PMT-1-X

Touchscreen Room Pressure Monitor Sheet 1 of 5

270120
Product Submittal Rev. G
2019/09/12

PMT SPECIFICATIONS:
ENVIRONMENTAL (OPERATING) 50⁰F to 95⁰F (10⁰C to 35⁰C), 0% to 95% R.H.(NON-CONDENSING)
ENVIRONMENTAL (STORAGE) -22⁰F to 122⁰F (-30⁰C to 50⁰C), 0% to 95% R.H.(NON-CONDENSING)
INPUT POWER 24 VAC +/- 10%, 50/60 Hz, 34 VA (EXTERNAL LOADS NOT INCLUDED), CLASS 2
INPUTS 1 BINARY INPUT, 1 BINARY/ANALOG INPUT, 1 SENSOR INFORMATION NETWORK INPUT
2 ANALOG OUTPUTS (0 to 10 VDC, MAX:10 mA),
OUTPUTS 1 DRY BINARY OUTPUT (MAX: 24 VAC/VDC, 100 mA),
1 SIN POWER OUTPUT (34 VDC, MAX: 300 mA)
DISPLAY TYPE CAPACITIVE TOUCH, 4.3in.(109mm) TFT/IPS, DIMMABLE
RESOLUTION WVGA RGB 480px x 800px
COMMUNICATION PROTOCOL BACNET, SIN
DEVICE TYPE B-ASC
COMMUNICATION TYPE MS/TP (RS-485)
COMMUNICATION SPEED 9600, 19200, 38400, 76800
BACNET
CERTIFICATION BTL

1. BACNET
CONTROL PRIORITY ORDER
2. NORMAL OPERATION

50⁰F TO 95⁰F (10⁰C TO 35⁰C)


ENVIRONMENTAL (OPERATING)
0% TO 95% R.H.(NON-CONDENSING)

-22⁰F TO 122⁰F (-30⁰C TO 50⁰C)


ENVIRONMENTAL (STORAGE)
0% TO 95% R.H.(NON-CONDENSING)
ROOM PRESSURE SENSORS
(SRPS) INPUT POWER POWERED FROM PMT
RANGE +/- 0.1 in.w .c. (+/- 25 Pa)
ACCURACY 3% OF READING
PRESSURE TUBING 24"(588mm) LONG, BLACK, FIRE-RATED
FACE PLATE ABS PLASTIC, WHITE

PMT SRPS

ROOM PRESSURE SENSORS:

ONE SIN ROOM PRESSURE SENSOR (SRPS1)


TWO SIN ROOM PRESSURE SENSORS (SRPS2)
THREE SIN ROOM PRESSURE SENSORS (SRPS3)
Solid Edge

NOTE: PLEASE REFER TO PMT MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2019


PMT-1-X
Touchscreen Room Pressure Monitor Sheet 2 of 5

270120
Product Submittal Rev. G
2019/09/12

DIMENSIONS:

.84 (21)

5.0 (127) 3.58 (91) MAX


2.8 (71) MIN

3.65 (93) 1.34 (34) PMT

3.0 (76)
DINRAIL .25 (6)
.7 (18)

3.56 (90)
3.91 (99) 4.50 (114) 3.25 (83)

2.10 (53) 2.36 (60)


2.75 (70) .83 (21)

SRPS FACE
PLATE

TERMINATION:
HOT INP UT P OWER, HOT

COM INP UT P OWER, GROUND

AO1 ANA LOG OUTPUT


Net COM

A O2 ANA LOG OUTPUT


Vcom
Vbus

D+
D --

BI
+
--

BINA RY INPUT
COM

CI +
CONFIGURAB LE INP UT
BACNet S.I.N. CI -

DRY CONTACT
BO
BINA RY OUTP UT

CONTACT CONFIG. BINARY ANALOG


CLOSURE INPUT INPUT OUTPUTS
24VAC Vbus S.I.N. POWER

Vco m S.I.N. GROUND

D+ S.I.N. NET +
AO1
BI
CI +

COM

COM
BO

CI --

AO2
HOT

D- S.I.N. NET -

+ BA CNet NET +

- BA CNet NET -

Net COM BA CNet NET COM


Solid Edge

NOTE: PLEASE REFER TO PMT MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS. SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2019


