Power Cable Test Report
Panel Tag no: EMCC-C4910-251 Make: Schneider Electric
Date : 05/03/2020 Feeder Ref no: TIE MAU-901
Location : QACC Building Second Floor | Cable From: TIE MAU-901
Cable To: MAU-C4910-901 Control Panel
jent Name: HIA EPSC
INSULATION RESISTANCE TEST
Duration test: IMIN Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth 32.260
Y phase to earth _ >2.262
B phase to earth >2.260
R Phase to Y phase >2.260 |
Y Phase to B phase 32260
B Phase to R phase >2.260
R Phase to Neutral 32.260
Y Phase to Neutral 22.262
B Phase to Neutral >2260
‘Acceptance criteria: 100 MO
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2021
DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020
Test Performed by KNT |” Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Parky-KAHRAMAA
TEM-AC ENGINEERING “A"GRADE CONTRACTOR)
‘Suresh Subbarayan Delwin Domi
Bio | agle Gk a
Manoj Viswanathan ‘Senthil KumarKLASS N TRENDS Ze
Trading, Contracting and Events W.LL
S Power Cable Test Report
Panel Tag no: EMCC-C4910-251 Make: Schneider Electric | Client Name: HIA EPSC
Cable size: 4Cx35mm? Cu/xlpe/swa/Ishf +
10x35mm? Cu/ishf ECC Feeder Ref no: TIE MAU 901 _| Date : 05/03/2020
Location : QACC Building Second Floor _| Cable From: MAU-C4910-901 Control Panel
Cable To Indoor unit
225A TP FIELD ISOLATOR MAU-C4910-901 INDOOR UNIT
INSULATION RESISTANCE TEST
Duration test: 1MIN- Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth >2.260
Y phase to earth - 22.260 7
B phase to earth >2.260
| RPhase to ¥ phase - — 22260 7 |
Y Phase to B phase 32.260
B Phase to R phase 32.260
‘Acceptance criteria: 100 MO
Remarks:
Test Equipment Used ‘Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2021
DIGITAL MULTIMETER Fuke-376 4603007 ws 190/202
7 ' Witnessed by ‘Approved by
Test tt Witne by
st Fetormedby ‘essed ov MUHIBBAH (Third Party-KAHRAMAA “A"GRADE
ENGINEERING CONTRACTOR)
Suresh Subbarayan Delwin Dominic Manoj Viswanathan Senthil Kumar
948) ey‘Trading, Contracting and Events W.L.L
KLASS N TRENDS Ke
Power Cable Test Report
Panel Tag no: EMCC-C4910-251 Make: Schneider Electric] Client Name: HIA EPSC
Cable size: 4Cx95mm™ Cu/xipe/swa/sht .
1650mm? Cu/lshf ECC Date 15/08/2020)
= = QACC Building Second Floor _| Cable From: MAU-C4910-901 Control Panel
Feeder Ref no: TIE MAU 901
Cable To Outdoor unit : 140A TP FIELD ISOLATOR MAU-C4910-901 OUTDOOR UNIT
INSULATION RESISTANCE TEST
Duration test: IMIN Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth >2.260
Y phase to earth 32.260
"— Bphase to earth "32.260
R Phase to V phase 32.260
Y Phase to 8 phase 22.260
| B Phase to R phase 32.260
‘Acceptance criteria: 100 MO
Remarks:
Test Equipment Used ‘Model no Serialno Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2024
DIGITAL MULTIMETER Fluke-376 460300785 4/10/2020
Witnessed by ‘Approved by
Test Performed by | Witnessed by og
Kar TEM AC MUHIBBAH (Third Party-KAHRAMAA “A” GRADE
ENGINEERING CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar
BA Ts &y esKLASSN TRENDS &
Trading, Contracting and Evonts W.LL
Power Cable Test Report 2
Panel Tag no: EMCC-C4910-251 Make: Schneider Electric | Client Name: HIA EPSC
Cable size: 4Cx35mm? Cu/xipe/swa/isht+ |
sf no: De
tex35mm? Cuylsht ECC Feeder Ref no: TIE MAU 901 | ate : 05/03/2020
ion : i Cable From: 25A TP FIELD ISOLATOR MAU-C4910-901
Location : QACC Building Second Floor INDOOR UNIT
Cable To Indoor unit :MAU-C4910-901 INDOOR UNITMOTOR
INSULATION RESISTANCE TEST
Duration test: 1MIN Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth >2.260
Y phase to earth 22.260
B phase to earth >2.260
R Phase to Y phase 22.260
Y Phase to B phase 22.260
l B Phase to R phase >2.260
Acceptance ria: 100 MQ. —
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
[INSULATION TESTER Fluke- 1587 27490055 27/02/2021
DIGITAL MULTIMETER Fluke 376 460300785 14/10/2020
Tw Witnessed by ‘Approved by
ftnessed by
Test Performed by wines ¥ MUHIBBAH (Third Party-KAHRAMAA “A"GRADE
ENGINEERING CONTRACTOR)
‘Suresh Subbarayan Delwin Dominic Manoj Viswanathan Senthil KumarKLASS N TRENDS K
‘Trading, Contracting and Events W.LL
____ MCCB insulation Resistance Test Report
Panel Tag no : EMCC-C4910-251 | Make: Schneider Electric | Client Name: HIA EPSC
Location: QACC Building -Second
Floor
Date : 05/03/2020 Ref no: TIE MAU 901.
INSULATION RESISTANCE TEST
Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V
Phase y Values in Giga ohms
R phase to earth >2.260
Y phase to earth 32.260
B phase to earth 32.260
R Phase to ¥ phase >2260
Y Phase to B phase >2.260
B Phase to R phase 32.269
Status: Breaker Open Position- Across Pole
Phase ] Values in Giga ohms
R phase to R’ phase 32.260
Y phase to V Phase - 32.260
B phase to B Phase 32.260 ~
‘Acceptance criteria: 100 MO
Test Equipment Used Model no Serial no. Calibration Due date
INSULATION TESTER ~~ Fluke- 1587 27490055 27/02/2021
DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR)
‘Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan ‘Senthil Kumar
4 0 [ok OY SSKLASS N TRENDS
Trading, Contracting and Events WALL
MCCB Mechnical and Visual Inspection Test Report
Panel Tag no : EMCC-C4910-251 | Make: Schneider Electric | Client Name: HIA EPSC
Date : 05/03/2020 Ref no: TIE.MAU.901___| Location:@ACC Building ~Second Floor
NETA Standard Reference below
7. Inspection and test procedures
7.6.1.1 Molded ~Case Circuit Breaker
Visual and Mechanical inspection:
Sno | Description NETA, Remarks
i : STANDARD | Checked
7 Inspect
Visual and Mechanical Inspection eas ony chekee
Molded case | NOT OK/ NA
Ref no
1 | Compare equipment nameplate data with drawings and 7614 Checked OK | Nil
Specifications 1. Visual
Inspection (1)
2 _ | inspect Physical and mechanical condition 7.6.1.1 Checked OK | Nil
1. Visual
Inspection (2)
3 | Inspect anchorage and alignment 76414 NA [Nil
1. Visual
Inspection (3)
4 _ | Verify the unit is clean Tedd Checked OK | Nil
1. Visual
Inspection (8)
5 | Operate the circuit breaker to insure smooth operation 76.1.4 Checked OK | Nil
1. Visual
Inspection (5)
6 | Contact Resistance Testing 7611 Checked OK | Nil
2. Visual
Rph Yh hi
phase pase 8 phase Inspection (6)
355.200 405.920 370.30
7 | inspect operating mechanism, contacts and arc chutes in [7.6.1.1 Checked OK | Nil
unsealed units 1. Visual
Inspection (7)
8 | Perform adjustments for final protective device settings in| 7.6.1.1 Final Setting | Nil
accordance with the co ordination study 1. Visual Applied and
Inspection (8) | tested OKKLASS N TRENDS Ze
‘Trading, Contracting and Events W.L.L
MCCB Mechnical and Visual In: Test Report
Panel Tag no : EMCC-C4910-251 | Make: Schneider Electric | Client Name: HIA EPSC
Date : 05/03/2020 Ref no: TIE.MAU.901 Location:QACC Building -Second Floor
Acceptance Criteri
Compare bolted connection resistance values to values of similar connections. Investigate values which
device from those of similar bolted connections by more than SO percent of the lowest value. NETA Ref
7. Inspection and test procedures 7.6.1.1 / 3.2
Note: NETA standard Reference no 7.6.1.2
Sub division 2: Electrical Tests
We do only insulation resistance tests for molded case circuit breaker and control wiring as per NETA
Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker.
