Professional Documents
Culture Documents
Manual Operação Inverso KSTAR BluE-S-H5 - H3-User-Manual
Manual Operação Inverso KSTAR BluE-S-H5 - H3-User-Manual
MAINTENANCE MANUAL
KSTAR BluE-H5/H3
ENERGY STORAGE SYSTEM
Stock code:002518
CONTENTS
01 Introduction 01 07 Routine Maintenance 65
1.1 System Introduction 01 7.1 Alarm code 65
1.2 Operation Modes 03 7.2 Error code 66
1.3 Safety Introduction 04
1.4 Battery Safety Datasheet 06 08 Fault diagnosis and solutions 67
1.5 General Precautions 07
1.6 Parts List 08
1.7 System Appearance 11 09 Machine Parameters 70
1.8 Liability Limitation 13
02 Installation 14
10 Routine Maintenance 75
2.1 Installation Site and Environment 14
2.2 Installation 16
2.3 External CT connection 27 11 Quality Assurance 76
2.4 DRED port connections(optional) 27
2.5 Single Line Diagram 28
12 Contact Informaition 77
03 System Operation 30
3.1 Switch On 30
3.2 Switch Off 31
3.3 Emergency Procedure 31
04 EMS Introduction And Set UP 32
CT PV
PV
Normal Loads
Normal Loads
LAN
01 www.kstar.com www.kstar.com 02
User Manual User Manual
1.2 Operation Modes: • PEAK SHIFT: This mode is designed for time-use mode customer. The customer is
able to set up the charging/discharging time & power via inverter screen or APP.
There are three basic modes that end users can choose via inverter screen/APP.
• SELF CONSUME: The energy generated by the solar panels will be used in the $
following order: Feed the home loads; Charge the battery and then, feed into the Electricity Price
grid.When the sun is off, the load will be supported by battery to enhance self
consumption. If the power supply from the batteries is not sufficient, the grid will
support the load demand.
TIME
03 www.kstar.com www.kstar.com 04
User Manual User Manual
This sign indicates a hazardous situation which, if not avoided, 1.3.7 Operation After Power Failure
could result in death or serious injury! The battery system is part of the energy storage system which stores life-threatening high
voltage even when the DC side is switched off. Touching the battery outlets is strictly
The Storion BluE-H5/H3 must not be touched or put into service until prohibited. The inverter can keep a life-threatening voltage even after disconnecting it
5 minutes after it has been switched off or disconnected to prevent from the DC and / or AC side. Therefore, for safety reasons, it must be tested with a
5min an electric shock or injury. properly calibrated voltage tester before an installer works on the equipment.
Other hazards
1.3.4.Setting of Warning Sign for Safety This product is a Lithium Iron Phosphate Battery with certified compliance under the
UN Recommendations on Transport of Dangerous Goods, Manual of Tests and
During instruction, maintenance and repair, follow the instructions below to prevent
non-specialist personnel from causing misuse or accident: Criteria, Part III, subsection 38.3. For the battery cell, chemical materials are stored in
Obvious signs should be placed at front switch and rear-level switch to prevent a hermetically sealed metal case, designed to withstand temperatures and pressures
accidents caused by false switching. encountered during normal use. As a result, during normal use, there is no physical
Warning signs or tapes should be set near operating areas.
danger of ignition or explosion and chemical danger of hazardous materials' leakage.
The system must be reinstalled after maintenance or operation.
However, if the product is exposed to a fire, added mechanical shocks, decomposed,
1.3.5 Measuring Equipment added electric stress by misuse, the gas release vent will be operated. The battery cell
case will be breached at the extreme. Hazardous materials may be released.
To ensure the electrical parameters to match requirements, related measuring
Moreover, if heated strongly by the surrounding fire, acrid or harmful fume may be
equipment are required when the system is being connected or tested.
Ensure that the connection and use matched specification to prevent electric arcs or emitted.
shocks.
1.4.2 Safety Datasheet
1.3.6 Moisture Protection For detailed information please refer to the provided battery safety datasheet.
It is very likely that moisture may cause damages to the system. Repair or maintaining
activities in wet weather should be avoided or limited.
05 www.kstar.com www.kstar.com 06
User Manual User Manual
1.5 General Precautions A certified ABC fire extinguisher with minimum capacity of 2kg must be carried
along when transporting.
DANGER It is totally prohibited to smoke in the vehicle as well as close to the vehicle when
loading and unloading.
Danger to life due to high voltages of the PV array, battery and electric shock. When For the exchange of a battery module, please request for new hazardous goods
exposed to sunlight, the PV array generates dangerous DC voltage which will be packaging if needed, pack it and let it be picked up by the suppliers.
present in the DC conductors and the live components of the inverter. Touching the DC In case of contact with electrolyte, rinse the affected areas immediately with
conductors or the live components can lead to lethal electric shocks. If you disconnect water and consult a doctor without delay.
the DC connectors from the system under load, an electric arc may occur leading to
electric shock and burns.
CAUTION:
Do not touch uninsulated cable ends.
Do not touch the DC conductors. Risk of injury through lifting or dropping the system. The inverter and battery are
Do not open the inverter and battery. heavy. There is risk of injury if the inverter or battery is lifted incorrectly or dropped
Do not wipe the system with damp cloth. during transport or when attaching to or removing from the wall.
Have the system installed and commissioned by qualified people with the Lifting and transporting the inverter and battery must be carried out by more
appropriate skills only. than 2 people.
Prior to performing any work on the inverter or the battery pack, disconnect the
inverter from all voltage sources as described in this document.
