Innovators in Protection Technology specified in this manual. Otherwise, a fire could result.
ŘEven when tightening the terminal screws and insulating tubes
after conductor connection, do not apply excessive interpole
barriers
or
insulating tape
force to the terminals. Otherwise, a fire may result.
ŘFor front-connected breakers, Insulate all bare
Instruction Manual for conductors of the line side until the breaker end. If interpole barriers are packed, be
sure to use the barriers; moreover, insulate all bare conductors by insulating tape or the
Moulded Case Circuit
like so that the tape overlaps with the barriers. Insufficient insulation may result in short-
Breakers circuit.
ŘDo not block the arc gas vents of the product to ensure adequate arc space. Blocking
(Types) these vents could result in failure of circuit interruption.
Packaged Items / Assembly Tools Operating Instructions Fitting Internal Accessories 2 Pole 5
Breaker: 1 uctio
n Instruction Manual: 1
Instr (This document)
Auxiliary Switch 4
Interpole Barrier 3
(Only FC) 2 T2AX00L
*
2P: 1 TRIPPED 3
リングマーク Ring Mark
3P: 2 Alarm Switch 補助スイッチ 警報スイッチ
4P: 3 * Auxiliary Switch Alarm Switch
T2AL00L a接点 b接点 a接点 b接点
1 a contact b contact a contact b contact
11/AXc-14/AXa 11/AXc-12/AXb 91/ALc 91/ALc
Handle 21/AXc-24/AXa 21/AXc-22/AXb - -
(OFF) Shunt Trip Undervoltage Trip 31/AXc-34/AXa 31/AXc-32/AXb 94/ALa 92ALb
Type * *
T2SH00L T2UV00L 10 mm 電圧引外し電源 不足電圧引外し電源
Connections/ S50-SF, S125-SF, E160-SF, S160-SCF, S160-SF, E160-SJ, S160-SCJ, S160-SJ Shunt Trip Undervoltage Trip
Poles power source power source
Qty Mounting screw Qty Connecting screw * Symbols of Accessories C1-C2 D1-D2
2P 2 2P 4 15∼50A Trip Button
3P 2 M 4 x 61 3P 6 M 5 x 12 Combination Pull Out Leads on Load Side Removal
Front
4P 2 4P 8 Fix Types
Connection 2P 2 2P 4 60∼160A 2 pole
3P 2 M 4 x 61 3P 6 M 8 x 14
4P 2 4P 8 Fix Types (ON)
(RC) 2P 2 2P 4 S50-SF M 6 x 22
Rear 3P 2 M 4 x 61 3P 6
Connection
M 8 x 23
4P 2 4P 8 Others (ON) (OFF)
2P 2 2P 4
or
Plug-in 3P 2 M 4 x 75 3P 6 M6 RESET
Connection 4P 2 4P 8 (OFF) (ON)
(FP) 2P 4 2P 4 S50-SF M 6 x 22
Flush Plate 3P 4 M 5 x 15 3P 6
M 8 x 23
Where Applicable 4P 4 4P 8 Others
(OFF) AX
AL
SH
UV V
Operation Operation effort In case of fiting one (or two) auxiliary
switch, fit in an order from a left sideslot.
( OFF) ( ON) 44,1 N
T2PM12LE
M type
3 4 4
2 Auxiliary Switch
*
T2AX00M
3 A B
Ring Mark
Alarm Switch
* Auxiliary Switch Alarm Switch
T2AL00M a b a b
1 a contact b contact a contact b contact
11/AXc-14/AXa 11/AXc-12/AXb 91/ALc 91/ALc
21/AXc-24/AXa 21/AXc-22/AXb - -
(OFF) Shunt Trip Undervoltage Trip 31/AXc-34/AXa 31/AXc-32/AXb 94/ALa 92ALb
* * M 4 x 61 M 4 x 61
T2SH00 T2UV00 A B
10 mm 1.3 ~ 1.7 Nm 1.3 ~ 1.7 Nm
Shunt Trip Undervoltage Trip
power source power source
* Symbols of Accessories C1-C2 D1-D2
(OFF) 4
C
(ON)
4 pole
D
(OFF) AX M 4 x 75
AL C
1.3 ~ 1.7 Nm
SH
UV V
In case of fiting one (or two) auxiliary
switch, fit in an order from a left sideslot.
A
M 5 x 15
D
After fitting, verify the function of the Accessory. 3.6 ~ 4.4 Nm 2G0944SAA(KRB-0602)
10 11 13 14 15
Conductor Connection Procedure for RC/F.P (Where Applicable) Adjustment procedure for adjustable Thermal Magnetic Types Interpole Barrier Terminal Cover Handle Holder / Lock Mounting Procedure
Mounting Procedure Mounting Procedure
Arrangement Set
Handle
(0°, 45°, 90°, 135°)
1
4
or Handle Holder/Lock
M 5 x 14 M 6 x 22
15~50A S50-SF T2HH25L
2.3 ~ 2.8 Nm 2.7 ~ 4.5 Nm
E F
M 6 x 18 M 8 x 23
60~125A
7.8 ~ 11.8 Nm Others 11.8 ~ 18.6 Nm
12
Conductor Connection Procedure for FC N
19
L 1
Q When removing, remove the items in 2 3
reverse order of mounting.
Flat Bar
4 T2FB12L*B
N Ø5
ØM ØM x 3 max.
P Connection Terminal Cover