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER 1587 27490055 27/02/2021
CONTACT RESISTANCE METER | DLRO 10 101322093 28/02/2021
‘Test Performed by | Witnessed by | Witnessed by MUHIBBAH J Approved by (Third Party-KAHRAMAA,
KNT TEM-AC ENGINEERING “A" GRADE CONTRACTOR)
‘Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar
BARE | aes C7 ee‘Trading, Contracting and Events W.LL
KILASS N TRENDS Ke
Molded Case Circuit Breaker Test Report
Panel Tag no : EMCC-C4910-251 | Make: Schneider Electric | Client Name: HIA EPSC
Date : 05/03/2020 Fear n:QACC Building -Second
——_____|
Ref no: TIE MAU 901
Breaker Dat:
Manufacturer: Schneider Electric Voltage Rating: 415V_ Model: NSX250F
Internal Rating: 200 Amperes
Thermal Element:
Adjustable: Yes__ Setting: 140-200 Amperes Final setting: 140 Amperes
‘Magnetic Element
Adjustable: Yes
Setting: 10
Front Identification-Left to | Pole 1 Pole 2 Pole 3
Right
Thermal Element | Thermal Element Thermal Element
Tripping time at 285% of 207 Seconds 211.5 Seconds 241.27 Seconds
Thermal Pickup
inst. Tested on | Trip NA NA NA
— setting | No Trip
Remarks: Nil
Test Equipment Used Model no Serial no Calibration Due date
Primary Injection Test Kit HO? i 13-8322 19/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT | Tewac ENGINEERING “A” GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | _ Manoj Viswanathan Senthil Kumar
pee [ss | OeTrading, Contracting and Evonts W.LL
KLASS N TRENDS Ke
Panel Tag no : EMCC-C4910-251
Test Report : Primary Injection Test (Stability)
Make: Schneider Electric | Client Name: HIA EPSC
Date : 05/03/2020 Ref no: TIE AHU 901
Location:QACC Bi
Floor
ling Second
Incomer Breaker Data:
Breaker Data:
Manufacturer: Schneider Electric Voltage Rating: 415V
Internal Rating: 680 Amperes Type: NSX630F
Outgoing Breaker Data:
Breaker Data:
Manufacturer:
‘Schneider Electric Voltage Rating: 415V
Internal Rating: 200 Amperes Type: TM200D
Description ‘Injected | Incomer Breaker | Outgoing
Current | (rip /no Trip) | Breaker
(Trip / No Trip)
Injected current between Incomer and Outgoing (R phase) | 363A | No Trip Tripped
Injected current between incomer and Outgoing ( Y phase) | 363A | No Trip Tripped
Injected current between Incomer and Outgoing (B phase) | 363A | No Trip Tripped
Acceptance Criteria: Outgoing breaker should trip before incomer trips as per the co ordination study.
Result: The Outing Tie AHU 901 breaker is tripped and Incomer breaker does not trip. Hence Protection
discrimination study is verified and found ok.
Test Equipment Used } ‘Model no
Serial no | Calibration Due date
Primary Injection Test Kit Model HC-2
13-8322, 19/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING
“R"GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan
‘Senthil Kumar
3. Bee wa ey
=KILASS N TRENDS
‘Trading, Contracting and Evonts W.L.L
i Power Cable Test Report_
Panel Tag no: EMCC-C4910-228 Make: Schneider Electric __| Client Name: HIA EPSC
Date : 05/03/2020 Feeder Ref no: TIE.MAU-902 |
Cable T
INSULATION RESISTANCE TEST
|AU-C4910-902 Control Panel
Location : QACC Building Second Floor | Cable From: TIE. May-902
Duration test: 1MIN Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth >2.260
Y phase to earth 2.260
B phase to earth 32.260)
R Phase to V phase 32.260
Y Phase to B phase 32.260
B Phase to R phase 32.260
R Phase to Neutral >2.260
Y Phase to Neutral 32260
B Phase to Neutral 32.260
‘Acceptance criteria: 100 MO
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2024
DIGITAL MULTIMETER Fluke-376 -46030078s 14/10/2020
Test Performed by KNT | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
TEM-AC ENGINEERING “A"GRADE CONTRACTOR)
| Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar
8. joe as wy ————.KILASS N TRENDS
Trading, Contracting and Evonts W.L.L
Cable Test Report
Powel e
Panel Tag no: EMCC-C4910-228 Make: Schneider Electric Client Name: HIA EPSC
~
Cable size: 4Cx35mm? Cu/xlpe/swa/Ishf +
1Cx35mm? Cu/Ishf ECC
Feeder Ref no: TIE MAU 902 | Date : 05/03/2020
Location : QACC Building Second Floor
Cable From: MAU-C4910-902 Control Pane!