1.6 Parts List
WARNING Check the following parts list to ensure it is complete.
Kstar delivers a total system separately on site to client, this consists of:
Risk of chemical burns from electrolyte or toxic gases. During standard operation, no
electrolyte shall leak from the battery pack and no toxic gases shall form. Despite
careful construction, if the Battery Pack is damaged or a fault occurs, it is possible that BluE-S 5000D/BluE-S 3680D
electrolyte may be leaked or toxic gases formed.
Do not install the system in any environment of temperature below -10°C or over
50°C and in which humidity is over 90%.
Do not touch the system with wet hands.
Do not put any heavy objects on top of the system.
Do not damage the system with sharp objects. 1xCT and
Do not install or operate the system in potentially explosive atmospheres or 4xM5*12 2xφ8*60 1xCT Connector 2xAC Collector
com cable
areas of high humidity.
Do not mount the inverter and the battery pack in areas containing highly
flammable materials or gases.
INSTALLATION, OPERATION &
If moisture has penetrated the system (e.g. due to a damaged enclosure), do not
MAINTENANCE MANUAL
KSTAR BluE-H5/H3
ENERGY STORAGE SYSTEM
Do not move the system when it is already connected with battery modules.
Secure the system to prevent tipping with restraining straps in your vehicle.
The transportation of Kstar BluE-H5/H3 must be made by the manufacturer or
2xMC4 1xCollector 1x Mounting Panel 1xUser Manual
an instructed personal. These instructions shall be recorded and repeated.
07 www.kstar.com www.kstar.com 08
User Manual User Manual
4xPower Cable
1x Mounting Panel 12xM6 Gasket (2 black, 2 red) 1x Battery Communication Cable
BluE-PACK10.2 (includ two pieces BluE-PACK5.1) BluE-PACK20.4 (includ four pieces BluE-PACK5.1)
6x Power Cable
8xM6 Gasket 2xPower Cable(1 black, 1 red) 1x Battery Communication Cable 16x M6 Gasket (3 black, 3 red) 1xBattery Communication Cable
09 www.kstar.com www.kstar.com 10
User Manual User Manual
2 3
Figure 4 BluE-H5/H3 Delivery Scope 1
Object Descripition
2 EMS Display Screen Figure 6 Cable Box Part without Covers – Front View
11 www.kstar.com www.kstar.com 12
User Manual User Manual
8 02 Installation
This Manual introduces the basic steps to install and set up Kstar BluE-H5/H3.
9
NOTE:
Please be cautious unpacking the battery, otherwise components could be damaged.
8 2.1.1 General
1 PV1+ DRM
ON GRID
4 This BluE-H5/H3 energy storage system is outdoor version and can be installed in an
2 PV1-
COM
BACK UP
PV2+
5 outdoor or an indoor location.
CT/METER
3 PV2- 6 When BluE-H5/H3 systems are installed in a room, BluE-H5/H3 must not be hampered by
the structure of the building, the furnishings and equipment of the room.
Figure 7 Cable Box Part without Covers
The Storion BluE-H5/H3 is naturally ventilated. The location should therefore be clean, dry
Object Description Object Description and adequately ventilated. The mounting location must allow free access to the unit for
DVC class DVC class
installation and maintenance purposes, and the system panels must not be blocked.
1 PV1, PV2 DVC C 2 GRID DVC C The following locations are not allowed for installation:
3 BACKUP DVC C 4 DRM DVC A habitable rooms;
5 COM DVC A 6 CT/METER DVC A ceiling cavities or wall cavities;
BAT+,BAT-
on roofs that are not specifically considered suitable;
7 INV DVC C 8 DVC C
access / exit areas or under stairs / access walkways;
9 RJ45 DVC C
where the freezing point can be reached, such as garages, carports or other places as
well as wet rooms (environmental category 2);
1.8 Liability Limitation
locations with humidity and condensation over 90%;
Any product damage or property loss caused by the following conditions, Kstar does
places where salty and humid air can penetrate;
not assume any direct or indirect liability.
seismic areas - additional security measures are required;
Product modified, design changed or parts replaced without Kstar authorization;
Sites with altitude below 2000m;
Changes, repair attempts and erasing of series number or seals by non Kstar
places with an explosive atmosphere;
technician;
locations with direct sunlight or a large change in the ambient temperature;
System design and installation are not in compliance with standards and regulations;
places with flammable materials or gases or an explosive atmosphere.
Fail to comply with the local safety regulations (VDE for DE, SAA for AU);
Transport damage (including painting scratch caused by rubbing inside packaging
during shipping). A claim should be made directly to shipping or insurance company 2.1.2 Restricted Locations
in this case as soon as the container/packaging is unloaded and such damage is The BluE-H5/H3 shall not be installed :
identified; (a) in restricted locations as defined for panels in AS / NZS 3000;
Fail to follow any/all of the user manual, the installation guide and the maintenance (b) within 600mm of any heat source, such as hot water unit, gas heater, air conditioning
regulations; unit or any other appliance.
Improper use or misuse of the device; (c) within 600mm of any exit;
Insufficient ventilation of the device; (d) within 600mm of any window or ventilation opening;
The maintenance procedures relating to the product have not been followed to an (e) within 900mm of access to 240Vac connections;
acceptable standard; (f) within 600mm of side of other device.
Force majeure (violent or stormy weather, lightning, overvoltage, fire etc.);
Damages caused by any external factors.
