Configuring Interlocks
http://www.free-powerpoint-templates-design.com
Interlocks
need configuring
There are some signals which can stop the system for the safety reason.
When we configure the working order, we need to think about them as well.
If the temperature inside the refrigerator is 5℃ and above for more than 5
seconds, a high temperature alarm shall be generated.
If the temperature inside the refrigerator is 1℃ and below for more than 5
seconds, a low temperature alarm shall be generated.
If there are 3 THA or TLA, the lock down alarm shall be generated. And it stops
the compressor regardless of the auto mode.
You need to add a reset button which can clear the lock down alarm.
The system shall be stopped when the emergency stop button is pressed,
there is a fire alarm from the building management system (BMS) or lock
down alarm.
Let’s do practice.
1
2
3
4
5