Professional Documents
Culture Documents
08840 Viladecans,
Barcelona-Spain
communications@ziv.es
www.communications.ziv.es Tel.: +34 933 490 700
Fax: +34 933 492 258
SAFETY SYMBOLS
WARNING OR CAUTION:
This symbol denotes a hazard. Do not follow the indicated
NOTE:
Information or important aspects to take into account in a
procedure, operation or such like.
TABLE OF CONTENTS
Page
1 MECHANICAL CHARACTERISTICS 7
2 FRONT-PLATE ELEMENTS 12
3 INTERNAL SETTINGS 26
4 BACK-PANEL ELEMENTS 39
5 CONNECTIONS 48
6 COMMISSIONING PROCEDURE 70
6.1 CHECKS 70
7 FILTER ADJUSTMENT 80
Page
12 MAINTENANCE 117
APPENDIX A
APPENDIX B
APPENDIX C
APPENDIX D
1 MECHANICAL CHARACTERISTICS
The OPU-1 basic terminals for 20 and 40 W are made up of two 19" shelves, one of 6 s.u
and the other of 3 s.u. in height, prepared for rack mounting. FIGURE 1 shows the overall
dimensions in mm of the shelves as well as the position of the fastening holes.
The OPU-1 terminal for 80 W, apart from the previous two, also needs an additional 19"
shelf of 3 s.u. in height. An additional 19" 3 s.u. shelf is also necessary in 20 and 40 W
terminals with additional filters. The overall dimensions in mm of an OPU-1 terminal with an
additional 19" 3 s.u. shelf is shown in FIGURE 2.
The shelves have endplate angles at the sides, in order to secure the unit to the frame of a
cabinet or wall cabinet. When installing the terminal in the frame, each shelf should be
connected to the earth bar of the cabinet by means of the braided earth cable provided for
this purpose.
The shelves have ventilation grids, at the top and at the bottom.
During installation it must be made sure that the ventilation grids are NOT obstructed in
any way.
To access the modules of the 3 s.u. shelf, the cover on the front must be released. The
release process is shown in FIGURE 3. The procedure for extracting the modules is
detailed in FIGURE 4 and FIGURE 5.
For the 6 s.u. shelf, in order to replace a module, turn the two fixing screws anti-clockwise
as far as they will go and, holding the handles, pull the module out of the shelf.
FIGURE 2 Overall dimensions in mm of the OPU-1 terminal for 80 W or for 20 and 40 W with
additional filters
FIGURE 4 Procedure for extracting the RXPU (RXPR) and HIPU modules
2 FRONT-PLATE ELEMENTS
Firstly, this section describes the function of the elements available on the front plate of the
OPU-1 terminal equipped with the basic modules for 20 and 40 W, see FIGURE 6. It goes
on to describe the function of the elements available in the 3 s.u. additional shelf for a 80 W
terminal (see FIGURE 7).
The front-plate elements associated with the options are described in the corresponding
specific documentation.
LOOP
LEDs that will light
Direct Level rec.
PILOT LOSS LED Red. When lit, indicates a loss of receive pilot in
the analog channel in reception.
LOW S/N LED Red. When lit, indicates that the signal/noise
(S/N) ratio in the analog channel is less than
the predetermined value.
Loss of synchronism.
Pilot loss.
Temperature alarm.
Hardware failure.
(1)
LAN INTERFACE LEDs Indicate the state of the LAN interface.
(1)
10 and 100 LEDs, as well as TX and FX LEDs, behave in an opposite way, that is to say,
when one is lit the other is turned off.
GPS TIME connector BNC type connector for coaxial cable that
allows the OPU-1 terminal to be connected to a
GPS time equipment in order to guarantee time
synchronization.
LOCAL LOOP LED Red. When lit, indicates that the loop has been
effected in the corresponding analog channel of
the local terminal
REMOTE LOOP LED Red. When lit, indicates that the loop has been
effected in the corresponding analog channel of
the remote terminal
LOW S/N LED Red. When lit, indicates that the signal/noise
(S/N) ratio in the corresponding analog channel
is less than the predetermined value.
GENERAL ALARM LED (LOC.) Red. It lights up when one of the following
alarms is produced:
Power-supply failure.
Amplifier overload of 3 s.u. shelf.
Low output level in amplifier of 3 s.u. shelf.
Loss of synchronism.
Pilot loss.
Low Signal/Noise ratio.
AF limiter operation in analog channel.
Temperature alarm.
Terminal configuration error.
Hardware failure.
BER 10 in digital channel.
-3
GENERAL ALARM LED (REM.) Red. Lights up when one of the alarms
indicated previously activates in the remote
terminal.
GPS TIME connector BNC type connector for coaxial cable that
allows the OPU-1 terminal to be connected to a
GPS time equipment in order to guarantee time
synchronization.
LOW RCV LEVEL LED Red. Lights up when the pilot level is lower than
the threshold specified
EXC. RCV LEVEL LED Red. Lights up when the pilot level is higher
than the threshold specified
SYNCH. LOSS LED Red. Lights up when the MQPU module has
lost the frame synchronism, either because of
excessive noise level in the channel or because
the link is broken.
SYNCH. LOSS LED Red. Lights up when the MQPU module has
lost the frame synchronism, either because of
excessive noise level in the channel or because
the link is broken.
-3
BER>10 LED Red. Lit indicates that the error rate evaluated
by the system is higher than the maximum error
rate permitted. The link could be interrupted if
the error rate does not improve
LOW RCV LEVEL LED Red. Lights up when the pilot level is lower than
the threshold specified
EXC. RCV LEVEL LED Red. Lights up when the pilot level is higher
than the threshold specified
G.703 PORT 1 connector 8 pin RJ-45 type female connector for G.703
signals associated with port 1
V.24 PORT 2 connector 9 pin SUB-D type female connector for V.24
signals associated with port 2
V.35/V.11 PORT 1 connector 25 pin SUB-D type female connector for V.11 or
V.35 signals associated with port 1
INPUT / GROUND
TEST POINTS HF signal input level (before the receive filter)
OUTPUT / GROUND
TEST POINTS HF signal level (after the receive filter)
3 INTERNAL SETTINGS
The MOPU.0X module has a microswitch and three jumpers, the location of which can be
seen in FIGURE 8.
()
The IP address programmed in factory is the 172.16.20.24 or the 172.16.20.25.
The MOPU.1X module has two jumpers, the location of which can be seen in FIGURE 9.
()
The IP address programmed in factory is the 172.16.20.24 or the 172.16.20.25.
The MQPU.11 module has a jumper, the location of which can be seen in FIGURE 10.
The RXPU module contains the receive filter for the frequency range from 40 to 500 kHz.
The adjustment and setting elements associated with it are indicated in FIGURE 11, and
are summarized below.
