㉿ Household plugs and
outlets
KS C 8305:2008

Industryman Circle Bookkeeping Mark Associate


Yuan
Regulation of Korean industry KS

㉿ Household plugs and outlets C 8305:2008

Plugs and socket-outlets for domestic and similar purposes

1. Scope of application This standard applies to plugs and outlets for household and similar purposes, and the scope
of application is in accordance with KS C IEC 60884-1 (1).

2. Citation Standards The standards shown in Schedule 1 form part of this standard by citing in the text, and such
cited standards apply to the latest version thereof.

3. Definition The definitions of the main terms used in this specification are as follows in KS C IEC 60884-1
3.Complies.
a) Hanging type As a type of plugging connector, it is a structure in which a knife and a knife tray are bent to insert a
suitable plug and rotate to the right to prevent the plug from coming off.
b) Room type It is a structure that can be used outdoors in a place where rainwater touches. They
range from unprotected (IPX0) to continuous immersion (IPX8) and are classified by IP code.
c) A ring-shaped nut used for waterproofing of the plug and knife rest connection of the union ring waterproof plug. In
general, it is attached to the plug, has a gasket, and the gasket is screwed and tightened on the male screw installed in
the plug base to make it waterproof.
d) For plugs adapter As a type of plug tray of the plug connector, it is a structure that can be easily used by connecting
plugs and plug holders with different pole placements, and is composed of a knife on the power supply side and a knife
tray on the load side.
e) What has a pilot lamp A pilot lamp is inserted into a part of the plugging connector, which is lit by the voltage of
the converter and lit by the load current that is energing.

4. General Requirements
General requirements are 4 of KS C IEC 60884-1 .Complies.

5. Type, structure dimensions and materials

5.1 The type, number of poles, pole layout and rated types, pole numbers, pole layouts and ratings of splicers
are in accordance with Table 1.

Table 1

Species Number of Pole double(1) Rated Bankruptcy


Ming Ching By Mould poles Outlet (knife Plug (knife)
tray)
plug Unprotected 2 16A 125V 1. a), c) (4)
(2) (2)
Outlets, cords (IPX0)
extension set, Vertical drop
32A 250V 1. b)
Cord-free (IPX1) (2) (2)
plugs Drop (IPX2)
Spray (IPX3) 2 16A 125V 2. a)
Splash (IPX4) (Grounding
Jetting (IPX5) type)
32A 250V 2. d)
Strong
spraying
(IPX6)
Temporary
immersion
(IPX7)
Continuous
immersion
(IPX8)
plug Unprotected 2 16A 250V 5. (c), (d)
Outlets, cords vertical fall, (Side
Grounding
extension set, dropping, type) (5)
Cord-free spraying,
plugs frying,
spraying, 2 16A 250V 5. (e)
(Double
Strong
Grounding
spraying, type)
(5)
Temporary
immersion,
Continuous
immersion

Table 1 (continued)

Species Number of Pole double(1) Rated Bankruptcy


Ming Ching By Mould poles Knife Receiver knife
Stuck plug, Unprotected 2 10A 250V 6. a)
jammed vertical fall, 20A 250V 6. b)
outlet, dropping, 2 10A 250V 7. a)
jammed cord spraying, (Grounding
extension set frying, type)
spraying, 3 20A 250V 7. b)
Strong 20A 480V 7. c)
spraying, 20A 600V
Temporary 32A 480V 7. d)
immersion, 32A 600V
Continuous 3 20A 480V 8. a)
immersion (Grounding 20A 600V
type)
32A 480V 8. b)
32A 600V
Multi-outlet, Unprotected 2 10A 125V 1. a)
Code-free 16A 125V
Multi-outlet 16A 125V 2. a)

16A 250V 5. c), d), e)

Adapter for Unprotected 2 16A 250V 9.


