KILASS N TRENDS Se Trading, Contracting and Events W.LL SS Power Cable Test Report Panel Tag no: EMCC-C4910-251 Make: Schneider Electric Date : 05/03/2020 Feeder Ref no: TIE MAU-901 Location : QACC Building Second Floor | Cable From: TIE MAU-901 Cable To: MAU-C4910-901 Control Panel jent Name: HIA EPSC INSULATION RESISTANCE TEST Duration test: IMIN Test Voltage: 1000V Phase Values in Giga ohms R phase to earth 32.260 Y phase to earth _ >2.262 B phase to earth >2.260 R Phase to Y phase >2.260 | Y Phase to B phase 32260 B Phase to R phase >2.260 R Phase to Neutral 32.260 Y Phase to Neutral 22.262 B Phase to Neutral >2260 ‘Acceptance criteria: 100 MO Remarks: Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2021 DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020 Test Performed by KNT |” Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Parky-KAHRAMAA TEM-AC ENGINEERING “A"GRADE CONTRACTOR) ‘Suresh Subbarayan Delwin Domi Bio | agle Gk a Manoj Viswanathan ‘Senthil Kumar KLASS N TRENDS Ze Trading, Contracting and Events W.LL S Power Cable Test Report Panel Tag no: EMCC-C4910-251 Make: Schneider Electric | Client Name: HIA EPSC Cable size: 4Cx35mm? Cu/xlpe/swa/Ishf + 10x35mm? Cu/ishf ECC Feeder Ref no: TIE MAU 901 _| Date : 05/03/2020 Location : QACC Building Second Floor _| Cable From: MAU-C4910-901 Control Panel Cable To Indoor unit 225A TP FIELD ISOLATOR MAU-C4910-901 INDOOR UNIT INSULATION RESISTANCE TEST Duration test: 1MIN- Test Voltage: 1000V Phase Values in Giga ohms R phase to earth >2.260 Y phase to earth - 22.260 7 B phase to earth >2.260 | RPhase to ¥ phase - — 22260 7 | Y Phase to B phase 32.260 B Phase to R phase 32.260 ‘Acceptance criteria: 100 MO Remarks: Test Equipment Used ‘Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2021 DIGITAL MULTIMETER Fuke-376 4603007 ws 190/202 7 ' Witnessed by ‘Approved by Test tt Witne by st Fetormedby ‘essed ov MUHIBBAH (Third Party-KAHRAMAA “A"GRADE ENGINEERING CONTRACTOR) Suresh Subbarayan Delwin Dominic Manoj Viswanathan Senthil Kumar 948) ey ‘Trading, Contracting and Events W.L.L KLASS N TRENDS Ke Power Cable Test Report Panel Tag no: EMCC-C4910-251 Make: Schneider Electric] Client Name: HIA EPSC Cable size: 4Cx95mm™ Cu/xipe/swa/sht . 1650mm? Cu/lshf ECC Date 15/08/2020) = = QACC Building Second Floor _| Cable From: MAU-C4910-901 Control Panel Feeder Ref no: TIE MAU 901 Cable To Outdoor unit : 140A TP FIELD ISOLATOR MAU-C4910-901 OUTDOOR UNIT INSULATION RESISTANCE TEST Duration test: IMIN Test Voltage: 1000V Phase Values in Giga ohms R phase to earth >2.260 Y phase to earth 32.260 "— Bphase to earth "32.260 R Phase to V phase 32.260 Y Phase to 8 phase 22.260 | B Phase to R phase 32.260 ‘Acceptance criteria: 100 MO Remarks: Test Equipment Used ‘Model no Serialno Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2024 DIGITAL MULTIMETER Fluke-376 460300785 4/10/2020 Witnessed by ‘Approved by Test Performed by | Witnessed by og Kar TEM AC MUHIBBAH (Third Party-KAHRAMAA “A” GRADE ENGINEERING CONTRACTOR) Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar BA Ts &y es KLASSN TRENDS & Trading, Contracting and Evonts W.LL Power Cable Test Report 2 Panel Tag no: EMCC-C4910-251 Make: Schneider Electric | Client Name: HIA EPSC Cable size: 4Cx35mm? Cu/xipe/swa/isht+ | sf no: De tex35mm? Cuylsht ECC Feeder Ref no: TIE MAU 901 | ate : 05/03/2020 ion : i Cable From: 25A TP FIELD ISOLATOR MAU-C4910-901 Location : QACC Building Second Floor INDOOR UNIT Cable To Indoor unit :MAU-C4910-901 INDOOR UNITMOTOR INSULATION RESISTANCE TEST Duration test: 1MIN Test Voltage: 1000V Phase Values in Giga ohms R phase to earth >2.260 Y phase to earth 22.260 B phase to earth >2.260 R Phase to Y phase 22.260 Y Phase to B phase 22.260 l B Phase to R phase >2.260 Acceptance ria: 100 MQ. — Remarks: Test Equipment Used Model no Serial no Calibration Due date [INSULATION TESTER Fluke- 1587 27490055 27/02/2021 DIGITAL MULTIMETER Fluke 376 460300785 14/10/2020 Tw Witnessed by ‘Approved by ftnessed by Test Performed by wines ¥ MUHIBBAH (Third Party-KAHRAMAA “A"GRADE ENGINEERING CONTRACTOR) ‘Suresh Subbarayan Delwin Dominic Manoj Viswanathan Senthil Kumar KLASS N TRENDS K ‘Trading, Contracting and Events W.LL ____ MCCB insulation Resistance Test Report Panel Tag no : EMCC-C4910-251 | Make: Schneider Electric | Client Name: HIA EPSC Location: QACC Building -Second Floor Date : 05/03/2020 Ref no: TIE MAU 901. INSULATION RESISTANCE TEST Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V Phase y Values in Giga ohms R phase to earth >2.260 Y phase to earth 32.260 B phase to earth 32.260 R Phase to ¥ phase >2260 Y Phase to B phase >2.260 B Phase to R phase 32.269 Status: Breaker Open Position- Across Pole Phase ] Values in Giga ohms R phase to R’ phase 32.260 Y phase to V Phase - 32.260 B phase to B Phase 32.260 ~ ‘Acceptance criteria: 100 MO Test Equipment Used Model no Serial no. Calibration Due date INSULATION TESTER ~~ Fluke- 1587 27490055 27/02/2021 DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR) ‘Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan ‘Senthil Kumar 4 0 [ok OY SS KLASS N TRENDS Trading, Contracting and Events WALL MCCB Mechnical and Visual Inspection Test Report Panel Tag no : EMCC-C4910-251 | Make: Schneider Electric | Client Name: HIA EPSC Date : 05/03/2020 Ref no: TIE.MAU.901___| Location:@ACC Building ~Second Floor NETA Standard Reference below 7. Inspection and test procedures 7.6.1.1 Molded ~Case Circuit Breaker Visual and Mechanical inspection: Sno | Description NETA, Remarks i : STANDARD | Checked 7 Inspect Visual and Mechanical Inspection eas ony chekee Molded case | NOT OK/ NA Ref no 1 | Compare equipment nameplate data with drawings and 7614 Checked OK | Nil Specifications 1. Visual Inspection (1) 2 _ | inspect Physical and mechanical condition 7.6.1.1 Checked OK | Nil 1. Visual Inspection (2) 3 | Inspect anchorage and alignment 