1071 WATERSIDE PROJECT

HOUSE INTERIOR RENOVATION


PROJECT FOR UNIT 1071
FORM J1AE ● ABRIDGED VERSION of MANUAL J, 8TH EDITION
Project 1555 HOLLYWOOD GARAGE Design State & City Florida Fort Lauderdale
Indoor Design Heating db 70 @ Outdoor (Winter) 99% db 50 HTD 20
Indoor Design Cooling db 75 @ Outdoor (Summer) 1% db 90 CTD 15
Indoor Design Cooling RH 50% Grains Difference 64 Daily Range Low
Latitude 26 Elevation 10 ACF 1,000 Block Load
Glass . Heating Cooling Net Heating Cooling
Direction Construction Detail HTM HTM Area BTUH BTUH

6A Windows N 1A-cuo-c Single pane 1/4" glass, operable glass Metal no break 25,40 23,00 11,00 279 253
& Glass NE/NW 1A-cuo-c Single pane 1/4" glass, operable glass Metal no break 25,40 36,00 12,00 305 432
Doors

Table6B
2A Construction
Skylights Numbers and Detailsthat Apply to this Load Estimate
0
0
0
7 Wood & a 11D-Wood Solid Core 12,00 18,00 18,0 216,0 324,0
Metal b 11F-Solid Core with Metal Storm 5,60 8,40 136,0 761,6 1142,4
Doors c

8 Above Grade Walls a 13AA-0occ Block, no exterior or interior finish, core filled 6,08 6,51 223,0 1355,8 1450,7

b 13AA-0occ Block, no exterior or interior finish, core filled 6,08 6,51 189,0 1149,1 1229,6

c 13AA-0occ Block, no exterior or interior finish, core filled 6,08 6,51 64,0 389,1 416,4
d
e
Partition Walls f
g
9 Below Grade Walls a
b
10 Ceilings a 16C-7-10w R-7 roof decking, 2,24 5,04 439,0 983,4 2212,6
b
c
Partition Ceilings d
e
11 Passive Floors a 19AP-0c No Wall Insulation, Vented Crawlspace, No Floor Insulation, Carpet
8,98 2,76 439,0 3941,9 1211,6
b
Exposed Floors c
Slab (Perimeter Ft.) d
Basement Floor e
Partition Floors f
g
Envelope Leakage Average Heated & Cooled
12 Infiltration 439 Above Grade = Cu. Ft. 4319,76 966 380
No. of Fireplaces Floor Area = Sq. Ft.

Number of Bedrooms 2 Occupants 3 460


13 Internal Gains
Appliance - 2400 BTUH 1200
14 Sub Totals 13609 11154
7E-T&B SA in Attic, RA Riser in Floor to Ceiling Chase, Perimeter Supply Outlets
15 Duct Loss & Gain R-Value = 6 Leakage Class .12/.24 0,144 0,272 957
Installed Square Feet of Surface or Default = 1 Supply 1 Return 1
Furnace Water Heater
16 Ventilation Combustion Air From Conditioned Space Table 8A CFM 42 923 692
19 Blower Heat Gain Manufacturer's performance data has no blower heat discount 1707
20 Total Sensible Loss or Gain 11270 12142
Latent Infiltration load for cooling 1003
Enter Company Name Here Latent load for occupants 600
Enter Company Address Here Latent load Small Medium Large
60
Enter Company City, State and Zip Code Here 21 for plants 1 1 1
Enter Company Phone Numbers Here Latent load for duct in unconditioned space
Enter Website or Email Address Here Latent ventilation load for cooling 1826
Total Latent Gain 3489
VERTICAL GLASS

Top of
Width
Heating Direction Clg Clg Clg Height of Overhang Opening Adjustment Clg
Htg of for Projected
# Table 2A Construction Numbers and Details Glass Unshaded Shaded Avg opening Distance to HTM
HTM opening Window or
that Apply to this Load Estimate Faces HTM HTM HTM H (Ft) X (Ft) Overhang French Door Adjustment
(Ft)
Y (Ft)