Plug (3)

Note (1) The pole layout of IPX7 and IPX8 types is not prescribed. 2) If it is not necessary to attach the polarity in use, or if it is difficult in
structure, it is not necessary to attach the polarity. ( 3) The pole placement of the adapter for the plug shall be towards the
outlet. 4) In the case of a plug-in with a ground wire
(5) The non-grounding type only allows plugs with a double insulated structure.
Note 1. The types are classified according to the waterproof structure. However, the normal type refers to the one that is
not waterproof.
2. The pole number is always indicated by the pole number of the knife or knife base for the purpose of
electrification, and does not include the pole for grounding.
3. The combination of type, number of poles, and ratings shall be stipulated in Division 1~12
together with the pole layout.4. The pole layout is indicated by the placement of the knife base hole.
5. In two-pole round outlets and plugs, only the grounding type is allowed. However, the plug with a double
insulated structure and the knife tray of the adapter for the plug are excluded.

The type, number of poles, pole placement, and rating of the splicer are non-interchangeable types of codes
(refers to a structure in which the cord cannot be exchanged unless the splicer is destroyed, such as a
single splicer.) The rated current of is according to Table 2 according to the cross-sectional area
(designation) of the attached cord.

Table 2

Cross-sectional area of attachment cord (conductor 0.5 0.75 1.0(7-1) 1.5(7-2) 2.5 4.0
minimum nominal cross-sectional area)
mm2
The rated current of the adapter A 2.5 6(6) 10 16 20 32
6
Note ( ) The flat type shall be 2.5A.
(7-1) In the case of a 10[A] plug, a 0.75㎟ wire can be used.
7-2
( ) In the case of a 16[A] plug, a 1.0㎟ wire can be used.
Note 1. If the allowable current of the attachment cord is In default 1~12 When it is greater than the rated current
of each specified splicer
The rated current of the Edo connector should not exceed the value of default 1~12.
5.2 Structure The general structure should be suitable for:
a) The through holes in the wires or cords should not damage the wires or cords.
b) When connecting the cord, there must be a space for terminal processing of the cord so that the tension of the cord is
not directly applied to the terminal of the terminal, or an appropriate tension relief device is provided.
c) The filling metal part on the back of the surface that may be touched and the exposed type (to be attached to the surface
of the contrast material, etc.) should be at least 3 mm deep on each side, At 70°C Insulating water-resistant admixtures
that do not soften (except sulfur.) However, if the filling metal part on the back has a distance of more than 6 mm of
space and more than 10 mm of creepage surface, it is not necessary to fill the admixture.
d) Outlet of the smoke type (Dishonored 10 reference) and the attachment part of the attachment frame should be a
structure that can firmly attach the outlet.
e) Plug & The cord extension set is It is a size that can be easily inserted and removed by hand and should be non-slip.
f) Ground pole(G.. Ground) or neutron pole(N. Neutral)It is the thing that these poles have a diaphoretic electrode(L.
Live)It should be a structure that connects faster and opens later.
g) The knife base of the plug food multi-outlet should not be directly molded with soft thermoplastic, soft vinyl chloride,
etc.
h) Folded and bent blade [Bankruptcy(1 a), Exhibit 2 a) The front end of the (the side that cannot be inserted into the
knife base) should be molded so that it does not fall out of the aircraft, such as folding and bending into an L-shape.
i) The outgoing wire of the one with an outgoing line instead of a terminal must be a wire or cord that conforms to
the regulations of the K60227 series standard, the K60245 series standard, KS C 3328, etc.
j) The plug [default (1 c)] with ground wire formed at the same time as the cord and the body shall be
suitable for:
1) The ground wire is a structure in which one core of the cord is drawn from the body to a length of 10 cm or more and
a clip is attached to the end.
2) The code shall conform to the provisions of i).
3) The clip should be made of a conductive material, and when attaching the clip, the part that can be touched
should be insulated with a cover made of rubber or an equivalent or higher material.
4) The biting force of the bite part should be more than 2 kg.
k) Removable outlets with a rating of more than 16A or more than 4 holes must have A fuse, circuit breaker or equivalent
overload protection device shall be attached.
l) Products with semiconductor devices should be subjected to EMI (electromagnetic interference) tests according
to the test method of KS C 0262.
m) The cord length of the corded multi-outlet must be greater than or equal to the indicated value.
n) When attaching the mains switch, a switch that cuts off two or more poles should be used.
o) In the case of a two-pole outlet shape without a safety device or shutter, it should be possible to supply an electric shock
protection cap for the outlet.
(Remarks) Electric shock protection cap for outlets A part for the prevention of electric shock that is
inserted into the part of the outlet where the plug is inserted similar to the type of plug so that it does not come into
contact with the outlet knife holder, and is made of insulating resin. In the plug-shaped electric shock protection cap that
is paired with the outlet, the length of the knife and the thickness of the plug body can be arbitrary.
5.3 Section soft insulations shall conform to KS C IEC 60884-1 in addition to the following:
The insulator to which the conductive rod is attached shall be magnetic , KS M 3340, KS M 3341 or similar sturdy,
low-hygroscopic heat-resistant insulation.

