MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 1/43
Field Industrial Engineering SI210 Controller Date July. 2006
(Fig.2)
(그림2) Clutch
클러치 grip계합
diagram
관계
② After adjusting fixed scale clutch is finished, main fastening should be performed, and
adjust clutch cam with liner so that opening of movable scale maybe 72±1mm with car
door closed completely. At this time, increasing inserting of liner, dimension of
opening will also increase.
1±0.5mm
Cam
캠
(Fig.3) Assembling
(그림4) 캠과 of cam &조립
스위치 switch
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 2/43
Field Industrial Engineering SI210 Controller Date July. 2006
Cam
캠
2±0.5mm
(Fig.5) Adjusting
(그림5) 캠과 cam
스위치& switch
조정
③ Disassemble switch cover, 중심선
Middle line
slowly close door, and adjust
카도어
Car door 카도어
Car door
the dimension of opening in
contacting point to be
18±2mm(See Figure 6).
18±2mm
(Fig.6) Adjusting
(그림6) 카도어 스위치 car door
조정
SW
② With stopper, verify if stroke is normal during door's complete opening and closing
(See Table 1)
Tab.1) Operating distance of safety shoe
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 3/43
Field Industrial Engineering SI210 Controller Date July. 2006
③ Connection of safety shoe Safety shoe should be connected with car upper junction
box and MIC connector. Safety shoe and close command are connected in serial,
so when disconnection of safety shoe, opening is possible, but closing is
impossible (See Figure 7).
P48(48V DC)
SES
CloseCLOSE지령
command
(Fig.7)
(그림7)
Connection
세이프트 of safety
슈 결선shoe
connection
※ When disconnection of safety shoe, door opening is possible, but closing not.
(This means shoe and CLOSE command input are in serial.)
2) DCD-230 PCB
1. Outlook
PJ3 CONN. PJ1 CONN.
LED
CN1 CONN
(ANN)
J6 CONN
(SAV1 PHOTO)
JN2 CONN.
JN1 CONN
ST CONN PJ2
(PDA connection, DCD-230 ONLY) CONN.
< Detail of LED >
H/B
OLS/ SBD
CLS
TRIP
SAV
SAFEOK
CLOSE
OPEN
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 5/43
Field Industrial Engineering SI210 Controller Date July. 2006
2. Connector
Connector comparison
Connector
Description DCD-221 DCD-212 Remark
of DCD230
No.8,17 is power line
PJ1/PJ3 Power, I/O PJ1/PJ3 PJ1/PJ3
in SAV1
PJ2 DOOR MOTOR PJ2 PJ2
JN1 CLS/OLS SWITCH N/A JN1
JN2 ROTARY ENCODER N/A JN2 SBD1
PJ6 PHOTO SENSER PJ6 N/A SAV1
CN1 SVC TOOL N/A N/A
ST PDA N/A N/A DCD-230 ONLY
Note: PJ1) When Door Type setting is SBD1 and in case cable is connected
to PJ6, then system will work as SAV1 mode. Otherwise if it is not connected to
PJ6, then Door system will work as SBD1 mode.
LED comparison
LED DCD-221 DCD-212 DCD-23X
ON : OPEN command signal triggered
OPEN LD2 LD2
OFF : OPEN command signal unable
3. Speed pattern
Speed pattern according to each fluent data(Close)
Close Direction
Speed Profile(CL)
Speed(Hz)
CL ACC Time CL DEC Time
CL Run Hz S-CL4
S-CL1 S-Curve
S-CL2
CL End Hz S-CL3
CL Start Hz
CL Creep Hz
Time
CL ACC Time * (1+S/50) CL DEC Time * (1+S/50)
Position OLS CL Start Pos CL Creep Pos SES Pos CLS
position.
SES Zone 1. Zone to keep Door Close When frequency to keep
2. Running from [S31] SES to CLS and keep CLS [S06]Close lower
status. than[F29]Start Hz, then can
3. Frequency to keep [S06]Close must bigger than
[F29]Start Hz .(Initial data:0.5Hz) not keep Close.
