Professional Documents
Culture Documents
Partner•Succeed
Presented by
Rick Hoadley
ABB, Inc.
New Berlin, WI
AC Motor Output
AC Line Input
should be answered in order to successfully
commission the drive system:
1) What is my power system like today
2) What impact will the additional drive(s) have on
the power quality for the other equipment
3) If needed, what harmonics mitigation method
should be used Converter DC Inverter
4) How long and what type of cable is used AC to DC Bus DC to AC
between the drive and motor Filter
This paper will deal with understanding IEEE Std Fig 2 - Power Sections of a Basic 6-Pulse AC Drive
519 and various mitigation methods in order to meet
First, the AC line is converted to fixed voltage DC
those recommendations. It will also review the types
and is filtered by the DC bus filter. This section may
of filtering that is available to reduce the reflected
be called a converter or a rectifier. The AC to DC
waves, first turn insulation stress, and common mode
conversion is what produces pulses of line currents
voltages seen at the motor terminals.
that are not sinusoidal, but contain harmonics of the
order (6n +/- 1) which are the 5, 7, 11, 13, 17, 19, etc.
POWER CONVERSION BY AC DRIVES
AC drives, also known as adjustable speed drives Next, the fixed voltage DC is changed (inverted) to
(ASDs) or variable frequency drives (VFDs), convert the adjustable voltage and frequency required by the
the fixed frequency, fixed voltage supplied by the utility motor to control its torque and speed. This process
produces a series of voltage pulses whose widths are
to an adjustable frequency, adjustable voltage that is
modulated (PWM) or varied. The inductance in the
connected to an AC motor in order to control the
motor integrates these voltage pulses and draws a
speed, torque and direction of rotation of the motor.
sinusoidal current from the drive. These voltage
Instead of being limited to its torque vs speed curve,
pulses have a high rate of change (dV/dt) which
the drive and motor has an area of operation on the
torque vs speed graph. See Fig 1. causes reflected wave voltage spikes at the motor
terminals.
An industrial drive uses a filter at its input and at its
output in order to minimize the impact the line current
pulses have on the line voltage, and the impact the
Per Unit Torque
Speed, rpm
However, in the process of converting the fixed 3- Fig 3 - Power Sections of an Industrial AC Drive
phase line voltage and frequency to an adjustable 3-
phase motor voltage and frequency, two power
conversions take place. See Fig 2.
1
AC DRIVE HARMONICS that even if you follow them, it does not guarantee you
Fig 4 shows that for a 3-phase system, utilizing a will not have harmonic issues. You can think of them
full-wave diode bridge rectifier with a capacitor DC bus as “best practices.”
filter, the only time current is allowed to charge the Two tables are critical to understanding what limits
capacitor is whenever the AC line-to-line voltage need to be met within a facility. They are reproduced
exceeds the DC bus voltage. This is the reason why in Table I and Table II below.
there are two current pulses per phase, which means Harmonic Voltage Limits Table 10.2
600.0 600.0 Current distortion Limits for General Distribution Systems (120V through 69,000V)
Maximum Harmonic Current Distortion in Percent of Iload
400.0
Van 400.0
Is c/Iload <11 11<=h<17 17<=h<23 23<=h<35 35<=h T D D
(% )
<20 4.0 2.0 1.5 0.6 0.3 5.0
20<50 7.0 3.5 2.5 1.0 0.5 8.0
200.0
Ia 200.0 50<100 10.0 4.5 4.0 1.5 0.7 12.0
100<1000 12.0 5.5 5.0 2.0 1.0 15.0
>1000 15.0 7.0 6.0 2.5 1.4 20.0
0 0
Even harmonics are limited to 25% of the odd harmonic limits above
-100.0 -100.0 Table 10.3
81.50m
82.50m 85.00m 87.50m 90.00m 92.50m
93.50m
2
maximum loading would include all linear and Each has pros and cons, and each reduces the
non-linear loads. [4][5][6] harmonic currents a different amount and in different
Users often request that harmonic measurements be ways. [9][10][11]
made at the input terminals of a piece of equipment
within their facility. This may be a point of interest, but MITIGATION METHOD – NONE
this usually is not the PCC where the IEEE 519 If no harmonic mitigation is added to the basic AC
recommends the measurements be taken. drive, the line current harmonics can be between 80-
Misunderstanding the above points has led several 120% Ithd. Fig 6 is a simplified version of Fig 2 which
users to purchase more harmonic filtering equipment is a basic AC drive, also showing the transformer
than is necessary. The additional filtering equipment feeding the rectifier. Fig 7 is an example of its line
did not hurt them with respect to their power system, current. The only impedance in the circuit is in the
but it did have an impact on their finances that could transformer.
have been avoided.