5.4 Materials of conductive rods The material of the conductive iron shall conform to KS C IEC 60884-1 in addition
to the following:
a) The material of the conductive iron shall be copper or copper alloy, except as stipulated in b).
b) The material of the spring-acting conductive iron must be phosphorus bronze specified in KS D 5506, brass
specified in KS D 5201, or a rust-resistant metal with spring properties equivalent thereto.

5.5 Shape and dimensions of knives and knife rest holes The shape and dimensions of ordinary knives and knife
base holes are in accordance with the number of poles, pole placement and ratings in accordance with the
number of poles, pole placement and ratings. In addition, the shape of the part that does not specify the dimensions
in the default figures 1~12 shows an example.

5.6 Dimensions of attachments of recessed outlets The dimensions, frame, and cover plate of ordinary recessed
outlets, smoke-type outlets, and round recessed outlets shall be suitable for default 10 and 12, respectively. However, the
dimensions of the attachment part of the apparatus and apparatus used for assembling the apparatus do
not have to comply with default 10 and default 12.
In addition, the dimensions of the smoke-type outlet without an attachment frame should be suitable for default 10
while fixed to the attachment frame.
5.7 Dimensions of wire through holes The dimensions of wire penetration holes of ordinary exposed outlets should
conform to Table 4.

Table 4
Unit:mm
Current rating 16 A or less 20 A 32 A
Wire through hole Single-core 7 8 9
(minimum value) 2 Sim 7.8 9.6 10.9
3 Sim 8.2 9.4 10.5
Note: The dimensions of the 2 and 3 cores are specified based on Table 1 of K60227-4.

5.10 Insulation distances (creepage distance, space distance and insulation distance through insulation)
27 of KS C IEC 60884-1, except as otherwise specified.It should be suitable for.

5.11 Connectors with pole symbols and color-specific polarities shall be marked with symbols or colors in a way
that is clearly visible to the terminals or their parts thereof, as follows:
a) The method of distinguishing by symbols is as follows.
1) Earth, Ground is indicated by the ground symbol or the letter symbols E and G.
2) The pole of the reference potential side (including the multilinear neutral pole N, Neutral.) is denoted by the letter
symbol N or W. However, if it is displayed only on the terminal screw, the terminal screw is processed so that it does
not fall out of the terminal.
b) The method of color distinction is as follows.
1) The terminal screw of the ground pole shall be green. In this case, the symbol according to a) 1) is displayed on the
terminal or its part as well.
2) The pole of the reference potential side (including the multilinear neutral pole N, Neutral.) It should be white or
brown. However, if it is displayed only on the terminal screw, it should be processed so that the terminal screw does
not fall out.
5.12 Hang plug connector The structure, dimensions and materials of the jammed plug connector should conform
to the following in accordance with 5.2~5.11.
a) When the jammed plug is inserted into the jamming outlet and the jamming cord extension set and rotated to the right,
the knife and the knife rest are connected correctly, and the snag structure is made to indicate the direction of rotation.
In addition, the jammed plug should not be easily rotated or pulled out due to the twisting of the cord.
b) Except for integral molding, connecting the cord shall have a cord clip or cord tensioning mechanism so that the tension
of the cord is not applied to the terminals and the connection of the cord.
c) The jammed plug and jammed cord extension set should be shaped to be easy to hold when inserting and retracting.
d) The shape and dimensions of the knife and the knife base hole are in accordance with Division 6~8.