Open Direction
Speed Profile(OP)
Speed(Hz)
OP ACC Time OP DEC Time
OP Run Hz S-OP4
S-OP1 S-Curve
S-OP2
S-OP3
OP Start Hz
OP Creep Hz
OP End Hz
Time
OP ACC Time * (1+S/50) OP DEC Time * (1+S/50)
Position CLS OP Start Pos OP Creep Pos OLS
4. Adjustment method
Use method of SVC-TOOL
① Connect SVC-TOOL, affirm elevator kinds and whether have Error on initial menu.
② Affirm variable kinds and then input ‘A22E’ on [S00] Menu.
③ Press ‘0’, ‘8’, ‘BBB’ turn to wanted Address.
④ Affirm present data, while want to change, input ‘AAE’, and then input Data ‘01E’.
⑤ When want to input radix point, input ‘2A5E(2.5)’and ‘A’.
⑥ After changed variables, input ‘FFFF’ return to initial menu.
⑦ Input ‘BBB’, ‘39E’ (S39 MENU)
⑧ Input ‘AAE’, and then input ‘1E’ to save changed data.
FAQ
1) Choose DOOR TYPE (SAV1, SBD1)
When the data on S[36] system Type Menu is “1”
Connect ‘J6’ SAV1 POSITION LINE: Automatically set as SAV1 DOOR TYPE
Not connect ‘J6’ SAV1 POSITION LINE: Automatically set as SBD1 DOOR TYPE
As connect PHOTO LINE to ‘J6’, automatically identify.
When the data on S[36] system Type Menu is “0”
Whether or not connect POSITION LINE to ‘J6’ both identify as SAV1.
2) Differences among PCB DCD-230, DCD-231, DCD-232
DCD-230: DOOR PCB of SAV1,SBD1 have ST PORT
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 11/43
Field Industrial Engineering SI210 Controller Date July. 2006
ANN specification
If it is ON will display 1
1:Open acceleration,
3:Open deceleration,
7:Close deceleration
Initial data
minim maximu
Group No Description SB unit Remark
SAV um m
D
Group display inverter work status
(A23E or A21E)
command or decelerate
D 15 DC Link voltage - - 1 - V Display voltage of DC Link
D 16 Encoder data - - - - - Encoder pulse input data x 10000
(ten thousand)
D 17 Encoder data - - - - - Encoder pulse input data
D 18 Photo sensor input - - 0 31 - 0: OPEN, 31: CLOSE
data
D 19 Door running times 0 0 0 10000 - X10000 times
(Ten thousand)
D 20 Door running times 0 0 0 9999 - 0~9999 times
D 21 Door reopen times 0 0 0 10000 - x10000 times
(Ten thousand)
D 22 Door reopen times 0 0 0 9999 - 0~9999 times
D 23 Door running mode 0 0 0 2 - 0: Normal running, 1: OP detecting running
2: Test mode running
D 24 Open Lock detection 0 0 0 65535 - 0~65535 times
times After recognize Open command,
during Open Lock of F40
waiting time, and when doesn’t
reach OLS, then add 1 unit
When reach CLS check again
D 25 Close Lock detect 0 0 0 65535 - 0~65535 times
times After recognize Close command, during
Close Lock of F41 waiting time, and
doesn’t reach CLS then add 1 unit
When reach OLS check again
D 26 Result of 0 0 0 1 - 0 : Normal
Rom Check 1 : Error (Only represent on ADS)
27 Result of 0 0 0 1 - 0 : Normal
D
Ram Check 1 : Error (Only represent on ADS)
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 17/43
Field Industrial Engineering SI210 Controller Date July. 2006
Initial
mini maximu
group No Description data unit Remark
mum m
SBD SAV
Group display error
status (A41E)
T 01 Error Info 0 - - - - - Current Error: Error occur time/Error
Code
T 02 Error Info 1 - - - - - Bypass Error: Error occur time/Error Code
T 03 Error Info 2 - - - - -
T 04 Error Info 3 - - - - -
T 05 Error Info 4 - - - - -
T 06 Error Info 5 - - - - -
T 07 Error Info 6 - - - - -
T 08 Error Info 7 - - - - -
T 09 Error Info 8 - - - - -
T 10 Error Info 9 - - - - -
