Industrial Generator Set Accessories

Remote Serial Annunciator

Remote Serial Annunciator RSA 1000


for Kohlerr Controllers
D Annunciator panel monitors the condition of a
generator set equipped with one of the following
controllers:
Overcrank Not-In-Auto
Decision-Makert550 version 2.10 and higher
High Engine Temp. Common Fault Decision-Makert3+ version 1.13 *
Low Oil Pressure Battery Charger Fault

Battery Voltage
D Meets the National Fire Protection Association
Overspeed On=High, Blink=Low
Standard NFPA 110 for critical facilities.
Emergency Stop User Input #1

Low Coolant Lvl/Aux. User Input #2


D Surface- or flush-mount box provided. Also fits in
a standard 203 mm x 203 mm (8 in. x 8 in.)
Low Coolant Temp. User Input #3
Hoffman box.
EPS Supplying Load Alarm Silenced
D Uses Modbusr RTU (Remote Terminal Unit), an
industry standard open communication protocol.
Low Fuel

Communication Status
D Controller connections:
System Ready RS-485 network communications
Generator Running 12-/24-volt DC power supply
D One remote serial annunciator (master) can
support additional remote serial annunciators
(slaves). The RSA 1000 is a Modbusr master
device to the generator set controller.
D RSA panel includes writable surfaces (four white
boxes in illustration) for user data.
W
W D Dimensions—W x H x D, mm (in.)
Surface Mounted:
203 x 203 x 51.5 (8.0 x 8.0 x 2.0)
Flush Mounted:
H 203 x 203 x 53.0 (8.0 x 8.0 x 2.1)
H Flush mounting plate W1: 229 (9.0)
Flush Mounted: [
203 x 203 x 103 (8.0 x 8.0 x 4.1)
Flush mounting plate W1: 229 (9.0)
D
D W1 * Requires controller main circuit board GM28725 and communication module
kit GM32644-KP1 or GM32644-KA1
[ Requires user-supplied Hoffman box 203 x 203 x 102 mm (8 x 8 x 4 in.)
Surface Mounted Flush Mounted Modbusr is a registered trademark of Schneider Electric.

G6-66 8/07c
System Generator Communication
Fault and Status Conditions Fault LEDs Fault Horn Ready LED Running LED Status LED
Overcrank Shutdown Red On Red Off Green
High Engine Temperature Warning * Yellow On Red Green Green
High Engine Temperature Shutdown Red On Red Off Green
Low Oil Pressure Warning * Yellow On Red Green Green
Low Oil Pressure Shutdown Red On Red Off Green
Overspeed Shutdown Red On Red Off Green
Emergency Stop * Red On Red Off Green
Low Coolant Level/Aux. (Shutdown) Red On Red Off Green
Low Coolant Temperature * Yellow On Red Off Green
Low Fuel—Level or Pressure * Yellow On Red Green or Off Green
Not-In-Auto Red On Red Green or Off Green
Common Fault Red On Green Green or Off Green
Battery Charger Fault (550 controller) * Yellow On Red Green or Off Green
Battery Charger Fault (16-light controller) * Yellow On Green Green or Off Green
High Battery Voltage * Yellow Off Green Green or Off Green
Low Battery Voltage * Yellow Off Green Green or Off Green
User Input #1 Red On Green Green or Off Green
User Input #2 Red On Green Green or Off Green
User Input #3 (550 controller) w Red On Green Green or Off Green
EPS Supplying Load Yellow Off Green Green Green
Green LEDs appear as steady on when activated.
Yellow LEDs slow flash when activated except steady on with EPS supplying load and high battery voltage.
Red LEDs slow flash when activated except fast flash with loss of communication and not-in-auto.

