Modulating control valve PN16


with magnetic actuator M2H...FY...N
for HTHW and steam,
with positioning control and position feedback

Control valve with magnetic actuator for modulating control in district heating
systems and HTHW and steam applications
• Fast positioning time (< 1 s)
• High resolution (> 1 : 1000)
• High rangeability
• Closed when de-energised
• With positioning control and position feedback
• Low friction, robust and maintenance-free

Use The M2H...FY...N valve types are through-port control valves with a fixed magnetic
actuator. The actuator is equipped with connecting electronics for positioning control
and position feedback. At zero current the valves are closed.

The short positioning time, high resolution and high rangeability make these valves ideal
for proportional control of district heating stations and heating plant using HTHW and
steam.
The low-friction, robust and maintenance-free construction makes regular service
unnecessary.

Type summary Operating data


q [mm2]
DN kvs PN Pmed 1.5 2.5 4.0
Valve type [mm] [m3/h] [VA] [VA] L [m]
M2H15FY06N 15 0.6 20 5 40 65 110
M2H15FY15N 15 1.5 20 5 40 65 110

M2H15FYN 15 3.0 20 5 40 65 110


M2H20FYN 20 5.0 20 5 40 65 110
M2H25FYN 25 8.0 20 5 40 65 110

M2H32FYN 32 12 26 6 30 50 80
M2H40FYN 40 20 40 10 20 30 50
M2H50FYN 50 30 40 10 20 30 50

Legend see page 2

Siemens Building Technologies CA1N4348E / 06.2001


Landis & Staefa Division 1/6
Legend :
PN = Nominal power
Pmed = Mean operating power
kvs = Flow rate to VDI/VDE2173, tolerance ±10 %
q = Cross section of AC 24 V or DC 20 V cable (Cu)
L = Max. cable length. With 4-wire connections, the maximum length of a separate 1.5 mm2 Cu
control signal cable may be extended to 200 m.

Ordering The valves are supplied complete with the magnetic actuator and the terminal housing.
The Z200/... damping device can be ordered on request: see 'Accessories'.
When placing an order, please specify the quantity, product description and type code.

Example:
1 control valve M2H25FYN and 1 damping device Z200/32

Technical / The control signal is converted in the terminal housing into a phase cut signal which
Mechanical design generates a magnetic field in the coil. This causes the only moving part, the armature, to
change its position in accordance with the interacting forces (magnetic field, counter-
spring, hydraulics etc.). The armature responds rapidly to any change in signal, trans-
ferring the corresponding movement directly to the control disc, enabling fast changes in
load to be corrected quickly and accurately.

The valve position is measured continuously. Any disturbance in the system is rapidly
corrected by the internal positioning controller, which ensures that the control signal and
the valve stroke are exactly proportional, and also provides a feedback signal indicating
the valve position.

Stroke [%]
94.0004
100

80

60

40

20

0 Control signal [V]


0 2 4 6 8 10

If the power is switched off or fails, the valve is automatically closed by the force of the
spring.

The valve stem is sealed with a maintenance-free O-ring gland.


See sheet 4028 for a detailed description of operation.

Manual adjustment The control path can be opened mechanically to between 0 and approximately 90 %, by
turning the handwheel clockwise. The manual adjustment facility can also be used as a
mechanical method of low limit control, i.e. the valve will exercise its normal control
function between the manually-set position and the 100 % open position. For full-stroke
automatic control, the handwheel must be set to 0 (the anticlockwise end-stop).

Accessories Z200/... Damping device to extend the closing time from <1s to 10... 30 s.
See sheet 4497.

See sheet 4000 for an overview of water and steam valves.

CA1N4348E / 06.2001 Siemens Building Technologies


2/6 Landis & Staefa Division
Sizing Flow / pressure differential relationship.
Water flow chart kvs signifies the volume of water V in m3/h, which flows through the open valve at a
pressure differential ∆pv of 100 kPa (1 bar).
See sheet 4023 for notes on calculating the value of kvs.
.
V
[m 3 / h ] 9I666E [l / s]

100

70 20
M2H..FY..N
50
40
30 10
30 k VS
50
DN 20
20 k VS
40 5
DN 12 4
k VS
32
10 DN 8 3
k VS
25 2
7
DN 5 7
5 k VS
20
4 DN 3 1
3 k VS
5
D N1 0 ,7
2
1 ,5 0 ,5
k VS
1 5 0 ,4
DN
0 ,3
1

0 ,7 0 ,6 0 ,2
k VS
5
0 ,5 D N1
0 ,4
0 ,1
0 ,3
0 ,0 7
0 ,2
0 ,0 5

10 20 30 50 70 100 200 300 50 0 700 1 0 00 [ k Pa ]

0 ,1 0 ,2 0,3 0 ,5 0,7 1 2 3 5 7 10 [b ar ]

pv

Saturated steam flow chart

9I667E

M2H..FY..N 0,
6
1,
5
3 5 8 12 20 30
]

k VS k VS k VS k VS k VS k V
S
k VS k VS
p 100 [

b
1
pv

0,42
0,30
0,20
0,15
0,10
0,05

100 200 300 500 1000 [k Pa] 3 4 5 7 10 1 2 3 4 5 7 10 2 2 3 4 5 7 10 3 2 3 [k g /h ]


1 2 3 5 7 10 [b ar] .
m
p1

Mounting notes Two sets of mounting instructions are enclosed with the valve: Ref. 35640 (valve) and
Ref. 35677 (terminal housing).