Cable To indoor unit : 254 TP FIELD ISOLATOR MAU-C4910-902 INDOOR UNIT
INSULATION RESISTANCE TEST
Duration test: 1MIN- Test Voltage: 1000V
ase Values in Giga ohms
R phase to earth 32.260
Y phase to earth 32.260
8 phase to earth 32.260
R Phase to Y phase im >2.260 |
‘Phase to B phase >2.260
B Phase to R phase 32.260
“Roceptance criteria: 100 MO
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke 1587 27490055 27/02/2024
DIGITAL MULTIMETER Fluke 376 46030078 ws 44/10/2020
- Witnesse iby
Test Performed by | Witnessed by seed by WR a
MUNIBBAH (Third Party-KAHRAMAA “A"GRADE
KNT TEM-AC
ENGINEERING CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar
g se | ph
&
SeKLASS NTRENDS (&%
‘Trading, Contracting and Evonts W.L.L
Power Cable Test Report
Panel Tag no: EMCC-C4910-228 Make: Schneider Electric Client Name: HIA EPSC
Cable size: 4CxS0mm? Cu/xIpe/swa/Ishf +
1CxSOmm? Cu/Ishf ECC
Location : QACC Building Second Floor __| Cable From: MAU-C4910-902 Control Panel
Feeder Ref no: TIE MAU 902 _| Date : 05/03/2020
Cable To Outdoor unit : 225A CIRCUIT BREAKER MAU-C4910-902 OUTDOOR UNIT
INSULATION RESISTANCE TEST
Duration test: MIN Test Voltage: 1000V
Phase Values in Giga ohms
Rphase to earth >2.260)
Y¥ phase to earth >2.269
B phase to earth >2.260
RPhasetoY phase (32260 -
Y Phase to 8 phase >2.260
[ 8 Phase to R phase 32.260
‘Acceptance criteria: 100 MQ
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke 1587 27480055 27/02/2024
DIGITAL MULTIMETER Flake 376 "46030078ws 14/10/2020
1
| Test Performed by | Witnessed by Witnessed by Approved by
MUHIBBAH | (Third Party-KAHRAMAA “A” GRADE
KNT TEM-AC
ENGINEERING CONTRACTOR)
Suresh Subbarayan_| _Delwin Dominie | Manoj Viswanathan Senthil Kumar
bbe | pple 6 SSKILASS N TRENDS K
‘Trading, Contracting and Evonts W.LL
Power Cable Test Report
Panel Tag no: EMCC-C4910-228 Make: Schneider Electric Client Name: HIA EPSC
Cable size: 4Gx35mni™ Cu/xipe/swa/shf + ~ 7
1exasmmn? ColshF ECC Feeder Ref no: TIE MAU 902 | Date: 05/03/2020
ocat 7 -C4910-
om : QACC Building Second Floor _| Cable From: 258 TP FIELD ISOLATOR MAU-C4910-902
INDOOR UNIT
Cable To indoor unit :MAU-C4910-902INDOOR UNIT MOTOR |
INSULATION RESISTANCE TEST
Duration test: 1MIN Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth >2.260
Y phase to earth : >2.260 —
B phase to earth >2.260
R Phase to Y phase >2.260
Y Phase to B phase 22.260
B Phase to R phase >2.260
‘Acceptance criteria: 100 MO
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2021
DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020
Witnessed by ‘Approved by
ed b
Test Performed by Wied by MUHIBBAH (Third Party-KAHRAMAA “A”GRADE
knT TEM-AC
ENGINEERING CONTRACTOR)
Suresh Subbarayan | _Delwin Dominic | Manoj Viswanathan ‘Senthil Kursar
& Bib | gle oy SSKLASS N TRENDS Be
‘Trading, Contracting and Evonts W.L.L
MCB Insulation Resistance Test Report
Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC
Location: QACC Building -Second
Floor
Date : 05/03/2020 Ref no: TIE MAU 902
INSULATION RESISTANCE TEST
Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth 32.260
Yphasetoearth 32.260
B phase to earth >2.260
R Phase to Y phase 32.260
Y Phase to B phase 7 >2.260
B Phase to R phase >2.260
Status: Breaker Open Position- Across Pole
Phase Values in Giga ohms
R phase to R’ phase 32.260
Y phase to Y ‘Phase 32.260
B phase to B Phase 32260
‘Acceptance criteria: 100 MO
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490085 27/02/2024
DIGITAL MULTIMETER. Fluke-376 46030078ws 14/10/2020
| Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic Manoj Viswanathan Senthil Kumar
BROS [Tas eL SsKLASS N TRENDS
‘Trading, Contracting and Events W.L.L
~
MCCB Mechnical and Visual inspection Test Report
Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC
Date : 05/03/2020 [Refno: TIEMAU902___| Location:QACC Building -Second Floor
NETA Standard Reference below
7. Inspection and test procedures
7.6.1.1 Molded ~Case Circuit Breaker
Visual and Mechanical Inspecti
Sino Description NETA Remarks
i STANDARD | Checked
Visual and Mechanical Inspection ee on/checked
Molded case | NOT OK/ NA
Ref no
1 | Compare equipment nameplate data with drawings and | 7.6.1.1 Checked OK | Nil
Specifications 1. Visual
Inspection (1)
2 _ | inspect Physical and mechanical condition 76.11 ‘Checked OK | Nil
1. Visual
Inspection (2)
3__ | inspect anchorage and alignment 7614 NA [NT
1. Visual
Inspection (3)
4 | Verify the u Checked OK | Nil
Inspection (4)
5 | Operate the circuit breaker to insure smooth operation 7614 Checked OK | Nil
1. Visual
Inspection (5)
& | Contact Resistance Testing 7614 Checked OK | Nil
2. Visual
Y phi B phi
R phase phase phase Inspection (6)
525u0 51010 568.5u0
7 | Inspect operating mechanism , contacts and arc chutesin | 7.6.1.4 Checked OK | Nil |
unsealed units 1. Visual
Inspection (7)
8 | Perform adjustments for final protective device settingsin [7.6.1.1 Final Setting | Nil
accordance with the co ordination study 1. Visual ‘Applied and
Inspection (8) | tested OKKILASS N TRENDS xq
Trading, Contracting and Evonts Wit OSX
MCCB Mechnical and Visual Inspection Test Report
Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC
Date : 05/03/2020 Ref no: TIEMAU902__[ Location:QACC Building -Second Floor
Acceptance Criteria:
Compare bolted connection resistance values to values of similar connections. Investigate values which
device from those of similar bolted connections by more than 50 percent of the lowest value. NETA Ref:
7. Inspection and test procedures 7.6.1.1 / 3.2
Note: NETA standard Reference no 7.6.1.1
Sub division 2: Electrical Tests
We do only insulation resistance tests for molded case circuit breaker and control wiring as per NETA
Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker.
