You are on page 1of 1

Chapter 2 Installation and Wiring

DANGER!

1. A charge may still remain in the DC bus capacitors with hazardous voltages even if the power
has been turned off. To prevent personal injury, please ensure that the power is turned off and
wait ten minutes for the capacitors to discharge to safe voltage levels before opening the AC
motor drive.
2. Only qualified personnel familiar with AC motor drives is allowed to perform installation, wiring
and commissioning.
3. Make sure that the power is off before doing any wiring to prevent electric shock.

2.1 Basic Wiring Diagram

Users must connect wires according to the following circuit diagram shown below.
Brake Resistor (optional)
Main Circuit Power
NFB AC Motor
R/L1 R/L1 B1 B2
U/T1
S/L2 S/L2
V/T2
IM
T/L3 T/L3
W/T3
3~
SA
Recommended Circuit RB
when power supply MC E
is turned OFF by a ON
RC Grounding
fault output OFF MC
The spec. of main circuit RA Multi-function indication
terminal is M3.0 output contact
Factory default RB
120VAC/250VAC 5A
Forward/Stop
M0 RC
24VDC less than 2.5A
Reverse/Stop Factory default:
M1
indicates malfunction
Reset MO1
M2 Multi-function Photocoupler
Multi-step 1 output contact 48VDC 50mA
M3
Multi-step 2 Factory default: Indicates
M4 MCM during operation
Multi-step 3
M5 VR(1KΩ)
Common signal AFM For adjustment
GND
Master Frequency setting E + Analog output
factory default is VR which is Power for speed setting
- DC 0~10V
on the digital keypad +10V 10mA(MAX) GND Factory default:
3 E
output frequency
Analog voltage RJ-11
0~10VDC VR 2 AVI 1:15V Main circuit (power)
RS-485 terminals
VR:3K~5KΩ series interface 2:GND
1 3:SG-
6←1 Control circuit terminals
Analog current ACI 4:SG+
GND 5:Reserved Shielded leads
E 6:Reserved
NOTE: Do not plug a Modem or telephone line to the RS-485 communication
port, permanent damage may result. Terminal 1& 2 are the power
sources for the optional copy keypad and should not be used while
using RS-485 communication.
* If it is single phase model, please select any of the two input power
terminals in main circuit power.
* Single phase model can be input 3-phase power.

2-2 Revision Aug. 2015, ME16, SW V3.13