FIGURE 11 Detail of the adjustment and setting elements of the RXPU module
MI1_0 (S100), Jumpers used to carry out the adjustment of the input
MI1_1 (S10) to MI1_10 (S19) resonance circuit. Each jumper connects a different capacitor.
of inductance L3
MI3_0 (S300), Jumpers used to carry out the adjustment of the output
MI3_1 (S30) to MI3_10 (S39) resonance circuit. Each jumper connects a different capacitor.
of inductance L4
MI2_0 (S20) to MI2_9 (S29) Jumpers used to select the central frequency of the line
of inductance L3 and L4 filter. Each jumper connects a different capacitor.
CM15, CM16 Selection of the impedance of the output load of the receive
filter.
S 8 kHz filter.
D 16 kHz filter.
T24K 24 kHz filter.
CM9, CM10, CM11 Switches used for adjustment and for the inclusion or
exclusion of the receive filter. TABLE 4 shows the positions of
these switches in the four possible cases: filter included and
excluded, adjustment of inductance L3 and adjustment of
inductance L4.
Adjustment of L3 ON OFF ON
The RXPR module contains the receive filter for the frequency range from 500 kHz to
1 MHz. The adjustment and setting elements associated with it are indicated in FIGURE 12,
and are summarized below.
MI1_0 (S11) to MI1_5 (S16) Jumpers used to carry out the adjustment of the input
of inductance L3 resonance circuit. Each jumper connects a different capacitor.
MI3_0 (S31) to MI3_5 (S36) Jumpers used to carry out the adjustment of the output
of inductance L4 resonance circuit. Each jumper connects a different capacitor.
MI2_0 (S200), Jumpers used to select the central frequency of the line
MI2_1 (S20) to MI2_8 (S27) filter. Each jumper connects a different capacitor.
of inductance L3 and L4
FIGURE 12 Detail of the adjustment and setting elements of the RXPR module
CM15, CM16 Selection of the impedance of the output load of the receive
filter.
S 8 kHz filter.
D 16 kHz filter.
T32K 32 kHz filter.
CM9, CM10, CM11 Switches used for adjustment and for the inclusion or
exclusion of the receive filter. TABLE 4 shows the positions of
these switches in the four possible cases: filter included and
excluded, adjustment of inductance L3 and adjustment of
inductance L4.
The AFPU module contains the line filter for the frequency range from 40 to 500 kHz. The
adjustment and setting elements associated with it are indicated in FIGURE 13, and are
summarized below.
KFPL3_1 to KPFL3_11 Jumpers used to carry out the adjustment of the input
of inductance L1 resonance circuit. Each jumper connects a different capacitor.
KFPL1_1 to KPFL1_11 Jumpers used to carry out the adjustment of the output
of inductance L2 resonance circuit. Each jumper connects a different capacitor.
KFPL2_1 to KPFL2_11 Jumpers used to select the central frequency of the line
of inductance L1 and L2 filter. Each jumper connects a different capacitor.
CM4, CM5, CM6 Switches used for the adjustment and for the inclusion or
exclusion of the line filter. TABLE 5 shows the position of the
switches in the four possible cases: filter included, filter
excluded, adjustment of inductance L1 and adjustment of
inductance L2.
Adjustment of L1 OFF ON ON
FIGURE 13 Detail of the adjustment and setting elements of the AFPU module
The AFPR module contains the line filter for the frequency range from 500 kHz to 1 MHz.
The adjustment and setting elements associated with it are indicated in FIGURE 14, and
are summarized below.
KFPL3_1 to KPFL3_7 Jumpers used to carry out the adjustment of the input
of inductance L1 resonance circuit. Each jumper connects a different capacitor.
KFPL1_1 to KPFL1_7 Jumpers used to carry out the adjustment of the output
of inductance L2 resonance circuit. Each jumper connects a different capacitor.
KFPL2_1 to KPFL2_9 Jumpers used to select the central frequency of the line
of inductance L1 and L2 filter. Each jumper connects a different capacitor.
CM4, CM5, CM6 Switches used for the adjustment and for the inclusion or
exclusion of the line filter. TABLE 5 shows the position of the
switches in the four possible cases: filter included, filter
excluded, adjustment of inductance L1 and adjustment of
inductance L2.
FIGURE 14 Detail of the adjustment and setting elements of the AFPR module
The HF hybrid module (HIPU) contains three switches, whose location in the card is
indicated in FIGURE 15.
FIGURE 15 Location of the CM1, CM2 and CM3 switches of the HIPU module
In the 80 W terminals, there is a second line filter that is located in the DIFFERENTIAL
TRANSFORMER module (DTPU). This module contains two switches, whose location in
the card is indicated in FIGURE 16.
CM1, CM2 Selection of the impedance of the output load of the line filter
in the same module.
S 8 kHz filter.
D 16 kHz filter.
T24k 24 kHz filter.
T32k 32 kHz filter.
The 3 s.u. back panel, WPPU, contains jumpers whose function is summarized below.
28R, 56R, 84R Selection of the bandwidth of the line filter (see FIGURE 19 or
FIGURE 21 depending on WPPU type).
28R 8 kHz filter.
56R 16 kHz filter.
84R 24 kHz filter or 32 kHz filter.
50, 75, 125, 140 The output impedance may be of 50, 75, 125 or 140 , by
carrying out the corresponding jumper.
4 BACK-PANEL ELEMENTS
The back panel elements of the OPU-1 terminal are shown in FIGURE 17 and FIGURE 18.
The 6 s.u. back panel contains the main power-supply switch, the fuses, the power-supply
sockets, the connector associated with the terminal and power-supply alarm signalling
relays, and the connectors for external connections of the AF input/output analog signals
and of the digital I/O interfaces (MQPU.0X). It also has a ground connection.
In the case of MQPU.1X module, the digital I/O interfaces are connected to the front
connectors.
The 3 s.u. back panel contains the line transformer, the coaxial connector for making the
connection to the line, the jumpers for selecting the output impedance of the HF amplifier,
the jumpers to connect the dummy load to line or the terminal, a setting to connect or not
the coaxial-cable shield to chassis, the line test points, and the corresponding elements for
selecting the bandwidth of the line filter. It also has two coaxial cables, two microswitches, a
jumper, as well as an interconnection card for connection to an additional 3 s.u. shelf for
80 W.
The OPU-1 terminal can work with different line filters, depending on the 3 s.u. backplane
type (WPPU.00 or WPPU.01).
The output impedance of the HF amplifier may be of 8 kHz, 16 kHz or 24 kHz, when the
switch is in the corresponding position (see FIGURE 20).
The output impedance of the HF amplifier may be of 8 kHz, 16 kHz or 32 kHz, when the
switch is in the corresponding position (see FIGURE 22).
The dummy load can be connected line-side or terminal-side by carrying out the
corresponding configuration (see FIGURE 23).