PMT-1-X
Touchscreen Room Pressure Monitor Sheet 3 of 5

270120
Product Submittal Rev. G
2019/09/12

BACNET POINTS LIST v2.4.0 OR NEWER


Write Settings
Object Name Units Range Description
Disabled Standard Open

ANALOG INPUTS

Pressure reading of the monitored room


AI1 Room Pressure 1 in.w .c. / Pa -0.1 to +0.1 R R R
using SRPS1

Pressure reading of the monitored room


AI2 Room Pressure 2 in.w .c. / Pa -0.1 to +0.1 using SRPS2 R R R
(Only available w hen SRPS2 connected)

Pressure reading of the monitored room


AI3 Room Pressure 3 in.w .c. / Pa -0.1 to +0.1 using SRPS3 R R R
(Only available w hen SRPS3 connected)

BINARY INPUTS

The Binary Input can be configured to


BI1 Binary Input 1 - [usage] - Open / Closed several types of input signals. R R R
See Input section of PMT manual for options

MULTISTATE INPUTS

2 or 3 States The Configurable Input can be configured to


Configurable Input 1 - Based on
MI1 based on several types of input signals. R R R
[usage] usage
usage See Input section of PMT manual for options

ANALOG OUTPUTS
Analog Output 1 can be configured
to provide VDC output
AO1 Analog Output 1 VDC 0-10 for several different values. R W W
See Output section of PMT manual for
options
Analog Output 2 can be configured
to provide VDC output
AO2 Analog Output 2 VDC 0-10 for several different values. R W W
See Output section of PMT manual for
options
BINARY OUTPUTS
Binary Output 1 can be configured
to provide 24VAC output
BO1 Binary Output 1 - On / Off for several different values. R W W
See Output section of PMT manual for
options
ANALOG VALUE
Alarm trip point of Low Pressure Alarm for
Room Low Pressure 0 to AV2 or the room using SRPS1
AV1 in.w .c. / Pa R R W
Alarm 1 AV2 to 0 (Value w ill change sign if the room is
configured for a Negative or Positive mode)

Alarm trip point of High Pressure Alarm


Room High Pressure AV1 to 0.1 for the room using SRPS1
AV2 in.w .c. / Pa R R W
Alarm 1 or 0 to AV1 (Value w ill change sign if the room is
configured for a Negative or Positive mode)

Alarm trip point of Low Pressure Alarm for


Room Low Pressure 0 to AV4 or the room using SRPS2
AV3 in.w .c. / Pa R R W
Alarm 2 AV4 to 0 (Value w ill change sign if the room is
Solid Edge

configured for a Negative or Positive mode)


ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
© Copyright Antec Controls by PRICE 2019
PMT-1-X
Touchscreen Room Pressure Monitor Sheet 4 of 5

270120
Product Submittal Rev. G
2019/09/12
BACNET POINTS LIST v2.4.0 OR NEWER (CONTINUED)
Write Settings
Object Name Units Range Description
Disabled Standard Open

Alarm trip point of High Pressure Alarm


Room High Pressure AV3 to 0.1 for the room using SRPS2
AV4 in.w .c. / Pa R R W
Alarm 2 or 0 to AV3 (Value w ill change sign if the room is
configured for a Negative or Positive mode)

Alarm trip point of Low Pressure Alarm for


Room Low Pressure 0 to AV6 or the room using SRPS3
AV5 in.w .c. / Pa R R W
Alarm 3 AV6 to 0 (Value w ill change sign if the room is
configured for a Negative or Positive mode)

Alarm trip point of High Pressure Alarm


Room High Pressure AV5 to 0.1 for the room using SRPS3
AV6 in.w .c. / Pa R R W
Alarm 3 or 0 to AV5 (Value w ill change sign if the room is
configured for a Negative or Positive mode)

Room 1 Temperature reading


AV7 Room 1 Temperature - BACnet ºF / ºC 0 - 200 R R R
from other BACnet device

Room 1 Relative Humidity reading


AV8 Room 1 Relative Humidity - BACnet % R.H. 0 - 100 R R R
from other BACnet device