5.13 Waterproofing Plug Splicer The structure, dimensions and materials of the waterproof plug splicing machine, in
addition to conforming to 5.2~5.11, shall be subject to the following and 16 of KS C IEC 60884-1.It should be
suitable for.
a) IPX1 and IPX2 are subject to:
1) Under normal use, it should be a structure that does not allow water to easily enter the inside of the apparatus from the
opening part such as wires, cord inlets, attachment holes, and other outskirts.
2) The outlet should be a structure that does not allow water to easily enter from the knife tray hole in a lid or other
suitable way without plugging.
3) As an exposed outlet, if there is a charging metal part on the attachment surface, the surface of the
part should be at least 4 mm from the attachment surface of the outlet, and the charging metal part
should be lowered at least 3 mm from that side, and insulating admixtures with low hygroscopicity (sulfur are excluded)
thereof. Fill it so that it does not fall out easily.
4) The shape and dimensions of the knife and the knife rest hole shall be in accordance with 5.5 and 5.12 d).
b) IPX7 and IPX8 shall conform to:
1) Under normal use, the structure should not allow water to penetrate into the inside of the device.
2) Union ring so that the plug does not fall out due to tension applied to the cord while the plug is inserted, and it
must be a structure that can prevent it from falling out in a suitable way.
3) The outlet and cord extension set must be designed so that water does not seep through the knife tray hole without
plugging.
4) The plug and cord extension set should have a cord clip so that the tension applied to the cord is not applied to the
connection of the cord and the terminal.
5) IPX7 and IPX8 include IPX0, IPX1, IPX3 and jam type (as specified in default.) It should be a structure that cannot
be plugged in.
c) The lid and union ring used for waterproofing should be connected to the splicer in a suitable way, such as a chain, so
that they do not lose it.
d) The metal material used for the part that is discolored by rainwater must be strong and does not rust or rust-
resistant steel, except that the spring material must be phosphorus bronze or stainless steel as specified in KS D 5506.
e) The material used for the gasket must not deteriorate easily, such as synthetic rubber.

6. General Notes on Testing 5 of KS C IEC 60884-1 .Complies.

7. Classification classification is defined in KS C IEC 60884-1 7.Complies.

8. Indication indications are 8 of KS C IEC 60884-1.and the following:


The naming method of the product The naming method of the product depends on the type, number of poles and
rating.
See 1. Plug Grounding Type 2-Pole 16A 125V
See 2. Plug polarity 2 pole 16A 125V
See 3. Plug 2 pole 16A 250V
See 4. Exposed outlet 3 pole 20A 250V
See 5. Recessed Outlet 2 Pole 20A 250V
See 6. Hang Plug 3 Pole 20A 480V
See 7. Hang Exposed Outlet 3 Pole 20A 600V
See 8. Round Side Ground Pole 2-pole outlet 16A 250V
See 9. Round Side Ground Pole 2-pole plug 16A 250V
See 10. Flat double insulated plug 2.5A 250V
See 11. IPX2 type outlet 2 pole 32A 250V
See 12. IPX3 Type Hanging Outlet 3 Pole 20A 250V
See 13. IPX7 type plug 2 pole 20A 250V
See 14. IPX8 Type Cord Extension Set 32A 250V
See 15. Cordless Plug 2 Pole 16A 250V

9 Dimensional inspection The dimensional inspection is 9 of KS C IEC 60884-1 .Complies.


10 Protection against electric shock Protection against electric shock is defined in KS C IEC 60884-1 of
10.Complies.
11 Grounding Regulations The Grounding Regulations are set forth in KS C IEC 60884-1 11.Complies.
12 terminals and permanent fixed terminals The terminals and permanent terminals are specified in 고정형KS
C IEC 60884-1 in addition to the following: 12.Complies.
The cross-sectional area (designation) of the terminal screw shall be greater than or equal to the value in
Table 3 depending on the rated current, but the terminal screw which is the ground pole shall be M 4 or more (M 3.5 or
more for the rated current of 16 A or less).