13 www.kstar.com www.kstar.com 14
User Manual User Manual
A BluE-H5/H3 installed in any corridor, hallway, lobby or the like and leading to an 2.2 Installation
emergency exit shall ensure sufficient clearance for safe egress of at least 1 meter. Step 1 Remove the battery and inverter from the packaging box.
The BluE-H5/H3 must also not be installed in potentially explosive atmospheres for gas
cylinders that are heavier than air gases and have a vent clamp in accordance with AS /
NZS 3000.
2.1.3 Barrier to Habitable Rooms
To protect against the spread of fire in living spaces where the BluE-H5/H3 is mounted or
on surfaces of a wall or structure in living spaces with a BluE-H5/H3 on the other side, the Figure 9 Unpacking the
wall or structure shall have a suitable non-combustible barrier. If the mounting surface inverter and battery
itself is not made of a suitable non-combustible material, a non-combustible barrier can be
placed between the BluE-H5/H3 and the surface of a wall or structure.
If the BluE-H5/H3 is mounted at a wall or at a distance of 300mm from the wall or the
structure separating it from the habitable space, the distances to other structures or
2.2.1 Battery Installation
objects must be increased. The following distances must remain free : Step 2 Assemble the battery mounting panel on the battery.
(i) 600 mm beside the BluE-H5/H3;
(ii) 500 mm above the BluE-H5/H3;
(iii) 600 mm before the BluE-H5/H3.
If the distance between the BluE-H5/H3 and the ceiling or any object above the system is
less than 500mm, the ceiling or structural surface above the system must be made of
noncombustible material within a radius of 600mm around the system.
The BluE-H5/H3 must be mounted to ensure the highest point is not more than 2.2m
above the ground or the platform.
Top----------- 500mm
Front--------- 600mm
Laterals------600mm M5*12 Screws
≥500mm
Figure 10 Assemble Battery Mounting Panel
Step 3 Position the battery parallell to the wall and use a Φ8mm drill to drill holes at a
depth of about 70mm in the wall for sub sequent fix ation of the mounting plates.
15 www.kstar.com www.kstar.com 16
User Manual User Manual
Step 4 Remove the debris baffle and secure the battery to the wall with screws and gaskets.
Gasket
Step 5 To assemble the second (and all other) battery, repeat steps 6 and 7,
respectively.
17 www.kstar.com www.kstar.com 18
User Manual User Manual
Step 8 Please make AC cables on site. d. Insert the crimped conductors L, N and PE into the corresponding terminals and tighten the
screw with a hex key wrench screwdriver(size:2.5, 1.2-2.0N.m). Ensure that all conductors are
Step 8-1 Please follow the AC cable requirements below.
securely in place in the screw terminals on the bush insert.
For all AC connections, 4-10mm² 105 XJ cable is required to be used. Please make
sure the resistance of cable is lower than 1 ohm. If the wire is longer than 20m, it's
recommended to use 10mm² cable.
WARNING:
There are"L" "N'' '' '' symbols marked inside the connector, the Line wire of
grid must be connected to "L" terminal; the Neutral wireof grid must be
connected to "N" terminal; the Earth of grid must be connected to '' ''
d
A Object Description Value e. Screw the swivel nut onto the threaded sleeve. This seals the AC connector and provides
B strain relief for the AC cable. When doing so, hold the bush insert firmly by the locking cap.
A External diameter 12mm to 18mm
This ensures that the swivel nut can be screwed firmly onto the threaded sleeve.
U B Copper conductor cross-section 4mm² to 10mm²
O C Stripping length of the insulated conductors approx.13mm
W
C D Stripping length of the outer sheath of the AC cable approx.53mm
D
The PE conductor must be 10mm longer than the L and N conductors
b. Insert the conductor into the suitable ferrule acc. to DIN 46228-4 and crimp the contact.
b f. Assembly the plug shell ,adapter as below picture, Push the adapter and Shell by hand until
a “Click” is heard or felt.
c. Unscrew the swivel nut from the threaded sleeve and thread the swivel nut and threaded
sleeve over the AC cable.
g. Plug the AC connector into the jack for the AC connection by hand until a “Click” is heard
or felt.
c
19 www.kstar.com www.kstar.com 20
User Manual User Manual
Step 8-2 Connect the Backup and Grid cables in advance according to the connector
(8) Use tool to clamp the AC wiring terminal and wire rod; screw the nut, but do not
mode, and connect them to the Backup and Grid board connectors in turn.
tighten it. Make sure that the cable is free to pass through the waterproof components.
Once the terminal is connected to the right site of the inverter, tighten the nut.
PV1+ DRM
ON GRID
PV1-
COM
PV2+
BACK UP
CT/METER
PV2-
Step 9 Take out the communication cable set provided in the accessory parts of one
BluE-H5/H3-BAT, cut off one end and crimp a new RJ45 connector. If there are two
batteries,you only need to remake one of battery communication cable on site.
Or/W Or/W
(9) Connect the AC wiring terminal to the corresponding hole site of the inverter and 1 1
Or Or
lock it with a screw driver or electric screw driver (suggestion: stem diameters and 2 2
G/W G/W
torsion of screwdriver or electric screwdriver should be 4mm and 8~12kg-f.cm 3 3
BI BI
respectively) 4 4
BI/W BI/W 5
5
(10) Tighten the nut. G G 6
6
Br/W Br/W
7 7
(11) Circuit breaker parameters are recommended: Br Br
8 8
Back-up 32A/400Vac 6KA
On-grid 40A/400Vac 6KA Figure 18 Network Cable Type B
NOTE:
The communication cable is in type B, see Figure 18. Leave the power cables
and communication cables hanging on outside. Leave the device aside.