Room 1 Air Change Rate reading


AV9 Room 1 Air Change Rate - BACnet A.C.H. 0 - 100 R R R
from other BACnet device

Room 2 Temperature reading


AV10 Room 2 Temperature - BACnet ºF / ºC 0 - 200 R R R
from other BACnet device

Room 2 Relative Humidity reading


AV11 Room 2 Relative Humidity - BACnet % R.H. 0 - 100 R R R
from other BACnet device

Room 2 Air Change Rate reading


AV12 Room 2 Air Change Rate - BACnet A.C.H. 0 - 100 R R R
from other BACnet device

Room 3 Temperature reading


AV13 Room 3 Temperature - BACnet ºF / ºC 0 - 200 R R R
from other BACnet device

Room 3 Relative Humidity reading


AV14 Room 3 Relative Humidity - BACnet % R.H. 0 - 100 R R R
from other BACnet device

Room 3 Air Change Rate reading


AV15 Room 3 Air Change Rate - BACnet A.C.H. 0 - 100 R R R
from other BACnet device

AV16 Room 1 Low Pressure Alarm Delay sec 0-600 Room 1 Low Pressure Alarm Delay Value R R R

AV17 Room 1 High Pressure Alarm Delay sec 0-600 Room 1 High Pressure Alarm Delay Value R R R

AV18 Room 2 Low Pressure Alarm Delay sec 0-600 Room 2 Low Pressure Alarm Delay Value R R R

AV19 Room 2 High Pressure Alarm Delay sec 0-600 Room 2 High Pressure Alarm Delay Value R R R

AV20 Room 3 Low Pressure Alarm Delay sec 0-600 Room 3 Low Pressure Alarm Delay Value R R R

AV21 Room 3 High Pressure Alarm Delay sec 0-600 Room 3 High Pressure Alarm Delay Value R R R

MULTISTATE VALUES
Displays the current status of all rooms.
(Value w ill change sign if any room
changes status)
MV1 Status Text 4 States 1 - Normal R R R
2 - Caution
3 - Alarm
Solid Edge

4 - Setback
ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.

© Copyright Antec Controls by PRICE 2019


PMT-1-X
Touchscreen Room Pressure Monitor Sheet 5 of 5

270120
Product Submittal Rev. G
2019/09/12

BACNET POINTS LIST v2.4.0 OR NEWER (CONTINUED)


Write Settings
Object Name Units Range Description
Disabled Standard Open

Indicates w hether the PMT has been


override to a specific mode
1 – No Override
MV2 Status Override Text 5 States 2 – Force Isolation R R W
3 – Force Caution
4 – Force Alarm
5 – Force Setback
Indicates the isolation mode of room
using SRPS1
MV3 Room Isolation Mode 1 Text 2 states R R W
1 - Positive
2 - Negative
Indicates the isolation mode of room
MV4 Room Isolation Mode 2 Text 2 states 1 - Positive R R W
2 - Negative
Indicates the isolation mode of room
MV5 Room Isolation Mode 3 Text 2 states 1 - Positive R R W
2 - Negative
Indicates the reason for any alarm
1 - No Alarm
2 - Netw ork Override
3 - Contact Input
MV6 Alarm Status Text 7 states R R R
4 - Missing Sensor
5 - Room Low Pressure
6 - Room High Pressure
7 - Extended Door Open
Indicates the reason for any caution
that may be present
1 - No Caution
2 - Netw ork Override
MV7 Caution Status Text 7 states 3 - Contact Input R R R
4 - Door Open
5 - Room Low Pressure
6 - Room High Pressure
7 - Missing Sensor
Indicates the state of the alarm
1 - Off
MV8 Audible Alarm Text 3 states R R R
2 - On
3 - Acknow ledged

NOTE: PLEASE REFER TO PMT MANUAL FOR INSTALLATION AND SETUP INSTRUCTIONS.
Solid Edge

SEE PROJECT SUBMITTAL SCHEDULE FOR SELECTED OPTIONS.


ALL METRIC DIMENSIONS ( ) ARE SOFT CONVERTED. IMPERIAL DIMENSIONS ARE CONVERTED TO METRIC AND ROUNDED TO THE NEAREST MILLIMETER.
SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.