T 11 Error Info 10 - - - - -
T 12 Error Info 11 - - - - -
T 13 Error Info 12 - - - - -
T 14 Error Info 13 - - - - -
T 15 Error Info 14 - - - - -
T 16 Error Info 15 - - - - -
T 17 Error Info 16 - - - - -
T 18 Error Info 17 - - - - -
T 19 Error Info 18 - - - - -
T 20 Error Info 19 - - - - -
T 21 Error count - - - - After initialization error occurred
total times (Automatically saved)
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 18/43
Field Industrial Engineering SI210 Controller Date July. 2006
Initial
mini maximu
Group No Description data unit Remark
mum m
SBD SAV
Door setting group
(A22E or A31E)
S 01 Close start zone 0 3 0 3000 When Close start, initial frequency apply zone
Ex.1) SBD
100: Before the number of encoder input pulse
reach 100, run by initial frequency
Ex.2) SAV
3: Before photo-sensor signal data reach 3
run by initial frequency
S 02 Close start 5.0 5.0 0.0 Max Hz Output frequency during Close start zone
frequency Freq
S 03 Close running 20.0 20.0 0.0 Max Hz Normal running frequency after Close
frequency Freq start zone
S 04 Close Creep start 600 14 0 30000 - During normal Close running, position of
position start deceleration by Creep speed
Ex.)SBD
500: From the position when Maximum of
encoder input data is 500, it start decelerate
* Max data is detected during the initial door
width measurement
S 05 Close Creep 2.5 2.0 0.0 Max Hz After Close deceleration, running frequency
frequency Freq until CLS position
S 06 Keep Close 5.0 0.5 0.0 Max Hz After CLS detection 1.0sec,frequency to keep
frequency Freq Close running
Ex.) SBD
5.0 : After CLS detection 1.0sec, run by 5.0Hz
S 07 Open start zone 100 3 0 3000 - When Open start, initial frequency apply zone
Ex.1) SBD
100: Before the number of encoder input pulse
reach 100, run by initial frequency
Ex.2) SAV
3: Before photo-sensor signal data reach
(31-3), run by initial frequency
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 19/43
Field Industrial Engineering SI210 Controller Date July. 2006
Initial
mini maximu
Group No Description data unit Remark
mum m
SBD SAV
Door setting group
(A22E or A31E)
S 08 Open start 5.0 5.0 0.0 Max Hz Output frequency during Open start zone
frequency Freq
S 09 Open running 27.0 20.0 0.0 Max Hz Normal running frequency after Open start zone
frequency Freq
S 10 Open Creep 50 14 0 30000 - During normal Open running,the position that
start position start deceleration by Creep speed
Ex.) SBD
500 : From the position when encoder input
data is 500, start decelerate
S 11 Open Creep 2.0 2.0 0.0 Max Hz After Open deceleration, running frequency
frequency Freq until OSL position
S 12 Frequency to 2.0 2.0 0.0 Max Hz After OLS detection 1.0sec, running frequency
keep Open Freq to keep Open
Ex.) SBD
5.0: After OLS detection 1.0sec, run by 5.0Hz
S 13 Close acceleration 0.5 0.7 0.1 30.0 sec When Close running, accelerate time during
time accelerate zone
S 14 Close deceleration 0.6 0.6 0.1 30.0 sec When Close running, decelerate time during
time decelerate zone
S 15 Open acceleration 0.5 0.7 0.1 30.0 sec When Open running, accelerate time during
time accelerate zone
S 16 Open deceleration 0.6 1.0 0.1 30.0 sec When Open running, decelerate time during
time decelerate zone
S 17 S-CL1 35.0 35.0 0.0 50.0 % Jerk of acceleration in initial zone when Close
running acceleration
