You are on page 1of 1

Fig.

08 MCV-PN16
Wet Type Alarm Fig.09 MCV-PN25

Brief
ZSFZ series wet alarm valve is a one-way valve which only allows the pressure water to flow into the
system and drive the alarm under the pressure and flow rate. The utility model is mainly used in the wet
system of the automatic sprinkler system, which is used to realize the alarm and start the fire pump. ZSJZ
series water flow indicator is a wet system used to convert water flow signals in the network as the electrical
signal output module or to indicate the location of the fire control center, and implementation of a regional
alarm alarm device.

Application scope
The product is mainly used in automatic
sprinkler system. Common application: all industrial and
general burning material warehouse, hotels, shopping
malls, hospitals, theaters, offices, conference center,
especially suitable for high-rise buildings and
underground engineering, and marine living and service
spaces, control stations etc.. These places generally
have one or more of the following characteristics:
personnel intensive, difficult to evacuate, external
support and fire fighting and rescue more difficult,
important nature, fire hazard.

Installation and maintenance


1. Wet alarm valve should be installed vertically, the height from the ground is generally about 1.2m, on both
sides of the wall distance of not less than 0.5m, the positive 1.2m from the wall, the valve should be
installed before the filter; the main channel hydraulic alarm should be located in a building or near often
have a place to stay, the diameter is 20mm, total length should not be more than 20 meters from the alarm
valve, height of not more than 5 meters. All drains shall be drained and the diameter of each drain shall not
be less than 2 times the diameter of the drain valve.
2. Regularly check the alarm valve, the alarm valve open monthly test, if it is found that the hydraulic alarm
does not ring, should check the alarm or alarm filter to the pipeline, seat hole obstruction, remove dirt, so
that water flow.
3. Found the water from the valve to check the leakage alarm pipeline, wet alarm valve inside no stolen
goods, will open the top valve by sealing. If the rubber seal wear, timely replacement.

Technical data
Model ZSFCZ100 ZSFCZ150 ZSFCZ200
Inlet and outlet path 100 150 200
Structure length 270 346 432
0.14 MPa 30 35
Alarm
0.7 MPa 50 67
flow
1.2 MPa 70 92
(L/min)
1.6MPa 80 104
Rated working pressure 1.6
Imports and exports flange GB/T9113 – 2010
Body material Land use : QT400-15 Ship use : S30408
Pressure Actuating pressure 0.035MPa - 0.05Mpa
switch Contact rating 220VAC 0.5A 24VDC 1A