76414 NA [Nil 1. Visual Inspection (3) 4 _ | Verify the unit is clean Tedd Checked OK | Nil 1. Visual Inspection (8) 5 | Operate the circuit breaker to insure smooth operation 76.1.4 Checked OK | Nil 1. Visual Inspection (5) 6 | Contact Resistance Testing 7611 Checked OK | Nil 2. Visual Rph Yh hi phase pase 8 phase Inspection (6) 355.200 405.920 370.30 7 | inspect operating mechanism, contacts and arc chutes in [7.6.1.1 Checked OK | Nil unsealed units 1. Visual Inspection (7) 8 | Perform adjustments for final protective device settings in| 7.6.1.1 Final Setting | Nil accordance with the co ordination study 1. Visual Applied and Inspection (8) | tested OK KLASS N TRENDS Ze ‘Trading, Contracting and Events W.L.L MCCB Mechnical and Visual In: Test Report Panel Tag no : EMCC-C4910-251 | Make: Schneider Electric | Client Name: HIA EPSC Date : 05/03/2020 Ref no: TIE.MAU.901 Location:QACC Building -Second Floor Acceptance Criteri Compare bolted connection resistance values to values of similar connections. Investigate values which device from those of similar bolted connections by more than SO percent of the lowest value. NETA Ref 7. Inspection and test procedures 7.6.1.1 / 3.2 Note: NETA standard Reference no 7.6.1.2 Sub division 2: Electrical Tests We do only insulation resistance tests for molded case circuit breaker and control wiring as per NETA Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker. Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER 1587 27490055 27/02/2021 CONTACT RESISTANCE METER | DLRO 10 101322093 28/02/2021 ‘Test Performed by | Witnessed by | Witnessed by MUHIBBAH J Approved by (Third Party-KAHRAMAA, KNT TEM-AC ENGINEERING “A" GRADE CONTRACTOR) ‘Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar BARE | aes C7 ee ‘Trading, Contracting and Events W.LL KILASS N TRENDS Ke Molded Case Circuit Breaker Test Report Panel Tag no : EMCC-C4910-251 | Make: Schneider Electric | Client Name: HIA EPSC Date : 05/03/2020 Fear n:QACC Building -Second ——_____| Ref no: TIE MAU 901 Breaker Dat: Manufacturer: Schneider Electric Voltage Rating: 415V_ Model: NSX250F Internal Rating: 200 Amperes Thermal Element: Adjustable: Yes__ Setting: 140-200 Amperes Final setting: 140 Amperes ‘Magnetic Element Adjustable: Yes Setting: 10 Front Identification-Left to | Pole 1 Pole 2 Pole 3 Right Thermal Element | Thermal Element Thermal Element Tripping time at 285% of 207 Seconds 211.5 Seconds 241.27 Seconds Thermal Pickup inst. Tested on | Trip NA NA NA — setting | No Trip Remarks: Nil Test Equipment Used Model no Serial no Calibration Due date Primary Injection Test Kit HO? i 13-8322 19/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT | Tewac ENGINEERING “A” GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic | _ Manoj Viswanathan Senthil Kumar pee [ss | Oe Trading, Contracting and Evonts W.LL KLASS N TRENDS Ke Panel Tag no : EMCC-C4910-251 Test Report : Primary Injection Test (Stability) Make: Schneider Electric | Client Name: HIA EPSC Date : 05/03/2020 Ref no: TIE AHU 901 Location:QACC Bi Floor ling Second Incomer Breaker Data: Breaker Data: Manufacturer: Schneider Electric Voltage Rating: 415V Internal Rating: 680 Amperes Type: NSX630F Outgoing Breaker Data: Breaker Data: Manufacturer: ‘Schneider Electric Voltage Rating: 415V Internal Rating: 200 Amperes Type: TM200D Description ‘Injected | Incomer Breaker | Outgoing Current | (rip /no Trip) | Breaker (Trip / No Trip) Injected current between Incomer and Outgoing (R phase) | 363A | No Trip Tripped Injected current between incomer and Outgoing ( Y phase) | 363A | No Trip Tripped Injected current between Incomer and Outgoing (B phase) | 363A | No Trip Tripped Acceptance Criteria: Outgoing breaker should trip before incomer trips as per the co ordination study. Result: The Outing Tie AHU 901 breaker is tripped and Incomer breaker does not trip. Hence Protection discrimination study is verified and found ok. Test Equipment Used } ‘Model no Serial no | Calibration Due date Primary Injection Test Kit Model HC-2 13-8322, 19/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan ‘Senthil Kumar 3. Bee wa ey = KILASS N TRENDS ‘Trading, Contracting and Evonts W.L.L i Power Cable Test Report_ Panel Tag no: EMCC-C4910-228 Make: Schneider Electric __| Client Name: HIA EPSC Date : 05/03/2020 Feeder Ref no: TIE.MAU-902 | Cable T INSULATION RESISTANCE TEST |AU-C4910-902 Control Panel Location : QACC Building Second Floor | Cable From: TIE. May-902 Duration test: 1MIN Test Voltage: 1000V Phase Values in Giga ohms R phase to earth >2.260 Y phase to earth 2.260 B phase to earth 32.260) R Phase to V phase 32.260 Y Phase to B phase 32.260 B Phase to R phase 32.260 R Phase to Neutral >2.260 Y Phase to Neutral 32260 B Phase to Neutral 32.260 ‘Acceptance criteria: 100 MO Remarks: Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2024 DIGITAL MULTIMETER Fluke-376 -46030078s 14/10/2020 Test Performed by KNT | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA TEM-AC ENGINEERING “A"GRADE CONTRACTOR) | Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar 8. joe as wy ————. KILASS N TRENDS Trading, Contracting and Evonts W.L.L Cable Test Report Powel e Panel Tag no: EMCC-C4910-228 Make: Schneider Electric Client Name: HIA EPSC ~ Cable size: 4Cx35mm? Cu/xlpe/swa/Ishf + 1Cx35mm? Cu/Ishf ECC Feeder Ref no: TIE MAU 902 | Date : 05/03/2020 Location : QACC Building Second Floor Cable From: MAU-C4910-902 Control Pane! Cable To indoor unit : 254 TP FIELD ISOLATOR MAU-C4910-902 INDOOR UNIT INSULATION RESISTANCE TEST Duration test: 1MIN- Test Voltage: 1000V ase Values in Giga ohms R phase to earth 32.260 Y phase to earth 32.260 8 phase to earth 32.260 R Phase to Y phase im >2.260 | ‘Phase to B phase >2.260 B Phase to R phase 32.260 “Roceptance criteria: 100 MO Remarks: Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke 1587 27490055 27/02/2024 DIGITAL