S 18 S-CL2 30.0 35.0 0.0 50.0 % When Close running acceleration, Jerk at the
end of acceleration
S 19 S-CL3 30.0 40.0 0.0 50.0 % Jerk of deceleration in initial zone when Close
running deceleration
S 20 S-CL4 50.0 50.0 0.0 50.0 % When Close running deceleration, Jerk at the
end of deceleration
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 20/43
Field Industrial Engineering SI210 Controller Date July. 2006
Initial
mini maximu
Group No Description data unit Remark
mum m
SBD SAV
Door setting group
(A22E or A31E)
S 21 S-OP1 35.0 35.0 0.0 50.0 % Jerk of acceleration in initial zone when Open
running acceleration
S 22 S-OP2 30.0 35.0 0.0 50.0 % When Open running acceleration, Jerk at the
end of acceleration
S 23 S-OP3 30.0 40.0 0.0 50.0 % Jerk of deceleration in initial zone when Open
running deceleration
S 24 S-OP4 50.0 50.0 0.0 50.0 % When Open running deceleration, Jerk at the
end of deceleration
S 25 Reopen 1.0 1.0 0.1 30.0 sec When Reopen, acceleration time
acceleration time
S 26 Reopen 0.3 0.3 0.1 30.0 sec When Reopen, deceleration time
deceleration time
S 27 OLS voltage 1 10.0 10.0 0.0 50.0 % Adjustment data of output voltage under OLS
status
S 28 OLS voltage 2 15.0 25.0 0.0 50.0 % Adjustment data of output voltage under OLS
status and when encoder input turn to Close
side
S 29 CLS voltage 1 10.0 10.0 0.0 50.0 % Adjustment data of output voltage under CLS
status
S 30 CLS voltage 2 15.0 25.0 0.0 50.0 % Adjustment data of output voltage
under CLS status and when encoder input turn
to Open side
S 31 SES position 250 14 0 10000 - Position setting that disable SES
Ex.) SBD
200: From CLS position until encoder pulse
reach 200, start output SES-Cut command
Ex.2) SAV
14: Photo-sensor input from position 14,
start output SES-Cut command
S 32 Supplemental Menu
S 33 OP measure mode 0 Use 0 1 - 0: When Power On, measure OP
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 21/43
Field Industrial Engineering SI210 Controller Date July. 2006
Initial
mini maximu
Group No Description data unit Remark
mum m
SBD SAV
Door setting group
(A22E or A31E)
x After OP measurement, automatically set as 1
1: Status that finish OP measurement
When Power On, and is not CLS/OLS,begin
low speed run
When Power On, and is CLS/OLS, begin
normal run
S 34 Door running mode 0 0 0 99 - 0: Normal run
99: Test run mode
If recognize Close or Open command then
disable test running mode
S 35 Automatically run 0 0 0 9999 - 9999: Test running mode
mode If recognize Close or Open command then
automatically set as 0 and disable auto
running mode
S 36 System Type 1 0 0 1 - 0 : SAV
1 : SBD(When Photo Sensor detect, SAV)
2 : ADS
S 37 1 1 0 Xx (ADS door set initial data by Type)
S 38 Door width setting 6.5 Use 0.0 Max Hz Running frequency of detecting SBD door width
frequency X Freq
S 39 Init Mode 0 0 0 2 0: No change.
1 : Parameter saved
2 : Error initialization
3 : Running times & Lock initialization
99 : Parameter initialization
S 40 F Modify 0 0 0 0 F Menu Access Code input
S 41 SAV side OP 0.0 0.0 0.0 1.0 SAV Side Open setting: 1
(It will be informed later)
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 22/43
Field Industrial Engineering SI210 Controller Date July. 2006
Initial
New Mnini Maximu
group Description data Unit Remark
No mum m
SBD SAV
SAV side OP 0.0 0.0 0.0 1.0 SAV Side Open setting: 1
F 37
(It will be informed later.)