Table 3
Rated Current A 6 or less 10, 16 20 32 50
8 8
The name of the If it is a wind-up screw terminal M 3.5( ) M 4( ) M4 M 4.5 M5
terminal screw When it is a terminal of other tightening M3 M 3.5 M4 M 4.5 M5
(minimum value) method
8
Note ( ) In attaching only the code, M 3 is good for 6 A or less, M 3 for 10 A and 16 A.

e) Terminal screws should not be used for attachment of parts, but this is not limited to cases where there is no risk of
loosening the attachment of parts when the attachment of wires and cords is removed.
f) The rating of the screwless terminal mechanism should be 20A or less.
g) The cord or cable used for integral molding shall comply with the regulations of the K60227 series standard, the
K60245 series standard, KS C 3328, etc. However, the cord used for the plug whose pole shape is pin-type should
use a cord insulated with an insulator and a sheath.
h) The terminal should be a structure capable of connecting a wire (at least 1.5 mm2) (1.78 mm  solid wire or 2.5
. (8-2
mm2 stranded wire) (8-2) corresponding to the mechanism rating Note ) See Table 2, Table 3

13 Fixed outlet structure 고정형 The outlet structure is 13 of KS C IEC 60884-1.Complies.


14 Plug and removable outlet structure Plug and outlet structure 이동형 is 14 of KS C IEC 60884-1.Complies.
15 Interlock outlet Interlock outlets are 15 of KS C IEC 60884-1 .Complies.
16 Aging resistance, protection and moisture resistance by enclosure Aging resistance, protection and
moisture resistance by enclosure are defined in KS C IEC 60884-1 16.Complies.
17 Insulation resistance and dielectric strength Insulation resistance and dielectric strength are specified in
KS C IEC 60884-1 17.Complies.
18 Operation of the ground pole The operation of the ground pole is defined in KS C IEC 60884-1 18.Complies.
19 Temperature rise Temperature rise is defined as 19 of KS C IEC 60884-1.Complies.
20 Opening and closing capacity The opening and closing capacity is 20 of KS C IEC 60884-1 .Complies.
21 Normal Operation Normal operation is 21 of KS C IEC 60884-1.Complies.
22 The force required to remove the plug is 22 of KS C IEC 60884-1.Complies.
23 Flexible cables and their connections Flexible cables and their connections are described in KS C IEC 60884-
1 23.Complies.
24 Mechanical strength Mechanical strength is 24 of KS C IEC 60884-1.Complies.
25 Heat resistance Heat resistance is 25 of KS C IEC 60884-1.Complies.
26 Screws, energing parts and connections Screws, sieging parts and connections are part of KS C IEC
60884-1 26. Complies.
27 Creepage, spatial distance, and distance through encapsulated compounds Creepage, spatial distance and
encapsulated compound are specified in KS C IEC 60884-1 27.Complies.
28 Overheating, fireproofing, and tracking resistance of insulating materials Overheat, fire resistance and tracking
resistance of insulating materials are specified in KS C IEC 60884-1 28.Complies.
29 Corrosion resistance Corrosion resistance is 29 of KS C IEC 60884-1 .Complies.
30 Additional tests of insulating sleeve-mounted pins Additional tests of insulating sleeve-mounted pins
are performed in KS C IEC 60884-1 in 30. Complies.
Note 1. The temperature rise, opening and closing capacity, normal operation, and the force required to remove the
plug are connected to each other and can be tested as a product with dimensions suitable for default drawings.
2. If there is no test content suitable for the test product in the KS C IEC 60884-1 standard, the item test is
treated as "not applicable".

Displaced 1 2-pole outlet and plug


a) 16A 125V
Unit:mm
Knife (plug) Knife hole (outlet)

(9)
(9)

(10)

Cross-section of the knife base


hole
11.7±0.4

11.7±0.4
The sword base (the
You may omit it.)
protrusion is

Knife tip enlargement


(In the case of a one-piece knife) (In the case of a folded and bent knife)(11)

week(9) When the polarity is not attached, it is made 6.3±0.3 mm of the blade butterfly, and 7±0.3 mm of the
butterfly of the knife base hole. The plucking of the knife hole is done on both sides.
(10) Some of the manufacturing difficulties may be omitted regarding the removal of the insertion hole.
(11) The thickness of the folded and bent knife should be 0.6 mm or more, and ribs may be attached. However, the thickness of
the finished product should be 1.5±0.1mm, and the rated current should be 6A or less.
Note 1. W in the figure represents the pole (or neutral) of the reference potential side (the same as in the default below).
2. The dimension without tolerance represents the standard dimension (the same is also the case in the
default below).
Displacement 1 2-pole outlet and plug (continued)
b) 32A
b) 250V
50A
Unit:mm
Knife (plug) Knife hole (outlet)
(12)

Cross-section of the knife


base hole

Knife base (protrusion may be

omitted.)