HARMONIC ANALYSIS
The readings obtained from the measurements do
not directly determine whether or not IEEE 519 is
being met. Some analysis is required. For example,
an up-to-date one-line diagram of the facility is
required in order to help determine the short circuit
current available at the measurement point(s). If the Fig 6 – Basic AC drive with No Harmonic Mitigation
equipment within the plant is not operating at
This can cause significant voltage distortion, and
maximum load (which may occur only once a year), an
leaves the drive open to over-voltage trips due to line
extrapolation is needed to determine what the
voltage transients seen during the switching of power
expected distortions may be under those extenuating
factor correction caps and large inductive loads.
circumstances.
These transients often cause the unprotected drive to
If the facility has back-up generators, a separate
trip on over-voltage.
analysis is needed when operating under those
conditions. Measurements taken when powered by
the back-up generators are very helpful. [7]
150.0m 162.5m 175.0m 187.5m 200.0m
400.0 La.I = f( ...
shown in Fig 9.
0 0
200.0 200.0
-400.0 -400.0
150.0m 162.5m 175.0m 187.5m 200.0m
0 0
between the rectifier and the bus capacitors. See Fig 150.0 Ia = f( S,...
50.0 50.0
0 0
-50.0 -50.0
-100.0 -100.0
-150.0 -150.0
-25.00m -20.00m -10.00m 0 10.00m 20.00m 24.90m
Fig 10 – DC Link Choke Fig 13 – Line Current for Passive Harmonic Filter
Ithd would typically be between 30-40% as shown in Since the harmonics are like reactive currents in that
Fig 11. they do not provide power to the load, they simply
4
move between the drive and the source with an others untouched. This produces 12-pulse like current
average of zero Watts every cycle. The filter now is a in the primary lines. See Fig 16.
source for those harmonics so the transformer feeding The phase sift between the two secondaries is equal
the drive does not have to provide them. The current to 360/(# of pulses desired). So, 360/12 = 30 deg.
into the drive still looks like Fig 9, but the current out of This is usually accomplished using a delta-wye
the transformer looks like Fig 13. transformer since it provides that phase shift. The
interesting thing is that as the harmonics go through
MITIGATION METHOD – MULTI-PULSE RECTIFIER the phase shifting transformer, they also experience a
A passive method for a dramatic reduction in line phase shift so that the primary current looks different,
current harmonics has been the use of multi-pulse but has the same set of harmonics with the same
rectifiers. These are typically 12-pulse and 18-pulse amplitudes, but at different phase angles with respect
rectifiers for low-voltage AC drives, and 24-pulse and to one another. Fig 17a shows the two sets of
36-pulse rectifiers for medium voltage AC drives. currents that combine to create a 12-pulse current
They are made up of multiple 6-pulse diode bridges waveform seen in Fig 17b. Ithd is between 9-12%.
fed from phase shifted transformer secondaries. [12] 184.00
2DGraphSel1
-100.00
-182.00
150.00m 160.00m 180.00m 200.00m
302.50
200.00
-200.00
AM1p.I [A]
-300.00
150.00m 160.00m 180.00m 200.00m
AC Motor Output
AC Line Input
-200.00 AM1p.I [A]
-290.00
150.00m 160.00m 180.00m 200.00m
100.0 100.0
50.0 50.0
0 0
-50.0 -50.0
-100.0 -100.0
Fig 24 – Current Magnitude, Phase Angle, and Direction
-150.0
-25.00m -20.00m -10.00m 0 10.00m 20.00m 24.90m
-150.0
Determined by Magnitude and Phase Angle of AFE
The current waveform, shown in Fig 25, requires an
Fig 22 – Line Current for Active Harmonic Filter additional LC filter in order to reduce the notching that
otherwise would be seen. With this LCL filter, though,
6
very low harmonic distortion can be achieved – within the motor windings which could lead to a
between 3-5%. shorted turn within a phase, or a line-to-line short
between phases, or a line-to-ground short to the frame
200.0
145.0m
150.0m 162.5m 175.0m 187.5m
195.0m
Lx1.I = ...
of the motor, a filter needs to be placed at the output of
the drive. Four types of filters have been successfully
100.0 100.0 used.