#1 1A-cuo-c Single pane 1/4" glass, operable glass Metal no break N 25,4 23 23 23 1 4 3,00 1,00 None None
#2 1A-cuo-c Single pane 1/4" glass, operable glass Metal no break NE/NW 25,4 36 23 36 1 4 None None
#3 None None
#4 None None
#5 None None
#6 None None
#7 None None
#8 None None
#9 None None
#10 None None
#11 None None
#12 None None

Table 2A/3A -- Construction Numbers 1 through 7 & 10 -- Vertical Glass Cooling HTM
Heat Loss Heating
SHGC
Enter Construction Number, Glass Type, # Panes, Sash Type, Frame Type, U-Value
N NE/NW E/W SE/SW S
Shading

1c-cuf-c Double pane, fixed sash Metal no break 0,69 0,63 23 36 45 31 30


1c-cuf-c Double pane, fixed sash Metal with break 0,63 0,63 23 36 45 31 30
1c-cuf-c Double pane, fixed sash Wood or wood clad 0,56 0,61 23 36 45 31 30
1c-cuf-c Double pane, fixed sash Insulated fiberglass 0,56 0,61 23 36 45 31 30
1A-cuf-c Single pane 1/4" glass, fixed sash Metal no break 1,13 0,74 23 36 45 31 30
1A-cuo-c Single pane 1/4" glass, operable glass Metal no break 1,27 0,71 23 36 45 31 30

Table 2A/3A -- Construction Numbers 8 & 9 -- Skylight Heat Loss Heating Cooling HTM
SHGC
Enter Construction Number, Glass Type, # Panes, Sash Type U-Value N NE/NW E/W SE/SW S
8cuf-c Flat generic skylight 1/4" glass Metal sash no break (U=1.13) 1,130 0,740

Table 4A -- Construction Number 11 -- Wood and Metal Doors


U-Value
Construction Number; Door Type; Core Insulation
11D-Wood Solid Core 0,390
11E-Solid Core with Wood Storm 0,260
11F-Solid Core with Metal Storm 0,280
11J-Metal, Fiberglass Core 0,600
11S-Overhead Door, Wood Panels or Sections 0,780

Table 4A -- Constructions 12, 13 & 15 -- Above Grade Walls


Shaded
Construction Number; Wall Type; Board R-Value; Cavity R-Value, Exterior U-Value Group
Wall
Finish
14F11-0-m 4 inch concrete wall, Metal studs, R-11 cavity 0,148 H No
12B-0s-m Frame wall, Metal studs, R-11 cavity, wood sheathing, siding 0,122 B No
13CB-0fc Block, Framing w/ R-13 cavity, drywall 0,073 I No
13A-5oc-b Block, brick exterior finish, R-5 insulation, open core, plus interior
finish 0,129 F No
13AA-0occ Block, no exterior or interior finish, core filled 0,304 E No
12E-Osm Frame wall, Metal studs, R-11 cavity, wood sheathing, siding 0,103 E No
15B11-4m-x, Eight inches brick, R-11 in 2 x 4 cavity, R-4 board insulation,
plus interior finish 0,830 K No
15B11-0m-x Eight inches brick or stone, fram- ing with R-11 in 2 x 4 cavity,
no board insulation, plus interior finish 0,125 J No
15B11-0m-x Eight inches brick or stone, fram- ing with R-11 in 2 x 4 cavity,
no board insulation, plus interior finish 0,990 J No

Table 4A -- Construction Numbers 16, 17 & 18 -- Ceilings


U-Value CLTD
Construction Number; Type of Ceiling; R-Value; Roof Material and Roof Color

17B-10w R-13 roof decking, dead air space, R-19 ceiling 0,049 70
16C-7-10w R-7 roof decking, 0,112 45

Table 4A -- Floors
Construction Number 19 -- Floor Over Enclosed Unconditioned Crawlspace or U-Value PTDH PTDC
Basement