Note (12) When the polarity is not attached, the calendula is 12.5±0.2 mm.
Minor 1 2-pole plug (continued)
c) Plug with ground wire
16A 125V
Unit:mm
12.7

1.5±0.15

11.7±0.4
17±1 10.8 or later

14.6 and

below

Knife tip enlargement

0.9 or less

+0.3
 3.5 or later  3 -0.2
Dishonored 2 grounded two-pole plug and outlet
a) 16A 125V

Unit:mm
Knife (plug) Knife hole (outlet)

2.2±0.3

Herein
6.05

after
5.4±0.2

Cross-section of the knife


base hole

5 or more
Knife base (protrusion may be omitted.)

Knife tip enlargement


(In the case of a one-piece knife) (For a folded knife)(14)

(13)

+0.3 +0.3
 3 -0.2  3 -0.2

Note (13) The cutting of the knife base hole may be done on both sides.
(14) The thickness of the folded and bent knife should be 0.6 mm or more, and ribs may be attached. However, the thickness of the
finished product should be 15±0.1 mm, and the rated current should be 6A or less.
Note 1. G in the figure represents the ground pole (the same as in the following default).
2. The ground pole may be a round pin [ Diagram 2 b), c), d) ].
Dishonored 2 grounded two-pole plug and outlet (continued)
b) 20A 125V

Unit:mm
Knife (plug) Knife hole (outlet)

Cross-section of the knife


base hole

5 or more

(You don't have to make a knife protrusion.)

Knife tip enlargement

+0.3
 3 -0.2

(The hole in the knife may be omitted) [ Vice 2 c), d) ]


Dishonored 2 grounded two-pole plug and outlet (continued)
c) 20A 250V
Unit:mm
Knife (plug) Knife hole (outlet)

Hereinaf

ter

nafter
Herei
Cross-section of the knife
 3.5 or later base hole
+0.3
 3 -0.2
Dishonored 2 grounded two-pole plug and outlet (continued)
32A
d) 250V
Unit:mm
Knife (plug) Knife hole (outlet)

Cross-section of the knife


base hole
Dishonored 3 3-pole plug and outlet

250V
Knife (plug) Knife hole (outlet)

Cross-section of the knife base


hole (ga-na-da)

(15)
Knife base (protrusion may be

omitted.)

Note (15) The H of the three poles is the same.

Dimensions of the knife


Unit:mm
Rated Current A a b c and h h d
16 8±0.15 10±0.15 6±0.15 1.4±0.1 17 20 0.9 or less
20 9.5±0.15 11±0.2 8±0.15 2±0.1 20 23 1.4 or less
32 13.5±0.2 13.5±0.2 12.5±0.2 2.6±0.1 30 33 2.0 and
50 below

Dimensions of the knife base hole


Unit:mm
Rated Current A A B C And H
16 8±0.15 10±0.15 7.5 2.5 5 or more
20 9.5±0.15 11±0.2 9.5 3 6 or more
32 13.5±0.2 13.5±0.2 14 4.5 9 or more
50
Budo 4 3-pole plug and outlet (grounding type)
250V
Knife (plug) Knife hole (outlet)

Cross-section of the knife


base hole

(16)
Knife base (protrusion may be

omitted.)
Note (16) The K of the four poles is the same.

Tooth count
Unit:mm
Rated Current A B C D And F G H I K L
A
16 15±0.2 11±0.15 7.5±0.15 6±0.15 1.4±0.1 20 17 7 2.5 5 or more 0.9 or
less
20 20.6±0.2 9.5±0.15 10.3± 8±0.15 2±0.1 23 20 9 3 6 or more 1.4 or
0.15 less
32 35±0.2 17.5± 17.5± 12.5±0.2 2.6±0.1 33 30 13.5 4.5 9 or more 2.0 and
0.15 0.15 below
Budo 5 Round Plug
a) 2.5A 250V 2-pole plug
Unit:mm

