Professional Documents
Culture Documents
MF ABB Transformer Protection
MF ABB Transformer Protection
Motaz Al-Fayomi
Senior Protection Engineer
00962795159787
Motaz.fayomi@yahoo.com
The International Council on Large Electric Systems (CIGRE)
Electrical Fault Types :
RET615 RET620
RET630 RET670
PCM600 V2.11
REX640 Protection and Control IED
Manager
OVER CURRENT
O/C Relay Testing
1-Pickup Testing
2- Timing Test
CONSTANTS
A P
IEC CURVE TYPE TIME (sec)
0.14 0.02 10.029
NORMAL INVERSE
13.5 1 13.500
VERY INVERSE
0.14 0.02 10.029
INVERSE
80 2 26.667
TOC
EXTREMLY INVERSE
0.05 0.04 1.778
SHORT TIME INVERSE
120 1 120.000
LONG TIME INVERSE
1
K1(TMS) set
1.15
I1> (set)
2.3
I(inj)
I(inj)/I1> (set)
2
"1 out of 3", the operation of PHxPTOC is enabled with the presence of high current in
one-phase.
"2 out of 3" or "3 out of 3", single-phase faults are not detected.
"3 out of 3" requires the fault to be present in all three phases.
Measurement modes
• RMS
• Peak-to-peak
The measurement quantity is made by calculating the average from the positive and
negative peak values. The DC component is not included.
Type of reset curve
Immediate reset
Timer resets immediately
Inverse reset
• available only for ANSI (IEEE) and user programmable curves.
• If you use other curve types, immediate reset occurs
Standard delayed inverse reset
EARTH FAULT RELAY
50N/51N Residual connection 50G/51G Neutral connection
Differential Protection (87) Application
The ratio of operate coil and restraint coil is 20%
(Iop/Ires) =((10A/50A)=0.2 , 0.2 * 100 =20%)
The pickup setting of this relay is 25% so the restraint coil is applying more force than
the operate coil and the relay will NOT TRIP
Method Manufacturer
Idiff=|Ip-Is|
ID>> Trip Characteristic
Sum
Blocking
Saturation
Tap changer/
Leakage
ID>
Magnetization
Ibias=|Ip|+|Is|
Fault inside protected Zone Internal
High Diff current
Normal Situation
External
Diff current is zero
Bias current according
Fault
to load current No Fault
Combined Characteristic
5,0 5,0
4,0
Trip 4,0
D
L1 + L2 + L3 Trip
3,0 3,0 D
L1 L2 + L3
D Characteristic
2,0 2,0
L2 + L3 L2 + L3
≥1 Trip
only L1 no Trip (OR)
1,0 1,0
0,0 0,0
2 4 6 8 10 12 14 16
16 2 4 6 8 10 12 14 16
IIbias
bias // IInn Ibias / In
Low operate value (Basic setting)
-CT errors
-Varying tap change position
(if not compensated)
-Transformer no-load current
Slope Section-2
-Differential current caused by CT error
and tap-changer position (if not
compensated) increase at the same
ratio as load current increases
Slop-1=0.0%
Idiff min=0.3 (0.5, 0.3)
`
End section-1=0.5 End section -2=3.0 4.0 I Bias ,A
Slop -2 =40%=(P1-0.3)/(3.0-0.5)→P1=40%(3.0-0.5)+0.3=1.3A
Slop -3 =80%=(P2-1.3)/(4.0-3.00)→P2=80%(4.0-3.00)+1.3=2.1A
DIFFRENTIAL PROTECTION
Idmin 0.3 Id section 1 0.3
End Section1 0.5 Id section 2 1.3
End Section2 3 Id section 3 2.1
Slop Section2 0.4
DIFF
+2 +3
IP = −1 IS = 0
1
I0 = ( IL1 + IL2 + IL3 )
3
−1 0
2 3 5 +2 +3 1
IBias = IP + IS = 1 + 0 = 1 IDiff = IP − IS = −1 − 0 = 1
1 0 1 −1 0 1
1/√3=
2nd and 5th harmonic analysis
i1 iDiff = i1
even
Inrush
2. Harm.
Y Y
t=0
i1 i2 = 0
iDiff = i1
even i1
Inrush
2. Harm.
Y
∆
t=0
i1 I2 = 0
t=0
Inrush -T2 t=0
2nd and 5th harmonic analysis
iDiff = i1 + i2
Over excitation (U/f)
UTr > UN uneven
5. Harm.
i1 i2
i1 i2
i1 I2 ≈ 0
2nd and 5th harmonic analysis
2-The excitation current cause high degree of fifth harmonic, if the transformer is inside
the protected zone.
3-If we have internal fault at the same time as the harmonic content is above set level
and the differential current is below IdMinHigh, will block a trip
Cross Cross
Winding IR IY IB
Block on Block Off
I > pickup
I > pickup with
without 2nd Block Trip
2nd harmonic
harmonic
I > pickup
I > pickup with
HV without 2nd Block Trip
2nd harmonic
harmonic
I > pickup
I > pickup with
without 2nd Block Trip
2nd harmonic
harmonic
I > pickup
I > pickup with
without 2nd Block Trip
2nd harmonic
harmonic
I > pickup
I > pickup with
l.V without 2nd Block Trip
2nd harmonic
harmonic
I > pickup
I > pickup with
without 2nd Block Trip
2nd harmonic
harmonic
Double-pole power outputs Dual single-pole
Dual single-pole power
PO3 and PO4 with trip circuit signal/trip output
outputs PO1 and PO2
supervision contact SO3
PO1 and PO2 are rated Contacts PO3 and PO4 output contact SO3
for continuous current of are almost always has a continuous rating
8 A. used for energizing the of 5 A.
The contacts are breaker trip coils Used as external contact,
normally used for closing such as breaker
circuit breakers and auxiliary contact, is
energizing high burden recommended to break the
trip relays. circuit
Dual single-pole high-speed power outputs HSO1, HSO2 and HSO3
Transformer Details:
Current In HV:
Tap: 11(Normal)
I= 60x10^6/(1.732x132x10^3)
Full Load Current = 262.43 A
Current In MV:
Tap: 11(Normal)
I= 60x10^6/(1.732x33x10^3)
Full Load Current = 1049.72 A
Applied 3 Phase Voltage From Generator or ACDB (400 V L-L) In HV Side
Before Diff. CT’s & Make 3 Phase Short With Ground at MV Side After Diff
CT’s.
Method 1:
HV Voltage × Short Circuit Impedance = 132000 × 0.0788 = 10401.6 V
At 10401.6 V Will Reached The Rated Currents At Both HV and MV
At 400 V The Current At HV Will Be
IHV = (400 × 262.43)/10401.6 = 10.09 A (L-L)
At 400 V The Current At MV Will Be
IMV = (400 × 1049.72)/10401.6= 40.367A (L-L)
Method 2:
I Short Circuit At MV=Full Load Current/%Imp
= (262.43/0.0788)=3330.329 A
At 400V Short Circuit Current Will Be:
=(3330.329 *400)/132000 = 10.09 A(HV)
=(3330.329 *400)/33000 = 40.367 A(MV)
CT Secondary Values = (Rated CT Secondary × Actual Primary
Current)/Rated CT Primary
IHV(Sec) = (1 × 10.09)/400 = 0.0252 A
IMV(Sec) = (1 × 40.367)/2000 = 0.02018 A