19AP-0c No Wall Insulation, Vented Crawlspace, No Floor Insulation, Carpet 0,368 24,4 7,5
Worksheet E: Infiltration
Design Values Heating Cooling Occupants Number Burner HTD CTD T1 Grains ACF
Floor area 439 439 (# BR + 1) Fireplaces Btuh 20 15 64 1,000
Conditioned above grade volume 4319,76 4319,76 3 0 130000 Note: Burner Btuh = 0 for direct-vent appliance
Table 8 Outdoor Air Requirement 0 Heating Cooling
Outdoor air Cfm for 0.35 ACH requirement: 0.35 x above
0 grade volume / 60 = 25 25
Outdoor air Cfm for occupants: 20 x number of occupants = 60
Outdoor air Cfm for burners that take combustion air from conditioned space: 0.50 x input capacity (Btuh) / 1000 = 65
Suggest value for fresh air Cfm: Maximum value from lines 1, 2 or 3 = 65
Envelope Infiltration Rate
Tightness of construction: Envelope = Average Cfm for 1 Fireplace = 20
Table 5A ACH for heating Envelope ACH (heating) = 0,61 Cfm for all fireplaces = 0
Table 5A ACH for cooling Envelope ACH (cooling) = 0,32 Heating Cooling
Infiltration Cfm for heating: Line 6 ACH x above grade volume for heating / 60 + Line 6 fireplace Cfm x number of fireplaces = 44
Infiltration Cfm for cooling: Line 7 ACH x above grade volume for cooling / 60 = 23
Infiltration load for heating (Btuh): To J1ae > 966 < 1.1 x ACF x Line 8 Cfm x HTD
Sensible infiltration load for cooling (Btuh): To J1ae > 380 < 1.1 x ACF x Line 9 Cfm x CTD
Latent infiltration load for cooling (Btuh): To J1ae> 1003 < 0.68 x ACF x Line 9 Cfm x Grains
Suggested Value for Engineered Ventilation Cfm
Compare infiltration rate with suggested fresh air rate: Line 4 Cfm - line 8 Cfm for heating = 21 Line 4 Cfm - line 9 Cfm for cooling = 42
Suggest value for engineered ventilation Cfm: 42 < Largest positive value from line 13 (see line 11, Worksheet H)

Worksheet H: Engineered Ventilation


Design Values Heating Cooling HTD CTD T1 Grains ACF
Above grade volume 4319,76 4319,76 20 15 64 1,00

Code Value for Outdoor Cfm


ACH per local code = 0,000 or Cfm required by local code = 0
Largest above grade volume = 4319,76
Outdoor air Cfm for code ACH value = 0 < ACH (line 1) x volume (line 2) / 60
Code value for outdoor air Cfm = 0 < Largest Cfm value from line 1 or 3
Code Cfm can be provided by a combination of infiltration and engineered ventilation (yes/no)
y Code Cfm shall be provided by engineered ventilation (yes/no)
Smallest infiltration Cfm value (see lines 8 & 9 Worksheet E) = 23
Code Cfm requirement 0 < If line 5 = yes; Cfm = line 4 - line 7) or if line 6 = yes (Cfm = line 4 value)

Design Value for Engineered Ventilation Cfm


Suggested ventilation Cfm (line 14 Worksheet E) = 30
Design value for ventilation Cfm = 50 To J1ae < See Section 3-13, Manual MJ8ae
Note 1: Code Cfm value is a mandatory minimum. The system designer may chose to use a larger value.
Note 2: Use the unabridged version of Manual J if the design Cfm value exceeds 50 Cfm.
Note 2: Use the unabridged version of Manual J if the design features heat recovery equipment.

Ventilation Loads
Ventilation load for heating (Btuh): To J1ae > 0 < 1.1 x ACF x Line 10 Cfm x HTD
Sensible ventilation load for cooling (Btuh): To J1ae > 0 < 1.1 x ACF x Line 10 Cfm x CTD
Latent ventilation load for cooling (Btuh): To J1ae > 0 < 0.68 x ACF x Line 10 Cfm x Grains