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER 1587 27490055 27/02/2021
CONTACT RESISTANCE METER | DLRO 10 101322093 28/02/2021
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
kNT TEM-AC ENGINEERING “GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan ‘Senthil Kumar
Saw | apa C7 =KILASS N TRENDS Ee
Trading, Contracting and Events W.LL
Molded Case Circuit Breaker Test Report
Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC
Date : 05/03/2020 Ref no: TIE MAU 902 Location:QACC Bullding Second
Breaker Data:
Voltage Rating: 415V. Model
Manufacturer: Schneider Elect
Internal Rating: 160 Amperes
‘Thermal Element:
‘Adjustable: Yes Setting: 112-160 Amperes Final setting: 112 Amperes
Magnetic Element
Non Adjustable: Yes
Setting: 1250 Amperes Fixed
Front Identification-Left to Right | Pole 1 Pole2 Pole 3
Thermal Element | Thermal Element | Thermal Element
Tripping time at 300% of Thermal _| 153.41 Seconds 158.9 Seconds 144 Seconds
Pick up
Inst. Tested on | Trip NA NA NA
setting }___ist
No Trip
Remarks: Nil
Test Equipment Used Model no. Serial no Calibration Due date
Primary Injection Test Kit HC2 | 13-8322 19/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR)
‘Suresh Subbarayan | Delwin Dominic | _ Manoj Viswanathan Senthil Kumar
g Ask | ps oF SsKLASS N TRENDS
‘Trading, Contracting and Evonts W.LL
‘Test Report : Primary Injection Test (Stability )
Panel Tag no : EMCC-C4910-228 | Make: Schneider Electric | Client Name: HIA EPSC
Location:QACC Building -Second
Date : 05/03/2020 Ref no: TIE MAU 902 Floor
Incomer Breaker Data:
Breaker Data:
Manufacturer: Merlin Gerin Voltage Rating: 415V
Internal Rating: 800 Amperes Type: NSXBOOH (M)
‘Outgoing Breaker Dat:
Breaker Data:
Manufacturer: Schneider Electric Voltage Rating: 415V
Internal Rating: 160 Amperes Type: TM160D
Description ” Injected | incomer Breaker | Outgoing
Current | trip j Norip) | Breaker
(Trip / No Trip)
Injected current between Incomer and Outgoing (R phase) | 336A | No Trip Tripped
injected current between Incomer and Outgoing (Y phase) | 3364 Tripped |
Injected current between Incomer and Outgoing (6 phase) | 336A _ | No Trip Tripped
Acceptance Criter
: Outgoing breaker should trip before incomer trips as per the co ordination study.
Result: The Outing Tie AHU 902 breaker is tripped and Incomer breaker does not trip. Hence Protection
discrimination study is verified and found ok.
| Test Equipment Used Model no Serial no | Calibration Due date
Primary Injection Test Kit Model HC-2 13-8322 | 19/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic ‘Manoj Viswanathan Senthil Kumar
Be. Boke qs oy a.KILASS N TRENDS Ke
Trading, Contracting and Evonts W.L.L
Power Cable Test Report |
Make: Schneider Electric _| Client Name: HIA EPSC
Feeder Ref no: TIE AHU-204 |
(Cable From: TIE AHU-204
Panel Tag no: DS-C4910-201
Date : 29/03/2020
Location : QACC Building Second Floor
Cable To: AHU -C4910-204 Control Panel
INSULATION RESISTANCE TEST
Duration test: MIN ‘Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth ~ >2.260
Y phase to earth >2.260
B phase to earth 32.260
R Phase to Y phase 32.260
Y Phase to B phase >2.260
BPhasetoRphase >2.269
R Phase to Neutral 32.269
Y Phase to Neutral 32260
B Phase to Neutral 32.260
‘Acceptance criteria: 100 MO
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2021
DIGITAL MULTIMETER Fluke-376 -46030078ws 14/10/2020
Test Performed by KNT | Witnessed by ] Witnessed by MUHIBBAH | Approved by (Third Party KAHRAMAA
TEM-AC ENGINEERING “R"GRADE CONTRACTOR)
‘Suresh Subbarayan Deivin Dominic Manoj Viswanathan — Senthil Kumar.
BGs B= G4 pheKLASS N TRENDS &%
Trading, Contracting and Events WiLL“
Power Cable Test Report
Panel Tag no:DS-C4910-201
Make:Schneider Electric _| Client Name:HIA EPSC
Location : QACC Building Second Floor
Cable size: 3Rx1cx10mm? cu/pve/Isht > ;
410c10mm? cu/ishf ece Feeder Ref n
Cable From:AHU-C4910-204 Control Panel
AHU-204 | Date :29/03/2020
Cable Te
}OA TP FIELD ISOLATOR AHU-C4910-204
INSULATION RESISTANCE TEST
Duration ert IM Test Voge: 10000
Phase Valuen Gigs obs
Rohae oer a6
Y phat arth 32260
phate to arth >2260
R Phase to Y phase 22.260 -
Phase to pave >a2c0
~ePhate to hace aaa
Tecan aa TOON
Remar
Test Egupment Used Modena Seriatno Calration Due dae
INSULATION TESTER Fluke- 1587, 27490055 27/02/2021
DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020
Witnessed by Approved by
TestPerormediy | Winesed
stPerormediy | wrnesedby | gquninoai’ | (Thicd Part KAHRAMAA A°GRADE
| eNcineeR CONTRACTOR)
SureshSubbarayan | Dalla Dominic | an] Vswoation SertaKLASS N TRENDS
‘Trading, Contracting and Evonts W.LL
Power Cable Test Report
Panel Tag no:DS-C4910-201 Make:Schneider Electric Client Name:HIA EPSC
Cable size: 3Rx1Cx10mm? cu/pve/Ishf + -
1¢x10mm? cu/lshf ecc Feeder Ref no:TIE AHU-204 | Date :29/03/2020
Location : QACC Building Second Floor Cable From:40A TP FIELD ISOLATOR AHU-C4910-204
Cable To:AHU-C4910-204 MOTOR ~]
INSULATION RESISTANCE TEST
Durationtest: IMIN Test Voltage: 2000v _
Phase Values in Giga ohms
Rphase to earth 32.260
Y phase to earth 7 32.260 -
8 phase to earth >2.260
Phase to ¥ phase 32260
Y Phase to B phase >2260
[ BPhasetoRphase | 7 22260 _
‘Acceptance criteria: 100 MQ
Remarks:
Test Equipment Used Model no Serial no Calibration Due date |
INSULATION TESTER Fluke- 1587 27490055 27/02/2021
DIGITAL MULTIMETER Fluke-376 ‘460300785 14/10/2020
Test Performed by | Witnessed by st sreencdy
MUHIBBAH | (Third Party-KAHRAMAA “A"GRADE
KNT TEM-AC
ENGINEERING CONTRACTOR)
Suresh Subbarayan | _Delwin Dominic | Manoj Viswanathan Senthil Kumar
4. fod
OY | ==KLASS N TRENDS K
‘Trading, Contracting and Events W.LL
Panel Tag no: DS-C4910-201 | Make: Schneider Electric | Client Name: HIA EPSC
Location: QACC Building Second
Floor
Date : 29/03/2020 Ref no: TIE AHU 204
INSULATION RESISTANCE TEST
Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth ~ >2.260
Y phase to earth 32.260
B phase to earth >2.260
R Phase to V phase >2260
Y Phase to B phase >2.260
B Phase to R phase 32.260
Status: Breaker Open Position- Across Pole
Phase Values in Giga ohms
R phase to R’ phase 32.260
Y phase to Y Phase >2.260
B phase to B Phase >2.260
Test Equipment Used ‘Model no [Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2024
DIGITAL MULTIMETER Fluke-376 460300785 14/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR)
Suresh Subbarayan_| Delwin Dominic ‘Manoj Viswanathan Senthil Kumar
am | C7 9‘Trading, Contracting and Events W.LL
KLASS N TRENDS K
‘MCCB Mechnical and Visual In:
Panel Tag no: DS-C4910-201 _| Make: Schneider Electric
Test Report
Client Name: HIA EPSC
Location: QACC Buil
iing Second
Floor
Date : 29/03/2020 Ref no: TIE AHU 204
NETA Standard Reference below
7. Inspection and test procedures
7.6.1.1 Molded Case Circuit Breaker
Visual and Mechanical Inspection:
Sino Description NETA Remarks
Visual and Mechanical Inspection a on Chechod
Molded Case | NOTOK/NA
Ref no
1 | Compare equipment nameplate data with drawings and | 7.6.1.1 Checked OK | Nil
Specifications 1. Visual
__| inspection (1)
2 | Inspect Physical and mechanical condition 76.11 Checked OK | Nil
4. Visual
Inspection (2)
3° [Inspect anchorage and alignment 76.11 NA Nil
1. Visual
Inspection (3)
Verify the unit is clean 7641 Checked OK | Nil
1. Visual
Inspection (4)
5 | Operate the circuit breaker to insure smooth operation 7614 Checked OK | Nil
1. Visual
Inspection (5)
6 | Contact Resistance Testing Checked OK | Nil
R phase Y phase B phase
E Phas , Inspection (6)
8.458m0 8.572m0 7.580ma
7 | Inspect operating mechanism , contacts and arc chutesin | 7.6.1.1 Checked OK | Nil
unsealed units 1. Visual
Inspection (7)
8 | Perform adjustments for final protective device settings In| 7.6.1.1 Final Setting | Nil
accordance with the co ordination study 1. Visual ‘Applied and
Inspection (8) | tested OK |‘Trading, Contracting and Events W.LLL
KLASS N TRENDS Ke
___ MCCB Mechnical and Visual inspection Test Report
$-C4910-201 ichneider Electric | Client Name: HIA EPSC
Panel Tag no:
Location: QACC Building -Second
Date : 29/03/2020 Ref no: TIE AHU 204
Floor
Acceptance Criteria:
Compare bolted connection resistance values to values of similar connections, Investigate values which
device from those of similar bolted connections by more than 50 percent of the lowest value. NETA Ref:
7. Inspection and test procedures 7.6.1.1 / 3.2
Note: NETA standard Reference no 7.6.1.1
Sub di
ion 2: Electrical Tests
‘We do only insulation resistance tests for molded case circuit breaker and control wiring as per NETA
Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker.
