ŘWhen connecting cable or busbar to the product, tighten terminal screws to the torque

Innovators in Protection Technology specified in this manual. Otherwise, a fire could result.
ŘEven when tightening the terminal screws and insulating tubes
after conductor connection, do not apply excessive interpole
barriers
or
insulating tape
force to the terminals. Otherwise, a fire may result.
ŘFor front-connected breakers, Insulate all bare
Instruction Manual for conductors of the line side until the breaker end. If interpole barriers are packed, be
sure to use the barriers; moreover, insulate all bare conductors by insulating tape or the
Moulded Case Circuit
like so that the tape overlaps with the barriers. Insufficient insulation may result in short-
Breakers circuit.
ŘDo not block the arc gas vents of the product to ensure adequate arc space. Blocking
(Types) these vents could result in failure of circuit interruption.

Safety Notices ŝHandling Precautions


Be sure to read these Instructions and other associated documents accompanying the Warning
product thoroughly to be familiarize yourself with the product handling, safety information, and
all other precautions before mounting, using, servicing, or inspecting the product. In these ŘNever touch terminals. Otherwise, electric shock may result.
Instructions, safety notices are divided into "Warning" and "Caution" according to the hazard
level: Caution
Warning : A warning notice with this symbol indicates that neglecting the suggested
procedure or practice could result in lethal or serious personal injury. ŘWhen the breaker trips open automatically, remove the cause, then return the
handle to the | (ON) position. Should a fault be interrupted, the breaker must be
Caution : A caution notice with this symbol indicates that neglecting the suggested
procedure or practice could result in moderate or slight personal injury and/or property damage. inspected. Otherwise, a fire may result.
Note that failing to observe Caution notices could result in serious results in some cases.
ŝMaintenance Precautions
Because safety notices contain important information, be sure to read and observe them.
■Mounting Precautions
Caution
Please retain this manual for future reference.The Manufacturer assumes no (For detailed mounting dimensions, refer to the TemBreak2 catalogue.)
ŘService and/or inspection of the product must be done by persons having expert
responsibility for damages resulting from non-application or incorrect application of the Caution knowledge.
instructions provided herein. ŘBefore servicing or inspecting the product, open an upstream circuit breaker or the
●Electrical work should only be undertaken by suitably qualified persons.
like to isolate all sources of power. Otherwise, electric shock may result.
●Do not place the product in an area that is subject to high temperature, high humidity,
ŘRegularly check that the breaker terminal screws are tightened to torque values
excessive dusty air, corrosive gas, strong vibration and shock, or other unusual
shown within this manual, failure to do so may result in fire.
conditions. Mounting in such areas could cause a fire or malfunction.
547- 0002 7 - 2 - 10 7-2-10 Kamihigashi, Hiranoku, Osaka
●Be careful to prevent foreign objects (debris, concrete powder, iron powder, etc.) and
06(6791)9320 547-0002, Japan ŝOther Precautions
rainwater from entering product. These materials inside the product could cause a fire
ĂDo not carry this product by accessory leads, as this may cause damage to the
06(6791)9274 TEL: 81-6-6791-9323/ FAX: 81-6-6791-9274 or malfunction.
product.
●Prior to commencing any work on the product, open an upstream circuit breaker or isolator to
www.terasaki.co.jp URL: www.terasaki.co.jp ĂUnauthorised opening of the breaker cover will invalidate product warranty.
ensure that no voltage is applied to the product. Otherwise, electrical shock may result.
E-mail:kiki-info@terasaki.co.jp E-mail: int-sales@terasaki.co.jp ĂWhen installing the product, use wires or conductors, the cross sectional areas of
●For 4-pole breakers, be sure to connect a neutral conductor to the N pole. Otherwise, an
which accommodate the rated current of the product. Using wires or conductors with
over-current may hinder the product from tripping, thus resulting in a fire.
2G0944SAA(KRB-0602) inadequate cross sectional areas may cause false tripping and overheat.

Packaged Items / Assembly Tools Operating Instructions Fitting Internal Accessories 2 Pole 5

Breaker: 1 uctio
n Instruction Manual: 1
Instr (This document)

Auxiliary Switch 4
Interpole Barrier 3
(Only FC) 2 T2AX00L

2P: 1 TRIPPED 3
リングマーク Ring Mark
3P: 2 Alarm Switch 補助スイッチ 警報スイッチ
4P: 3 * Auxiliary Switch Alarm Switch
T2AL00L a接点 b接点 a接点 b接点
1 a contact b contact a contact b contact
11/AXc-14/AXa 11/AXc-12/AXb 91/ALc 91/ALc
Handle 21/AXc-24/AXa 21/AXc-22/AXb - -
(OFF) Shunt Trip Undervoltage Trip 31/AXc-34/AXa 31/AXc-32/AXb 94/ALa 92ALb
Type * *
T2SH00L T2UV00L 10 mm 電圧引外し電源 不足電圧引外し電源
Connections/ S50-SF, S125-SF, E160-SF, S160-SCF, S160-SF, E160-SJ, S160-SCJ, S160-SJ Shunt Trip Undervoltage Trip
Poles power source power source
Qty Mounting screw Qty Connecting screw * Symbols of Accessories C1-C2 D1-D2
2P 2 2P 4 15∼50A Trip Button
3P 2 M 4 x 61 3P 6 M 5 x 12 Combination Pull Out Leads on Load Side Removal
Front
4P 2 4P 8 Fix Types
Connection 2P 2 2P 4 60∼160A 2 pole
3P 2 M 4 x 61 3P 6 M 8 x 14
4P 2 4P 8 Fix Types (ON)

