Professional Documents
Culture Documents
DESCRIPTION OF UAPA-1
Rev. 9 - October 2014
www.communications.ziv.es
TABLE OF CONTENTS
Page
1 INTRODUCTION 4
1.1 GENERAL 4
1.2 CONSTITUTION 5
1.2.1 Protection elements 7
1.2.2 Tuning elements 7
1.2.3 Matching unit 7
1.2.4 Hybrid circuits 7
2 TUNING CIRCUITS 15
3 LINE COUPLING 17
4 INSTALLATION 19
4.2 CONNECTIONS 20
4.2.1 Phase-to-earth coupling 21
4.2.2 Phase-to-phase coupling 22
4.2.3 Three-phase coupling 23
5 COMMISSIONING 25
5.2 TUNING 25
APPENDIX A
1 INTRODUCTION
1.1 GENERAL
The coupling units allow, in conjunction with coupling capacitors, the transmission of carrier
frequency signals over high-voltage power lines and, at the same time, offer an efficient
protection against the effects of the power frequency voltage and transient overvoltages for
personnel and equipment.
The UAPA-1 unit is used for coupling Power-Line Carrier (PLC) equipment to a single phase
of high-voltage power lines, carrying out the following:
Draining to earth of power frequency current, limitation of voltage surges coming from the
power line and earthing of the coupling device for protection purposes.
The UAPA-1 allows different tuning elements to be inserted between the coupling capacitor
and the PLC equipment. These elements, together with the coupling capacitor, make up a
resonant circuit that can be configured as a third-order high-pass filter or a second-order
band-pass filter.
One outstanding feature of the UAPA-1 unit is that it can be equipped with a differential
transformer, which acts as a hybrid circuit. This makes it possible to carry out
phase-to-phase coupling with two UAPA-1 units, connected through the differential
transformer included in one of them.
The UAPA-1 units can be used for phase-to-earth or three-phase couplings. One UAPA-1
unit is used for phase-to-earth coupling. Three UAPA-1 units are needed for three-phase
coupling, two of the units being equipped with a differential transformer.
The UAPA-1 coupling unit consists of protection, tuning and impedance matching elements.
If necessary, a differential transformer acting as a hybrid circuit can be added to this basic
configuration.
The different elements, except for the earthing switch, the drain coil, the semiconductor
surge arrester and the air surge arrester, are distributed in modules fixed to the inside of a
cabinet prepared for outdoor mounting. The arrangement of these modules inside the
cabinet can be seen in Figure 1. In some UAPA-1 versions, see section 1.3, the protection
elements are mounted on the outside.
Figure 1 Internal front view of the UAPA-1 coupling unit with hybrid circuit included
NOTE 1: In some UAPA-1 versions, the protection elements are mounted on the outside.
NOTE 2: Taps B1 and B2 (both the same point) of the UAPS module are not the same taps
as those of B1 and B2 (both the same point) of the UAPC module.
Line side, this block is made up of the drain coil, the earthing switch and the air surge
arrester. As an option, for higher security, a solid-state surge arrester can be included at the
factory, in parallel with that of air.
Equipment side, it comprises a gas surge arrester connected between the isolating
transformer equipment-side terminals. The purpose of this surge arrester being to protect
the PLC equipment.
The drain coil has an air core to minimize intermodulation, and is wound on a multisection
coil former to reduce the distributed capacitance. The coil is moulded in an epoxide resin
block, which also holds the earthing switch and the surge arresters.
This block is made up of the tuning coil, variable in steps, which is located in the UAPS
module, and a Cs capacitance, obtained by means of tap connection, located in the UAPC
optional module, and used in the high-pass filter configuration.
The isolating transformer is installed in the UAPS module and matches the primary
impedance of the phase-to-earth coupling, line side, to the secondary one, equipment side.
Primary winding is referred to earth whereas the secondary one is balanced.
Line impedance matching is carried out by means of the combination of primary and
secondary winding taps.
The connection of the UAPA-1 units used in a phase-to-phase or three-phase coupling is carried
out, respectively, by means of one or two differential transformers acting as a hybrid circuit. The
use of the said circuits allows links to be designed that are fault tolerant, which means that if one
or more phases fail only a moderate additional attenuation is introduced in the link.