Jumper J37-J38 can be removed if complete isolation of the terminal with respect to
the line is required.
The high-frequency input of the terminal is protected with gas surge arresters of 230 V.
These surge arresters are printed on the board as DSC1 and DSC2.
Terminals J32 and J33 are used to connect ground and chassis when necessary.
5 CONNECTIONS
The external connections are carried out by means of the connectors located at the rear of
the 6 s.u. shelf, see FIGURE 28.
In the case of MQPU.1X module, the digital I/O interfaces are connected to the front
connectors.
FIGURE 28 Connectors located at the back of the equipment in 20 and 40 W terminals (MQPU.0X)
The use of the power-supply sockets, the alarm relay connector, the plug-in terminal blocks
associated with the AF input/output analog signals, the plug-in terminal blocks associated
to the digital I/O interfaces (MQPU.0X) and, in the case of the MQPU.1X module, the front
connectors.
Then, it is followed by the Ethernet data port connection and by the connection of the LAN
interface for terminal management and by the instructions for making the connection to the
line balanced or not.
External connections associated with the optional modules are described in their specific
documentation.
In normal operation conditions the relays are energized, that is to say, the N.O. and C
contacts are short-circuited.
5.1.2 Use of the plug-in terminal blocks associated with the analog AF signals
FIGURE 32 Input/output signals associated with the ZIPU plug-in terminal block
FIGURE 33 V.35 signals associated with the ZQPU plug-in terminal block
FIGURE 34 V.11 signals associated with the ZQPU plug-in terminal block
FIGURE 36 G.703 signals associated with the ZQPU plug-in terminal block
The Ethernet data port located on the front, and associated with the MQPU module, is a
female 8-pin RJ-45.
TABLE 6 shows the use of each one of the pins of the RJ-45 connector, as well as the pair
it belongs to according to ANSI/TIA/EIA-568-A standard, in the 10/100Base-TX LAN
interface.
The OPU-1 terminal has a 10/100Base-TX LAN interface, which allows it to be integrated
into any network (LAN) that uses this interface. The 10/100Base-TX connector located on
the front, and associated with the MOPU module, is a female 8-pin RJ-45.
The cable used to carry out the connection between the terminal and the computer must be
an unshielded twisted pair category five cable (UTP-5) with 8-pin RJ-45 connectors.
TABLE 6 shows the use of each one of the pins of the RJ-45 connector, as well as the pair
it belongs to according to ANSI/TIA/EIA-568-A standard, in the 10/100Base-TX LAN
interface.
The UTP-5 cable is made up of eight copper wires that form the four twisted pairs, covered
in different coloured insulating material. FIGURE 41 shows the colour of the wires that
make up each one of the pairs, according to ANSI/TIA/EIA-568-A standard.
FIGURE 41 Unshielded twisted pair category five cable (UTP-5) with RJ-45 connector
according to ANSI/TIA/EIA-568-A standard
The connection to the line can be non-balanced, FIGURE 44, or balanced, FIGURE 45,
according to whether or not the coaxial-cable shield is connected to the chassis. In this
way, by carrying out jumper J10-J11 on the 6 s.u. back panel (see FIGURE 23), the output
is referred to chassis. On the contrary, by carrying out jumper J9-J11, the output
is balanced.
When the shield is connected to the chassis, the DSC2 surge arrester is short circuited.
For external connection, the OPU-1 terminal can be supplied, on demand, with the
necessary cabinet-mounting terminal blocks, see an example in FIGURE 46 and
FIGURE 47, together with the necessary cables.
FIGURE 48 to FIGURE 53 show the use of the cabinet-mounting terminal blocks. In the
case of MQPU.1X module, the digital I/O interfaces are connected to the front connectors,
see FIGURE 37 to FIGURE 40.
The use of the cabinet-mounting terminal blocks associated with the options is described
in their specific documentation.
The general dimensions of the main cabinet-mounting terminal block can be seen in
FIGURE 54.
POWER-SUPPLY TERMINALS: Terminals that do not have disconnect devices and that are suitable for
flexible conductors of up to 4 mm2 of section or rigid conductors of up
to 6 mm2 of section.
THE REST OF THE TERMINALS: Terminals that have disconnect devices and that are suitable for
flexible conductors of up to 2.5 mm2 of section or rigid conductors of up
to 4 mm2 of section.
POWER-SUPPLY TERMINALS: Terminals that do not have disconnect devices and that are suitable for
flexible conductors of up to 4 mm2 of section or rigid conductors of up
to 6 mm2 of section.
THE REST OF THE TERMINALS: Terminals that have disconnect devices and that are suitable for
flexible conductors of up to 2.5 mm2 of section or rigid conductors of up
to 4 mm2 of section.
FIGURE 50 Signals associated with V.35 connector of the ZQPU (MQPU.0X module) terminal block
FIGURE 53 Signals associated with G.703 connector of the ZQPU (MQPU.0X module) terminal block
6 COMMISSIONING PROCEDURE
6.1 CHECKS
1. Make sure that the conditions in which the terminal will operate are suitable (see section
OPERATING CONDITIONS in manual General Description).
2. Make sure, with the help of a multimeter, that the power-supply voltage is within the
range specified for the operating nominal voltage and that the polarity is correct.
The range is the following:
- from 38.4 to 57.6 Vdc for equipment with power-supply nominal voltage of 48 Vdc,
- from 88 to 132 Vdc for equipment with power-supply nominal voltage of 110 Vdc,
- from 88 to 132 Vdc and of 176 a 264 Vac for equipment with power-supply nominal
voltage of 110 to 220 Vdc and Vac
3. Verify that the line connection is in accordance with the type of cable used to carry out
coupling system connection.
- Balanced configuration.
The balanced configuration must be used when the cable connecting the coupling
system is a shielded pair. In this case, is the pair shield, which must be connected to
earth, equipment side.
- Non-balanced configuration.
The non-balanced configuration must be used when the cable connecting the
coupling system is coaxial. The earthing of the coaxial shield must be carried out
equipment side.
4. Verify that the output impedance of the terminal is in accordance with the type of cable
used to carry out coupling system connection.
6. Verify that the bandwidth of the line filter is the right one.
7. Verify that the output impedance of the HF amplifier is the right one.
Microswitch J29 linked Do NOT link S3, S4 & S5 Do NOT link PM3
Digital 2 in ON & PM10 --
position Link 1-2 in S1 & S2
Microswitch J29 linked Do NOT link S3, S4 & S5 Do NOT link PM3
Mixed Do NOT link
2 in ON & PM10
(Analog+Digital) Link 1-2 in S1 & S2 7-8 of J12
position
Microswitch J29 linked Do NOT link S3, S4 & S5 Do NOT link PM3
Digital + In-band Link 7-8 of
2 in ON & PM10
TP Link 1-2 in S1 & S2 J12
position
See Figure 8 for location of MI1 in the MOPU.0X module, and Figure 9 for location of J29 in
the MOPU.1X module.