MULTIMETER Fluke 376 46030078 ws 44/10/2020 - Witnesse iby Test Performed by | Witnessed by seed by WR a MUNIBBAH (Third Party-KAHRAMAA “A"GRADE KNT TEM-AC ENGINEERING CONTRACTOR) Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar g se | ph & Se KLASS NTRENDS (&% ‘Trading, Contracting and Evonts W.L.L Power Cable Test Report Panel Tag no: EMCC-C4910-228 Make: Schneider Electric Client Name: HIA EPSC Cable size: 4CxS0mm? Cu/xIpe/swa/Ishf + 1CxSOmm? Cu/Ishf ECC Location : QACC Building Second Floor __| Cable From: MAU-C4910-902 Control Panel Feeder Ref no: TIE MAU 902 _| Date : 05/03/2020 Cable To Outdoor unit : 225A CIRCUIT BREAKER MAU-C4910-902 OUTDOOR UNIT INSULATION RESISTANCE TEST Duration test: MIN Test Voltage: 1000V Phase Values in Giga ohms Rphase to earth >2.260) Y¥ phase to earth >2.269 B phase to earth >2.260 RPhasetoY phase (32260 - Y Phase to 8 phase >2.260 [ 8 Phase to R phase 32.260 ‘Acceptance criteria: 100 MQ Remarks: Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke 1587 27480055 27/02/2024 DIGITAL MULTIMETER Flake 376 "46030078ws 14/10/2020 1 | Test Performed by | Witnessed by Witnessed by Approved by MUHIBBAH | (Third Party-KAHRAMAA “A” GRADE KNT TEM-AC ENGINEERING CONTRACTOR) Suresh Subbarayan_| _Delwin Dominie | Manoj Viswanathan Senthil Kumar bbe | pple 6 SS KILASS N TRENDS K ‘Trading, Contracting and Evonts W.LL Power Cable Test Report Panel Tag no: EMCC-C4910-228 Make: Schneider Electric Client Name: HIA EPSC Cable size: 4Gx35mni™ Cu/xipe/swa/shf + ~ 7 1exasmmn? ColshF ECC Feeder Ref no: TIE MAU 902 | Date: 05/03/2020 ocat 7 -C4910- om : QACC Building Second Floor _| Cable From: 258 TP FIELD ISOLATOR MAU-C4910-902 INDOOR UNIT Cable To indoor unit :MAU-C4910-902INDOOR UNIT MOTOR | INSULATION RESISTANCE TEST Duration test: 1MIN Test Voltage: 1000V Phase Values in Giga ohms R phase to earth >2.260 Y phase to earth : >2.260 — B phase to earth >2.260 R Phase to Y phase >2.260 Y Phase to B phase 22.260 B Phase to R phase >2.260 ‘Acceptance criteria: 100 MO Remarks: Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2021 DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020 Witnessed by ‘Approved by ed b Test Performed by Wied by MUHIBBAH (Third Party-KAHRAMAA “A”GRADE knT TEM-AC ENGINEERING CONTRACTOR) Suresh Subbarayan | _Delwin Dominic | Manoj Viswanathan ‘Senthil Kursar & Bib | gle oy SS KLASS N TRENDS Be ‘Trading, Contracting and Evonts W.L.L MCB Insulation Resistance Test Report Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC Location: QACC Building -Second Floor Date : 05/03/2020 Ref no: TIE MAU 902 INSULATION RESISTANCE TEST Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V Phase Values in Giga ohms R phase to earth 32.260 Yphasetoearth 32.260 B phase to earth >2.260 R Phase to Y phase 32.260 Y Phase to B phase 7 >2.260 B Phase to R phase >2.260 Status: Breaker Open Position- Across Pole Phase Values in Giga ohms R phase to R’ phase 32.260 Y phase to Y ‘Phase 32.260 B phase to B Phase 32260 ‘Acceptance criteria: 100 MO Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490085 27/02/2024 DIGITAL MULTIMETER. Fluke-376 46030078ws 14/10/2020 | Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic Manoj Viswanathan Senthil Kumar BROS [Tas eL Ss KLASS N TRENDS ‘Trading, Contracting and Events W.L.L ~ MCCB Mechnical and Visual inspection Test Report Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC Date : 05/03/2020 [Refno: TIEMAU902___| Location:QACC Building -Second Floor NETA Standard Reference below 7. Inspection and test procedures 7.6.1.1 Molded ~Case Circuit Breaker Visual and Mechanical Inspecti Sino Description NETA Remarks i STANDARD | Checked Visual and Mechanical Inspection ee on/checked Molded case | NOT OK/ NA Ref no 1 | Compare equipment nameplate data with drawings and | 7.6.1.1 Checked OK | Nil Specifications 1. Visual Inspection (1) 2 _ | inspect Physical and mechanical condition 76.11 ‘Checked OK | Nil 1. Visual Inspection (2) 3__ | inspect anchorage and alignment 7614 NA [NT 1. Visual Inspection (3) 4 | Verify the u Checked OK | Nil Inspection (4) 5 | Operate the circuit breaker to insure smooth operation 7614 Checked OK | Nil 1. Visual Inspection (5) & | Contact Resistance Testing 7614 Checked OK | Nil 2. Visual Y phi B phi R phase phase phase Inspection (6) 525u0 51010 568.5u0 7 | Inspect operating mechanism , contacts and arc chutesin | 7.6.1.4 Checked OK | Nil | unsealed units 1. Visual Inspection (7) 8 | Perform adjustments for final protective device settingsin [7.6.1.1 Final Setting | Nil accordance with the co ordination study 1. Visual ‘Applied and Inspection (8) | tested OK KILASS N TRENDS xq Trading, Contracting and Evonts Wit OSX MCCB Mechnical and Visual Inspection Test Report Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC Date : 05/03/2020 Ref no: TIEMAU902__[ Location:QACC Building -Second Floor Acceptance Criteria: Compare bolted connection resistance values to values of similar connections. Investigate values which device from those of similar bolted connections by more than 50 percent of the lowest value. NETA Ref: 7. Inspection and test procedures 7.6.1.1 / 3.2 Note: NETA standard Reference no 7.6.1.1 Sub division 2: Electrical Tests We do only insulation resistance tests for molded case circuit breaker and control wiring as per NETA Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker. Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER 1587 27490055 27/02/2021 CONTACT RESISTANCE METER | DLRO 10 101322093 28/02/2021 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA kNT TEM-AC ENGINEERING “GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan ‘Senthil Kumar Saw | apa C7 = KILASS N TRENDS Ee Trading, Contracting and Events W.LL Molded Case Circuit Breaker Test Report Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC Date : 05/03/2020 Ref no: TIE MAU 902 Location:QACC Bullding Second Breaker Data: Voltage Rating: 415V. Model Manufacturer: Schneider Elect Internal Rating: 160 Amperes ‘Thermal Element: ‘Adjustable: Yes Setting: 112-160 Amperes Final setting: 112 Amperes Magnetic Element Non Adjustable: Yes Setting: 1250 Amperes Fixed Front Identification-Left to Right | Pole 1 Pole2 Pole 3 Thermal Element | Thermal Element | Thermal Element Tripping time at 300% of Thermal _| 153.41 Seconds 158.9 Seconds 144 Seconds Pick up Inst. Tested on | Trip NA NA NA setting }___ist No Trip Remarks: Nil Test Equipment Used Model no. Serial no Calibration Due date Primary Injection Test Kit HC2 | 13-8322 19/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR) ‘Suresh Subbarayan | Delwin Dominic | _ Manoj Viswanathan Senthil Kumar g Ask | ps oF Ss KLASS N TRENDS ‘Trading, Contracting and Evonts W.LL ‘Test Report : Primary Injection Test (Stability ) Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC Location:QACC Building -Second Date : 05/03/2020 Ref no: TIE MAU 902 Floor Incomer Breaker Data: Breaker Data: Manufacturer: Merlin Gerin Voltage Rating: 415V Internal Rating: 800 Amperes Type: NSXBOOH (M) ‘Outgoing Breaker Dat: Breaker Data: Manufacturer: Schneider Electric Voltage Rating: 415V Internal Rating: 160 Amperes Type: TM160D Description ” Injected | incomer Breaker | Outgoing Current | trip j Norip) | Breaker (Trip / No Trip) Injected current between Incomer and Outgoing (R phase) | 336A | No Trip Tripped injected current between Incomer and Outgoing (Y phase) | 3364 Tripped | Injected current between Incomer and Outgoing (6 phase) | 336A _ | No Trip Tripped Acceptance Criter : Outgoing breaker should trip before incomer trips as per the co ordination study. Result: The Outing Tie AHU 902 breaker is tripped and Incomer breaker does not trip. Hence Protection discrimination study is verified and found ok. | Test Equipment Used Model no Serial no | Calibration Due date Primary Injection Test Kit Model HC-2 13-8322 | 19/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic ‘Manoj Viswanathan Senthil Kumar Be. Boke qs oy a. KILASS N TRENDS Ke Trading, Contracting and Evonts W.L.L Power Cable Test Report | Make: Schneider Electric _| Client Name: HIA EPSC Feeder Ref no: TIE AHU-204 | (Cable From: TIE AHU-204 Panel Tag no: DS-C4910-201 Date : 29/03/2020 Location : QACC Building Second Floor Cable To: AHU -C4910-204 Control Panel INSULATION RESISTANCE TEST Duration test: MIN ‘Test Voltage: 1000V Phase Values in Giga ohms R phase to earth ~ >2.260 Y phase to earth >2.260 B phase to earth 32.260 R Phase to Y phase 32.260 Y Phase to B phase >2.260 BPhasetoRphase >2.269 R Phase to Neutral 32.269 Y Phase to Neutral 32260 B Phase to Neutral 32.260 ‘Acceptance criteria: 100 MO Remarks: Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2021 DIGITAL MULTIMETER Fluke-376 -46030078ws 14/10/2020 Test Performed by KNT | Witnessed by ] Witnessed by MUHIBBAH | Approved by (Third Party KAHRAMAA TEM-AC ENGINEERING “R"GRADE CONTRACTOR) ‘Suresh Subbarayan Deivin Dominic Manoj Viswanathan — Senthil Kumar. BGs B= G4 phe KLASS N TRENDS &% Trading, Contracting and Events WiLL“ Power Cable Test Report Panel Tag no:DS-C4910-201 Make:Schneider Electric _| Client Name:HIA EPSC Location : QACC Building Second Floor Cable size: 3Rx1cx10mm? cu/pve/Isht > ; 410c10mm? cu/ishf ece Feeder Ref n Cable From:AHU-C4910-204 Control Panel AHU-204 | Date :29/03/2020 Cable Te }OA TP FIELD ISOLATOR AHU-C4910-204 INSULATION RESISTANCE TEST Duration ert IM Test Voge: 10000 Phase Valuen Gigs obs Rohae oer a6 Y phat arth 32260 phate to arth >2260 R Phase to Y phase 22.260 - Phase to pave >a2c0 ~ePhate to hace aaa Tecan aa TOON Remar Test Egupment Used Modena Seriatno Calration Due dae INSULATION TESTER Fluke- 1587, 27490055 27/02/2021 DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020 Witnessed by Approved by TestPerormediy | Winesed stPerormediy | wrnesedby | gquninoai’ | (Thicd Part KAHRAMAA A°GRADE | eNcineeR CONTRACTOR) SureshSubbarayan | Dalla Dominic | an] Vswoation Serta KLASS N TRENDS ‘Trading, Contracting and Evonts W.LL Power Cable Test Report Panel Tag no:DS-C4910-201 Make:Schneider Electric Client Name:HIA EPSC Cable size: 3Rx1Cx10mm? cu/pve/Ishf + - 1¢x10mm? cu/lshf ecc Feeder Ref no:TIE AHU-204 | Date :29/03/2020 Location : QACC Building Second Floor Cable From:40A TP FIELD ISOLATOR AHU-C4910-204 Cable To:AHU-C4910-204 MOTOR ~] INSULATION RESISTANCE TEST Durationtest: IMIN Test Voltage: 2000v _ Phase Values in Giga ohms Rphase to earth 32.260 Y phase to earth 7 32.260 - 8 phase to earth >2.260 Phase to ¥ phase 32260 Y Phase to B phase >2260 [ BPhasetoRphase | 7 22260 _ ‘Acceptance criteria: 100 MQ Remarks: Test Equipment Used Model no Serial no Calibration Due date | INSULATION TESTER Fluke- 1587 27490055 27/02/2021 DIGITAL MULTIMETER Fluke-376 ‘460300785 14/10/2020 Test Performed by | Witnessed by st sreencdy MUHIBBAH | (Third Party-KAHRAMAA “A"GRADE KNT TEM-AC ENGINEERING CONTRACTOR) Suresh Subbarayan | _Delwin Dominic | Manoj Viswanathan Senthil Kumar 4. fod OY | == KLASS N TRENDS K ‘Trading, Contracting and Events W.LL Panel Tag no: DS-C4910-201 | Make: Schneider Electric | Client Name: HIA EPSC Location: QACC Building Second Floor Date : 29/03/2020 Ref no: TIE AHU 204 INSULATION RESISTANCE TEST Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V Phase Values in Giga ohms R phase to earth ~ >2.260 Y phase to earth 32.260 B phase to earth >2.260 R Phase to V phase >2260 Y Phase to B phase >2.260 B Phase to R phase 32.260 Status: Breaker Open Position- Across Pole Phase Values in Giga ohms R phase to R’ phase 32.260 Y phase to Y Phase >2.260 B phase to B Phase >2.260 Test Equipment Used ‘Model no [Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2024 DIGITAL MULTIMETER Fluke-376 460300785 14/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR) Suresh Subbarayan_| Delwin Dominic ‘Manoj