The hybrid circuit is installed in the UAPH optional module and is made up of a differential
transformer, with a 1:2 turn ratio between primary and secondary windings, and a resistor,
the value of which is half that of the nominal impedance of the equipment, connected between
the centre tap of the secondary-winding and the terminal for connecting the shield of the
coaxial cables to earth. This resistor only dissipates power if one of the phases used fails.
UAPA-1/B The simplest version with tuning circuit with pass-band structure.
UAPA-1/BD It is exactly the same as the UAPA-1/B but also has a solid-state surge
arrester.
UAPA-1/BE It is exactly the same as the UAPA-1/B but the drain coil is mounted on the
outside, together with the earthing switch.
UAPA-1/BDE It is exactly the same as the UAPA-1/BD but the drain coil is mounted on
the outside, together with the earthing switch and the solid-state surge
arrester.
UAPA-1/A Version with two types of tuning circuits, one with high-pass structure and
one with pass-band structure.
UAPA-1/AD It is exactly the same as the UAPA-1/A but also has a solid-state surge
arrester.
UAPA-1/AE It is exactly the same as the UAPA-1/A but the drain coil is mounted on the
outside, together with the earthing switch.
UAPA-1/ADE It is exactly the same as the UAPA-1/AD but the drain coil is mounted on
the outside, together with the earthing switch and the solid-state surge
arrester.
UAPA-1/H Version with tuning circuit with pass-band structure which includes the
differential transformer.
UAPA-1/HD It is exactly the same as the UAPA-1/H but also has a solid-state surge
arrester.
UAPA-1/HE It is exactly the same as the UAPA-1/H but the drain coil is mounted on
the outside, together with the earthing switch.
UAPA-1/HDE It is exactly the same as the UAPA-1/HD but the drain coil is mounted on
the outside, together with the earthing switch and the solid-state surge
arrester (see Figure 3).
UAPA-1/AH The most complete version which includes the differential transformer and
two types of tuning circuits, one with high-pass structure and one with
pass-band structure.
UAPA-1/AHE It is exactly the same as the UAPA-1/AH but the drain coil is mounted on
the outside, together with the earthing switch.
UAPA-1/AHDE It is exactly the same as the UAPA-1/AHD but the drain coil is mounted on
the outside, together with the earthing switch and the solid-state surge
arrester
UAPA-1 coupling units with special application details can be developed on request.
Nominal impedance
Gap 0.6 mm
Model SBMG660
Model CG2-350L
Drain coil
Nominal inductance 26 mH
Nominal resistance 7
Maximum impedance
at power frequency 13
Earthing switch
Weight 11.5 kg
PLC equipment side connection By means of cable gland type PG-21, suitable
for cables of between 9 and 18 mm diameter
2
Selection terminals Internal. Suitable for conductors of 0.3 to 1 mm
2 TUNING CIRCUITS
The coupling unit type UAPA-1 allows two coupling-capacitor tuning circuits to be
configured, one with high-pass structure and one with pass-band structure, according to
whether the unit includes the UAPC optional module or not, respectively. These circuits as
well as counteracting the reactive component of the coupling impedance also enhance the
transmission of signals in a specific frequency band.
The main characteristics of each structure are presented in a simplified way in the following
sections. Only the elements used for the synchronization appear in the diagrams, the drain
coil not being shown.
According to Recommendation IEC-481, the bandwidth is defined as the pass band within
which composite loss is lower than 2 dB and return loss is greater or equal to 12 dB. The
latter condition is more stringent as composite loss in points with return loss of 12 dB is
normally lower than 1 dB.
The coupling capacitor together with the tuning coil and a series capacitance (Cs), obtained
by means of a capacitor bank, which is located in the UAPC optional module, form a
resonant circuit, which acts as a third-order high-pass filter. This circuit is shown in Figure 6.
UAPA-1
The lowest available cut-off frequencies depend on the capacity of the coupling capacitor
and the nominal impedance of the high-voltage line.
The coupling capacitor together with the tuning coil form a resonant circuit, which acts as a
second-order band-pass filter. This circuit is shown in Figure 7.
