.062 0.8
240 Max.
50 NDVE(T) 264 1.0 0.13 0.8
63 NDVE(T) 1.1 0.13 0.9
20 · 25 · 32 PDVE 0.9 0.062 0.7
20 · 25 · 32 PDVET Min. 0.8 0.062 0.7
198
40 NDVE(T) 60 220 1.1 16 0.062 0.9
Max.
50 NDVE(T) 242 1.3 0.13 1.0
63 NDVE(T) 1.4 0.13 1.1
MCA: Minimum Circuit Amps (A) MFA:Max. Fuse Amps (A)
KW: Fan motor output (kW) FLA:Full Load Amps (A)

10 English

3P432203-7B

45
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

10. WIRING EXAMPLE [ PRECAUTIONS ]


• Refer to the “REMOTE CONTROLLER INSTALLATION
10-1 HOW TO CONNECT WIRINGS MANUAL” on how to install and lay the wiring for the remote
• Wire only after removing the control box lid as shown in controller.
Fig. 17. • See also the “Wiring Diagram plate” attached to the control
box lid when laying electrical wiring.
Control box lid
• Connect the remote controller and transmission wiring their
Power supply wiring respective terminal blocks.
Earth wire
CAUTION
• Do not, under any circumstances, connect the power sup-
ply wiring to the remote controller or transmission wiring
terminal block. Doing so can destroy the entire system.
Wiring Diagram
(Rear) [ Connecting electrical wiring, remote controller wiring,
and transmission wiring ] (Refer to Fig. 18)

Terminal block (3P)

∗Transmission wiring Power supply wiring Indoor PC board (ASSY) Power supply wiring
∗Remote controller wiring Earth wire Earth wire
∗ Do not connect power
supply wiring here. Clamp (for fixing in place) P1P2 F1F2T1 T2
Wiring through hole
REMOTE TRANSMISSION FORCED

That may cause


CONTRL WIRING OFF

Match up the wiring sheath with L N

malfunctions. the fixing clasp with the clamping


material for preventing slippage on
the power supply side and clamp
(accessory (9)). Terminal block (6P)
Wiring through hole
Clamp Remote controller wiring
Clamp Transmission wiring
Clamp
Remove the clasp with screwdriver.
Let a wire go through the clasp, P1 P2 F1 F2 T1 T2
and be sure to attach the clasp to REMOTE
CONTRL
TRANSMISSION
WIRING
FORCED
OFF

the control box.


Clamp (for prevent slippage)
Clamp the wiring sheaths (accessory (10))

• Make sure to let a wire go through a wire penetration area.


• After wiring, seal the wire and wire penetration area to prevent
moisture and small creatures from the outside.
• Wrap the strong and weak electric lines with the sealing Fig. 18
material (12) as shown in the figure below.
(Otherwise, moisture or small creatures such as insects from
the outside may cause short-circuit inside the control box.) • Power supply and Earth wiring
Attach securely so that there are no gaps. Remove the control box lid.
Sealing Next, pull the wires into the unit through the wiring through
material (12) hole and connect to the terminal block (3P).
Penetration area
(accsessory) Be sure to put the part of the sheathed vinyl into the control
box.
• Remote controller and transmission wiring
Pull the wires into the unit through the wiring through hole
Wire
Outside Inside
and connect to the terminal block (6P).
unit unit Be sure to put the part of the sheathed vinyl into the control
[How to adhere it] box.
Fig. 17

CAUTION
• When clamping the wiring, use the included clamp material
(9) and (10) as shown in the Fig.17 to prevent outside pres-
sure being exerted on the wiring connections and clamp
firmly.
• Be sure to attach power supply wiring and earth wire to the
control box with the clamp.
• When doing the wiring, make sure the wiring is neat and
does not cause the control box lid to stick up, then close the
cover firmly. When attaching the control box lid, make sure
you do not pinch any wires.
• Outside the air conditioners, separate the weak wiring (remote
controller and transmission wiring) and strong wiring (earth
wire and power supply wiring) at least 50 mm so that they do
not pass through the same place together. Proximity may
cause electrical interference, malfunctions, and breakage.