1.00 DC Bus
0
M
-1.00
CIV Level
-2.00
VM1.V [V]
VM2.V [V]
-3.00
500.00u 750.00u 1.00m 1.25m 1.50m 1.75m 2.00m 2.25m 2.50m 2.75m 3.00m Fig 28 – dV/dt Filter
Fig 26 – Ringing Reflected Wave at the Motor (blue)
Exceeding the CIV of the Motor Insulation System REFLECTED WAVE MITIGATION – SINEWAVE
NEMA MG-1 parts 30 and 31 [22] state that a motor FILTER
designed for drive applications should meet their A sinewave filter is larger and more complex than a
standard such that its insulation system can withstand dV/dt filter in the sense that it must trap all of the
2.04 x rated voltage peaks with rise times of 1us or harmonics other than the fundamental. Usually, the
greater. in order to reduce the risk of causing corona output inverter operates at a fixed carrier frequency or
7
within a frequency window. The filter is then tuned to
that carrier frequency and multiples of it in order to
leave only the fundamental for the motor. A drive
using this type of filter must operate with a scalar
control since the motor’s parameters cannot be
determined by the drive. With this filter, though,
cables as long as 10km is possible. Also, motors older
than 25 years may work well with this drive and filter
without causing degradation to their insulation system.
See Fig 29.
filter is in parallel with the motor, one filter size can be 200
-200
-300
-400
M -500
175.00m 180.00m 182.50m 185.00m 187.50m 190.00m 192.50m 195.00m 200.00m
8
common mode currents from the motor back to the motor. The consultant or the specifier should work
drive. This way, those currents will not affect other with the drive manufacturer in order to determine the
pieces of equipment within the facility. Another is to most cost effective solution for this issue. [19][20]
provide a high frequency path within the drive between One other solution that was not mentioned since it
ground and its DC bus for these currents to follow. isn’t a “filter” to speak of is the use of shielded cable
Common mode reactors will reduce the currents as between the drive and motor. The inherent properties
well. This will also reduce bearing currents. See Fig of a shielded cable provide a dV/dt type of filter and
33. will usually lower the peak reflected wave voltages at
CM Reactor dV/dt Filter Shielded Cable the motor. In addition, the shielded cable provides a
controlled path for common mode currents to return
directly to the drive without finding their own way
through the facility, causing odd behavior in other
equipment. [21]
To summarize:
1. No output Filter
CM Filter
a. Acceptable for most short distance
Fig 33 – Proper filters and shielded cables to mitigate applications
common mode currents
2. dV/dt Filter
a. Low cost
b. Good for distances up to 1000 ft
SUMMARY OF HARMONIC MITIGATION
3. Broadband Filter
Installations where the majority of the load is AC
drives, harmonic mitigation is critical for each drive or a. Greater voltage drop for the motor
for each group of drives. Most installations usually 4. RC Filter
require a minimal amount of harmonic mitigation since a. One-size-fits-all
the fundamental current far exceeds the harmonic b. Must be located at the motor
current. However, most specifications call for 5. Sine-wave Filter
harmonic levels to be measured at the input to AC a. Best waveform
drives, at levels significantly lower than the b. Good for very long distances
recommendations of the IEEE 519 standard. This c. Most expensive
leads to an increase in the cost of the equipment
SUMMARY OF FIRST TURN FAILURE MITIGATION
which is not necessary. A simple study can help
1. Improve the insulation system of the winding
determine how much mitigation is required instead of
2. Use a form wound construction
demanding the most expensive solution for every
3. Add a dV/dt filter to the output of the drive
piece of equipment installed. [14][15][16][17][18]
To summarize: SUMMARY OF COMON MODE MITIGATION
1. At a minimum, use a Line Reactor Common mode currents can be more difficult to
2. 18-Pulse trace and reduce, but there are some basic practices
a. Widely accepted that should always be followed:
b. Most often specified 1. Insulate both bearings on the motor
c. Works well 2. Use a shaft grounding brush
3. Passive Filters 3. Use a bonding strap to connect the motor to its
a. Suited to lower power ratings <100 hp driven equipment
b. Numerous suppliers 4. Use shielded cables between the drive and
c. Leading PF at no load motor, and ground both ends
4. Active Filters 5. If needed, use an isolation transformer on the
a. Showing up on specifications input to the drive
b. Versatile – used for single drives or
multiple drives CONCLUSION
5. AFE Being aware of these issues and the many solutions
a. Widely accepted in Europe available, the AC drive installation can be made
b. Growing in acceptance in North America problem free for the lifetime of the equipment.