- Release the MQPU.11 module from the shelf and configure the J54 jumper
according to the desired modulation (Jumper linked: OFDM/OQAM.
Jumper not linked: QAM).
Output power:
For the frequency range between 40 kHz and 500 kHz, the terminal can have an output
power of 20 W or 40 W (see FIGURE 59), 80 W (see FIGURE 60) or independent
20 W+20 W or independent 40 W+40 W by means of an additional 3 s.u. shelf (see
FIGURE 61).
For the frequency range between 500 kHz to 1 MHz, the terminal can have an output
power of 10 W or 20 W.
The modules contain components sensitive to static electricity, so great care must be
taken when handling them. It is advisable to use an antistatic wristband connected
to earth.
3. The terminal is powered by means of the main switch located at the rear of the 6 s.u. shelf.
When the power supply is connected, the POWER ON LED on the front plate should light
up and then, the STATUS LED of the management & analog signal processing unit
(MOPU) lights up in red and that of the digital modem unit (MQPU).
Once the internal voltages become stabilized, the MOPU processing module initiates a
self-check process. Once finished, if carried out successfully, the STATUS LED lights up
in green and then that of the MQPU processing module. Furthermore, in the last
module, the ACTIVE LEDs for ports 1 and 2 light up if a valid programming for these
ports exist. Should a configuration error alarm be detected, however, the STATUS LED
remains red, as well as that of the MQPU module. The configuration error alarm
indicates that the memories have been corrupted. When this alarm is activated the
GENERAL ALARM LED lights up in the MOPU module.
4. Start up the internal web management (see chapter 11, STARTING UP THE INTERNAL
WEB MANAGEMENT) and, with the PC connected to the terminal, program the date
and time in the real time clock of the terminal, as well as the terminal configuration
according to the one established in point 1.
5. Carry out the receive filter adjustment, see section 7.3, RECEIVE FILTER
ADJUSTMENT PROCEDURE.
For 20 or 40 W terminals with an additional 3 s.u. shelf, adjust the receive filter of the
said shelf.
For 20 or 40 W terminals with an additional 3 s.u. shelf, adjust the line filter of the said
shelf.
For the 80 W terminals, the adjustment is carried out in the 0.1 VAMP1 tests points for
the line filter located in the AFPU base module and in the 0,1 VAMP2 test points for the
line filter located in the DTPU module.
7. Revise the configuration of the jumpers and switches. This is necessary because, after
carrying out the previous adjustments, they may not be in the correct position.
8. Check the levels of transmission and reception, see chapter 8, LEVEL CHECKS.
10. Once the link is established, carry out test loops, see chapter 10, TEST LOOPS.
7 FILTER ADJUSTMENT
The OPU-1 Management System can generate high-frequency tones to carry out the
adjustment of the line filter and receive filter as well as a manual or automatic sweep in
order to check the frequency response.
The following describes the procedure for adjusting the line filters, beginning with that of the
receive filter and finishing with that of the line filter. It is advisable to begin with the receive
filter as, when carrying out the adjustment, the different setting elements remain in normal
operation condition.
Firstly, the location of the filters and the description of the different setting elements
involved in the adjustment are detailed.
Before carrying out any adjustment it is recommended that the coaxial cable be
disconnected in order to avoid possible interference with other equipment connected to
the same line.
On the other hand, the test load must be in NORMAL position (jumper J37-J38 on the
rear of the 3 s.u. back panel).
The receive filter and line filter are located, respectively, in the RECEPTION FILTER
(RXPU or RXPR) and LINE FILTER (AFPU or AFPR). To access the RXPU (RXPR) and
AFPU (AFPR) modules, the cover on the front must be released. The release process is
shown in FIGURE 3, whilst the procedure for extracting each of the said modules is
detailed in FIGURE 4 and FIGURE 5, respectively. The HF HYBRID (HIPU) module is
extracted in the same way as the RXPU (RXPR) module.
FIGURE 62 shows an internal view of the terminal where the location of the filters and HF
hybrid modules can be seen. In the terminals for 20 or 40 W with additional 3 s.u. shelf, the
location of the additional filters and the additional HF hybrid is the same.
There is a second line filter for terminals of 80 W, the location of which can be seen in
FIGURE 63.
FIGURE 62 Location of the modules associated with the filters and HF hybrid
FIGURE 63 Location of the modules associated with the filters and HF hybrid in a terminal of 80 W
1. From the Management System, access the option RCV-filter adjustment of the Basic
equipment submenu of the Alignment help menu.
3. Then, the CONTINUE button must be pressed, after which a list labelled TYPE OF
ADJUSTMENT will appear where it is possible to select any of the options: L3 inductance
adjustment, L4 inductance adjustment and Whole filter.
4. Access the option L3 inductance adjustment to start the adjustment of the input
resonance circuit.
CM4 CM5 CM6 CM12 CM13 CM14 CM8 CM9 CM10 CM11 CM15 CM16
24 kHz filter or
T T NA T T OFF OFF OFF
32 kHz filter
8. Insert the modules once again, and connect the power-supply of the OPU-1 terminal.
Wait until the STATUS LED is green.
9. From the Management System, generate a test tone. In order to do so, press the
GENERATE button so that the terminal can begin to generate the test tone.
10. With the help of a flat-headed screwdriver, adjust inductance L3 until the minimum
voltage possible is obtained at the test points 0.1 Vline and ground of the HIPU module.
11. Once the inductance has been adjusted, press the STOP button at the bottom of the
page.
12. Access the option L4 inductance adjustment to start the adjustment of the output
resonance circuit.
CM4 CM5 CM6 CM12 CM13 CM14 CM8 CM9 CM10 CM11 CM15 CM16
24 kHz filter or
T T NA T T OFF OFF OFF
32 kHz filter
15. Insert the modules once again, and connect the power-supply to the OPU-1 terminal.
Wait until the STATUS LED is green.
17. Adjust inductance L4 until the minimum voltage possible is obtained at the test points
0.1 VLINE and ground of the HIPU module.
18. Once the inductance has been adjusted, press the STOP button at the bottom of the
page.
The procedure for checking proper operation of the receive filter is as follows:
1. Remove the selection jumper (28R, 56R, 84R) of the bandwidth of the line filter.
2. Exclude the line filter. To do so, put CM4, CM5 and CM6 switches of the Line filter
(AFPU or AFPR) module in OFF position.
3. Put CM3 switch of the HF hybrid (HIPU) module in NA position (exclude HF hybrid).
4. From the Management System, access the Receive-filter adjustment option of the
Basic equipment submenu of the Alignment help menu.
5. In the associated screen, acquire the configuration values from the terminal by means
of the RETRIEVE button.