Warning : Always disconnect the power before fitting or removing the terminal
housing. The terminal housing is calibrated and matched to the actuator,
and should be replaced only by qualified personnel.

– A fine mesh strainer installed on the inlet side of the valve is essential to prevent the
ingress of grit.
– Vertical to horizontal mounting: Protection standard IP31. The valve must not be
suspended below the horizontal.
– The actuator must not be lagged.
– For special information on use in steam applications, see sheet 4026.

Siemens Building Technologies CA1N4348E / 06.2001


Landis & Staefa Division 3/6
Recommendation Water systems should be cleaned, flushed and treated in accordance with current good
practice, as described, for example, in BSRIA Application Guides AG 8/91 and AG2/93.
For other relevant information, see also CIBSE Guide B (Section 7).

Technical data Electrical interface: Only admissisble with low voltage (SELV, PELV)
Supply voltage AC 24 V, 50/60 Hz
– Max. voltage tolerance +15/–10 %
Nominal power See table 'Operating data' page 1
Control signal DC 0 ...10 V or DC 4 ... 20 mA
Position feedback (output signal) DC 0 ...10 V = 0 ...100 % stroke
– Max. load 1.5 mA
– Accuracy ± 3 % of full scale
Nominal pressure PN16
Operating pressure pemax:
Water up to 120 °C 1.6 MPa (16 bar)
Above 120 °C 1.3 MPa (13 bar)
Saturated steam 0.9 MPa ( 9 bar)
Pressure differential ∆pvmax 1.0 MPa (10 bar)
Leakage at ∆pv = 0.1 MPa (1 bar) Max. 0.05 % kvs (to VDE/VDI2174)
Temperature of medium 2 ...180 °C
Valve characteristic (stroke, kv) Linear, optimised in low opening range
Resolution ∆H / H100 > 1 : 1000 (H = Stroke)
Type of operation Modulating
Manual adjustment Up to max. 90 %, depending on DN
Position when de-energised Closed
Orientation Upright to horizontal
Positioning time *) <1s
Materials:
Housing Spheroidal graphite cast iron (GGG40.3)
Seat / inner valve CrNi steel
Valve stem seal EPDM (O ring)
Connection terminals Screw terminals for 4 mm2 wire
Protection standard Upright to horizontal mounting IP31 to IEC529
Ambient temperature 2 ... 50 °C
Weight (incl. packaging) See table 'Dimensions' on page 6
Conformity Meets the requirements for CE marking

*) The valve can be fitted with a Z200/... damping device to achieve a slower closing time of 10 ... 30 s.

CA1N4348E / 06.2001 Siemens Building Technologies


4/6 Landis & Staefa Division
Connection Warning : If the controller and the valve receive their supply from a separate source,
terminals the valve transformer must not be earthed on the secondary side.

40555B

1 ~ AC 24 V supply
2 ⊥ Common
3 Input DC 0 ...10 V
4 Output DC 0 ...10 V
5 Input DC 4 ... 20 mA
6
TE

Connection • with DESIGO 30 – refer to manual R21


diagrams • with INTEGRAL RS – refer to manual K21

• with MULTIREG Warning : The T2 transformer must not be earthed on the secondary side and
should be suitably fused.

T1 T2
AC 24 V AC 24 V

RPR1 M2H...FY...N 50243en

1
AC 24 V
2 1 ~ AC 24 V Supply
GND 3 2 Common
Output DC 0 ...10 V 15 3 Input DC 0 ..10 V
1)
Input DC 0 ...10 V 9 4 Output DC 0 ..10 V
5
1) 6 T E
Valve position indication
U
DC 0 ...10 V = 0 ...10 %

T2
• with other controllers AC 24 V
(output DC 0 ...10 V)
M2H...FY...N 50244en

1 ~ AC 24 V Supply
2 Common
Output DC 0 ...10 V 3 Input DC 0 ...10 V
4 Output DC 0 ...10 V
5
1) 6 T E

Valve position indication U


DC 0 ...10 V = 0 ...100 %

T2
• with other controllers AC 24 V
(output DC 4... 20 mA)
M2H...FY...N 50996en

1 ~ AC 24 V Supply
2 Common
Output DC 4 ... 20 mA 3
4 Output DC 0 ... 10 V
5 Input DC 4 ... 20 mA
1) 6 T E

Valve position indication U


DC 0 ...10 V = 0 ...100 %

1) only if needed

Siemens Building Technologies CA1N4348E / 06.2001


Landis & Staefa Division 5/6
Application Examples of installation in straight-through applications (principles only, without
examples installation-specific details)
9H808 A

9H807 A

D E

D : District heating (supply heating) system, indirect connection


E : District heating (supply heating) system, directly connected to water-heating system.

Dimensions All dimensions in mm

940224

ø 40
min.
100

øE
H

Cable connection max. 2 x ø 11,8

b ød

Flange dimensions to DIN2533, PN16


øD
øk

1 2
DN

Valve type L øD ød b øk H øE F W
M2H15FY...N 130 95 4x14 14 65 318 80 84 7.3
M2H20FYN 150 105 4x14 16 75 320 80 84 8.3
M2H25FYN 160 115 4x14 16 85 338 80 84 9.3

M2H32FYN 180 140 4x18 18 100 373 100 94 14.3


M2H40FYN 200 150 4x18 18 110 434 100 94 16.8
M2H50FYN 230 165 4x18 20 125 518 125 108 27.0

W = Weight (incl. packaging) in kg