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER 1587 27480055 277022024
‘CONTACT RESISTANCE METER DLRO 10 101322093 — 28/02/2021
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA |
kNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan | Senthil Kumar
Zo OY eeTrading, Contracting and Evonts W.LL
KLASS N TRENDS. Ke
Molded Case Circuit Breaker Test Report
Panel Tag no: DS-C4910-201__| Make: Schneider Electric | Client Name: HIA EPSC
Date : 29/03/2020 Ref no: TIE AHU 204 in QACC Building “Second
Breaker Data:
Manufacturer: Schneider Electric Voltage Rating: 415V. Model: NSX100-F
Internal Rating: 25 Amperes
‘Thermal Element
Adjustable: Yes_ Setting:
Magnetic Element
Non- Adjustable: Yes
18-25 Amperes Final setting: 25 Amperes
Setting: Fixed 3004
Front Identification-Left to Right | Pole 1 [Pole 2 Pole 3
Thermal Element | Thermal Element Thermal Element
Tripping time at 300% of thermal _| 76.05 Seconds 70.74 Seconds 73.54 Seconds
pickup
inst. Tested on | Trip NA NA NA
— setting TNotrip ———|
Remarks: Nil
Test Equipment Used Model no Serial no Calibration Due date
Primary Injection Test Kit C2 13-8322 19/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR)
‘Suresh Subbarayan | Delwin Dominic |" Manoj Viswanathan - ‘Senthil Kumar,
g. gud cake yy SSKLASS N TRENDS
‘Trading, Contracting and Events W.L.L
Test Report : Primary Injection Test (Stability )
Panel Tag no : DS-C4910-201 Make: Schneider Electric nt Name: HIA EPSC
Location: QACC Building Second
Date : 29/03/2020 Ref no: TIE AHU 204 Floor
lncomer Breaker Data:
Breaker Data:
Manufacturer: Schneider Electric Voltage Rating: 415V
Internal Rating: 630 Amperes Type: NSX630F
Outgoing Breaker Data:
Breaker Data:
Manufacturer: Schneider Electric Voltage Rating: 415V
Internal Rating: 25 Amperes Type: TM25D
[Description injected | Incomer Breaker | Outgoing
Current | rip jo trip) | Breaker
| (Trip / No Trip)
Injected current between incomer and Outgoing (R phase) | 75A | No Trip. Tripped
Injected current between incomer and Outgoing ( ¥ phase) | 75A ‘No Trip Tripped
Injected current between incomer and Outgoing (8 phase) | 75A | No Trip Tripped
Acceptance Criteria: Outgoing breaker should trip before incomer trips as per the co ordination study.
Result: The Outing Tie AHU204 breaker is tripped and Incomer breaker does not trip. Hence Protection
discrimination study is verified and found ok.
Test Equipment Used ‘Model no [Serial no Calibration Due date
Primary Injection Test Kit ‘Model HC-2 13-8322 19/10/2020
Test Performed by | Witnessed by nessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT | TeM-ac ENGINEERING “R”GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar
E08 Be OYKILASS N TRIENIDS:
‘Trading, Contracting and Evonts W.L.L
Power Cable Test Report —
Make: Schneider Electric _| Client Name: HIA EPSC
Feeder Ref no: TIE FCU-B022 |
Cable From: TIE FCU-B022
Panel Tag no: PNL-C4910-B63
Date : 21/03/2020
Location : QACC Building Second Floor
Cable To: FCU -C4910-B022 Control Panel
INSULATION RESISTANCE TEST
Duration test: MIN Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth >2.260
Y phase to earth ~ >2.2G0
B phase to earth 32.260
R Phase to Y phase 32.260
[ Y Phase to B phase >2.260
B Phase to R phase >2.260 |
R Phase to Neutral 32260
Y Phase to Neutral 32269
B Phase to Neutral >2.260
‘Acceptance criteria: 100 MO
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 2702/2024
DIGITAL MULTIMETER Fluke-376 "46030078 ws 14/10/2020
Test Performed by KNT | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
TEM-AC ENGINEERING “A/GRADE CONTRACTOR)
‘Suresh Subbarayan Delvin Dominic | Manoj Viswanathan Senthil Kumar
Gg Ao ey ——— _KLASS N TRENDS
‘Trading, Contracting and Events W.LL
Power Cable Test Report
Panel Tag no:PNL-C4910-B63 Make:Schneider Electric _| Client Name:HIA EPSC
Cable size: 3Cx35mm? Cu/xlpe/swa/ishf +
10x16mm?Cu/Ishf
Location : QACC Building Second Floor
Feeder Ref no:TIE FCU BO22 | Date :21/03/2020
Cable From:FCU-C4910-8022 Control Panel
Cable To:25A TP FIELD ISOLATOR FCU-C4910-B022
INSULATION RESISTANCE TEST
Duration test: IMIN____Test Voltage: 1000V.