English 11

3P432203-7B

46
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

[ WIRING EXAMPLE ]
CAUTION FOR WIRING
• For connection to the terminal block, use ring type crimp style No. 1 system When using 1 remote controller for
terminals with insulation sleeve or insulate the wirings 1 indoor unit
properly. Power supply
single phase
Wiring 50Hz 220-240V
Insulation sleeve or
single phase
60Hz 220V Outdoor unit
Ring type crimp
L N
style terminal IN/D OUT/D
F1 F2 F1 F2
Fig. 19

• Connect the terminal as shown in Fig. 20.


• Do not carry out soldering finish when stranded wires are Most
used. (Otherwise, the loosening of wires may result in downstream
abnormal heat radiation.) Indoor unit A Indoor unit B Indoor unit

L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2

P1 P2 P1 P2 P1 P2

Remote controller Remote controller Remote controller


(option) (option) (option)

Fig. 21
Use wires the same in size
(if the air conditioner is in No. 2 system For group control or use with 2 remote
simultaneous multi operation)
controllers
Fig. 20
Power supply
single phase
(Abnormal heating may occur if the wirings are not tightened
50Hz 220-240V
securely.) or
• Use the required wirings, connect them securely and fix single phase
these wirings securely so that external force may not apply to 60Hz 220V Outdoor unit Note) There is not need to set the indoor unit
the terminals. L N
IN/D OUT/D
address when using group control.
• Use a proper screw driver for tightening the terminal screws.
F1 F2 F1 F2 (It is automatically set when the power
is turned on.)
If an improper screw driver is used, it may damage the screw
head and a proper tightening cannot be carried out.
• If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of Most down-
terminals. L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 L N P1 P2 F1 F2 T1 T2 stream
Table 3 indoor unit
Indoor Indoor unit B

Tightening torque (N·m) unit A


Terminal block for remote controller and P1 P2 P1 P2 P1 P2
0.88 ± 0.08 Case of group control
transmission wirings
Remote controller Remote controller Remote controller
Terminal for power supply 1. 4 7 ± 0 . 1 4 (option)
(option)
Ear th terminal 1.47 ± 0.14 For use with 2
remote controllers
• Do not carry out soldering finish when stranded wirings are Fig. 22
used.

WARNING
• When wiring, form the wirings orderly so that the control box
lid can be securely fastened. If the control box lid is not in
place, the wirings may come out or be sandwiched by the box
and the lid and cause electric shocks or a fire.

12 English

3P432203-7B

47
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

No. 3 system When including BS unit (4) Add remote controller 2 (SUB) to the terminal block for
remote controller (P1, P2) in the control box.
Power supply
single phase (There is no polarity.)
50Hz 220-240V
or P1 P2 F1 F2 T1 T2
REMOTE TRANSMISSION FORCED

single phase CONTRL WIRING OFF

Outdoor unit BS unit


60Hz 220V
L N
IN/D OUT/D OUT/D IN/D
Remote controller wiring
F1 F2 F1 F2 F1 F2 F1 F2 terminal block

Remote Remote
controller 1 controller 2
(MAIN) (SUB)

[ PRECAUTIONS ]
LN P1 P2 F1 F2 T1 T2 • Crossover wiring is needed when using group control and
2 remote controllers at the same time.
Indoor unit A • Connect the indoor unit at the end of the crossover wire
(P1, P2) to remote controller 2 (SUB).
Max. No. of
P1 P2
Indoor unit 1 Indoor unit 2 indoor units

Remote controller
(option)