Viswanathan Senthil Kumar am | C7 9 ‘Trading, Contracting and Events W.LL KLASS N TRENDS K ‘MCCB Mechnical and Visual In: Panel Tag no: DS-C4910-201 _| Make: Schneider Electric Test Report Client Name: HIA EPSC Location: QACC Buil iing Second Floor Date : 29/03/2020 Ref no: TIE AHU 204 NETA Standard Reference below 7. Inspection and test procedures 7.6.1.1 Molded Case Circuit Breaker Visual and Mechanical Inspection: Sino Description NETA Remarks Visual and Mechanical Inspection a on Chechod Molded Case | NOTOK/NA Ref no 1 | Compare equipment nameplate data with drawings and | 7.6.1.1 Checked OK | Nil Specifications 1. Visual __| inspection (1) 2 | Inspect Physical and mechanical condition 76.11 Checked OK | Nil 4. Visual Inspection (2) 3° [Inspect anchorage and alignment 76.11 NA Nil 1. Visual Inspection (3) Verify the unit is clean 7641 Checked OK | Nil 1. Visual Inspection (4) 5 | Operate the circuit breaker to insure smooth operation 7614 Checked OK | Nil 1. Visual Inspection (5) 6 | Contact Resistance Testing Checked OK | Nil R phase Y phase B phase E Phas , Inspection (6) 8.458m0 8.572m0 7.580ma 7 | Inspect operating mechanism , contacts and arc chutesin | 7.6.1.1 Checked OK | Nil unsealed units 1. Visual Inspection (7) 8 | Perform adjustments for final protective device settings In| 7.6.1.1 Final Setting | Nil accordance with the co ordination study 1. Visual ‘Applied and Inspection (8) | tested OK | ‘Trading, Contracting and Events W.LLL KLASS N TRENDS Ke ___ MCCB Mechnical and Visual inspection Test Report $-C4910-201 ichneider Electric | Client Name: HIA EPSC Panel Tag no: Location: QACC Building -Second Date : 29/03/2020 Ref no: TIE AHU 204 Floor Acceptance Criteria: Compare bolted connection resistance values to values of similar connections, Investigate values which device from those of similar bolted connections by more than 50 percent of the lowest value. NETA Ref: 7. Inspection and test procedures 7.6.1.1 / 3.2 Note: NETA standard Reference no 7.6.1.1 Sub di ion 2: Electrical Tests ‘We do only insulation resistance tests for molded case circuit breaker and control wiring as per NETA Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker. Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER 1587 27480055 277022024 ‘CONTACT RESISTANCE METER DLRO 10 101322093 — 28/02/2021 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA | kNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan | Senthil Kumar Zo OY ee Trading, Contracting and Evonts W.LL KLASS N TRENDS. Ke Molded Case Circuit Breaker Test Report Panel Tag no: DS-C4910-201__| Make: Schneider Electric | Client Name: HIA EPSC Date : 29/03/2020 Ref no: TIE AHU 204 in QACC Building “Second Breaker Data: Manufacturer: Schneider Electric Voltage Rating: 415V. Model: NSX100-F Internal Rating: 25 Amperes ‘Thermal Element Adjustable: Yes_ Setting: Magnetic Element Non- Adjustable: Yes 18-25 Amperes Final setting: 25 Amperes Setting: Fixed 3004 Front Identification-Left to Right | Pole 1 [Pole 2 Pole 3 Thermal Element | Thermal Element Thermal Element Tripping time at 300% of thermal _| 76.05 Seconds 70.74 Seconds 73.54 Seconds pickup inst. Tested on | Trip NA NA NA — setting TNotrip ———| Remarks: Nil Test Equipment Used Model no Serial no Calibration Due date Primary Injection Test Kit C2 13-8322 19/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR) ‘Suresh Subbarayan | Delwin Dominic |" Manoj Viswanathan - ‘Senthil Kumar, g. gud cake yy SS KLASS N TRENDS ‘Trading, Contracting and Events W.L.L Test Report : Primary Injection Test (Stability ) Panel Tag no : DS-C4910-201 Make: Schneider Electric nt Name: HIA EPSC Location: QACC Building Second Date : 29/03/2020 Ref no: TIE AHU 204 Floor lncomer Breaker Data: Breaker Data: Manufacturer: Schneider Electric Voltage Rating: 415V Internal Rating: 630 Amperes Type: NSX630F Outgoing Breaker Data: Breaker Data: Manufacturer: Schneider Electric Voltage Rating: 415V Internal Rating: 25 Amperes Type: TM25D [Description injected | Incomer Breaker | Outgoing Current | rip jo trip) | Breaker | (Trip / No Trip) Injected current between incomer and Outgoing (R phase) | 75A | No Trip. Tripped Injected current between incomer and Outgoing ( ¥ phase) | 75A ‘No Trip Tripped Injected current between incomer and Outgoing (8 phase) | 75A | No Trip Tripped Acceptance Criteria: Outgoing breaker should trip before incomer trips as per the co ordination study. Result: The Outing Tie AHU204 breaker is tripped and Incomer breaker does not trip. Hence Protection discrimination study is verified and found ok. Test Equipment Used ‘Model no [Serial no Calibration Due date Primary Injection Test Kit ‘Model HC-2 13-8322 19/10/2020 Test Performed by | Witnessed by nessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT | TeM-ac ENGINEERING “R”GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar E08 Be OY KILASS N TRIENIDS: ‘Trading, Contracting and Evonts W.L.L Power Cable Test Report — Make: Schneider Electric _| Client Name: HIA EPSC Feeder Ref no: TIE FCU-B022 | Cable From: TIE FCU-B022 Panel Tag no: PNL-C4910-B63 Date : 21/03/2020 Location : QACC Building Second Floor Cable To: FCU -C4910-B022 Control Panel INSULATION RESISTANCE TEST Duration test: MIN Test Voltage: 1000V Phase Values in Giga ohms R phase to earth >2.260 Y phase to earth ~ >2.2G0 B phase to earth 32.260 R Phase to Y phase 32.260 [ Y Phase to B phase >2.260 B Phase to R phase >2.260 | R Phase to Neutral 32260 Y Phase to Neutral 32269 B Phase to Neutral >2.260 ‘Acceptance criteria: 100 MO Remarks: Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 2702/2024 DIGITAL MULTIMETER Fluke-376 "46030078 ws 14/10/2020 Test Performed by KNT | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA TEM-AC ENGINEERING “A/GRADE CONTRACTOR) ‘Suresh Subbarayan Delvin Dominic | Manoj Viswanathan Senthil Kumar Gg Ao ey ——— _ KLASS N TRENDS ‘Trading, Contracting and Events W.LL Power Cable Test Report Panel Tag no:PNL-C4910-B63 Make:Schneider Electric _| Client Name:HIA EPSC Cable size: 3Cx35mm? Cu/xlpe/swa/ishf + 10x16mm?Cu/Ishf Location : QACC Building Second Floor Feeder Ref no:TIE FCU BO22 | Date :21/03/2020 Cable From:FCU-C4910-8022 Control Panel Cable To:25A TP FIELD ISOLATOR FCU-C4910-B022 INSULATION RESISTANCE TEST Duration test: IMIN____Test Voltage: 1000V. Phase Values in Giga ohms R phase to earth 32.260 Y phase to earth 32.260 " Bphase to earth 32.260 R Phase to ¥ phase 32.260 Y Phase to B phase >2.260 | BPhase to R phase — _ 22.260 ‘Acceptance = Remarks: Test Equipment Used Model no Serial no Calibration Due date | INSULATION TESTER Fluke- 1587 27490055 27/02/2024 DIGITAL MULTIMETER Fluke-376 '46030078ws 14/10/2020 - Wi Test Performed by | Witnessed by messed by Approved by MUHIBBAH (Third Party-KAHRAMAA “A"GRADE KN TEM-AC ENGINEERING CONTRACTOR) Suresh Subbarayan ‘Manoj Viswanathan Senthil Kumar | & KLASS N TRENDS ‘Trading, Contracting and Events W.L.L Power Cable Test Report Panel Tag no:PNL-C4910-B63 Make:Schneider Electric Client Name:HIA EPSC Cable size: 3Cx35mm? Cu/xIpe/swa/Ishf +10x16mm?Cu/Ishf Location : QACC Building Second Floor | Cable From:25A TP FIELD ISOLATOR FCU-C4910-B022 Feeder Ref no:TIE FCU 8022 _| Date :21/03/2020 Cable To:FCU-C4910-8022 MOTOR INSULATION RESISTANCE TEST Duration test: MIN Test Voltage: 1000 Phase Values in Giga ohms phase to earth >2260 Y phase to earth 32260 : B phase to earth >2.260) RPhase to phase ~ >2.260 Y Phase to B phase 32.260 B Phase to R phase r~ - "32.260 a ‘Acceptance eiteriar 100 MO Remarks: Test Equipment Used Modeino | Setial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2024 DIGITAL MULTIMETER Fluke-376 46030078ws 1471072020 Witnessed by ‘Approved by ed by a Test Performed by | Witnessed by MUHIBBAH | (Third Party-KAHRAMAA “A"GRADE knT TEM-AC ENGINEERING CONTRACTOR) Suresh Subbarayan | _Delwin Dominic | Manoj Viswanathan Senthil Kumar 8. ud dab. @py a> KLASS N TRENDS Be Trading, Contracting and Evonts W.LL MCCB Insulation Resistance Test Report Panel Tag no: PNL-C4910-B63__| Make: Schneider Electric | Client Name: HIA EPSC Location: QACC Building -Second Floor Date : 21/03/2020 Ref no: TIE FCU-B022 INSULATION RESISTANCE TEST Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V Phase Values in Giga ohms. R phase to earth >2.260 Y phase to earth 32.260 7 B phase to earth >2.260 R Phase to Y phase 32.260 Y Phase to B phase >2.260 ~ B Phase to R phase >2.260 Status: Breaker Open Position- Across Pole Phase Values in Giga ohms R phase to R’ phase ~ >2.260, Y phase to ¥ ‘Phase >2260 B phase to B ‘Phase 32.260 ‘Acceptance criteria: 100 MO Test Equipment Used Model no Serialno Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2024 DIGITAL MULTIMETER Fluke-376 ‘4603007805 14/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR) Suresh Subbarayan | Delwin Domi Manoj Viswanathan: Senthil Kumar g R= Be (7 = KLASS N TRENDS EG Trading, Contracting and Events W.L.L MCCB Mechnical and Visual inspection Test Report Panel Tag no : PNL-C4910-B63_| Make: Schneider Electric | Client Name: HIA EPSC Location: QACC Bui Floor Date : 21/03/2020 Ref no: TIE FCU-B022 NETA Standard Reference below 7. Inspection and test procedures 7.6.1.1 Molded ~Case Circuit Breaker Visual and Mechanical Inspection: Sl.no Description NETA Remarks STANDARD —_| Checked OK/Checked NOT OK/NA Visual and Mechanical Inspection 76.1.4 Molded Case Refno 1 | Compare equipment nameplate data with drawings and 7614 Checked OK | Nil Specifications 1. Visual Inspection (1) 2 | inspect Physical and mechanical condition \7.6.1.2 Checked OK | Nil 1. Visual Inspection (2) 3 __ | Inspect anchorage and alignment 7611 NA [Nil 1. Visual Inspection (3) 4 | Verify the units clean 76.11 Checked OK | Nil 4. Visual Inspection (4) 5 | Operate the circuit breaker to insure smooth operation 7644 Checked OK | Nil 1. Visual Inspection (5) 6 | Contact Resistance Testing 7eaa Checked OK | Nil 2. Visual Inspection (6) R phase Y phase B phase 2.278m0 2.324ma 2.198m0, 7 | Inspect operating mechanism , contacts and arc chutesin | 7.6.1.1 Checked OK | Nil unsealed units 1. Visual Inspection (7) 8 | Perform adjustments for final protective device settings in| 7.6.1.1 Final Setting | Nil accordance with the co ordination study 1. Visual Applied and Inspection (8) | tested OK KLASS N TRENDS Trading, Contracting and Evonts W.LL MCCB Mechnical and Visual Inspection Test Report Panel Tag no: PNL-C4910-863_| Make: Schneider Electric | Client Name: HIA EPSC Date : 21/03/2020 Ref no: TIE FCU-B022 | Loratlon: QACC Building Second Acceptance Criteria: ‘Compare bolted connection resistance values to values of similar connections. Investigate values which device from those of similar bolted connections by more than 50 percent of the lowest value. NETA Ref: 7. Inspection and test procedures 7.6.1.1 / 3.2 Note: NETA standard Reference no 7.6.1.1 Sub division 2: Electrical Tests We do only insulation resistance tests for molded case circuit breaker and contro! wiring as per NETA Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker. Test Equipment Used ‘Model no ‘Serial no Calibration Due date INSULATION TESTER 1587 27490055 27/02/2024 ‘CONTACT RESISTANCE METER DLRO 10 101322093 28/02/2021 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR) ‘Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar 5 Re gaia Ca el Panel Tag no : PNL-C4910-B63 Date : 21/03/2020 Molded Case Circuit Breaker Test Report KILASS N TRENDS ‘Trading, Contracting and Events W.LL Make: Schneider Electric | Client Name: HIA EPSC Location: QACC Building -Second Floor Ref no: TIE FCU-B022 Breaker Dat: Manufacturer: ABB Voltage Rating: 415V_ Model: Tmax XT1C 160 Internal Rating: 40 Amperes ‘Thermal Element: Adjustable: Yes_ Magnetic Element Non- Adjustable: Yes Setting: Fixed 450 