(RC) 2P 2 2P 4 S50-SF M 6 x 22
Rear 3P 2 M 4 x 61 3P 6
Connection
M 8 x 23
4P 2 4P 8 Others (ON) (OFF)
2P 2 2P 4
or
Plug-in 3P 2 M 4 x 75 3P 6 M6 RESET
Connection 4P 2 4P 8 (OFF) (ON)
(FP) 2P 4 2P 4 S50-SF M 6 x 22
Flush Plate 3P 4 M 5 x 15 3P 6
M 8 x 23
Where Applicable 4P 4 4P 8 Others
(OFF) AX
AL
SH
UV V
Operation Operation effort In case of fiting one (or two) auxiliary
switch, fit in an order from a left sideslot.
( OFF) ( ON) 44,1 N

4 5 ( ON) ( OFF) 37,2 N


13 19 TRIP ( OFF) 78,4 N After fitting, verify the function of the Accessory.
5 Fitting Internal Accessories 3-4 Pole 6 7 9
5 5
Breaker Mounting Procedure Breaker Mounting Procedure for PM
for FC
DIN Rail Adaptor (Optional)
or
3-4 Pole Plug-in Base

T2PM12LE
M type

3 4 4
2 Auxiliary Switch

T2AX00M
3 A B
Ring Mark
Alarm Switch
* Auxiliary Switch Alarm Switch
T2AL00M a b a b
1 a contact b contact a contact b contact
11/AXc-14/AXa 11/AXc-12/AXb 91/ALc 91/ALc
21/AXc-24/AXa 21/AXc-22/AXb - -
(OFF) Shunt Trip Undervoltage Trip 31/AXc-34/AXa 31/AXc-32/AXb 94/ALa 92ALb
* * M 4 x 61 M 4 x 61
T2SH00 T2UV00 A B
10 mm 1.3 ~ 1.7 Nm 1.3 ~ 1.7 Nm
Shunt Trip Undervoltage Trip
power source power source
* Symbols of Accessories C1-C2 D1-D2

Combination Pull Out Leads on Load Side Removal 8


Breaker Mounting Procedure for FP
(ON)
3 pole

(OFF) 4

C
(ON)
4 pole

D
(OFF) AX M 4 x 75
AL C
1.3 ~ 1.7 Nm
SH
UV V
In case of fiting one (or two) auxiliary
switch, fit in an order from a left sideslot.
A
M 5 x 15
D
After fitting, verify the function of the Accessory. 3.6 ~ 4.4 Nm 2G0944SAA(KRB-0602)

10 11 13 14 15
Conductor Connection Procedure for RC/F.P (Where Applicable) Adjustment procedure for adjustable Thermal Magnetic Types Interpole Barrier Terminal Cover Handle Holder / Lock Mounting Procedure
Mounting Procedure Mounting Procedure
Arrangement Set
Handle
(0°, 45°, 90°, 135°)

Flat bar stud Interpole Barrier


S50-SF T2RP05L S 13 T2BA16L SH
E E125-SF
S125-SCF T2RP12L S
F (OFF)
⌀9
5 S125-SF
2
1 2

1
4
or Handle Holder/Lock
M 5 x 14 M 6 x 22
15~50A S50-SF T2HH25L
2.3 ~ 2.8 Nm 2.7 ~ 4.5 Nm
E F
M 6 x 18 M 8 x 23
60~125A
7.8 ~ 11.8 Nm Others 11.8 ~ 18.6 Nm

12
Conductor Connection Procedure for FC N
19
L 1
Q When removing, remove the items in 2 3
reverse order of mounting.
Flat Bar
4 T2FB12L*B
N Ø5
ØM ØM x 3 max.
P Connection Terminal Cover

H RC T2CR16L SG Connection Terminal Cover

K FC ( Long Type ) T2CF16L SLNG


J G T2CF16L SSNG
FC ( Short Type )
M 5 x 12 1
G 16,5 mm 15 ~ 50 A 2
2.3 ~ 3.4 Nm
H 9 mm N
M 8 x 14
J 16,5 mm 60 ~ 125 A
4.9 ~ 6.9 Nm Handle holder/ lock can be fitted in any position of (ON) and (OFF).
K 9 mm M 8 x 30
L 5 mm P
11.8 ~ 18.6 Nm When you use this item as the handle lock, please fit padlocks in the procedure of
M 9 mm max M6 When removing, remove the items in
Q
Insulate all bare conductors of the line side until the breaker end. 6 ~ 8 Nm reverse order of mounting. When removing, remove the items in reverse order of mounting.