Fig. 23
Crossover wire (P1.P2)
10-2 CONTROL BY 2 REMOTE CONTROLLERS
Remote controller 1 Remote controller 2
(Controlling 1 indoor unit by 2 remote controllers) (MAIN) (SUB)
• When using 2 remote controllers, one must be set to “MAIN”
and the other to “SUB”.
MAIN/SUB CHANGEOVER
10-3 REMOTE CONTROL (FORCED OFF AND ON/
OFF OPERATION)
(1) Insert a screwdriver into the recess between the
• Connect input lines from the outside to the terminals T1
upper and lower part of remote controller and, working
and T2 on the terminal block (6P) for remote controller to
from the 2 positions, pry off the upper part (2 locations).
achieve remote control.
The remote controller PC board is attached to the upper • See the “11. FIELD SETTING AND TEST RUN” for
part of remote controller. details on operation.
Upper part of
remote controller
P1 P2 F1 F2 T1 T2
REMOTE TRANSMISSION FORCED
CONTRL WIRING OFF

Input A

Lower part of Wire specification Sheathed vinyl cord or cable (2 wires)


remote controller
Gauge 0.75 - 1.25 mm
2

Insert the screwdriver here and gently work


off the upper part of remote controller. Length M ax. 100 m
Contact that can ensure the minimum
(2) Turn the MAIN/SUB changeover switch on one of the External terminal
applicable load of 15 V DC, 1 mA.
two remote controller PC boards to “S”.
(Leave the switch of the other remote controller set to “M”.)
10-4 CENTRALIZED CONTROL
• For centralized control, it is necessary to designate the group
S No. For details, refer to the manual of each optional
(Factory setting)
M controllers for centralized control.
Remote controller
PC board
Only one remote controller
S
needs to be changed
M
if factory settings have
remained untouched.

Wiring Method (See ‘‘9. ELECTRIC WIRING WORK’’)


(3) Remove the control box lid.

English 13

3P432203-7B

48
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

11. FIELD SETTING AND TEST RUN 11-3 SETTING THE FILTER SIGN DISPLAY INTERVAL
• Explain the following to the customer if the filter dirt settings
〈Field settings may have to be performed using the
have been changed.
remote controller, depending on the type of installation.〉
• The filter sign display time is set to 2500 hours
(1) Make sure the control box lids are closed on the indoor (equivalent to 1 year’s use) when shipped.
and outdoor units. • The settings can be changed to not display.
(2) Depending on the type of installation, make the field • When installing the unit in a place with much dusts, set the
settings from the remote controller after the power is filter sign display time to shorter intervals (1,250 hours).
turned on, following the “Field Settings” manual which • Explain it to the customer that the filter needs to be cleaned
came with the remote controller. regularly to prevent clogging and also the time that is set.
• The settings can select “Mode No.”, “FIRST CODE NO.”
SECOND
and “SECOND CODE NO.”. CODE NO.
Mode No. FIRST CODE NO.
• The “Field Settings” included with the remote controller
01 02
lists the order of the settings and method of operation.
0 Filter dirt low high
Displayed time 2500/ 10000/
SECOND 1 (low/high)
10 (20) (units: hours) 1250 5000
CODE NO. Mode No. Filter sign
3 ON OFF
FIRST display
CODE NO.
SETTING
FIELD SET 11-4 SETTINGS FOR SEPARATELY SOLD
MODE ACCESSORIES
• See the instruction manuals included with separately sold
• Lastly, make sure the customer keeps the “Field Settings” accessories for the necessary settings.
manual, along with the operating manual, in a safe place. 〈 When using a wireless remote controller 〉
• A wireless remote controller address needs to be set when
11-1 SETTING THE STATIC PRESSURE SELECTION
using a wireless remote controller. See the installation
• Select the SECOND CODE NO. for the resistance of the con- manual included with the wireless remote controller for
nected duct. details on how to make the settings.
(The SECOND CODE NO. is set to “01” when shipped.)
• See the technical documentation for details. 11-5 SWITCHING TIME OF THE DRY OPERATION AT
External static FIRST SECOND VRTsmart control SETTING.
Mode No. • If you change the operation mode to “Dry” when VRTsmart
pressure CODE NO. CODE NO.
control is in effect, the operation mode is change to “Cooling”
Standard (10Pa) 01 after certain period of time.
High static pres- 13(23) 5 If you want to continue dry operation longer, please change
02 the setting position as mentioned in the table below.
sure setting (30Pa) (Setting position of factory setting is “0”.)
11-2 REMOTE CONTROL SETTING ※ If you keep dry operation longer, energy saving
performance decrease.
• Forced off and ON/OFF operation should be selected by
Mode Setting switch Setting position
selecting the SECOND CODE NO. as shown in the table Dry operation
number number number
below.
30 min 01
(The SECOND CODE NO. is set to “01” when shipped.)
60 min 02
FIRST SECOND
External ON/OFF input Mode No.
CODE NO. CODE NO. 90 min
10 10
03
Forced off 01 Continuous (Not return 04
12(22) 1 to Cooling)
ON/OFF operation 02
• Input A of forced off and ON/OFF operation work as shown in ※ At the time of Group control setting, Dry operation time for the
indoor units in the same group shall be the same setting value.
the table below.
Forced off ON/OFF operation NOTE
Input A “on” to force a stop Unit operated by changing input A from For VRTsmart control function it is necessary to connect
(remote controller reception prohibited) “off” to “on” with an outdoor unit with a compatible function.
Unit stopped by changing input A from “on”
Input A “off” to allow remote controller
to “off”