Specifications NFPA Requirements


D Power source with circuit protection: 12- or 24-volt DC D To meet NFPA 110 requires the RSA 1000 must comply with
D Power draw: 200 mA Section 5.6.6.
D Humidity range: 0% to 95% noncondensing D Engine functions:
d High battery voltage warning *
D Operating temperature range: --20°C to +70°C
(--4°F to +158°F) d High engine temperature shutdown
d High engine temperature warning *
D Storage temperature range: --40°C to +85°C d Low battery voltage warning *
(--40°F to +185°F)
d Low coolant level/aux. shutdown
D Standards: d Low coolant temperature warning *
d CE Directive d Low fuel warning (level or pressure) *
d EN61000-4-4 Fast Transient Immunity d Low oil pressure shutdown
d NFPA 99 d Low oil pressure warning *
d NFPA 110, Level 1 d Overcrank shutdown
d UL 508 Recognized d Overspeed shutdown
D RS-485 Modbusr isolated port D General functions:
D 19200 baud rate d Audible alarm silence
D NEMA 2 enclosure d Battery charger fault *
d Lamp test
Standard Features d Master switch not-in-auto
D Up to twenty-five LED indicating lights for status, warning, Accessories
and/or shutdown. See the above chart for details.
- Additional remote serial annunciators can report to one RSA
D DIP Switches: master.
d 1—Local or remote ATS (EPS supplying load) [
d 2—User input #1 - Communication module GM32644-KA1 or GM32644-KP1 is
d 3—User input #2 required with Decision-Makert 3+ controllers.
d 4—Master or slave - Modbusr/Ethernet Converter GM41143-KP2 for network
d 5— Generator Set Controller or Modbusr/Ethernet connections.
network connection ]
* May require optional kit or user-provided device to enable function and LED indication.
[ User may connect the ATS (EPS Supplying Load) signal wiring at either the controller (remote) or at the RSA master (local).
] RSA Version 2.0 or higher.
w Digital input #3 is factory-set for high battery voltage on the 16-light controller.
Modbusr is a registered trademark of Schneider Electric.
G6-66 8/07c
Fault and Status LEDs and Lamp Test Switch
Alarm Horn. Horn sounds giving a maximum 65 dB at 1 m Low Coolant Level/Aux. LED lights when engine coolant level
(3.3 ft.) audible alarm when a warning or shutdown fault is below acceptable range on radiator-mounted generator sets
condition exists except on high/low battery voltage or EPS only. When used with a 16-light controller, the LED indicates
supplying load. low coolant level or an auxiliary fault shutdown. Requires
customer-supplied low coolant level switch on remote radiator
Alarm Silenced. Red LED lights when alarm horn is models.
de-activated by alarm silence switch.
Low Coolant Temperature. LED lights if optional engine block
Alarm Silence Switch. Switch quiets the alarm during heater malfunctions and/or engine coolant temperature is too
servicing. The horn will reactivate upon additional faults. low. Requires prealarm sender on some models.
Aux. See Low Coolant Level/Aux. Low Fuel Pressure. LED lights if fuel level in tank approaches
Battery Charger Fault. LED lights if battery charger empty. Requires customer-supplied level switch.
malfunctions. Requires battery charger with alarm contact. Low Oil Pressure. Red LED lights if generator set shuts down
Battery Voltage. LED flashes if battery or charging voltage because of insufficient oil pressure. Yellow LED lights if engine
drops below preset level. LED lights steady if battery voltage oil pressure approaches shutdown range. Requires warning
exceeds preset level. sender on some models.
Common Fault. LED lights when a single or multiple common Overcrank. LED lights and cranking stops if engine does not
faults occur. start in either continuous cranking or cyclic cranking modes.
Communication Status. Green LED lights indicating Overspeed. LED lights if generator set shuts down because of
annunciator communications functional. Red LED indicates overspeed condition.
communication fault. System Ready. Green LED lights when generator set master
Emergency Power System (EPS) Supplying Load. LED switch is in AUTO position and the system senses no faults.
lights when the generator set is supplying output current (550 Red LED indicates system fault.
controller) or when transfer switch is in the emergency position User-Defined Digital Inputs #1, #2, and #3. Monitors three
(16-light controller). digital auxiliary inputs (status, warnings, and/or shutdowns).
Emergency Stop. LED lights and engine stops when Individual red LEDs flash when a fault occurs or the status
emergency stop is made. May require a local emergency stop changes. User-defined digital input #1 and #2 are selected via
switch on some 16-light controllers. the RSA master DIP switches for local or remote.
Generator Running. LED lights when generator set is in 16-Light Controller. When remote, digital input #1 and #2 are
operation. tied to the communication module. When local, they are tied
directly to the RSA master. Digital input #3 is factory-set for
(Generator Switch) Not In Auto. LED lights when generator high battery voltage.
set master switch is in RUN or OFF/RESET position.
550 Controller. When remote, digital inputs #1, #2, and #3 are
High Engine Temperature. Red LED lights if engine has shut tied to controller digital inputs (D7, D8, and D10). When local,
down because of high engine coolant temperature. Yellow LED user-defined digital inputs #1 and #2 are tied directly to the
lights if engine coolant temperature approaches shutdown RSA master. Input #3 is remote only.
range. Requires warning sender on some models.
Lamp Test Switch. Switch tests all the annunciator indicator
LEDs and horn.
Communications
Local Single (Master) Connection Local Multiple (Master/Slave) Connections
A single RSA connects directly to the controller’s A single RSA master connects directly to the controller’s
communication port with an RS-485 cable for applications communication port with an RS-485 cable for applications up to
up to 1220 m (4000 ft.) from the device. 1220 m (4000 ft.) from the controller. Additional RSAs (slaves)
can connect to the single master RSA up to 1220 m (4000 ft.)
Communication from the controller. Status of the RSA (master) is annunciated
Module on the RSA (slave) panel.
(16-light only)
Communication
Remote serial Generator set Module
annunciator controller (16-light only)
(master) Remote serial
RS-485 Generator set
annunciator
up to 1220 m controller
(master)
(4000 ft.) RS-485
up to 1220 m
RS-485 (4000 ft.)
up to 1220 m
(4000 ft.) RS-485 up to
Available on 1220 m (4000 ft.)
PC 550 controller with from controller
(user supplied) KBus only Remote serial Remote serial
annunciator annunciator
(slave) (slave)