21 www.kstar.com www.kstar.com 22
User Manual User Manual
Step10 Connect the BAT communication cable of the cable box from Step 13 to the Step12 Close the lid and tighten the screw.
topmost battery at the right side. Then use the communication cable supplied with the
batteries to connect the batteries to each other via the respective connectors on the
left side. After you have connected all the modules together, close all covers (if you
want to connect further battery modules, you must mount them before closing).
Figure 21
Step13 Close the battery covers and connect the PV-MC4 connectors to the system
(connection on both sides). Also, connect all AC cables, the meter communications
Figure 19 Wiring the Communication Cable cable METER, and the Ethernet cable LAN. Then close the cable box cover.
The installation is now complete.
Step11 Connect the power cables of the bottom battery from Step 4 to the side
terminals of the top battery. Make sure that red connects to red and black connects to
4*MC4
black.
PV1-
COM
PV2+
BACK UP
CT/METER
PV2-
Figure 22 PV Wiring
23 www.kstar.com www.kstar.com 24
User Manual User Manual
Step14 Open the front cover of the last battery and remove the DIP cover. Now set
the DIP switch 2 to "on" mode and close the cover again. NOTE:
The DIP setting is only changed on the last battery.
If you connect more than 2 battery modules to the system, please only install the
additional batteries 3-4 on the side of the system. You can connect up to 4 batteries, 2
BAT
each mounted on top of each other, to the BluE-H5/H3.
To do this, carry out the individual installation steps as for the first two batteries,
BAT
including the DIP setting on the last module.
DIP Switch
ON
12345
25 www.kstar.com www.kstar.com 26
User Manual User Manual
Figure 25
Figure 26 DRM connector
2. Install the waterproof component and screw on the waterproof sheath nut.
3. Open the external CT wiring port, the arrow points to the direction of the power grid,
2.5 Single Line Diagram
put the wire into the external CT card slot, and buckle the buckle. The single line diagrams of DC-, AC- and Hybrid-coupled sysyem are as below:
Power grid
line L Normal Load
BACKUP Load
BluE-S 5000D
5kW Hybrid Inverter Back up
Switch
PV1
AC
DC CT Grid Meter Grid
PV2
DC Grid Switch
PV Switch DSP
BluE-PACK
BluE-PACK
DRED means demand response enable device. The AS/NZS 4777.2:2015 required inverter BluE-PACK
need to support demand response mode(DRM). This function is for inverterthat comply with
AS/NZS 4777.2:2015 standard. KSG single phase inverter is fully comply with all DRM. A 6P BluE-PACK
27 www.kstar.com www.kstar.com 28
User Manual User Manual
03 System Operation
Normal Load
BACKUP Load
BluE-S 5000D
3.1 Switch On
5kW Hybrid Inverter Back up
Switch When turning on the system, it is very important to follow the steps below to prevent
AC
DC CT Grid Meter Grid damage to the system.
DC Grid Switch
DSP WARNING: Please check the installation again before turning on the system.
EMS Router
Battery
Switch
DC
PV Meter
BluE-PACK AC
BluE-PACK
Normal Load
BACKUP Load
BluE-S 5000D
5kW Hybrid
Back up
Inverter Switch
PV1
AC
DC CT Grid Meter Grid
PV2
DC Grid
PV Switch DSP Switch
Step 1: Turn on the external PV switch.
PV Panels
EMS Router
Battery
Switch
Step 2: Turn on the external grid switch.
DC
PV Meter Step 3: If backup load is applied, turn on the external Backup switch.
BluE-PACK AC
BluE-PACK
PV Inverter PV Panels
BluE-PACK NOTE:
Step 4: Open the outer shell of the cable box. Open the battery switch cover and turn on
Figure 29 Hybrid-coupled system
the battery switch on the cable box.
Step 5: Press power button on all the batteries until the indicator lights turn on.
Step 6: Close the battery switch cover and the outer shell of the cable box.
29 www.kstar.com www.kstar.com 30
User Manual User Manual
described below:
Inhalation: Evacuate the contaminated area, and seek medical attention. Fault indicator
Eye contact: Rinse eyes with running water for 5 minutes, and seek medical Running light
attention.
Reset button
Contact with skin: Wash the affected area thoroughly with soap and water, and
D E F H
seek medical attention.
Ingestion: Induce vomiting and seek medical attention. Figure 30 BluE-H5/H3 EMS Interface Figure 31 BluE-PACK Interface
31 www.kstar.com www.kstar.com 32
User Manual User Manual
33 www.kstar.com www.kstar.com 34
User Manual User Manual
4.2.10 Power
Interface
4.2.6 BMS parameters
Interface POWER
Inverter real - time total power
INV: W
BMS PRMETER CT real-time total power
METER: W
Battery charging voltage
CHAR VOLT: 54.5V Load real-time total power
Battery charging current: (select LOAD: W
CHARGE: 25A according to battery type)
DISCHA: 100A Battery discharging current
4.2.11 Power
Interface
4.2.7 Grid-connected output
POWER PV real-time total power.
Interface
PV I/P: W BACKUP real-time power.
TEMPERATURE
4.2.8 Inverter output Real-time temperature of inverter system radiator.
INV: 25℃
Interface Real-time temperature of Bidirectional DCDC
DCDC: 26℃ system radiator.
Internal ambient temperature.
INV OUTPUT AMBIENT: 27℃
Inverter real-time voltage
VOLT: 0.0V
Inverter real-time current
CURR: 0.00A Inverter real-time frequency
FREQ: 0.00HZ
35 www.kstar.com www.kstar.com 36
User Manual User Manual
--SETUP--
4.2.15 System setting
→1:SYS SETTING
This interface is used for various information
Interface Description 2:BAT SETTING
inquiry options.