6. Then, the CONTINUE button must be pressed, after which a list labelled TYPE OF
ADJUSTMENT will appear where it is possible to select the Whole filter option.
7. In the Whole filter option, select the manual or automatic sweep, introduce the required
data and measure in the test points OUTPUT and ground of the RXPU (RXPR) module.
8. Check that the frequency response of the filter, obtained by using a wideband voltmeter,
does not present valleys or ripples within the band in question and that its ends coincide
with the filter cut-off frequencies, see Figure 64 and explanatory text.
Manual sweep
If one wishes to stop the generation of a tone, the STOP button at the bottom of the
page must be pressed or any other option of the Management System selected. If the
generation of a tone is stopped by means of the PAUSE button, it is possible to resume
the transmission of the tone at the same frequency by means of the START button.
Automatic sweep
As with the manual sweep option, if one wishes to stop the automatic sweep, the STOP
button at the bottom of the page must be pressed or any other option of the
9. Once the check is finished, configure the jumper for selection of the line filter bandwidth
(28R, 56R, 84R) again.
10. Include the line filter. To do so, put CM4, CM5 and CM6 switches of the Line filter
(AFPU) module, respectively, in ON, ON and OFF position.
11. Put CM3 switch of the HF hybrid (HIPU) module in A position (normal operation).
CM4 CM5 CM6 CM12 CM13 CM14 CM8 CM9 CM10 CM11 CM15 CM16
24 kHz filter or
T T A T T OFF OFF ON
32 kHz filter
13. If necessary, carry out the receive filter adjustment, see section 7.4.
1. From the Management System, access the Line-filter adjustment option of the Basic
equipment submenu of the Alignment help menu.
3. Then, the CONTINUE button must be pressed, after which a list labelled TYPE OF
ADJUSTMENT will appear where it is possible to select any of the options: L1 inductance
adjustment, L2 inductance adjustment and Whole filter.
4. Access the option L1 inductance adjustment to start the adjustment of the input
resonance circuit.
6. Extract the AFPU (AFPR), RXPU (RXPR) and HIPU modules and set the jumpers and
switches with the position shown on the screen that appears when the VIEW button is
pressed and with the position shown at the bottom of the main screen. The position is
summarized in TABLE 11, whilst the position of the jumpers is summarized in Appendix B
(Appendix D).
CM4 CM5 CM6 CM12 CM13 CM14 CM8 CM9 CM10 CM11 CM15 CM16
24 kHz filter or
T T A T T OFF OFF ON
32 kHz filter
8. From the Management System, generate a test tone. In order to do so, press the
GENERATE button so that the terminal can begin to generate the test tone.
9. Put the dummy load in TERMINAL position and adjust inductance L1·until the minimum
voltage possible is obtained at the test points 0.1 Vline and ground of the HIPU module.
In the 80 W terminals, there is a second line filter that is located in the DIFFERENTIAL
TRANSFORMER module (DTPU). In this case, the measurements for the line filter
located in the AFPU module are carried out in the 0.1 VAMP1 test points of the DTPU
module and not in the 0.1 VLINE test points of the HIPU module. For the filter located in
the DTPU module, measurements are carried out in the 0.1 VAMP2 test points.
10. Once the inductance has been adjusted, press STOP button at the bottom of the page.
11. Access the option L2 inductance adjustment to start the adjustment of the output
resonance circuit.
13. Extract the AFPU (AFPR), RXPU (RXPR) and HIPU modules and set the jumpers and
switches in accordance with the position shown on the screen when the VIEW button is
pressed and with the position shown at the bottom of the main screen. The position is
summarized in TABLE 12, whilst the position of the jumpers is summarized in
Appendix B (Appendix D).
14. Insert the modules once again, and connect the power supply to the OPU-1 terminal.
Wait until the STATUS is green.
CM4 CM5 CM6 CM12 CM13 CM14 CM8 CM9 CM10 CM11 CM15 CM16
24 kHz filter or
T T A T T OFF OFF ON
32 kHz filter
16. Adjust inductance L2 until the minimum voltage possible is obtained at test points
0.1 Vline and ground of the HIPU module.
17. Once the inductance has been adjusted, press STOP button at the bottom of the page.
The procedure for checking proper operation of the line filter is as follows:
2. From the Management System, access the Line-filter adjustment option of the Basic
equipment submenu of the Alignment help menu.
3. In the associated screen, acquire the configuration values from the terminal by means
of the RETRIEVE button.
4. Then, the CONTINUE button must be pressed, after which a list labelled TYPE OF
ADJUSTMENT will appear where it is possible to select the Whole filter option.
5. In the Whole filter option, select the manual or automatic sweep, introduce the required
data and measure in the test points 0.1 VLINE and ground of the HIPU module.
6. Check that the frequency response of the filter, obtained by using a wideband voltmeter,
does not present valleys or ripples within the band in question and that its ends coincide
with the filter cut-off frequencies, see Figure 65 and explanatory text.
7. Once the check is finished, put the dummy load in NORMAL position.
8. If necessary, carry out the line filter adjustment, see section 7.6.
Manual sweep
If one wishes to stop the generation of a tone, the STOP button at the bottom of the
page must be pressed or any other option of the Management System selected. If the
generation of a tone is stopped by means of the PAUSE button, it is possible to resume
the transmission of the tone at the same frequency by means of the START button.
Automatic sweep
As with the manual sweep option, if one wishes to stop the automatic sweep, the STOP
button at the bottom of the page must be pressed or any other option of the
The figures below show an example of 32 kHz filter, adjusted and centered at 400 kHz, an
example of 24 kHz filter, adjusted and centered at 400 kHz, an example of 16 kHz filter,
adjusted and centered at 200 kHz, and an example of 8 kHz filter, adjusted and centered at
400 kHz.
8 LEVEL CHECKS
The analog transmit pilot level is measured in the LINE SIGNAL and GROUND SIGNAL
test points, located at the rear of the shelf, next to the coaxial connector.
The measurement should be carried out with a selective voltmeter set at the corresponding
frequency, see Figure 78.
Channel 1
Channel 2
To adjust the level to the value indicated in Table 13, put the dummy in TERMINAL
position, and then access the Transmit level option of the Configuration menu.
The value indicated in the page can be modified in fixed quantities by using the function
keys.
The digital transmit pilot level is measured in the LINE SIGNAL and GROUND SIGNAL test
points, located at the rear of the shelf, next to the coaxial connector.
The measurement should be carried out with a selective voltmeter set at the corresponding
frequency, see Figure 79.
To adjust the level to the value indicated in Table 13, put the dummy load in TERMINAL
position, and then access the Transmit level option of the Configuration menu.
The value indicated in the page can be modified in fixed quantities by using the function
keys.