14 English

3P432203-7B

49
FXDQ-PDVE(T) / FXDQ-NDVE(T) EDFMT391749

(3) Perform a test run according to the outdoor unit’s


installation manual.
• The operation lamp of the remote controller will flash
when a malfunction occurs. Check the malfunction code
on the liquid crystal display to identify the point of trouble.
An explanation of malfunction codes and the corresponding
trouble is provided in “CAUTION FOR SERVICING” of the
outdoor unit.
If the display shows any of the following, there is a
possibility that the wiring was done incorrectly or that the
power is not on, so check again.
Remote control display Content
• There is a short circuit at the FORCED
“ ” display OFF terminals (T1, T2).

“ ” display • The test-run has not been performed.


• The power on the outdoor unit is off.
• The outdoor unit has not been wired for
“ ” display power supply.
“ ” display • Wiring is incorrect for the transmission
wiring and / or FORCED OFF wiring.
• The transmission wiring is cut.
“ ” display • Reversed transmission wiring
• The power on the indoor unit is off.
• The indoor unit has not been wired for
power supply.
No display • Wiring is incorrect for the remote
controller wiring, the transmission wiring
and / or the FORCED OFF wiring.
• The remote controller wiring is cut.

CAUTION
• Always stop the test run using the remote controller to stop
operation.

(4) After finishing the test run, make sure to check


drainage in the drain pump according to “7. DRAIN
PIPING WORK”.

12. WEIGHT AND DIMENSION


Width Depth Height Weight
Model
(mm.) (mm.) (mm.) (kg.)
FXDQ20 • 25 • 32PDVE(T) 700 620 200 23
FXDQ40NDVE(T) 900 620 200 27
FXDQ50NDVE(T) 900 620 200 28
FXDQ63NDVE(T) 1100 620 200 31

English 15

3P432203-7B

50
Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorised parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the user’s manual carefully before using this product. The user’s manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
If you have any enquiries, please contact your local importer, distributor and/or retailer.

Cautions on product corrosion


1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.
2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install
the outdoor unit close to the sea shore, contact your local distributor.

VRV is a trade mark of Daikin Industries, Ltd.


VRV Air Conditioning System is the world’s first individual air conditioning system with variable refrigerant flow control and was commercialised by Daikin in 1982.
VRV is the trade mark of Daikin Industries, Ltd., which is derived from the technology we call “variable refrigerant volume.”

●Specifications, designs and other content appearing in this brochure are current as of October 2017 but subject to change without notice.

©All rights reserved 10/17 FS

You might also like