Professional Documents
Culture Documents
Control Philosophy BIogas Compression Package ZI-3765 - HZ
Control Philosophy BIogas Compression Package ZI-3765 - HZ
1. Index
2. Introduction ............................................................................................................................................... 2
2.1- Reference documentation ................................................................................................................. 2
2.2- General Information .......................................................................................................................... 2
3. System Operation Description................................................................................................................... 2
3.1- Gas Circuit .......................................................................................................................................... 2
3.2- Oil Circuit ........................................................................................................................................... 3
3.3- Suction Pressure Control ................................................................................................................... 4
3.4- Suction Condensate Drain System..................................................................................................... 5
3.5- Supply Air System .............................................................................................................................. 5
3.6- Ambient Air Recirculation.................................................................................................................. 5
3.7- Chiller and chilled water pumping Unit ............................................................................................. 5
4. Operational prerequisites.......................................................................................................................... 6
4.1- Manual checks ................................................................................................................................... 6
5. Automatic Actions at Power Up ................................................................................................................ 6
6. Automatic Actions at Start Up ................................................................................................................... 6
7. Automatic Actions at Stop ......................................................................................................................... 7
8. Trip and Emergency Shutdown ................................................................................................................. 7
9. Control modes ........................................................................................................................................... 8
9.1- Local Mode ........................................................................................................................................ 8
9.2- Remote Mode .................................................................................................................................... 9
10. Signals for customer .............................................................................................................................. 9
11. Safety Devices ........................................................................................................................................ 9
1 / 11
2. Introduction
This document describes the control philosophy of the biogas compression package ZI-3765 that is equipped
with a Termomeccanica screw block, intended to deliver a biogas flow increasing its pressure.
This package consists mainly of a screw compressor with its oil lubrication system, driven by main electric
motor, complete with suction heat exchanger and filter, discharge oil separator, heat exchangers and filters,
equipped with chiller for cooling suction heat exchanger and with pumping unit to pump chilled water, along
with electrical panel (MCC) and control panel (UCP).
Compressor is controlled by a PLC (Allen Bradley Compact Logix) and HMI (Allen Bradley)
The system operation description described in detail below shall be read in conjunction with the latest
version of P&ID ADI10690.
2 / 11
Gas inlet pressure, expected between 1 and 35 mbarg, is firstly detected by PT6, which can stop the
compressor in case inlet pressure reaches LL level of 0 mbarg. Gas is cooled down from 20-40°C to 4°C in HE6
which is a shell&tube plate type heat exchanger with chilled water in the shell side as cooling media. Chilled
water is provided by chiller and relevant chilled water pumping unit (see dedicated section below).
Downstream HE6, temperature transmitter TT15 detects gas temperature and gives warning if H value (i.e.
6°C) is reached, while it stops the compressor if HH (i.e. 8°C) temperature is reached. The H and HH value are
adjustable via HMI in the UCP.
Alarm setting of PT2 and PT6?
After being filtered by CF1 gas pressure is sensed by PT2, which gives the feedback to control the motor
speed and bypass valve thus regulating the gas flow delivered by the compressor (see the relevant section
below on “Suction Pressure Control”). In case sensed pressure reaches the LL level of -50mbarg the
compressor is tripped, as excessive vacuum is dangerous for the compressor’s operation considering that
oxygen can be sucked in from the atmospheric air through connections upstream screw block, which may
potentially lead to explosive conditions during compression. The complementary use of an oxygen analyzer
to detect oxygen content in the gas stream to be compressed is strongly recommended.
Gas then goes through the water/ gas cooler HE2. Here the gas is cooled down to a temperature of 45 °C by
cooling water supplied by User. A thermostatic valve TV3 is installed in the water circuit and is set to maintain
a temperature of 45°C on the discharge gas line from HE2, so that TV3 is mechanically regulated to allow
more or less cooling water flow and keep this temperature. Since the pressure dew point of the gas in the
discharge line is around 37°C a temperature of 45°C is suitable to avoid condensation. TV3 set point can be
adjusted manually. Method to change TV3 setpoint manually
At next stage the residual oil and particles present in the gas are removed by discharge filters CF3 and CF4.
The residual oil is drained by automatic condensate drains CDF1 and CDF2. Any details of automatic condensate
drain?
In the discharge line, before the gas outlet connection, temperature is detected by TT4, which has a warning
L set point (i.e. 42°C) and LL trip set point (i.e. 39°C). Pressure is detected by PT1 with H (i.e 6.5 barg) and L
(i.e. 5 barg) warning and HH (7.0 barg) and LL (4.7 barg) trip set points.
Oil passes through thermostatic 3-way valve TV1, which is a mechanical auto-regulated type temperature
valve. The valve is set at a temperature of 95°C sensed upstream so that in case the temperature is higher
part of the oil flow is diverted to heat exchanger HE1 which cools the oil down by means of cooling water,
provided by User. Oil is then mixed and goes through oil filter OF1 -which retains all the impurities before
being re-injected in the screw block.
A small quantity of oil is collected by gas/oil separator cartridge SF1-4 during the last stage of filtration in the
gas/oil separator and is returned to the screw block suction side though the scavenge line and oil scavenge
visors SG1-4.
Details related to CR2 and SCLF1 are missing in oil
circuit.
For this control the Inverter VSD and the gas recycle control valve PCV1 operate jointly.