Phase Values in Giga ohms
R phase to earth 32.260
Y phase to earth 32.260
" Bphase to earth 32.260
R Phase to ¥ phase 32.260
Y Phase to B phase >2.260
| BPhase to R phase — _ 22.260
‘Acceptance =
Remarks:
Test Equipment Used Model no Serial no Calibration Due date |
INSULATION TESTER Fluke- 1587 27490055 27/02/2024
DIGITAL MULTIMETER Fluke-376 '46030078ws 14/10/2020
- Wi
Test Performed by | Witnessed by messed by Approved by
MUHIBBAH (Third Party-KAHRAMAA “A"GRADE
KN TEM-AC
ENGINEERING CONTRACTOR)
Suresh Subbarayan ‘Manoj Viswanathan Senthil Kumar
| &KLASS N TRENDS
‘Trading, Contracting and Events W.L.L
Power Cable Test Report
Panel Tag no:PNL-C4910-B63 Make:Schneider Electric Client Name:HIA EPSC
Cable size: 3Cx35mm? Cu/xIpe/swa/Ishf
+10x16mm?Cu/Ishf
Location : QACC Building Second Floor | Cable From:25A TP FIELD ISOLATOR FCU-C4910-B022
Feeder Ref no:TIE FCU 8022 _| Date :21/03/2020
Cable To:FCU-C4910-8022 MOTOR
INSULATION RESISTANCE TEST
Duration test: MIN Test Voltage: 1000
Phase Values in Giga ohms
phase to earth >2260
Y phase to earth 32260 :
B phase to earth >2.260)
RPhase to phase ~ >2.260
Y Phase to B phase 32.260
B Phase to R phase r~ - "32.260 a
‘Acceptance eiteriar 100 MO
Remarks:
Test Equipment Used Modeino | Setial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2024
DIGITAL MULTIMETER Fluke-376 46030078ws 1471072020
Witnessed by ‘Approved by
ed by a
Test Performed by | Witnessed by MUHIBBAH | (Third Party-KAHRAMAA “A"GRADE
knT TEM-AC
ENGINEERING CONTRACTOR)
Suresh Subbarayan | _Delwin Dominic | Manoj Viswanathan Senthil Kumar
8. ud dab. @py a>KLASS N TRENDS Be
Trading, Contracting and Evonts W.LL
MCCB Insulation Resistance Test Report
Panel Tag no: PNL-C4910-B63__| Make: Schneider Electric | Client Name: HIA EPSC
Location: QACC Building -Second
Floor
Date : 21/03/2020 Ref no: TIE FCU-B022
INSULATION RESISTANCE TEST
Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V
Phase Values in Giga ohms.
R phase to earth >2.260
Y phase to earth 32.260 7
B phase to earth >2.260
R Phase to Y phase 32.260
Y Phase to B phase >2.260 ~
B Phase to R phase >2.260
Status: Breaker Open Position- Across Pole
Phase Values in Giga ohms
R phase to R’ phase ~ >2.260,
Y phase to ¥ ‘Phase >2260
B phase to B ‘Phase 32.260
‘Acceptance criteria: 100 MO
Test Equipment Used Model no Serialno Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2024
DIGITAL MULTIMETER Fluke-376 ‘4603007805 14/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Domi Manoj Viswanathan: Senthil Kumar
g R= Be (7 =KLASS N TRENDS EG
Trading, Contracting and Events W.L.L
MCCB Mechnical and Visual inspection Test Report
Panel Tag no : PNL-C4910-B63_| Make: Schneider Electric | Client Name: HIA EPSC
Location: QACC Bui
Floor
Date : 21/03/2020 Ref no: TIE FCU-B022
NETA Standard Reference below
7. Inspection and test procedures
7.6.1.1 Molded ~Case Circuit Breaker
Visual and Mechanical Inspection:
Sl.no Description NETA Remarks
STANDARD —_| Checked
OK/Checked
NOT OK/NA
Visual and Mechanical Inspection
76.1.4
Molded Case
Refno
1 | Compare equipment nameplate data with drawings and 7614 Checked OK | Nil
Specifications 1. Visual
Inspection (1)
2 | inspect Physical and mechanical condition \7.6.1.2 Checked OK | Nil
1. Visual
Inspection (2)
3 __ | Inspect anchorage and alignment 7611 NA [Nil
1. Visual
Inspection (3)
4 | Verify the units clean 76.11 Checked OK | Nil
4. Visual
Inspection (4)
5 | Operate the circuit breaker to insure smooth operation 7644 Checked OK | Nil
1. Visual
Inspection (5)
6 | Contact Resistance Testing 7eaa Checked OK | Nil
2. Visual
Inspection (6)
R phase Y phase B phase
2.278m0 2.324ma 2.198m0,
7 | Inspect operating mechanism , contacts and arc chutesin | 7.6.1.1 Checked OK | Nil
unsealed units 1. Visual
Inspection (7)
8 | Perform adjustments for final protective device settings in| 7.6.1.1 Final Setting | Nil
accordance with the co ordination study 1. Visual Applied and
Inspection (8) | tested OKKLASS N TRENDS
Trading, Contracting and Evonts W.LL
MCCB Mechnical and Visual Inspection Test Report
Panel Tag no: PNL-C4910-863_| Make: Schneider Electric | Client Name: HIA EPSC
Date : 21/03/2020 Ref no: TIE FCU-B022 | Loratlon: QACC Building Second
Acceptance Criteria:
‘Compare bolted connection resistance values to values of similar connections. Investigate values which
device from those of similar bolted connections by more than 50 percent of the lowest value. NETA Ref:
7. Inspection and test procedures 7.6.1.1 / 3.2
Note: NETA standard Reference no 7.6.1.1
Sub division 2: Electrical Tests
We do only insulation resistance tests for molded case circuit breaker and contro! wiring as per NETA
Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker.
Test Equipment Used ‘Model no ‘Serial no Calibration Due date
INSULATION TESTER 1587 27490055 27/02/2024
‘CONTACT RESISTANCE METER DLRO 10 101322093 28/02/2021
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR)
‘Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar
5 Re gaia Ca elPanel Tag no : PNL-C4910-B63
Date : 21/03/2020
Molded Case Circuit Breaker Test Report
KILASS N TRENDS
‘Trading, Contracting and Events W.LL
Make: Schneider Electric | Client Name: HIA EPSC
Location: QACC Building -Second
Floor
Ref no: TIE FCU-B022
Breaker Dat:
Manufacturer: ABB Voltage Rating: 415V_ Model: Tmax XT1C 160
Internal Rating: 40 Amperes
‘Thermal Element:
Adjustable: Yes_
Magnetic Element
Non- Adjustable: Yes
Setting: Fixed 450
Setting: 28-40 Amperes
Final setting: 40 Amperes
Front Identification-Left to Right
Pole 1 Pole 2 Pole 3
Thermal Element | Thermal Element Thermal Element
Tripping time at 300% of thermal
pickup
23.56 Seconds 20.59 Seconds 24.40 Seconds
[inst. Tested on [Trip NA NA NA
— setting No Trip
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
Primary Injection Test Kit C2 13-8322 19/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “R"GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar
das
SFO
SS
OyKILASS N TRENDS.