20 W 20 W 40 W 40 W 20 W 20 W 40 W 40 W
ANALOG ANALOG ANALOG ANALOG MIXED MIXED MIXED MIXED
SINGLE TWIN SINGLE TWIN SINGLE TWIN SINGLE TWIN 20 W 40 W
CHANNEL CHANNEL CHANNEL CHANNEL CHANNEL CHANNEL CHANNEL CHANNEL DIGITAL DIGITAL
3.87 Vrms 1.94 Vrms 5.48 Vrms 2.74 Vrms 1.94 Vrms 0.97 Vrms 2.74 Vrms 1.37 Vrms
ANALOG PILOT
(+23 dBm) (+17 dBm) (+26 dBm) (+20 dBm) (+17 dBm) (+11 dBm) (+20 dBm) (+14 dBm)
1.94 Vrms 1.94 Vrms 2.74 Vrms 2.74 Vrms 3.87 Vrms 5.48 Vrms
DIGITAL PILOT
(+17 dBm) (+17 dBm) (+20 dBm) (+20 dBm) (+23 dBm) (+26 dBm)
QAM without TP in
digital channel (1) +29.1 dBm +29.1 dBm +32.1 dBm +32.1 dBm +35.1 dBm +38.1 dBm
QAM with TP in
digital channel (1) +32.91 dBm +35.92 dBm
7.75 Vrms 3.87 Vrms 10.95 Vrms 5.48 Vrms 3.87 Vrms 1.94 Vrms 5.48 Vrms 2.74 Vrms 7.75 Vrms 10.95 Vrms
GUARD SIGNAL
(+29 dBm) (+23 dBm) (+32 dBm) (+26 dBm) (+23 dBm) (+17 dBm) (+26 dBm) (+20 dBm) (+29 dBm) (+32 dBm)
If a selective voltmeter instead of a true rms voltmeter is used, the measurement values will differ from those indicated in Table 13
by -0.6 dB to -0.7 dB.
The analog receive pilot level is measured in the LINE SIGNAL and GROUND SIGNAL test
points, located at the rear of the shelf, next to the coaxial connector.
The measurement should be carried out with a selective voltmeter set at the corresponding
frequency, see Figure 80.
Channel 1
Channel 2
The minimum receive level for proper operation of the automatic gain control (AGC)
is -30 dBm. Below this value, the analog link is interrupted.
Display the measurement from the Management System, by means of the Received pilot
level option of the Analog part submenu of the Monitoring menu.
The digital receive pilot level is measured in the LINE SIGNAL and GROUND SIGNAL test
points, located at the rear of the shelf, next to the coaxial connector.
The measurement should be carried out with a selective voltmeter set at the corresponding
frequency, see Figure 81.
The minimum receive level for proper operation of the automatic gain control (AGC)
is -30 dBm. Below this value, the digital link is interrupted.
The high-frequency hybrid is located in the HF HYBRID (HIPU) module. The adjustment is
carried out by means of resistive, inductive and capacitive elements. These elements are
accessible from the front of the terminal, see FIGURE 82, and are named as indicated in
FIGURE 15.
R
(P1 potentiometer) To adjust the resistive component of the HF hybrid.
C
(microswitches 1 to 8) To adjust the capacitive component of the HF hybrid.
FIGURE 82 Detail of the elements accessible from the front associated with the HF hybrid adjustment
The measurement should be carried out with a selective voltmeter (that do not load the
line), being the collateral terminal in rest state, that is to say, not transmitting any kind of
signal, and if the noise of the line so permits.
The level of the re-injected signals is measured in the receive input, after the channel filter,
at the OUTPUT and ground test points of the RECEPTION FILTER module.
The OPU-1 Management System can generate a tone that is necessary in the
high-frequency hybrid adjustment process. The tone is activated from the Hybrid adjust
option of the Basic equipment submenu of the Alignment help menu.
The procedure that is proposed to carry out the HF hybrid adjustment is the following:
2. Verify that the modulation percentage of the pilot is 10% and that the different services
have a modulation percentage assigned. In digital equipment, verify that the modulation
percentage of the QAM signal is 90%.
3. Activate the test tone (analog or digital) from the Hybrid adjust option of the Basic
equipment submenu of the Alignment help menu.
If the equipment is analog+digital, any of the two tones can be used. As the level of the
digital tone is higher than that of the analog tone, it is recommended to use the digital
test tone.
5. Connect the selective voltmeter at the OUTPUT and test points of the RECEPTION
FILTER module.
6. Follow the instructions of the flow diagram, see Figure 83. The maximum attenuation
must be obtained in the transmission band (minimum 60 dB).
7. Once the adjustment is completed, the test tone should be deactivated by pressing the
STOP button.
Table 14 shows the microswitch configuration that increase and decrease the capacity (pF).
10 TEST LOOPS
On the other hand, in the digital channel, port loops can be carried out with the help of the
Management System.
A high-frequency loop allows the complete equipment to be locally checked by checking the
transmit circuits on one side and the receive circuits on the other.
First at all, check if the terminal has an internal teleprotection unit or exists the
programming of an external teleprotection. If so, block the teleprotection receiver to prevent
false commands.
Before programming the loop, check if the dummy load is in TERMINAL position.
Afterwards, configure the switches of the terminal for the exclusion of the filters.
For the exclusion of the receive filter, CM9, CM10 and CM11 switches of the Receive filter
module should be, respectively, in the OFF, ON and OFF position.
For the exclusion of the line filter, CM4, CM5 and CM6 switches of the Line filter module
should be in the OFF position.
Loop activation is carried out by programming the MAKE HF LOOP parameter from the
Basic equipment option of the Configuration menu.
The Management System automatically matches the receive frequency to the transmit
frequency.
The only way to de-activate the high-frequency loop is to program the deactivation of the
loop in the web page. The reset of the terminal DOES NOT de-activate the loop.
Once the loop is de-activated, the Management System restores the receive frequency
to its original value.
To know the amplitude response of a link, two types of loop are provided in the OPU-1
terminal. These loops are timed to last 20 minutes.
The first, with level recovery at the looped end, allows the user to know the
backward-channel amplitude response. The second, without level recovery, allows the user
to know the response curve of the looped circuit. The results of both tests allow the user to
calculate the amplitude response of the forward channel.
The amplitude responses are obtained by carrying out a 4 kHz channel sweep by means of
the internal test-signal or an external generator.
The loops are carried out by means of the OPU-1 Management System and can be
executed from either of the two link ends, both in the terminal in question as well as in the
collateral terminal. If the terminal is twin channel, the loop can be carried out in any of the
two channels. Any type of audio-frequency loop is signalled, both on the front of the local
terminal as well as the front of the remote one.
It is possible, by means of the Management System, to generate, in both the local and
remote terminals, a loop in the data ports of module MQPU, as well as in the data and
speech ports of the optional modules of the built-in multiplexer.
