Bare soft annealed copper, Class Code 760. B, 7-strand concentric per ASTM B-8. The isolated individual shields over each Flame-retardant Okoseal (PVC) pair, when properly grounded, prevent per UL 83, 15 mils nominal thickness, 90°C crosstalk or capacitive coupling between temperature rating. adjacent pairs which occurs with ac signals, Nylon per UL 83, 4 mils nominal particularly the pulse type. thickness. The overall shield eliminates most of the Pigmented black and static interference from the electric field radi- white in pairs, black, white and red in triads. ated by power cables and other electrical equipment. Aluminum polyester tape over- lapped to provide 100% coverage, and a The C-L-X sheath provides physical protec- 7-strand tinned copper drain wire, two sizes tion against mechanical damage as required smaller than the conductor. All group shields are in NEC Section 725-8 as well as complete completely isolated from each other. protection against moisture or gases entering the cable. Pairs or triads assembled with left- hand lay. Non-wicking fillers included where re- For dc service in wet locations, X-Olene insu- quired to provide a round cable. lation is recommended. Aluminum/polyester tape over- lapped to provide 100% coverage, and a • UL listed for cable tray use, direct burial 7-strand tinned copper drain wire, same size as and sunlight resistant. conductor. • Passes the IEEE 383-1974 and IEEE Black, flame-retardant Okoseal 1202 vertical tray flame tests. per UL Standard 1569. A rip cord is laid longitu- • Passes the 210,000 BTU Vertical Tray Flame dinally under the jacket to facilitate removal. Test utilizing the corner configuration and the A close-fitting, impervious, con- ICEA T-29-520 Vertical Tray Flame Test. tinuously welded and corrugated, aluminum • C-L-X enclosure permits installation in ca- sheath meeting UL 1569 provides complete pro- ble tray containing light and power cables without a barrier separator. tection against moisture, liquids, and gases, has excellent mechanical strength, and provides • Individual pairs or triads are numbered and color coded for simplified hook-up. equipment grounding through the sheath. Black, flame-retardant Okoseal • Individual units are completely isolated for maximum noise rejection. per UL Standard 1569. UL Listed as Type MC-HL Arti- • Impervious, continuous sheath excludes moisture, gases and liquids. cles 501, 502, and 503 of the National Electrical Code. • C-L-X sheath exceeds equipment ground- ing conductor requirements of NEC Article 250. Okonite C-L-X type SP-OS (shielded pairs or tri- • Excellent compression and impact resis- ads - overall shield) instrumentation cables are tance. designed for use on Class 1 Remote-Control • Lower installed system cost than conduit Signaling circuits or where a 600V cable is de- or EMT systems. Bare Stranded Copper sired, as instrumentation, process control, or • OSHA Acceptable. Conductor Okoseal Insulation/Nylon Jacket computer cable transmitting signals at levels • Complies with NEC Articles 501, 502 & above 100 mili-volts in circuits where maximum 503 for hazardous locations. Tinned Stranded Copper Group Drain Wire noise protection is required. Protection from in- • UL 1309 (CWCMC) listed & UL classified Aluminum/Polyster Tape terference among groups as well as external in accord with IEEE 1580 as Marine sources is provided by individual group shields Shipbloard Cable rated 600/1000 volts. Twisted, Shielded Pairs/Triads Tinned Stranded Copper Drain Wire as well as an overall cable shield. For use in- • American Bureau of Shipping Type Aluminum/Polyester Tape doors or outdoors; wet or dry locations; in cable approved as CWCMC Type MC-HL. Rip Cord trays’ in raceways; supported by a messenger • Recognized by US Coast Guard as Type Inner Black Okoseal Jacket wire; for direct burial; in Classes I, II, and III, Di- MC and CWCMC. Impervious, Continuous, Corrugated visions 1 and 2 and Class I, Zones 1 and 2 • Suitable for low temperature installation to Aluminum C-L-X Sheath hazardous locations per NEC Articles 501, 502, -40°C. Outer Black Okoseal Jacket 503 and 505. For use as non-power limited fire • Meets API Standards 14 F and 14FZ. C-L-X Okoseal-N SP-OS UL R
Multiple Shielded Pairs or Triads - Individual and Overall Shield
Conductor Resistance, nominal ........................ohms/1000 ft. @20°C * for calculation of cable tray fill in accordance with 16 AWG ......................................................................4.1 NEC Section 392.22. Insulation Test Voltage (spark test) ...............................6000 Volts ac Optional jacket types available - consult local sales office. Dielectric Test Voltage .................................2000 Volts ac for 60 sec. available on special order. Insulation Resistance Constant @60°F minimum To order C-L-X Type SP-OS without the outer Okoseal jacket (not “HL” (natural material typical value) ..2000 Megohms-1000 ft. listed), change the sixth digit of the catalog number from 3 to 1, for exam - Loop Resistance, nominal (2 conductor)............ohms-1000 ft @20°C ple to order 1 pr. 20 AWG with a bare aluminum C-L-X, the catalog number would be 564-10-1212. 16 AWG ......................................................................8.2 Mutual Capacitance (PF/ft.)* Cut lengths of 1000 ft. or longer are subject to a toler- ance of + \ -10%; less than 1000 ft. + \ -15% #16 ..............................................................................60 *Typical Value