Setting: 28-40 Amperes Final setting: 40 Amperes Front Identification-Left to Right Pole 1 Pole 2 Pole 3 Thermal Element | Thermal Element Thermal Element Tripping time at 300% of thermal pickup 23.56 Seconds 20.59 Seconds 24.40 Seconds [inst. Tested on [Trip NA NA NA — setting No Trip Remarks: Test Equipment Used Model no Serial no Calibration Due date Primary Injection Test Kit C2 13-8322 19/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar das SFO SS Oy KILASS N TRENDS. Trading, Contracting and Events W.L.L a ‘Test Report : Primary Injection Test (Stability ) anel Tag no : PNL-C4910-B63_| Make: Schneider Electric | Client Name: HIA EPSC Location: QACC Building -Second Date : 21/03/2020 Ref no: TIE FCU-B022 rm Floor Incomer Breaker Data: Breaker Data: Manufacturer: Schneider Electric Voltage Rating: 415V Internal Rating: 63 Amperes Type: NSX100F ‘Outgoing Breaker Dat: Breaker Data: Manufacturer: Schneider Electric Voltage Rating: 415V Internal Rating: 40 Amperes Type: Tmax XT1C 160 [ Description Injected | incomer Breaker | Outgoing Current | rip fo rip) | Breaker (Trip / No Trip) Injected current between Incomer and Outgoing (R phase) | 120A | No Trip "| Tipped Injected current between Incomer and Outgoing (Y phase) | 120A _| No Trip Tripped Injected current between Incomer and Outgoing (B phase) | 120A | No Trip Tripped Acceptance Criteria: Outgoing breaker should trip befor \comer ips as per the co ordination study. Result: The Outing Tie FCU BO22 breaker is tripped and Incomer breaker does not trip. Hence Protection discrimination study is verified and found ok. Test Equipment Used J Model no Serial no Calibration Due date Primary Injection Test Kit | Model HC-2 13-8322, 19/10/2020 Test Performed by | Witnessed by KNT TEM-AC ENGINEERING essed by MUHIBBAH ‘Approved by (Third Party-KAHRAMAA “R"GRADE CONTRACTOR) | Suresh Subbarayan | Delwin Dominic ‘Manoj Viswanathan Senthil Kumar 3B. oe Gy = KLASS N TRENDS KE = ‘Trading, Contracting and Events W.LL Power Cable Test Report Panel Tag no: PNL-C4910-B26 Make: Schneider Electric __| Client Name: HIA EPSC Date : 21/03/2020 Feeder Ref no: TIE FCU-B023 | Location : QACC Building Second Floor | Cable From: TIE FCU-B023 Cable To: FCU -C4910-B023 Control Panel INSULATION RESISTANCE TEST Duration test: MIN Test Voltage: 1000V Phase Values in Giga ohms R phase to earth >2.260 Y phase to earth >2.260 B phase to earth 32.260 R Phase to Yphase >2.260 ~ Y Phase to B phase 32.260 B Phase to R phase ~>2.260 R Phase to Neutral 32260 Y Phase to Neutral 32260 B Phase to Neutral 32.260 ‘Acceptance criteri Remarks: Test Equipment Used Modelno Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490085 27/02/2021 DIGITAL MULTIMETER Fluke-376 ‘46030078ws 14/10/2020 Test Performed by KNT | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA TEM-AC ENGINEERING “R”GRADE CONTRACTOR) ‘Suresh Subbarayan Delvin Dominic | Manoj Viswanathan Senthil Kumar Bf Bore “pS CW =—— ssa KLASS N TRENDS ‘Trading, Contracting and Events W.LL Power Cable Test Report i Make:Schneider Electric Client Name:HIA EPSC Panel Tag no:PNL-C4910-826 Cable size: 3Rx1Cx10mm? Cu/Ishf + 10x10mm?Cu/IshF Location : QACC Building Second Floor Cable From:FCU-C4910-8023 Control Panel Feeder Ref no:TIE FCU B023_| Date :21/03/2020 INSULATION RESISTANCE TEST Duration test:IMIN Test Voltage: 1000V. Phase Values in Giga ohms R phase to earth 32.260 Y phase to earth 32260 B phase to earth 32.262 Phase to phase 32.260 YPhasetoB phase >2.260 B Phase to R phase 7 32260 —Y ‘Acceptance criteria: 100 MQ Remarks: Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2024 DIGITAL MULTIMETER Fiuke-376 '46030078ws 14/10/2020 B ‘Approved Test Performed by Wiimesseg OY a ewe MUHIBBAH (Third Party-KAHRAMAA “A"GRADE ENGINEERING CONTRACTOR) Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar pa | ape yy | Se ‘Trading, Contracting and Events W.L.L KLASS N TRENDS K __ Power Cable Test Report Panel Tag no:PNL-C4910-826 Make:Schneider Electric Client Name:HIA EPSC Cable size: 3Rx1Cxi0mm? Cu/Ishf + 1¢x10mm?Cu/Isht Location : QACC Building Second Floor __| Cable From:25A TP FIELD ISOLATOR FCU-C4920-8023 | Feeder Ref no:TIE FCU 8023 | Date :21/03/2020 Cable To:FCU-C4910-8023 MOTOR INSULATION RESISTANCE TEST Duration test: 1MIN Test Voltage: 1000V Phase Values. ohms a R phase to earth >2.260 Y phase to earth >2.260 Bphase to earth 22.262 R Phase to ¥ phase 32.260 Y Phase to B phase 32.260 ~_BPhase to R phase a "32.260 _ ‘Acceptance criteria: 100 MQ. Remarks: Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055, 27/02/2021 DIGITAL MULTIMETER Fluke 376 60300785 19/10/2020 Witnessed by ‘Approved by 1 ed by jest Performed by’ ‘Witnessed by MUHIBBAH (Third Party-KAHRAMAA “A”GRADE KNT TEM.AC ENGINEERING CONTRACTOR) Suresh Subbarayan | _Delwin Dominic | Manoj Viswanathan Senthil Kumar B: fa Ta OY a KLASS N TRENDS Ke Trading, Contracting and Events W.LL MCCB Insulation Resistance Test Report 4910-826 _| Make: Schneider Electric | Client Name: HIA EPSC Location: QACC Building -Second Floor ranel Tag no : PN Date : 21/03/2020 Ref no: TIE FCU-B023 INSULATION RESISTANCE TEST Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V Phase Values in Giga ohms ] Rphase to earth 32260 Y phase to earth 32.260 B phase to earth 32.260 R Phase to V phase 32.260 Y Phase to B phase >2.260 B Phase to R phase 32.260 Status: Breaker Open Position- Across Pole Phase Values in Giga ohms R phase to R’ phase ~>2.260 Y phase to Phase >2.260 B phase to 6 ‘Phase 32260 ‘Acceptance criteria: 100 MA. Test Equipment Used Model no Serial no Calibration Due date INSULATION TESTER Fluke- 1587 27490055 27/02/2021 DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party KAHRAMAA KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR) ‘Suresh Subbarayan | Delwin Dominic ‘Manoj Viswanathan Senthil Kumar 8A | pe C7 ae Panel Tag no : PNL-C4910-B26 ‘Trading, Contracting