When a loop is carried out, the port input data returns at input/output level to its original
source, whilst the data received from line is sent back to the line.
Therefore, when a data loop is carried out in the remote terminal from the PC, it is possible
to check the correct functioning of the transmit and receive circuits of the two OPU-1
terminals of a link, and verify the state of the transmission line.
When the data loop is carried out in the remote terminal, with a local data terminal
equipment (DTE) being connected, the local OPU-1 terminal sends data down the line
through the remote receiver to the remote transmitter, which sends the data back to the
local receiver.
On the other hand, in order to check the port connector and its input/output connections a
data loop may be carried out in the same terminal.
In order to carry out a data loop it is necessary to gain access to the corresponding option
of the Alignment help menu of the local or remote terminal, whichever corresponds. Once
the page of the option is displayed, the CheckBox associated with the port in question
should be selected and then the button PROGRAM should be pressed.
Hardware
A LAN module with 10/100Base-TX or, as be the case, with 100Base-FX interface.
A mouse.
Software
TCP/IP protocol.
The network configuration of the web server can be modified, if the terminal has already
been accessed, from the option Network parameters of the Network submenu of the OPU-1
Management System Configuration menu.
From the said option, it is possible to modify parameters such as IP address, subnet mask,
etc., in order for them to be compatible with the computer or computers that are going to be
connected to the terminal.
Configure the network parameters of the PC according to the IP address, the subnet mask and
the default gateway of the web server of the OPU-1 terminal.
If the OPU-1 terminal and the computer are connected directly or through a LAN (they belong
to the same network), the IP address of each of them must have the same network number
and a different host number, so the subnet mask must be the same for both. The default
gateway does not need to be configured.
If the OPU-1 terminal and the management computer belong to different LANs and the
connection between them is via WAN, their IP addresses may have a different network
number, but both must be connected to some device (default gateway) capable of
interconnecting LANs.
Having configured the web server and the management computer, open the
Microsoft Internet Explorer browser from the management computer.
3. The cache memory of the Java virtual machine has been deleted.
In order to do so, from the Start button of Windows, access the option Java Plug-in
of the Control panel and press on the Cache tab. Next, eliminate the position
enabling in the cache buffer. Depending on the version, it is necessary to look for the
General tab and press the Delete files button.
FIGURE 84 shows the page that appears when the IP address is entered correctly. It can
be seen that the system asks for a new password before allowing access.
Access to the Web Management from the OPU-1 terminals requires a user password,
which comprises a user identification and a password.
If the user identification or password are not introduced correctly, the system asks for the
user password again, up to two times. The third consecutive time that the user identification
or password are entered incorrectly a web page is displayed in the browser with the
message "This object on the Web Server is protected. You need a valid username and
password". In order for the system to request the user password again, the IP address of
the web server must be introduced in the browser.
Once the user password has been introduced correctly, a security message appears
and, once accepted, the user password is requested once again before access to the
Management System is permitted.
If the user password has been introduced correctly but the system detects that the file of
the web pages is defective, the browser displays a message which depends on the profile
of the user password that has been introduced. If the user password introduced is basic
user, the system displays the message "The web pages on the server are missing or
If one chooses to update the file of the web pages, an FTP window appears that will ask for
the user password. Once the administrator user password has been introduced correctly,
an Open file window of Windows opens in which the disk unit and the directory where the
file of the web pages is to be found must be selected.
If one does not wish to update the file of the web pages the browser will close.
The administrator user profile can modify the default user passwords of the system, from
the option User passwords of the Network submenu of the Configuration menu of the OPU-1
Management System. Once a user password has been modified from the said option it will
not be effective until the web server is reinitiated.
Once the user password has been entered correctly (user name and password) a security
warning appears on the screen of the browser requesting permission to install and execute
a file (ZIVCommunications.cer).
If this file is not executed it is not possible to access the OPU-1 Management System.
This step can be avoided subsequently by marking the “Always trust contents from this
publisher” box.
To close the Internet Explorer browser by selecting Close in the File option of the main
menu, or by clicking the X button located in the upper right hand corner of the window of
the browser.
Before leaving, a window appears in the form of a warning asking whether you wish to save
the information.
It is advisable to save the data on the disk or the terminal before leaving, as any unsaved
modification will be lost.
On-line Web Management means that the OPU-1 terminal is managed from a computer
connected to it, whilst in off-line Web Management, the management can be carried out
without any need for it to be connected to the terminal.
The off-line management takes on special meaning when one wishes to configure the
terminal from somewhere where there is no connection with it. The terminal configuration
can be programmed and stored in the management computer or in a magnetic support and
when the connection is possible, load the configuration in the terminal.
In the off-line management menu, only the options that make sense in this kind of
management (management without being connected to the terminal) appear and, for
example, no options appear relative to the Monitoring of the terminal.
These pages can only be downloaded by an ADMINISTRATOR user from the option
Software download of the MOPU submenu of the OPU-1 Management System Software
updating menu.
The option Management and control software update of the MOPU submenu of the
OPU-1 Management System Software updating menu allows an ADMINISTRATOR user
to update the web pages stored on the server that is in the OPU-1 terminal.
This updating should be carried out when a new version of the current web pages is
developed.
After updating the web application, the cache memory of the web browser must be
erased from the Tools menu (Internet options) in Microsoft Internet Explorer and the IP
address of the web server must be reintroduced in the browser.
12 MAINTENANCE
Although the equipment does not need special maintenance, it is advisable to carry out
periodic checks to make sure that it is working correctly.
The following measurements are suggested, which give a good indication of the state of the
equipment:
a) Power-supply voltage.
The main power supply can be measured at terminals J25-J26, which are located
at the rear of the 6 s.u. shelf, and the alternative power supply at terminals J30-J31.
The measurement should be made with a multimeter.
See range in point 2 of section 6.1, CHECKS.
b) Check the transmit level of the pilot (see section 8.1, TRANSMIT PILOT IN
ANALOG CHANNEL, and section 8.2, TRANSMIT PILOT IN DIGITAL CHANNEL).
c) Check the receive level of the pilot (see section 8.3, RECEIVE PILOT IN ANALOG
CHANNEL, and section 8.4, RECEIVE PILOT IN DIGITAL CHANNEL).
e) Final checks.
- If any of the ports remain in loop, then the loop should be deactivated.
- Verify that none of the terminal-block terminals are open.
- Set the date and time of the terminal clock using the Setting the clock option of
the Basic equipment submenu of the Alignment help menu.
- Reset the chronological register using the Chronological register option of the
Basic equipment submenu of the Monitoring menu.