Status mode: Self-generation and self- 3:GRID STD Press UP/DOWN button to move the corresponding
consumption,Peak load shifting,and Battery 4:RUN SETTING options.
priority. 5:485 ADDRESS Press ENTER to enter the selected menu.
SYSTEM
Grid-connection standards: China, Germany, Press ESC button to return to the user interface.
STATE: PEAKS HIFT 6:BAUD RATE There are 13 options in total, including system
Australia, Italy, Spain, UK, Hungary, Belgium,
GRID STD: China 7:LANGUAGE mode, battery parameters, grid standard, operation
Western Australia, Greece, France, Bangkok,
PV I/P: INDEPN 8:BACKLIGHT parameters, 485 address, 485 baud rate, language
Thailand, local and 60HZ.
PV input mode:independent connection, parallel display, LCD backlight, date/time, clear history,
9:DATE/TIME
connection,constant voltage. password setting and maintenance, and factory
10:CLEAR REC
Press ESC button to enter user setting setting.
11:PASSWORD
① Working mode
② Input mode
Interface Description
Interface Description
After completing the setup of peak load shifting mode, the time for charging and discharging also ③ZERO EXPORT
needs to be set.
Interface Description
-- ZERO EXPORT --
Back-flow-prevention function.
→1:DISABLE
Default option is disabling.
2:ENABLE
39 www.kstar.com www.kstar.com 40
User Manual User Manual
--EPS ENABLE--
It is enabled when BACKUP load needs power.
→1:DISABLE
Default option is Enabling.
① Battery type
2:ENABLE
Interface Description
41 www.kstar.com www.kstar.com 42
User Manual User Manual
Lead-acid battery parameter ④ Discharge Power limitation of discharge power( inverter power)
Interface Description Interface Description
This interface is used to select other Li battery Press UP/DOWN button to increase or decrease
--LEAD-ACID --
parameter. the input figure;
→1:CHARG-VOLT Press UP/DOWN button to move corresponding
--DISC PERCENT-- Press Enter button to move cursor backward,
2:EQUAL VOLT options;
INPUT: 080% confirm input and return to battery parameters
3:BAT CAP Press ENTER button to enter the selected menu;
interface;
Options include battery charge voltage, battery
4:BAT END VOLT Press ESC button to move cursor forward and
capacity,battery discharge end voltage, battery
5:BAT OVP return to battery parameters interface.
over voltage protection .(see from④to⑦)
⑤ Charge Power
② Discharge depth
Interface Description
Interface Description
Press UP/DOWN button to increase or decrease
Press UP/DOWN to increase or decrease the the input figure;
input figure; --CHAR PERCENT-- Press Enter to move cursor backward, confirm
--DISC DEPTH-- Press Enter to move cursor backward, confirm input and return to battery parameters interface;
INPUT: 020%
INPUT: 60 input and return to battery parameters interface; Press ESC button to move cursor forward and
Press ESC to move cursor forward and return to return to battery parameters interface.
UNIT: %
battery parameters interface;
The value ranges between 10% and 100%. ⑥BAT WAKE-UP
--BAT WAKE-UP--
Battery wake-up enable setting.
→1: DISABLE
The default option is disabling.
2: ENABLE
43 www.kstar.com www.kstar.com 44
User Manual User Manual
--RUN SETTING--
Reactive Power
→ 1:REACT POWER Interface Description
Press UP/DOWN button to move corresponding
2:GRID POWER
options;
3:VOLT MAX -REACT POWER- Press UP/DOWN button to adjust the input figure;
Press Enter to enter the selected menu;
Press ENTER button to confirm or ESC button to
5:VOLT MIN Press ESC button to return to setting interface. INPUT: +60%
cancel the input and return to working interface;
6:FREQ MAX Options include reactive compensation mode, grid
The input value should range between -60% and
7:OVER VOLT power, discharge/charge power, low/high grid Value range
+60%, which varies with the standard.
8:UNDER VOLT power, low/high grid voltage, low/high grid (-60%~+60%)
9: OVER FREQ frequency, VoltOverStart and FreqOverStart (see
10:UNDER FREQ
from①to⑨)
11:REACT RESP
12:VRT_ENABLE
13:POW SI RATE
45 www.kstar.com www.kstar.com 46
User Manual User Manual
③Volt Max -VOLT MIN- Enter option 1 to adjust the minimum volt of
Interface Description →1:VAC-MIN the INV. Enter option 2 to adjust the minimum
2:GRID MIN volt of the grid.
-VOLT MAX -
Enter option 1 to adjust the maximum volt of the INV.
→1:INV MAX
Enter option 2 to adjust the maximum volt of the grid.
2:GRID MAX Low INV voltage
Interface Description
High INV voltage INV Low Voltage Protection Point
-INV VOLT LOW- Press UP/DOWN button to adjust the input figure;
Interface Description Press Enter to confirm the input and enter restart
INPUT:
INV Over Voltage Protection Point interface;
UNIT: V
-INV VOLT HIGH- Press UP/DOWN to adjust the input figure; Press ESC button to cancel the input and return
INPUT: Press Enter to confirm the input and enter restart to operation parameters interface;
Value range
interface; The value should range between 150V and 220V,
UNIT: V
Press ESC to cancel the input and return to (150~200V) which varies with different standards.
operation parameters interface;
Value range The value should range between 240V and 280V,
(240~280V) which varies with different standards. Grid Volt Min
Interface Description
47 www.kstar.com www.kstar.com 48
User Manual User Manual
Interface Description
GRID Freq Min
INV Over Frequency Protection Point
-INV FREQ HIGH-
Press UP/DOWN to adjust the input number; Interface Description
INPUT: 52.0 Press ENTER to confirm the input and enter restart
GRID Low Frequency Protection Point
UNIT: Hz interface; -GRID MIN-
Press UP/DOWN to adjust the input figure;
Press ESC to cancel the input and return to
INPUT: 50.5Hz Press Enter to confirm the input.