Trading, Contracting and Events W.L.L
a
‘Test Report : Primary Injection Test (Stability )
anel Tag no : PNL-C4910-B63_| Make: Schneider Electric | Client Name: HIA EPSC
Location: QACC Building -Second
Date : 21/03/2020 Ref no: TIE FCU-B022
rm
Floor
Incomer Breaker Data:
Breaker Data:
Manufacturer: Schneider Electric Voltage Rating: 415V
Internal Rating: 63 Amperes Type: NSX100F
‘Outgoing Breaker Dat:
Breaker Data:
Manufacturer: Schneider Electric Voltage Rating: 415V
Internal Rating: 40 Amperes Type: Tmax XT1C 160
[ Description Injected | incomer Breaker | Outgoing
Current | rip fo rip) | Breaker
(Trip / No Trip)
Injected current between Incomer and Outgoing (R phase) | 120A | No Trip "| Tipped
Injected current between Incomer and Outgoing (Y phase) | 120A _| No Trip Tripped
Injected current between Incomer and Outgoing (B phase) | 120A | No Trip Tripped
Acceptance Criteria: Outgoing breaker should trip befor
\comer
ips as per the co ordination study.
Result: The Outing Tie FCU BO22 breaker is tripped and Incomer breaker does not trip. Hence Protection
discrimination study is verified and found ok.
Test Equipment Used J
Model no
Serial no
Calibration Due date
Primary Injection Test Kit |
Model HC-2
13-8322,
19/10/2020
Test Performed by | Witnessed by
KNT TEM-AC
ENGINEERING
essed by MUHIBBAH
‘Approved by (Third Party-KAHRAMAA
“R"GRADE CONTRACTOR)
| Suresh Subbarayan | Delwin Dominic
‘Manoj Viswanathan
Senthil Kumar
3B. oe
Gy
=KLASS N TRENDS KE
=
‘Trading, Contracting and Events W.LL
Power Cable Test Report
Panel Tag no: PNL-C4910-B26 Make: Schneider Electric __| Client Name: HIA EPSC
Date : 21/03/2020 Feeder Ref no: TIE FCU-B023 |
Location : QACC Building Second Floor | Cable From: TIE FCU-B023
Cable To: FCU -C4910-B023 Control Panel
INSULATION RESISTANCE TEST
Duration test: MIN Test Voltage: 1000V
Phase Values in Giga ohms
R phase to earth >2.260
Y phase to earth >2.260
B phase to earth 32.260
R Phase to Yphase >2.260 ~
Y Phase to B phase 32.260
B Phase to R phase ~>2.260
R Phase to Neutral 32260
Y Phase to Neutral 32260
B Phase to Neutral 32.260
‘Acceptance criteri
Remarks:
Test Equipment Used Modelno Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490085 27/02/2021
DIGITAL MULTIMETER Fluke-376 ‘46030078ws 14/10/2020
Test Performed by KNT | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
TEM-AC ENGINEERING “R”GRADE CONTRACTOR)
‘Suresh Subbarayan Delvin Dominic | Manoj Viswanathan Senthil Kumar
Bf Bore “pS CW =—— ssaKLASS N TRENDS
‘Trading, Contracting and Events W.LL
Power Cable Test Report i
Make:Schneider Electric Client Name:HIA EPSC
Panel Tag no:PNL-C4910-826
Cable size: 3Rx1Cx10mm? Cu/Ishf +
10x10mm?Cu/IshF
Location : QACC Building Second Floor Cable From:FCU-C4910-8023 Control Panel
Feeder Ref no:TIE FCU B023_| Date :21/03/2020
INSULATION RESISTANCE TEST
Duration test:IMIN Test Voltage: 1000V.
Phase Values in Giga ohms
R phase to earth 32.260
Y phase to earth 32260
B phase to earth 32.262
Phase to phase 32.260
YPhasetoB phase >2.260
B Phase to R phase 7 32260 —Y
‘Acceptance criteria: 100 MQ
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2024
DIGITAL MULTIMETER Fiuke-376 '46030078ws 14/10/2020
B ‘Approved
Test Performed by Wiimesseg OY a
ewe MUHIBBAH (Third Party-KAHRAMAA “A"GRADE
ENGINEERING CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan Senthil Kumar
pa | ape yy | Se‘Trading, Contracting and Events W.L.L
KLASS N TRENDS K
__ Power Cable Test Report
Panel Tag no:PNL-C4910-826 Make:Schneider Electric Client Name:HIA EPSC
Cable size: 3Rx1Cxi0mm? Cu/Ishf +
1¢x10mm?Cu/Isht
Location : QACC Building Second Floor __| Cable From:25A TP FIELD ISOLATOR FCU-C4920-8023 |
Feeder Ref no:TIE FCU 8023 | Date :21/03/2020
Cable To:FCU-C4910-8023 MOTOR
INSULATION RESISTANCE TEST
Duration test: 1MIN Test Voltage: 1000V
Phase Values. ohms
a R phase to earth >2.260
Y phase to earth >2.260
Bphase to earth 22.262
R Phase to ¥ phase 32.260
Y Phase to B phase 32.260
~_BPhase to R phase a "32.260 _
‘Acceptance criteria: 100 MQ.
Remarks:
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055, 27/02/2021
DIGITAL MULTIMETER Fluke 376 60300785 19/10/2020
Witnessed by ‘Approved by
1 ed by
jest Performed by’ ‘Witnessed by MUHIBBAH (Third Party-KAHRAMAA “A”GRADE
KNT TEM.AC
ENGINEERING CONTRACTOR)
Suresh Subbarayan | _Delwin Dominic | Manoj Viswanathan Senthil Kumar
B: fa Ta OY aKLASS N TRENDS Ke
Trading, Contracting and Events W.LL
MCCB Insulation Resistance Test Report
4910-826 _| Make: Schneider Electric | Client Name: HIA EPSC
Location: QACC Building -Second
Floor
ranel Tag no : PN
Date : 21/03/2020
Ref no: TIE FCU-B023
INSULATION RESISTANCE TEST
Duration test: 1MIN Status: Breaker (Closed Position) Test Voltage: 1000V
Phase Values in Giga ohms ]
Rphase to earth 32260
Y phase to earth 32.260
B phase to earth 32.260
R Phase to V phase 32.260
Y Phase to B phase >2.260
B Phase to R phase 32.260
Status: Breaker Open Position- Across Pole
Phase Values in Giga ohms
R phase to R’ phase ~>2.260
Y phase to Phase >2.260
B phase to 6 ‘Phase 32260
‘Acceptance criteria: 100 MA.