The inverter VSD regulates the compressor flow rate in the range of 100% down to approximately 50%. (PCV1
fully closed). Any data related to % VSD and Biogas flow rate/pressure
The screw block is selected to reach the design operating conditions, max flow 100% @ max discharge
pressure) given the minimum suction pressure, running at a certain speed. The inverter VSD varies the motor
speed and therefore compressor flow by varying the supply frequency.
If the suction pressure monitored by PT2 is higher than the set point, PCV1 is closed and the VSD increases
the frequency thus increasing the main motor speed provided that it is below the maximum allowable motor
speed.
Conversely, if the suction pressure decreases and goes below the set point, VSD decreases the frequency so
decreasing the motor speed provided that it is above the minimum allowable motor speed and consequently
the gas flow rate decreases.
In case the motor is running at minimum speed and the suction pressure continues decreasing, the PCV1
opens modularly and gas is recycled into the suction so that a stable suction pressure is maintained.
4 / 11
is it PT6? or PDT1? please elaborate it
further?
When SV2 opens at H level and starts discharging, after it reaches L level, it waits 90 seconds after which the
valve is forced closed.
Is the timer adjustable in HMI?
At each start of the compressor HH level of LT1 is inhibited for 90 seconds after which it is enabled.
Additionally, there is an analog gas detector AS1 inside the compressor which has 2 levels (H: 20% LEL; HH:
40% LEL).
When the gas detector reads for H level the fan is started. If gas concertation rises up to HH, then fan still
runs but compressor will trip. What happens when there is "LEL
methane LEL is 4%
sensor failure"? so why alarm is at
20%
3.7- Chiller and chilled water pumping Unit
Once compressor package is started, automatically also the water chiller and the chilled water pumping unit
are started. They are intended to provide chilled water as cooling media to HE6. Similarly, as the compressor
is stopped also the water chiller and pumping units are switched off. Compressor PLC gives the start and stop
command to the Chiller, which as its own standard manufacturer integrated controller, which in turn starts
/ stops the pumping unit. Water chiller is sized and designed to provide chilled water to the inlet heat
exchanger HE6 in a closed circuit. With respect to the chiller, the temperature of chilled water at inlet is 7°C
and at the outlet it is 2°C and water flowrate is approx.. 8178 liters/hour. The water chiller is water cooled,
with cooling water supplied by User, intended to be provided at 32°C at inlet of the chiller and coming out at
44°C at the outlet. For more details on the operation of the chiller and on its own integrated controls please
refer to the Operation and Maintenance Manual of the chiller.
5 / 11
4. Operational prerequisites
Some manual operations and checks must be done by the plant operator as part of the necessary conditions
before starting the compressor package. They are listed below.
- Make sure that the main and auxiliary motors, the starting and control electrical panel (MCC & UCP)
are powered and that the automatic control mode has been selected;
- Make sure that all local stop and emergency buttons are reset;
- Make sure that the supply of instrument compressed air is available;
- Make sure that all manual valves are in the correct position;
- Make sure that cooling water is available;
- Make sure that chiller and chilled water pumping unit are powered and chilled water is available;
- Check that the oil level in the main gas / oil separator is correct. In case, top up.
4. When minimum pressure (i.e. 4.9 barg) is reached in the compressor, MPV1 opens and allows gas to
flow to the outlet. PCV1 is fully open so gas is recirculated in the system.
5. When the motor reaches the minimum speed, then:
the PCV1 starts closing and the motor speed is increased to the set value by the inverter and then
controlled by suction pressure set point;
Inst: Remote Start/
6. Upon reaching the load condition, the suction pressure alarm from PT6 is enabled.
Stop from AETP
(Customer) PLC
There is no check of Lube oil pressure also.
7. Automatic Actions at Stop and temperature in startup
Normal Stop of the compressor can be initiated by pushing the “Stop” button in the Local Operator Panel on
board of the compressor (Local control) or by stop command from HMI in the Control panel (Remote control)
The following sequence is performed when “Stop” is pressed on the HMI display:
The SIS uses a safety relay to ensure a safe shutdown of the compressor upon a trip condition, regardless of
the PLC operation. When a trip is activated, the supply circuit of the main motor is opened thus stopping the
main motor immediately.
7 / 11
Inst: Please confirm
SIL certification of
ESD loop
The ESD signals can be generated by:
When a trip/emergency condition occurs, the relevant safety relay will be latched in the trip state. This relay
can be re-energized by pressing the RESET ALARMS button on the ALARMS window, after all relevant trip
causes have been removed.
1° condition = INLET pressure PT2 (PV) ABOVE the SET POINT (SP)
One signal will regulate the proportional command for opening/closing of the PCV1. Once the PCV1 is
completely closed and compressor is running at minimum speed then another signal can drive the VSD (4-20
mA) regulating its speed.
Similarly once the compressor is running at minimum speed, then PCV1 can be regulated (opening).
Connected to PLC.
TE1 Temp. Probe PTC Main motor high temperature protection. please
--- give the trip value
TT20 Temp Probe PT100 High temperature protection oil circuit 100°C 120°C
10 / 11
Inst.
What about other transmitters warning and
trip valve.
1.PS1
2.PDT-2
3.PDT-5
4.PDT-6
5.TT12
6. PCV1 If PCV performs malfunction.
11 / 11