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 23/43
Field Industrial Engineering SI210 Controller Date July. 2006
Error catalog
Code Error name When it is detected, then act Detect condition
1 Arm Short After Err.Info saved, stop Arm Short
LVLVLV of IPM Gate power
3 OV Trip After Err.Info saved, stop DC Link voltage > 200V
4 After Err.Info saved, stop Keep DC Link voltage < 90V
500msec
5 ETH After Err.Info saved, stop 2A, continuous action is possible
When 50%(3A), and continuously act 60sec
then thermal starter trigger
8 MTH After Err.Info saved, stop Detect when Motor Thermal is triggered
9 Position signal abnormal After Err.Info saved, stop Inverter Run speed feedback = 0
0.7A<output current < 2A output
frequency 1.5Hz
Detect when keep above condition 1sec
21 OC U Err.Info save U phase output current > OC level
22 OC V Err.Info save V phase output current > OC level
23 OC W Err.Info save W phase output current > OC level
24 Output Unbalance Err.Info save Inverter Run
Output frequency > OPW detect frequency
When keep Ia + Ib + Ic > 0.5A
over 100msec
25 Ia Offset Err.Info save Offset of la > 10% of rating
26 Ib Offset Err.Info save Offset of lb > 10% of rating
27 Ic Offset Err.Info save Offset of lc > 10% of rating
28 Over Load Err.Info save When keep output current > 2A
over 5sec
29 Over Speed Err.Info save Neither OLS nor CLS
When keep output frequency > 10Hz
feedback speed > 110% of output frequency
over 1sec
30 Velocity Tracking Error Err.Info save Neither OLS nor CLS
When keep output frequency > OPW detect
frequency
output frequency – feedback speed > 5Hz
output current > 0.7A over 1sec
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 24/43
Field Industrial Engineering SI210 Controller Date July. 2006
③ After DMC switch OFF and connector is inserted, check door driving with DMC
switch ON.
D.M.C switch ON
YES
48V
DOLS output
DOLS출력
0V
48V
Gate
게이트 switch
output
스위치 출력
0V
Full Full
(전개)
opened (전폐)
closed
DOLS
DOLS동작 Gate
게이트 switch
스
movement operation
위치 동작
(Fig.11)스위치
(그림11) SW OPR & output
동작과 출력
(
(F
그ig
림.12
1)
2)SetD
tingm
IP et
스위ho
치do
설fD
정IP
요SW
령 ((
Fig.림
그 13
1)3C
)rea
패tio
턴n의
ofp
생att
성ern
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 28/43
Field Industrial Engineering SI210 Controller Date July. 2006
Caution: After change of DIP switch, definitely press RESET SW(SW6) for 1 sec or
more.(See outside view of DCD-20X PCB). When adjusting switch door speed
changes determined by above conversion table.
Thus, the door speed of SW 4 ON is faster than when SW(SPEC.) 1,2,3 is ON.
Start
½ÃÀÛ
SpeedOPEN½Ã
pattern when opening
¼ÓµµÆÐÅÏ OP-DOLS
OP-OLT(4)
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 29/43
Field Industrial Engineering SI210 Controller Date July. 2006
(Note) Grip: Operation of car & hall door are connected by clutch.
① Meaning of indication and operation state of each LED Explanation of LED attached to
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 31/43
Field Industrial Engineering SI210 Controller Date July. 2006
door PCB(See Tab.11) With the exception of these, when abnormalities occur, door
PCB decides type of abnormality and indicates failure with LED that indicates OPEN
command output(LD2) and CLOSE command output(LD3) in normal conditions
(See Tab.12).
Tab.11) LED operation state indication when abnormal operation occur
closing.
③ When above item ② is O.K, check 1-phase from 3-phases for lost.
④ Check door input voltage(connector PJ1-8, 9, 17).
SAV1: If 108V or less, lost.
MAV1: If 118V or less, lost.
2) When IPM error(LD5 lights ON)
① Firstly decide error or no of control power supplied to IPM. As Fig.16, inspect power
voltage(See Tab.11, Fig.16).
② If there is no power voltage error, switch ON again and perform open/close operation.
If IPM error occurs again, replace PCB.
3) Only OPEN operation or only CLOSE operation is possible
① After inserting connector, verify if OPEN command(PJ1-10) or CLOSE
command(PJ1-1) is inputted from CTRL panel.
※ Verify if pin voltage changes from 48V to near to 0V(See Fig.11).
If OPEN or CLOSE command is properly inputted from CTRL panel, for opening, LD2
and for closing, LD3 must light ON.