Value range operational parameters interface;
The value ranges between 50.5 and 55, which
(50.5 ~55)
varies with different standards.
⑦OVER VOLT
Interface Description
GRID Freq Max
Enter the option 1 to enable or disable the function
Interface Description -OVER VOLT- that the power of inverter derates when voltage is
GRID Over Frequency Protection Point →1:ENABLE too high. Enter the option 2 to adjust the exact
-GRID MAX-
Press UP/DOWN to adjust the input figure; 2:VOLT value of the voltage when power starts to derate.
INPUT: 53.5Hz
Press Enter to confirm the input.
-FREQ MIN- Enter option 1 to adjust the minimum frequency -OVER VOLT-
Derate power when Voltage over.
→1:INV MIN of the INV . Enter option 2 to adjust the minimum →1:DISABLE
The default option is enable.
2:GRID MIN frequency of the grid . 2:ENABLE
49 www.kstar.com www.kstar.com 50
User Manual User Manual
-OVER START- Press UP/DOWN to adjust the input figure; -OVER FREQ-
Derate power when Frequency over.
INPUT: 264V Press Enter to confirm the input. →1:DISABLE
The default option is enable.
2:ENABLE
⑧UNDER VOLT
Interface Description OVER FERQ START
Enter the option 1 to enable or disable the function Interface Description
-UNDER VOLT- that the power of inverter derates when voltage is
→1:ENABLE too low. Enter the option 2 to adjust the exact -OVER START- Press UP/DOWN to adjust the input figure;
2:VOLT value of the voltage when power start to derate. INPUT: 50.50Hz Press Enter to confirm the input.
Interface Description
Enter the option 1 to enable or disable the function
-OVER FREQ- that the power of inverter derates when frequency
→1:ENABLE is too high. Enter the option 2 to adjust the exact
2:FREQ value of the frequency when power start to derate.
51 www.kstar.com www.kstar.com 52
User Manual User Manual
13 POW SI RATE
Description
4.3.8 LCD backlight
Interface
Interface Description
53 www.kstar.com www.kstar.com 54
User Manual User Manual
55 www.kstar.com www.kstar.com 56
User Manual User Manual
Threshold setting value: The value set by upper Threshold setting value: The value set by upper
VACMAX(S1) computer software. FACMIN(S1)
computer software.
Set:253.0V 603s Threshold setting trip time: The trip time set by Set:49.8Hz 100ms Threshold setting trip time: The trip time set by
Tes:253.0V 603s upper computer software. Tes:49.8Hz 97ms
upper computer software.
Cur:230.0V Pass! Threshold auto test value: The value of threshold Cur:49.9Hz Pass!
Threshold auto test value: The value of threshold
during coincidence between the threshold and
current measured value. during coincidence between the threshold and
Threshold auto test trip time: The time from the FACMIN(S2) current measured value.
VACMAX(S2) coincidence between the threshold and current Threshold auto test trip time: The time from the
Set:47.5Hz 100ms
Set:264.0V 190ms to the trip signal of disconnection switch. coincidence between the threshold and current
Tes:47.5Hz 94ms
Tes:264.0V 188ms Current measured voltage or frequency value:
Cur:49.9Hz Pass! to the trip signal of disconnection switch.
Cur:230.0V Pass! The measurement value of grid voltage or
Current measured voltage or frequency value:
frequency during the coincidence.
The measurement value of grid voltage or
Interface Description
frequency during the coincidence.
Threshold setting value: The value set by upper
4.4 Inquiry
computer software.
Threshold setting trip time: The trip time set by Interface Description
upper computer software.
Press UP/DOWN button to move corresponding
Threshold auto test value: The value of threshold --INQUIRE--
VACMIN options;
during coincidence between the threshold and
Set:195.0V 1.52s →1:INV MODULE Press Enter button to jump to the selected menu;
current measured value.
Tes:195.0V 1.50s Press ESC button to return to user interface;
Threshold auto test trip time: The time from the 2:MODULE SN
Cur:230.0V Pass! There are four alternative options: machine
coincidence between the threshold and current
3:FIRMWARE
to the trip signal of disconnection switch. model,serial number,firmware version and
Current measured voltage or frequency value: 4:RECORD
running records (refer to 1 to 4).
The measurement value of grid voltage or
frequency during the coincidence.
① Machine model
Interface Description
Interface Description
Threshold setting value: The value set by upper
FACMAX(S1)
computer software. This interface displays machine model of the
Set:50.2Hz 100ms Threshold setting trip time: The trip time set by --INVERTER--
inverter;
Tes:50.2Hz 94ms upper computer software. BluE H3-5 Press ESC button to return to inquiry interface.
Cur:49.9Hz Pass! Threshold auto test value: The value of threshold
during coincidence between the threshold and
current measured value.
FACMAX(S2) Threshold auto test trip time: The time from the
Set:51.5Hz 100ms coincidence between the threshold and current
Tes:51.5Hz 94ms to the trip signal of disconnection switch.
