Professional Documents
Culture Documents
6A Windows N 1A-cuo-c Single pane 1/4" glass, operable glass Metal no break 25,40 23,00 11,00 279 253
& Glass NE/NW 1A-cuo-c Single pane 1/4" glass, operable glass Metal no break 25,40 36,00 12,00 305 432
Doors
Table6B
2A Construction
Skylights Numbers and Detailsthat Apply to this Load Estimate
0
0
0
7 Wood & a 11D-Wood Solid Core 12,00 18,00 18,0 216,0 324,0
Metal b 11F-Solid Core with Metal Storm 5,60 8,40 136,0 761,6 1142,4
Doors c
8 Above Grade Walls a 13AA-0occ Block, no exterior or interior finish, core filled 6,08 6,51 223,0 1355,8 1450,7
b 13AA-0occ Block, no exterior or interior finish, core filled 6,08 6,51 189,0 1149,1 1229,6
c 13AA-0occ Block, no exterior or interior finish, core filled 6,08 6,51 64,0 389,1 416,4
d
e
Partition Walls f
g
9 Below Grade Walls a
b
10 Ceilings a 16C-7-10w R-7 roof decking, 2,24 5,04 439,0 983,4 2212,6
b
c
Partition Ceilings d
e
11 Passive Floors a 19AP-0c No Wall Insulation, Vented Crawlspace, No Floor Insulation, Carpet
8,98 2,76 439,0 3941,9 1211,6
b
Exposed Floors c
Slab (Perimeter Ft.) d
Basement Floor e
Partition Floors f
g
Envelope Leakage Average Heated & Cooled
12 Infiltration 439 Above Grade = Cu. Ft. 4319,76 966 380
No. of Fireplaces Floor Area = Sq. Ft.
Top of
Width
Heating Direction Clg Clg Clg Height of Overhang Opening Adjustment Clg
Htg of for Projected
# Table 2A Construction Numbers and Details Glass Unshaded Shaded Avg opening Distance to HTM
HTM opening Window or
that Apply to this Load Estimate Faces HTM HTM HTM H (Ft) X (Ft) Overhang French Door Adjustment
(Ft)
Y (Ft)
#1 1A-cuo-c Single pane 1/4" glass, operable glass Metal no break N 25,4 23 23 23 1 4 3,00 1,00 None None
#2 1A-cuo-c Single pane 1/4" glass, operable glass Metal no break NE/NW 25,4 36 23 36 1 4 None None
#3 None None
#4 None None
#5 None None
#6 None None
#7 None None
#8 None None
#9 None None
#10 None None
#11 None None
#12 None None
Table 2A/3A -- Construction Numbers 1 through 7 & 10 -- Vertical Glass Cooling HTM
Heat Loss Heating
SHGC
Enter Construction Number, Glass Type, # Panes, Sash Type, Frame Type, U-Value
N NE/NW E/W SE/SW S
Shading
Table 2A/3A -- Construction Numbers 8 & 9 -- Skylight Heat Loss Heating Cooling HTM
SHGC
Enter Construction Number, Glass Type, # Panes, Sash Type U-Value N NE/NW E/W SE/SW S
8cuf-c Flat generic skylight 1/4" glass Metal sash no break (U=1.13) 1,130 0,740
17B-10w R-13 roof decking, dead air space, R-19 ceiling 0,049 70
16C-7-10w R-7 roof decking, 0,112 45
Table 4A -- Floors
Construction Number 19 -- Floor Over Enclosed Unconditioned Crawlspace or U-Value PTDH PTDC
Basement
19AP-0c No Wall Insulation, Vented Crawlspace, No Floor Insulation, Carpet 0,368 24,4 7,5
Worksheet E: Infiltration
Design Values Heating Cooling Occupants Number Burner HTD CTD T1 Grains ACF
Floor area 439 439 (# BR + 1) Fireplaces Btuh 20 15 64 1,000
Conditioned above grade volume 4319,76 4319,76 3 0 130000 Note: Burner Btuh = 0 for direct-vent appliance
Table 8 Outdoor Air Requirement 0 Heating Cooling
Outdoor air Cfm for 0.35 ACH requirement: 0.35 x above
0 grade volume / 60 = 25 25
Outdoor air Cfm for occupants: 20 x number of occupants = 60
Outdoor air Cfm for burners that take combustion air from conditioned space: 0.50 x input capacity (Btuh) / 1000 = 65
Suggest value for fresh air Cfm: Maximum value from lines 1, 2 or 3 = 65
Envelope Infiltration Rate
Tightness of construction: Envelope = Average Cfm for 1 Fireplace = 20
Table 5A ACH for heating Envelope ACH (heating) = 0,61 Cfm for all fireplaces = 0
Table 5A ACH for cooling Envelope ACH (cooling) = 0,32 Heating Cooling
Infiltration Cfm for heating: Line 6 ACH x above grade volume for heating / 60 + Line 6 fireplace Cfm x number of fireplaces = 44
Infiltration Cfm for cooling: Line 7 ACH x above grade volume for cooling / 60 = 23
Infiltration load for heating (Btuh): To J1ae > 966 < 1.1 x ACF x Line 8 Cfm x HTD
Sensible infiltration load for cooling (Btuh): To J1ae > 380 < 1.1 x ACF x Line 9 Cfm x CTD
Latent infiltration load for cooling (Btuh): To J1ae> 1003 < 0.68 x ACF x Line 9 Cfm x Grains
Suggested Value for Engineered Ventilation Cfm
Compare infiltration rate with suggested fresh air rate: Line 4 Cfm - line 8 Cfm for heating = 21 Line 4 Cfm - line 9 Cfm for cooling = 42
Suggest value for engineered ventilation Cfm: 42 < Largest positive value from line 13 (see line 11, Worksheet H)
Ventilation Loads
Ventilation load for heating (Btuh): To J1ae > 0 < 1.1 x ACF x Line 10 Cfm x HTD
Sensible ventilation load for cooling (Btuh): To J1ae > 0 < 1.1 x ACF x Line 10 Cfm x CTD
Latent ventilation load for cooling (Btuh): To J1ae > 0 < 0.68 x ACF x Line 10 Cfm x Grains