13.1 TRANSPORT
When delivered the OPU-1 terminals are packed in wooden boxes prepared for easy
transportation. Each wooden box contains two cardboard boxes. One of the cardboard
boxes contains the equipment, which is properly packed. The equipment is wrapped in a
bag alveolar film (bubble wrap) and, after introducing it in the cardboard box, it is covered
with porexpan chips to protect it from bumps. The cardboard box is closed with staples and
adhesive band. The other cardboard box contains the equipment accessories, which are
properly packaged. Inside the wooden box, the two cardboard boxes are covered with
porexpan plates.
To ease handling, the maximum weight of a box does not exceed 25 Kg.
If the number of boxes to be transported is high, they are stacked on pallets and wrapped
with shrink film and reinforced with shrink plastic.
The OPU-1 terminals meet specifications EN 60721-3-2 class 2M2 transport regarding
vibration and shock.
For shipments on pallets, each box is identified by a package label, which includes: The
box number, content, number of item and total of package.
13.2 STORAGE
Check that the boxes received do not have bumps or dents and that the packaging is not
damaged. In the case of cardboard boxes check that the seal is not broken in any side.
The user must immediately notify ZIV of any anomaly about the original
packaging.
Before storing the box check that the material supplied corresponds to the requested. To do
this, check the supplied material in the delivery note enclosed in the bag labelled “Contains
Documentation. Packing List”.
The user must immediately notify ZIV of any anomaly about the material received
and, if applicable, return all material to ZIV in the original package.
The OPU-1 terminals should be stored in its own packaging until installation.
Storage must be done in premises protected from the weather, Class C according
to EN 60870-2-2 standard.
The boxes should be stacked in a flat position. A maximum of six boxes, one
above the other can be stacked.
In protected installations (Class C), neither the temperature nor the humidity are controlled.
The equipment are protected from direct sunlight, rain and other precipitation and wind.
APPENDIX A
From From From From From From From From From From From From From From From From From From From
40 48 58 68 84 102 110 122 136 158 166 196 230 244 278 326 376 400 460
to a a a a a a a a a a a a a a a a a a
46 56 66 82 100 108 120 134 156 164 194 228 242 276 324 374 398 458 500
S100
S10
S11
S12
S13
S14
S15
S16
S17
S18
S19
S20
S21
S22
S23
S24
S25
S26
S27
S28
S29
S300
S30
S31
S32
S33
S34
S35
S36
S37
S38
S39
From From From From From From From From From From From From From From From From
40 58 68 80 94 112 134 160 194 220 264 290 302 342 400 480
to to to to to to to to to to to to to to to to
56 66 78 92 110 132 158 192 218 262 288 300 340 398 478 500
S100
S10
S11
S12
S13
S14
S15
S16
S17
S18
S19
S20
S21
S22
S23
S24
S25
S26
S27
S28
S29
S300
S30
S31
S32
S33
S34
S35
S36
S37
S38
S39
From From From From From From From From From From From From From From From From
52 64 76 90 108 126 138 158 174 206 240 270 332 350 396 442
to to to to to to to to to to to to to to to to
62 74 88 106 124 136 156 172 204 238 268 330 348 394 440 500
S100
S10
S11
S12
S13
S14
S15
S16
S17
S18
S19
S20
S21
S22
S23
S24
S25
S26
S27
S28
S29
S300
S30
S31
S32
S33
S34
S35
S36
S37
S38
S39
APPENDIX B
From From From From From From From From From From From From From From From From From From From From
40 46 54 64 76 84 100 118 136 162 190 218 252 270 300 330 364 400 430 466
to to to to to to to to to to to to to to to to to to to to
44 52 62 74 82 98 116 134 160 188 216 250 268 298 328 362 398 428 464 500
KPFL1_1
KPFL1_2
KPFL1_3
KPFL1_4
KPFL1_5
KPFL1_6
KPFL1_7
KPFL1_8
KPFL1_9
KPFL1_10
KPFL1_11
KPFL2_1
KPFL2_2
KPFL2_3
KPFL2_4
KPFL2_5
KPFL2_6
KPFL2_7
KPFL2_8
KPFL2_9
KPFL2_10
KPFL2_11
KPFL3_1
KPFL3_2
KPFL3_3
KPFL3_4
KPFL3_5
KPFL3_6
KPFL3_7
KPFL3_8
KPFL3_9
KPFL3_10
KPFL3_11
From From From From From From From From From From From From From From From From From From From From
48 52 58 64 74 84 96 108 122 134 144 172 196 232 268 310 322 368 410 448
to to to to to to to to to to to to to to to to to to to to
50 56 62 72 82 94 106 120 132 142 170 194 230 266 308 320 366 408 446 500
KPFL1_1
KPFL1_2
KPFL1_3
KPFL1_4
KPFL1_5
KPFL1_6
KPFL1_7
KPFL1_8
KPFL1_9
KPFL1_10
KPFL1_11
KPFL2_1
KPFL2_2
KPFL2_3
KPFL2_4
KPFL2_5
KPFL2_6
KPFL2_7
KPFL2_8
KPFL2_9
KPFL2_10
KPFL2_11
KPFL3_1
KPFL3_2
KPFL3_3
KPFL3_4
KPFL3_5
KPFL3_6
KPFL3_7
KPFL3_8
KPFL3_9
KPFL3_10
KPFL3_11
From From From From From From From From From From From From From From From From From From From
48 56 64 72 86 94 106 122 140 164 186 210 236 264 294 344 384 436 468
to to to to to to to to to to to to to to to to to to to
54 62 70 84 92 104 120 138 162 184 208 234 262 292 342 382 434 466 500
KPFL1_1
KPFL1_2
KPFL1_3
KPFL1_4
KPFL1_5
KPFL1_6
KPFL1_7
KPFL1_8
KPFL1_9
KPFL1_10
KPFL1_11
KPFL2_1
KPFL2_2
KPFL2_3
KPFL2_4
KPFL2_5
KPFL2_6
KPFL2_7
KPFL2_8
KPFL2_9
KPFL2_10
KPFL2_11
KPFL3_1
KPFL3_2
KPFL3_3
KPFL3_4
KPFL3_5
KPFL3_6
KPFL3_7
KPFL3_8
KPFL3_9
KPFL3_10
KPFL3_11
APPENDIX C
FREQUENCY
FREQUENCY
From From From From From From From From From From From
342 400 480 502 526 570 658 740 810 890 914
to to to to to to to to to to to
398 478 500 524 568 656 738 808 888 912 1000
S11
S12
S13
S14
S15
S16
S200
S20
S21
S22
S23
S24
S25
S26
S27
S31
S32
S33
S34
S35
S36
FREQUENCY
From From From From From From From From From From
312 388 502 532 576 638 694 774 862 976
to to to to to to to to to to
386 500 530 574 636 692 772 860 974 1000
S11
S12
S13
S14
S15
S16
S200
S20
S21
S22
S23
S24
S25
S26
S27
S31
S32
S33
S34
S35
S36
APPENDIX D