Cur:49.9Hz Pass! Current measured voltage or frequency value:
The measurement value of grid voltage or
frequency during the coincidence.
57 www.kstar.com www.kstar.com 58
User Manual User Manual
② Grid-connection frequency
--FIRMWARE-- This interface displays firmware version for ARM
Interface Description
ARM VER:1.0.0 and DSP of the inverter;
Press ESC button to return to inquiry interface.
DSP VER:1.0.0 This interface displays grid-connection
-- CONNE.TIMES --
frequency of the inverter;
TIMES: 0
④ Running records Press ESC button to return to statistics interface.
Interface Description
--REC (170)-- 1:F10-1 utmost)(the latest fault or alarm marked as No.1) Interface Description
Time of the fault:
DATE: 2018 - 12-01 Press UP/DOWN button to view the record; --PEAK POWER--
Press ENTER button to enter the description This interface displays power peak in history and
TIME: 00 :01:02 HISTORY: 5000
interface for corresponding records; for the day.
Press ESC button to return to Inquiry interface. TODAY: 0
Press ESC button to return to statistics interface.
UNIT: W
4.5 Statistics
Interface Description
④ The day
This interface is used to select statistics items;
Interface Description
--STAT-- Press UP/DOWN button to move corresponding
→1:TIME STAT. options;
2:CONNE. TIMES Press Enter to enter the selected menu; --E-TODAY-- This interface displays power generation for the
3:PEAK POWER Press ESC button to return to user interface;
PV: 0.0KWH day(kWh);
There are eight alternative options in total: time
4:E-TODAY PV power generation;
METER: 0.0KWH
5:E-MONTH accounting,grid-connection frequency/ peak Electric energy selling to grid;
power/ power generation for the day / power GRID: 0.0KWH Electric energy buying from grid;
6:E-TEAR
LOAD: 0.0KWH Power consumption of load;
7:E-TOTAL generation for the month/ power generation for the
year/gross power generation (refer to 1 to8).
59 www.kstar.com www.kstar.com 60
User Manual User Manual
⑤The month
05 Wireless Router Connection
Interface Description
5.1 Download APP
--E-MONTH-- This interface displays power generation for the
Step 1: Scan the QR Code on the right side and download the APP.
PV: 0.0KWH month(kWh);
METER: 0.0KWH PV power generation;
Electric energy selling to grid;
GRID: 0.0KWH Electric energy buying from grid;
LOAD: 0.0KWH Power consumption of load;
⑥The year
iOS Android
Interface Description
WLAN
CHOOSE A NETWORK...
W2015
Please enter user name
W0016250020617 Login
Wifi-test
Wi-Fi Config
--E-TOTAL- Wifi111
Register
This interface displays gross power generation;
PV: 0.0KWH DEMO>
PV power generation;
METER: 0.0KWH Electric energy selling to grid;
GRID: 0.0KWH Electric energy buying from grid;
Power consumption of load;
LOAD: 0.0KWH
Please Restart! Step 3: After the Wi-Fi PlugII is restarted,reconnect the Wi-Fi which connected
by step 5.1.
61 www.kstar.com www.kstar.com 62
User Manual User Manual
W2015
PASSWORD
Confirm password:
Eybond2015
12345678
Step 2: Scan the PN on the Wi-Fi PlugII,or input it manually.
Eybond 2.4g
Connect
Wi-Fi Datalogger
W0016250020617
Step 3: According to the prompts, type in the information to finish add datalogger.
Wifi-test
Wifi111
新建电站
Add datalogger
新建电站
Setting
Datalogger List Add datalogger Confirm massage
Network Setting Network Diagnose Search
Design Power(kW) Enter
Datalogger Name
PN:12345667898 Datalogger PN Datalogger PN Enter
Installer Enter
Country Enter
Step 1: Open the APP, tap the Register button to enter this page. Device Datalogger Alarm Me
Finish
Register
User Name
Password
Please enter user name
Confirm Password
Please enter password
E-mail
Keeppassword
Wi-Fi Config
Register
Demo> Register
63 www.kstar.com www.kstar.com 64
User Manual User Manual
W25 CT Reverse
65 www.kstar.com www.kstar.com 66
User Manual User Manual
The inverter is easy to maintain. When you encounter the following problems, please (1) Check the input mode setting is correct.
refer to the Solutions below, and contact the local distributor if the problem remains
(2) Disconnect the PV input, restart the inverter and wait
unsolved. The following table lists some of the basic problems that may occur during PV Input Short Circuit F08
until it functions normally.
the actual operation as well as their corresponding basic solutions.
(3) Contact customer service if error warning continues.
Fault diagnosis table
F09 (1) Disconnect the PV input, restart the inverter and wait
Types Codes Solutions until it functions normally.
Relay Fault F14
F19 (2) Contact customer service if error warning continues.
(1) Restart the inverter and wait until it functions normally;
Soft Time 0ut F00
(2) Contact customer service if error warning continues.
(1) Wait five minutes for the inverter to automatically restart;
(2) Check whether the load is in compliance with the
(1) Cut off all the power and shut down all the machines; INV Current Over F10
specification;
disconnect the load and plug in to restart machines, then
(3) Contact customer service if error warning continues.
check whether the load is short circuited if the fault has
INV Volt Short F01
been eliminated;
(1) Restart the inverter and wait until it functions normally.
(2) Contact customer service if fault remains unremoved. INV DC Over F11
(2) Contact customer service if error warning continues.