UAPA-1
This circuit adapts well in the proximity of the resonant frequency. It is therefore a good
option when the UAPA-1 is not required to work with very separate frequencies.
The bandwidths available depend on the coupling capacitor, the tuning-coil inductance
value, and the nominal impedance of the high-voltage line.
3 LINE COUPLING
The main types of line couplings used nowadays are phase-to-earth, phase-to-phase and
three-phase coupling. This section gives a brief description of each one.
Phase-to-earth coupling requires less equipment, so it is widely used for short-lines and
links which do not require high reliability under line fault. In this type of coupling, the PLC
equipment is connected between a phase-conductor and earth, thus requiring a single
coupling capacitor, one line trap, and one coupling unit at each end of the link. Although
coupling is only carried out in one phase, the other conductors are also involved in the
transmission, so that attenuation due to high loss of earth is partly bypassed. Nevertheless,
this coupling offers the worst attenuation figures, and is the least reliable in case of line fault.
Phase-to-phase coupling is based on distributing the transmitted power equally between the
two phase conductors used. This transmission mode reduces the attenuation at PLC
frequency. The drawback is that at least twice as much equipment is required as for
phase-to-earth coupling.
Link reliability against line faults can be increased by insulating the signals injected in the
phase conductors, by means of the UAPH optional module which contains a differential
transformer acting as a hybrid circuit (see Figure 8). This is the operating principle of the
phase-to-phase coupling with connection through a differential transformer. When there is a
fault in one of the phase conductors used, the other conductor works as a phase-to-earth
coupling, with an additional attenuation of 6 dB.
Three-phase coupling consists of injecting the carrier signal power into the three power line
conductors, half into the centre conductor and half equally shared between the outer
conductors (see Figure 9).
The advantage of this type of coupling is that it has the lowest attenuation and allows
communication to be maintained should there be a failure in one or two line phases.
Supplementary attenuation in such conditions depends on the phase or phases involved
and is slightly different according to whether open circuit or short circuit, or a combination of
both, is involved. A failure in the centre phase or in both outer phases results in
approximately a 6 dB supplementary attenuation, that of an outer phase in a 2.5 dB
attenuation and that affecting the centre and one outer phase in a 12 dB loss.
4 INSTALLATION
The following sections describe the mechanical and electrical characteristics of the coupling unit
type UAPA-1, and the connections to be carried out according to the type of coupling to the line.
The different elements that make up the coupling unit type UAPA-1 are contained in a
glass-fiber reinforced polyester cabinet prepared for outdoor mounting. The position of the
fixing holes are shown in Figure 4.
There is a M12 rod on the outside of the cabinet, at the top, for the connection to the
coupling capacitor. In the UAPA-1 versions with protection elements mounted on the
outside, there is a M8 terminal.
If the coupling capacitor is not equipped with an earthing switch it is advisable to install one in
an easily visible place, for personnel protection during installation operations. The earthing
switch housed in the coupling unit should only be used during the adjustment or test of the unit.
It is also advisable to connect the coupling capacitor to the external earthing switch and then
to the coupling unit instead of making separate connections between capacitor and the
other two elements.
At the bottom of the cabinet, there is a M10 rod for the connection to earth, a ventilation hole
protected against insects, and cable glands type PG-21 for the input of PLC equipment side
cables, suitable for cables of between 9 and 18 mm in diameter.
The PLC equipment side cables, in the inside of the cabinet, are connected to the
corresponding terminals.
The coaxial cable shield should only be earthed at one end of the cable, usually
equipment-side, in order to avoid the current flow caused by voltage differences between
different points of the earth mesh.
The connections for the tuning-circuit configuration, in the inside of the cabinet, are carried
out by means of the easily accessible screw terminals, and allow the connection of 0.3 to
2
1 mm cables with a 2.5 mm terminal at each end. Various connection cables are supplied
with the unit for these terminals.