Test Equipment Used Model no Serial no Calibration Due date
INSULATION TESTER Fluke- 1587 27490055 27/02/2021
DIGITAL MULTIMETER Fluke-376 46030078ws 14/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party KAHRAMAA
KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR)
‘Suresh Subbarayan | Delwin Dominic ‘Manoj Viswanathan Senthil Kumar
8A | pe C7 aePanel Tag no : PNL-C4910-B26
‘Trading, Contracting and Events W.LL
KILASS N TRENDS Ke
(MCCB Mechnical and Visual inspection Test Report
[ Make: Schneider Electric | Client Name: HIA EPSC
Location: QACC Building -Second
Date : 21/03/2020 Ref no: TIE FCU-B023
Floor
NETA Standard Reference below
7. Inspection and test procedures
7.6.1.1 Molded ~Case Circuit Breaker
Visual and Mechanical Inspection:
‘Sno Description NETA Remarks
: STANDARD —_| Checked
7
Visual and Mechanical Inspection ee Ok/Checkee
Molded Case | NOT OK/ NA
Ref no
1 | Compare equipment nameplate data with drawings and 7611 Checked OK | Nil
Specifications 1. Visual
I. Inspection (1)
2 | inspect Physical and mechanical condition 7.6.1.1 Checked OK | Nit
4. Visual
Inspection (2)
3 [Inspect anchorage and alignment - 7.6.1.1 NA Nil
1. Visual
Inspection (3)
4 | Verify the unitis clean 76i4 Checked OK | Nil
1. Visual
Inspection (4)
5 | Operate the circuit breaker to insure smooth operation 7644 Checked OK | Nil
1. Visual
Inspection (5)
6 | Contact Resistance Testing 7614 Checked OK | Nil
2. Visual
y 8
R phase phase phase Inopection (6)
2.235m0 2.018ma 2.1880,
7 | Inspect operating mechanism , contacts and arc chutes in | 7.6.1.1 Checked OK | Nit
unsealed units 1. Visual
Inspection (7)
8 | Perform adjustments for final protective device settings in| 7.6.1.1 Final Setting | Nil
accordance with the co ordination study 1. Visual ‘Applied and
Inspection (8) | tested OK‘Trading, Contracting and Evonts W.LL
MCCB Mechnical and Visual inspection Test Report
Panel Tag no: PNL-C4910-B26__| Make: Schneider Electric | Client Name: HIA EPSC
Date : 21/03/2020 Ref no: TIE FCU-B023 Pecan ‘QACC Building -Second
KLASS N TRENDS Ka
Acceptance Criteri
Compare bolted connection resistance values to values of similar connections. Investigate values which
device from those of similar bolted connections by more than 50 percent of the lowest value. NETA Ref:
7. Inspection and test procedures 7.6.1.1 / 3.2
Note: NETA standard Reference no 7.6.1.1
Sub division 2: Electrical Tests
We do only insulation resistance tests for molded case circuit breaker and control wiring as per NETA
Standard reference 7.6.1.2. The other tests are not applicable for molded case circuit breaker.
Test Equipment Used |_ Modelno Serial no | Calibration Due date
"INSULATION TESTER 1587 27490055 ~~ 27/02/2024
CONTACT RESISTANCE METER | DLRO 10 101322093 wrapoa |
Test Performed by ‘Witnessed by ‘Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “A”GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic Manoj Viswanathan ‘Senthil Kumar
Bele ta Oi eeKILASS N TRENDS
‘Trading, Contracting and Evonts W.L.L
Molded Case Circuit Breaker Test Report
Panel Tag no : PNL-C4910-B26
Date : 21/03/2020
Ref no: TIE FCU-B023
Floor
‘Make: Schneider Electric | Client Name: HIA EPSC
Location:
‘QACC Building Second
Breaker Dati
Manufacturer: ABB Voltage Rating: 41SV_ Model: T max XT1C 160
Internal Rating: 40 Amperes
Thermal Elemen
Adjustable: Yes_ Setting: 28-40 Amperes Final setting: 40 Amperes
Magnetic Element
Non- Adjustable: Yes
Setting: Fixed 4508
Front identification-Left to Right | Pole 1 Pole 2 Pole 3
Thermal Element Thermal Element Thermal Element
Tripping time at 300% of 20.56 Seconds 22.84 Seconds 724.69 Seconds
‘thermal pickup
Inst. Tested on | Trip NA NA NA
— setting OTP
Remarks: Nil
Test Equipment Used Model no Serial no Calibration Due date
Primary Injection Test Kit HC2 13-8322 19/10/2020
‘Suresh Subbarayan | Delwin Dominic Manoj Viswanathan |
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party-KAHRAMAA
KNT TEM-AC ENGINEERING “A"GRADE CONTRACTOR)
‘Senthil Kumar
A | tala oY
SSKILASS N TRENDS Ka
Trading, Contracting and Events W.LL
Test Report : Primary Injection Test (Stability )
[Panel Tag no: PNL-C4910-826 | Make: Schneider Electric | Client Name: HIA EPSC |
Date : 21/03/2020 Ref no: TIE FCU-B023 rpeatio # QACC Building “Second |
incomer Breaker Data
Breaker Dat
Manufacturer: Schneider Electric Voltage Rating: 415V
Internal Rating: 63 Amperes Type: NSX100F
Outgoing Breaker Data:
Breaker Data:
Manufacture
hneider Electric
Internal Rating: 40 Amperes Type: Imax xT1¢ 160
Description Injected] income Breaker | Outgoing —
Current | rip fo Trip) | Breaker
(Trip / No Trip)
Injected current between Incomer and Outgoing (R phase) | 120A | No Trip Tripped |
Injected current between Incomer and Outgoing (Y phase) | 120A | No Trip Tripped
Injected current between Incomer and Outgoing (B phase) | 120A | No Trip Tripped
Acceptance Criteria: Outgoing breaker should trip before incomer
as per the co ordination study.
Result: The Outing Tie FCU 8023 breaker is tripped and incomer breaker does not trip. Hence Protection
discrimination study is verified and found ok.
Test Equipment Used Model no Serial no Calibration Due date
Primary Injection Test Kit Model HC-2 13-8322 19/10/2020
Test Performed by | Witnessed by | Witnessed by MUHIBBAH | Approved by (Third Party KAHRAMAA
KNT TEM-AC ENGINEERING “A”GRADE CONTRACTOR)
Suresh Subbarayan | Delwin Dominic | Manoj Viswanathan ~ ‘Senthil Kumar
g-40% | ee Cy ee.vm Chu ’ nally halle
a
Letter
M/s Al Ajjaj Limited Company
Head of Distribution Protection Section
270220202 —=~S*~*S*«S*«C OTN AL
ED/EDR/1086/2020
1 lla g pp
RENEWAL OF LICENSE FOR LV PANEL esas
PROTECTION TESTING ED/EDR/P3-015 ses
This has the reference to your fee payment receipt dated on 26/02/2020
(Receipt No. 6260220000065) for renewal of license for LV Panel
Protection Testing of Mr. Mr. Senthilkumar Kailyamoorthy License No.
ED/EDR/ P3-015.
This is to inform you that your license has been renewed for further 1 (One)
year until 31-12-2020.
ae
ing. Abdulla Ebrahim M H Ahmad
Head — Distribution Protection
Page 4 ofAHLMOOWVANTWS U VINTDCIHANS@ WHEN
et ent Sutin pyfey in
¢ | omy THO pte a voquedns39,
: viant Aieuonen
_ va - hr
( e a mt oz0z60120 Aude
ai ain og sis tia 1 iter Cast /taz aoa
IA vos rey ae ae dels ewRS Crew: — gogerasecez onal
Trg ead owt woaud
3 ey, - Ns Orey iy Wueg Aruepisey
tert ‘ copy oe SS 2/ 18180 40 24815
A echeewt