(1) Cut off all the power, Restart the inverter and wait until (1) Restart the inverter, restart the machine after a few
GFCI Sensor Fault F02 it functions normally. minutes of cooling, and observe whether the machine can
(2) Contact customer service if error warning continues. F12 return to normal.
NTC/Sink
F13 (2) Check if the ambient temperature is outside the normal
Temp Over
operating temperature range of the machine.
(1) Check the input mode setting is correct.
F04 (3) Contact customer service if error warning continues.
Bus Volt Low (2) Restart the inverter and wait until it functions normally.
F05
(3) Contact customer service if error warning continues. (1) Wait one minute for the inverter to restart;
(2) Check whether the load is in compliance with the
Dischg Curr Over F15
(1) Restart the inverter and wait until it functions normally. specification;
Bus Volt Short F06
(2) Contact customer service if error warning continues. (3) Contact customer service if error warning continues.
67 www.kstar.com www.kstar.com 68
User Manual User Manual
(1) Restart the inverter and wait until it functions normally. (1) Restart the inverter and wait until it functions normally.
Communication Fault F32 Fan Fault W12
(2) Contact customer service if error warning continues. (2) Contact customer service if error warning continues.
(1) Check if the local voltage and frequency is in BMS Fault W14~W25 (1) Please contact the distributor.
compliance with the machine specification;
W00
(2) If voltage and frequency are within the accepted
W01 range, then wait 2 minutes for the inverter to function
Grid Fault normally; but if no recovery or fault repeats, please 09 Machine Parameters
W02
contact the local inverter customer service;
W03 (3) Contact the local power company if voltage and Battery Specifications BluE-PACK5.1 BluE-PACK10.2
frequency are beyond range or unstable. Electrical
(1) PV is not connected; Energy Capacity 5.12kWh 10.24kWh
Solar Loss W04 (2) Check grid connection; Battery type LFP (LiFePO4)
(3) Check PV availability. Depth of Discharge (DoD) 90%
(1) Battery is not connected; Rated voltage 51.2V
Bat Loss W05 (2) Check if battery wiring port is short circuited; Operating Voltage Range 44.8~56.5Vdc
(3) Contact customer service if error warning continues. Operation
W06 (1) Check the battery availability; Maximum Charging Current 50A (0.5C) 100A (0.5C)
Bat Volt Low
W07 (2) Contact customer service if error warning continues. Maximum Discharging Current 80A (0.8C) 100A (0.5C)
Operating temperature range 0℃~+50℃(Charging)/-10℃~+50℃(DisCharging)
(1) Check if the battery is in line with the presetting;
Storage temperature range -20℃~+50℃
Bat Volt High W08 (2) If so, power off and restart;
Humidity 0% ~ 90%
(3) Contact customer service if error warning continues.
BMS
(1) Wait one minute for the inverter to restart; Modules Connection max. 4 batteries in parallel
Over Load Warning W09 (2) Check whether the load is in compliance with the System voltage, current, cell voltage,
specification; Monitoring Parameters
cell temperature, PCBA temperature measurement
CFCI Over W10 (2) Check peripherals of machine for current leakage;
(3) Contact the local inverter customer service if fault
remains unremoved.
69 www.kstar.com www.kstar.com 70
User Manual User Manual
Vmax. PV 580Vd.c.
Rated voltage 230Va.c.
Rate Voltage 400Vd.c.
Rated frequency 50Hz
MPPT Voltage Range 120~550Vd.c.
Rated output Current 16Aa.c. 20Aa.c.
MPPT Range (full load) 184~550Vd.c. 230~550Vd.c.
Maximum continious output current 16Aa.c. 20Aa.c.
MPPT Tracker / Strings 2
Rated frequency 50/60Hz(Fluctuation range±0.2%)
Max. continuous PV input current 13Ad.c.×2
Isc PV 16Ad.c. Rated continious output power 3680W 4600W
Max backfeed current 0Ad.c. Maximum output apparent power 4000VA 5000VA
Max. continuous PV input power 4800W 6500W Max. output fault current 99Apeak
Maximum charge/discharge current 50Ad.c./80Ad.c. 100Ad.c./100Ad.c. Overvoltage Category II(DC side), III(AC side)
71 www.kstar.com www.kstar.com 72
User Manual User Manual
73 www.kstar.com www.kstar.com 74
User Manual User Manual
Please contact us in time if there are any conditions that could not be explained in the manual.
10.1.2 Equipment Cleaning
(Every six months to one year, depending on the site environment and dust content,
etc.)Ensure that the ground is clean and tidy, keep the maintenance access route 11 Quality Assurance
unblocked,and ensure that the warning and guiding signs are clear and intact.
Monitor the temperature of the battery module and clean the battery module if
When product faults occur during the warranty period, KSTAR or his partner will
necessary.
provide free service or replace the product with a new one.
In the following circumstances, KSTAR has the right to refuse to honor the quality
guarantee:
75 www.kstar.com www.kstar.com 76
User Manual
• The free warranty period for the whole machine/components has expired.
• The device is damaged during transport.
• The device is incorrectly installed, refifitted, or used.
• The device operates in harsh environment, as described in this manual.
• The fault or damage is caused by installation, repairs, modifification, or disassembly
performed by a service provider or personnel not from KSTAR or his authorized
partner .
• The fault or damage is caused by the use of non-standard or non-KSTAR.
components or software.
• The installation and use range are beyond stipulations of relevant international
standards.
• The damage is caused by unexpected natural factors.
For faulty products in any of above cases, if the customer requests maintenance, paid
maintenance service may be provided based on the judgment of KSTAR.
12 Contact Informaition
77 www.kstar.com