and Events W.LL KILASS N TRENDS Ke (MCCB Mechnical and Visual inspection Test Report [ Make: Schneider Electric | Client Name: HIA EPSC Location: QACC Building -Second Date : 21/03/2020 Ref no: TIE FCU-B023 Floor NETA Standard Reference below 7. Inspection and test procedures 7.6.1.1 Molded ~Case Circuit Breaker Visual and Mechanical Inspection: ‘Sno Description NETA Remarks : STANDARD —_| Checked 7 Visual and Mechanical Inspection ee Ok/Checkee Molded Case | NOT OK/ NA Ref no 1 | Compare equipment nameplate data with drawings and 7611 Checked OK | Nil Specifications 1. Visual I. Inspection (1) 2 | inspect Physical and mechanical condition 7.6.1.1 Checked OK | Nit 4. Visual Inspection (2) 3 [Inspect anchorage and alignment - 7.6.1.1 NA Nil 1. Visual Inspection (3) 4 | Verify the unitis clean 76i4 Checked OK | Nil 1. Visual Inspection (4) 5 | Operate the circuit breaker to insure smooth operation 7644 Checked OK | Nil 1. Visual Inspection (5) 6 | Contact Resistance Testing 7614 Checked OK | Nil 2. Visual y 8 R phase phase phase Inopection (6) 2.235m0 2.018ma 2.1880, 7 | Inspect operating mechanism , contacts and arc chutes in | 7.6.1.1 Checked OK | Nit unsealed units 1. Visual Inspection (7) 8 | Perform adjustments for final protective device settings in| 7.6.1.1 Final Setting | Nil accordance with the co ordination study 1. Visual ‘Applied and Inspection (8) | tested OK ‘Trading, Contracting and Evonts W.LL MCCB Mechnical and Visual inspection Test Report Panel Tag no: PNL-C4910-B26__| Make: Schneider Electric | Client Name: HIA EPSC Date : 21/03/2020 Ref no: TIE FCU-B023 Pecan ‘QACC Building -Second KLASS N TRENDS Ka Acceptance Criteri Compare bolted connection resistance values to values of similar connections. Investigate values which device from those of similar bolted connections by more than 50 percent of the lowest value. NETA Ref: 7. Inspection and test procedures 7.6.1.1 / 3.2 Note: NETA standard Reference no 7.6.1.1 Sub division 2: Electrical Tests We do only insulation resistance tests for molded case circuit breaker and control wiring as per NETA Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker. Test Equipment Used |_ Modelno Serial no | Calibration Due date "INSULATION TESTER 1587 27490055 ~~ 27/02/2024 CONTACT RESISTANCE METER | DLRO 10 101322093 wrapoa | Test Performed by ‘Witnessed by ‘Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “A”GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic Manoj Viswanathan ‘Senthil Kumar Bele ta Oi ee KILASS N TRENDS ‘Trading, Contracting and Evonts W.L.L Molded Case Circuit Breaker Test Report Panel Tag no : PNL-C4910-B26 Date : 21/03/2020 Ref no: TIE FCU-B023 Floor ‘Make: Schneider Electric | Client Name: HIA EPSC Location: ‘QACC Building Second Breaker Dati Manufacturer: ABB Voltage Rating: 41SV_ Model: T max XT1C 160 Internal Rating: 40 Amperes Thermal Elemen Adjustable: Yes_ Setting: 28-40 Amperes Final setting: 40 Amperes Magnetic Element Non- Adjustable: Yes Setting: Fixed 4508 Front identification-Left to Right | Pole 1 Pole 2 Pole 3 Thermal Element Thermal Element Thermal Element Tripping time at 300% of 20.56 Seconds 22.84 Seconds 724.69 Seconds ‘thermal pickup Inst. Tested on | Trip NA NA NA — setting OTP Remarks: Nil Test Equipment Used Model no Serial no Calibration Due date Primary Injection Test Kit HC2 13-8322 19/10/2020 ‘Suresh Subbarayan | Delwin Dominic Manoj Viswanathan | Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR) ‘Senthil Kumar A | tala oY SS KILASS N TRENDS Ka Trading, Contracting and Events W.LL Test Report : Primary Injection Test (Stability ) [Panel Tag no: PNL-C4910-826 | Make: Schneider Electric | Client Name: HIA EPSC | Date : 21/03/2020 Ref no: TIE FCU-B023 rpeatio # QACC Building “Second | incomer Breaker Data Breaker Dat Manufacturer: Schneider Electric Voltage Rating: 415V Internal Rating: 63 Amperes Type: NSX100F Outgoing Breaker Data: Breaker Data: Manufacture hneider Electric Internal Rating: 40 Amperes Type: Imax xT1¢ 160 Description Injected] income Breaker | Outgoing — Current | rip fo Trip) | Breaker (Trip / No Trip) Injected current between Incomer and Outgoing (R phase) | 120A | No Trip Tripped | Injected current between Incomer and Outgoing (Y phase) | 120A | No Trip Tripped Injected current between Incomer and Outgoing (B phase) | 120A | No Trip Tripped Acceptance Criteria: Outgoing breaker should trip before incomer as per the co ordination study. Result: The Outing Tie FCU 8023 breaker is tripped and incomer breaker does not trip. Hence Protection discrimination study is verified and found ok. Test Equipment Used Model no Serial no Calibration Due date Primary Injection Test Kit Model HC-2 13-8322 19/10/2020 Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party KAHRAMAA KNT TEM-AC ENGINEERING “A”GRADE CONTRACTOR) Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan ~ ‘Senthil Kumar g-40% | ee Cy ee. vm Chu ’ nally halle a Letter M/s Al Ajjaj Limited Company Head of Distribution Protection Section 270220202 —=~S*~*S*«S*«C OTN AL ED/EDR/1086/2020 1 lla g pp RENEWAL OF LICENSE FOR LV PANEL esas PROTECTION TESTING ED/EDR/P3-015 ses This has the reference to your fee payment receipt dated on 26/02/2020 (Receipt No. 6260220000065) for renewal of license for LV Panel Protection Testing of Mr. Mr. Senthilkumar Kailyamoorthy License No. ED/EDR/ P3-015. This is to inform you that your license has been renewed for further 1 (One) year until 31-12-2020. ae ing. Abdulla Ebrahim M H Ahmad Head — Distribution Protection Page 4 of AHLMOOWVANTWS U VINTDCIHANS@ WHEN et ent Sutin pyfey in ¢ | omy THO pte a voquedns39, : viant Aieuonen _ va - hr ( e a mt oz0z60120 Aude ai ain og sis tia 1 iter Cast /taz aoa IA vos rey ae ae dels ewRS Crew: — gogerasecez onal Trg ead owt woaud 3 ey, - Ns Orey iy Wueg Aruepisey tert ‘ copy oe SS 2/ 18180 40 24815 A echeewt

You might also like