SUMMARY OF REFLECTED WAVE MITIGATION
The behavior of reflected waves is well understood. REFERENCES
The switching speed of the IGBTs along with the [1] ANSI/IEEE Std 519-1992, IEEE Recommended
length of cable between the drive and motor have a Practices and Requirements for Harmonic Control in
significant impact on the peak voltage seen at the
9
Electrical Power Systems, New York, NY: IEEE [16] F.L. Hoadley, “Harmonic Fundamentals and a
Press, 1992 Comparison of Harmonic Mitigation Methods for AC
Drives,” a tutorial from PCIC, 2006
[2] IEEE P519.1/D9a, IEEE Draft: Guide for Applying
Harmonic Limits on Power Systems, New York, NY: [17] M.H.L. Bollen, Understanding Power Quality
IEEE Press, 2004 Problems, New York, NY, IEEE Press, 2000
[3] T.M. Blooming and D.J. Carnovale, “Application of [18] R.C. Dugan, M.F. McGranaghan, S. Santoso, H.W.
IEEE Std 519-1992 Harmonic Limits,” in IEEE PPIC Beaty, Electrical Power Systems Quality, New York,
Conference Record, 2006, pp14-22 NY, McGraw-Hill, second edition, 2003
[4] ANSI C57.110-1986, “IEEE Recommended practice [19] G. Skibinski, R. Kerkman, D. Leggate, J. Pankau, D.
for establishing transformer capability when supplying Schlegel, “Reflected Wave Modeling Techniques for
non-sinusoidal load currents”, 1430 Broadway, New PWM AC Motor Drives,” in IEEE IAS Conference
York, NY Record, 1998
[5] A. Kelly et al, " Transformer De-rating for Harmonic [20] G.L. Skibinski, “A Series Resonant Sinewave Output
current a wide band measurement approach for Filter for PWM VSI Loads,” in IEEE IAS Conference
energized transformers” IEEE Transactions on Record, 2002
Industry Applications, Vol. 35, No. 6, Nov, 1999, pp.
1450-1458 [21] G. Skibinski, D. Leggate, R. Kerkman, “Cable
Characteristics and Their Influence on Motor Over-
[6] J. Frank, " Origin, development and design of K-rated Voltages,” in IEEE IAS Conference Record, 1997
Transformers” IEEE Industry Applications Magazine,
Sept, 1997, pp. 67-70 [22] NEMA Standards Publication MG 1-2009, Motors and
Generators, Rosslyn, VA, 2009
[7] R. Paes, T. McDaniel, G. Seggewiss, “Application of
Medium Voltage Adjustable Speed Drives on
Generator Fed Supplies,” in IEEE PCIC Conference
Record, 2004, pp189-198
Frederick (Rick) Hoadley
[8] IEEE Std 1459-2000, IEEE Standard Definitions for
the Measurement of Electric Power Quantities Under ABB
Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced 16250 W Glendale Dr
Conditions, New York, NY: IEEE Press, 2000 New Berlin, WI 53151
Rick.L.Hoadley@us.abb.com
[9] F.L. Hoadley, “Comparison of Methods for the www.abb.com
Mitigation of Line Disturbances due to PWM AC
Drives,” in IEEE PPIC Conference Record, 2007
10