② If there are no change of voltage, line from CTRL panel could have failure. If voltage
changes, for opening, LD2 and for closing, LD3 must light ON according to command
of CTRL panel. Otherwise, it means input circuit error in PCB. Replace PCB.
Tab.13) Output voltage of IPM control power
Control
제어반 panel
R S T 48V
카위접속상자
Safety switch of
car안전 스위치
upper junction
box
PJ1-8 PJ1-9 PJ1-17 PJ1-4
Inverter
인버터 door도어
circuit기판
board
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 33/43
Field Industrial Engineering SI210 Controller Date July. 2006
-
1 2 3
PC1 + PC3 + PC5 +
- - -
PJ2
IPM Á¶¸³
assembling
(Fig.16) Checking
(그림16) IPM 의 p전원
ower 전압
voltage
체크of IPM
※ This is standard of
CENTER OPEN, and
for SIDE OPEN,
switch ON switch 4 of
SPEC DIP SW, and
set as Tab.14.
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 34/43
Field Industrial Engineering SI210 Controller Date July. 2006
※ This is standard of CENTER OPEN, and for SIDE OPEN, switch ON switch 4 of SPEC
DIP SW, and set as Tab.15.
③ After setting change for DIP switch press reset SW(SW6) hard for 1 sec. or more.
Door speed
command Motor speed command
Real door
speed
Processor
PJ3
(5P)
Heat JN2
detection (4P)
PJ1 circuit
(17P)
PJ4 SSR
Currnt IPM
(13P) Sensor
TBC
THB
(2P)
DCD-30F PCB
CLS,OLS
Sensor
PJ4 PJ2 Motor RE
(13P) (5P) Filter
Condenser
Heater
0 2
1 3
0 1
2 3
4 5
6 7
8 9
10 11
12
3 EW 950 ± 25mm
4 EW 1000 ± 25mm
5 EW 1050 ± 25mm
6 EW 1100 ± 25mm
7 EW 1150 ± 25mm
8 EW 1200 ± 25mm
9 EW 1250 ± 25mm
10 EW 1300 ± 25mm
11 EW 1350 ± 25mm
12 EW 1400 ± 25mm
13 Non Use
14 Non Use
15 Non Use
※ Note : Above configurations will be set from the factory, but it must be verified before
power is supplied.
※ Caution : With improper setting, door operation speed may become too fast or slow.
※ Dip switch adjustment for speed pattern
HAV door uses actual speed and position detected by ROTARY ENCODER to control speed
(CLOSED LOOP SPEED CONTROL), and speed pattern is optimally set at the factory. Thus,
speed pattern adjustment is almost not required. Only for required cases, speed pattern
should be adjusted according to below.
OP-ACC2 OP-DEC
RAC
OP-OLT
OPEN
OP-ACC1
CL-TERM CLOSE
RST
CL-ACC
CL-DEC
CL-SPD
Rev. No. 0
MMR Elevator_SI Doc. No.
DL EL)
06-008
FOD Test & Commissioning for Page 40/43
Field Industrial Engineering SI210 Controller Date July. 2006
※ SPEC2 detail of S6
Dip Switch SPEC name Detail Variable Description
0 Standard
Door M/C base 1 +200mm up
position 2 +300mm up
3 +400mm up
S6 SPEC2
0 Ordinary door
Door Spec
1 Fire door
0 Center open
CO/SO
1 Side open
♣Standard : 800mm from bottom of M/C base to top of entrance height.
★ Note1 : After installation with low machine room temperature, door error may occur at
initial power input, but, after 10-20 minutes, error will be cleaned.
★ Note2: If door speed is not normal even though dip-switch adjustment, Check the CLS and
OLS signal or in cage of rear door, replace the rotary encoder phase.
★ Note3 : If photo sensor does not work, check that the used contact is normally close or
open. Most of case, photosensor contact is normal close from factory. So it needs to modify
its contact to normal open in jobsite.
★ Note4 : Jumper the safety shoe(Left,Right) with P48V in DCD-30M. And connect the safety
shoe signal line to communication board on car top. And it needs to set I/O for this signal. If
there line was not jumpered, car door will not close.