OPTIONAL
UAPS UAPC
MODULE MODULE
Connection to
B1 B2
line and to the
tuning coil
Capacitor bank
Tuning coil L1 C13 C14
C11 C12
C9 C10
L_IN C7 C8
Tuning coil taps
LS1
LS3
LS5
LS4
LS6
LS7
LS8
LS2
C5 C6
C3 C4
L_OUT
C1 C2
CS1
CS3
CS2
CS5
CS4
CS6
CS7
CS8
B2 C5
Line-side impedance
T1 T2 T3 T4 T5 T6
matching taps
Differential
transformer
Matching impedance
transformer TF1 TF2
Connection to earth
of the coaxial
shields in the hybrid
Equipment-side (Optional)
TA TB TC TD TE TF D1 D2 D3 D4 D5 D6 D7 D8
impedance
matching taps
DSC 1
Auxiliary taps for
phase-to-phase
connection with hybrid J1 J2 J3 J4
A B C D E F G H
NOTE: Taps B1 and B2 (both the same point) of the UAPS module are not the same taps
as those of B1 and B2 (both the same point) of the UAPC module.
4.2 CONNECTIONS
The cable connections for the three types of line couplings are described in the following
sections.
In the phase-to-earth coupling, the central conductor of the coaxial cable is connected to
terminal A, the shield being connected to terminal B (see Figure 11).
Line-side nominal impedance is selected by carrying out the jumpers indicated in the tables
at the end of the manual.
NOTE: B1 and B2 are the same point and connection can be made in either of the two taps.
For phase-to-phase coupling two UAPA-1 units are needed at each end of the line. They
can be connected to the PLC equipment by means of the differential transformer included in
one of them (UAPH optional module) in order to establish a phase-to-earth coupling, in case
of open circuit or short circuit of one of the phases used.
Figure 13 shows the test arrangement of the three-phase coupling, the power distribution
between the phases being indicated.
The composite-loss measurements must be carried out over the whole link, as shown in the
test arrangement in Figure 13, and not on the devices at one end of the line, due to the fact
that as the transmission is over three conductors, there cannot be bipolar elements
line side.
The three-phase coupling configuration is shown in Figure 14. The transformer polarity of
the unit connected to the OUTER PHASE 2 must be inverted so that the phase of the
signals applied to the outer conductors is the opposite of that of the central conductor. In
order to do this, the line-side taps of the transformer of the outer phase 2 unit must be
connected the other way round. The tap connected to the tuning coil or Cs capacitance in
the outer phase 1 unit must be earthed in the outer phase 2 unit and viceversa.
The shields of the coaxial cables connecting the coupling units to the differential transformer
can be earthed by means of jumper D7-D8 of the hybrid circuits.
5 COMMISSIONING
Before carrying out any tuning or impedance matching operations, the earthing switch of the
UAPA-1 unit must be in the closed position in order to drain any dangerous voltage. Once
the adjustments have been made, the earthing switch must be in the open position.
Before carrying out the tuning circuit configuration it is advisable to verify the capacity of the
coupling capacitor and the nominal impedance of the high-voltage line.
5.2 TUNING
The coupling unit type UAPA-1 allows two tuning circuits to be configured, one with
high-pass structure, obtained by means of the UAPC optional module, see the example in
Figure 16, and another with pass-band structure, see the example in Figure 15.
A table is shown, Table 3 and Table 4, for high-pass structure, indicating the available cut-
off frequencies, with a tolerance of 10%, depending on the capacity of the coupling
capacitor and the nominal impedance of the phase-to-earth line.
In the high-pass structure, the value of the series capacitance Cs, configurable for tap
connection, is given in Table 1, and the tuning coil in Table 2.
B1 B2
To line
L1
C13 C14
C11 C12
L_IN C9 C10
LS1
LS3
LS5
LS4
LS6
LS7
LS8
LS2
C7 C8
C5 C6
L_OUT
C3 C4
C1 C2
B1
DSC 2
B2 C5
CS1
CS3
CS2
CS5
CS4
CS6
CS7
CS8
T1 T2 T3 T4 T5 T6
TF1
NOTE:
L is not connected
TA TB TC TD TE TF D1 D2
DSC 1
J1 J2
A B C D
NOTE: Taps B1 and B2 (both the same point) of the UAPS module are not the same
taps as those of B1 and B2 (both the same point) of the UAPC module.
For pass-band structure, the adjustment is carried out by means of the tuning coil, using the
Table 5 to Table 26 as a guide. These tables show the available frequencies, with a
tolerance of 10%, depending on the capacity of the coupling capacitor and the nominal
impedance of the phase-to-earth line, for an initial tap configuration of the impedance-
matching transformer.