G6-66 8/07c
KOHLER CO., Kohler, Wisconsin 53044 USA Kohler Power Systems
Phone 920-565-3381, Fax 920-459-1646 Asia Pacific Headquarters
For the nearest sales and service outlet in the 7 Jurong Pier Road
US and Canada, phone 1-800-544-2444 Singapore 619159
KohlerPower.com Phone (65) 6264-6422, Fax (65) 6264-6455

Modbusr/Ethernet, Single Master or Multiple


Remote serial Modbusr/ Generator
Master/Slave Connections Ethernet set
annunciator
(master) converter controller
An RSA master communicates with a controller and RSA slaves
RS-485
through an Ethernet network. A Modbusr/Ethernet converter is RS-485
Category up to 1220 m
5e
required for each RSA and controller. RS-485 cable connects up to 1220 m (4000 ft.)
(4000 ft.)
the RSA to the converter. Category 5e (Cat 5e) network cable
connects the Modbusr/Ethernet converter to the Ethernet. Modbusr/
Ethernet Communication
Ethernet module
converter
(16-light only)
RS-485
up to 1220 m RS-485
(4000 ft.) Category 5e up to 1220 m
(4000 ft.)
Remote serial Modbusr/ Remote serial
annunciator Ethernet annunciator
(slave) converter (slave)

Communication Connections
Generator Set Decision-Makert 3+ Controller Generator Set 550 Controller RS-485 Port
RS-485 Port The remote serial annunciator connects to the controller circuit
The remote serial annunciator connects to the controller circuit board.
board.

2 TT-1366 TT-1310
1
1 2 3
1. Main circuit board GM28725 (top view)
2. P21 for RSA 1000 RS-485 communication connection 1. Main circuit board (top view)
2. P21 for KBus RS-485 communication connection
3. P20 for RSA 1000 RS-485 communication connection
Remote Serial Annunciator Connections
5 4 3 2 1 RS--485 ISOLAT RS--485 NON--ISOLATED TZ2 TZ3
T1 U1 C13
T2 U6
SW1 R15
1 C5 R13R16
L5 L6
Availability is subject to change without notice. Kohler Co. reserves the
+ + C7
T3 R11 U4 U5 -- + GND -- + GND
right to change the design or specifications without notice and without any
+ C1 P27 RS485 obligation or liability whatsoever. Contact your local Kohlerr generator
TZ1

XMIT

2
GND

RXD
VCC

TXD

VR1 C14
P30 R12 R14 R17U7
U2
R18
R19
R30
R31
set distributor for availability.
C2
D1

D2

K1 C3 C6 R20 R32
17 U3 7 R21 R33
Y1
C4 C15
18 6 R22 R34
+BAT

6
12 Q1
JP1
1
U8
R23 R35 DISTRIBUTED BY:
11 D3 D5 JP2 JP3 R24 R36
DISPLAY
P28

5 L1 40 R25 R37
28
10
4 L2 D4 D6 C16
9 29 39
R26 R38
3 L3 RN1 R1 U9
8 R6 C8 R27 R39
Z1
2 L4 R2 R7 C9 R28 R40
7
1 R29 R41
3 T5
R3
Z2
R8 C10

GND
TB12 + R4
Q2 R5 Z3 R10 C12
R9 C11 L7

T4
HN1 BARCODE

1. SW1 DIP switches 1--5 for digital inputs and master/slave options
2. P27 RS-485 communication connection
3. TB12 input/outputs and DC power supply connections © 2004, 2005, 2007 by Kohler Co. All rights reserved.

G6-66 8/07c