Taps Capacity
CS2 1,1 nF
CS4 2,2 nF
CS6 3,3 nF
CS6+(CS2-CS5) 4,4 nF
CS6+(CS4-CS5) 5,5 nF
CS5+(CS6-CS7) 6,6 nF
CS1+(CS2-CS5)+(CS6-CS7) 7,7 nF
CS3+(CS4-CS5)+(CS6-CS7) 8,8 nF
CS1+(CS2-CS3)+(CS4-CS5)+(CS6-CS7) 9,9 nF
When the value of the central frequency, Fo, and that of the coupling capacity, Ca, is
known, the necessary inductance value can be found by means of the following formulae:
1
L
4 2 Fo 2 Ca
Once the inductance value is found, the most suitable taps can be selected (see Table 2).
Due to the tolerances of the devices involved in the coupling, it is possible that the selected
taps do not coincide exactly with the calculated value.
LS6, LS7 7 LS4, LS7 90 LS2, LS4 277 LS1, LS5 867
LS5, LS6 14 LS5, LS8 91 LS1, LS3 381 LS1, LS6 1016
LS7, LS8 21 LS1, LS2 100 LS3, LS8 390 LS1, LS7 1140
LS4, LS5 26 LS2, LS3 103 LS2, LS5 423 LS1, LS8 1387
NOTE: LS are tuning coil taps. One LS tap must be connected to the corresponding matching transformer
taps and the other LS tap to the line. See Figure 15
Table 3 Available cut-off frequencies for the high-pass tuning circuit (characteristics equipment-side impedance: 50 )
Table 3 (Cont.) Available cut-off frequencies for the high-pass tuning circuit (characteristics equipment-side impedance: 50 )
Table 4 Available cut-off frequencies for the high-pass tuning circuit (characteristics equipment-side impedance: 75 )
Table 4 (Cont.) Available cut-off frequencies for the high-pass tuning circuit (characteristics equipment-side impedance: 75 )
Table 5 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 100 )
Table 6 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 150 )
Table 7 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 200 )
Table 8 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 250 )
Table 9 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 300 )
Table 10 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 350 )
Table 11 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 400 )
Table 12 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 450 )
Table 13 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 500 )
Table 14 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 550 )
Table 15 Available frequencies for the pass-band tuning circuit for a equipment impedance of 50 (Line impedance 600 )
Table 16 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 100 )
Table 17 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 150 )
Table 18 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 200 )
Table 19 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 250 )
Table 20 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 300 )
Table 21 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 350 )
Table 22 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 400 )
Table 23 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 450 )
Table 24 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 500 )
Table 25 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 550 )
Table 26 Available frequencies for the pass-band tuning circuit for a equipment impedance of 75 (Line impedance 600 )
Table 3 and Table 4 refer to a 100 and 400 nominal line impedance in a phase-to-earth
coupling. Table 5 to Table 26 refer to 100 and 600 nominal line impedance in a
phase-to-earth coupling.
As far as two and three-phase coupling is concerned, the first stage consists of tuning each
unit as for phase-to-earth coupling, carrying out the return loss measurement. A method for
measuring such a response is given in section 2 of Appendix A. After that, the set should
be tuned to achieve the best return loss response possible over the whole bandwidth.
Once impedance matching is carried out, it is advisable to repeat the tuning operation.
Another way of carrying out impedance matching is to select the transformer tap
combination that gives the lowest composite loss. Section 1 of Appendix A describes a
method for measuring such a response.
APPENDIX A
A method for measuring the composite loss is shown in the following figure.
where VO is the open circuit voltage of the generator with internal impedance Z 2 and V the
output voltage across the nominal line impedance Z1.
According to IEC 481 Publication, composite loss has to be lower than 2 dB within the
coupling device band.
A method for measuring the return loss is shown in the following figure.
Ar = 20 log(V1/V2) (dB)
where V1 and V2 are the voltmeter readings when switch J is open and closed respectively,
keeping VO constant.
According to IEC 481 Publication, return loss has to be higher than 12 dB within the
coupling device band.