A:Pin insulation required only for flat plugs


B:Gold pins
17
Note ( ) Within 18 mm of the plug contact surface, this dimension should not be exceeded.
Note 1. The shape represents an example.
2. When there is an end to it, do the brushing.
3. The tip of the pin should be conical or round, as shown in the enlarged figure.
Vice 5 round plug (continued)
b) 16A 250V 2 pole plug
Unit:mm

(18)
Pin tip
enlargement

※ The diagonal part is the part that can be changed


A:Pin insulation
B:Gold pins
) Within 18 mm of the plug contact surface, this dimension should not be exceeded.
Note (18
Note 1. The shape represents an example.
2. When there is an end to it, do the brushing.
3. The tip of the pin should be conical or round, as shown in the enlarged figure.
4. When the plug contact surface is of maximum dimension (including diagonal part), there is no need for
insulation on the plug pin.
5. In the case of a shape with a thickness of more than 6 [mm] on the bottom of the plug contact
that touches the outlet surface, either side of the plug
The side ridge thickness should be at least 6 [mm]. (Hereinafter It's the same in bankruptcy.)
Budo 5 Round Outlet (continued)
c) 16A 250V two-pole outlet (side ground pole)

Unit:mm

(19)

(20)
ideal

(21)
(24)

The outside should be removed.


or(22)
or

Part K Details
later
less
4.2
4.8

(23)

(21)

4.8 or later

A:Recessed outlet
B: 3.5~5.1mm elastic knife base (the shape does not have to be cylindrical.)
C:Exposed outlet F:Safety device or shutter
Note (19) Tolerance for molding +0.3 mm Tolerance for porcelain or rubber products +0.5 mm
(20) The length of the cylindrical part of the plug pin inlet (including the safety device part)
(21) Applies only to single-prong exposed outlets.
(22) The distance between the center line of the contact tube and the center line of the fixing hole should not exceed 1 mm. However, it can be arranged so that
the center line of the contact tube is perpendicular to the fixing hole.
(23) This figure should be applied to the gap of the ground terminal without plugging and should be able to be elastically
opened up to at least 33 mm.
24) When it is a
( recessed outlet, a portable outlet, or a multi-outlet, it is not necessary to put a connection groove.
Note 1. The depth dimension of the plug into the outlet, which is 17.5 [mm], is the cover lid of a standard
recessed outlet.
plate) may be a dimension that includes the thickness.

Vice 5 round plug (continued)


d) 16A 250V 2-pole plug (side ground pole)

Unit:mm

(25)

Note (25) Within 18 mm of the plug contact surface, this dimension should not be exceeded.
Note 1. The shape represents an example.
2. The pin tip should be conical or rounded as shown in the enlarged figure.
Vice 5 round plug (continued)
e) 16A 250V 2-pole plug (double ground pole)
Unit:mm

(26)

Pin tip enlargement

A: 4.3~5.1mm elastic knife base (the shape does not need to be cylindrical)
26 Within
Note 18 mm of the plug contact surface, this dimension should not be exceeded.
Note 1. The shape represents an example.
2. The pin tip should be conical or rounded as shown in the enlarged figure.
Budo 6 2-pole jammed plug and outlet
a) 10A 250V

Unit:mm

knife base hole

Note (27) The one without polarity is 7±0.15 mm.

Cross-section of the knife base hole

kn The knife of the reference potential side


ife pole when indicating polarity
Budo 6 Two-pole jammed plug and outlet (continued)
b) 20A 250V
Unit:mm
knife base hole

Cross-section of the
knife base hole

Note (28) The one without polarity is 11.7±0.15 mm.

The knife of the reference potential side pole when


exhibiting knife polarity
Displacement 7 Two-pole jammed plug and outlet (grounding type)
a) 10A 250V

Unit:mm

knife base hole

The central position of the

knife hole The central position of the

protuberance of the sword base The central position of the

protuberance of the sword base

The central position of the


The central position of the knife
The central position of the knife
protuberance of the sword base
hole base hole

Cross-section of the knife


base hole

Code Clips
Knife base thickness 0.5 or more

Knives of voltage pole Knives of ground pole (G)


Gently plunge outwards.
Budo 7 3-pole jammed plug and outlet (continued)
b) 20A 250V

Unit:mm

knife base hole

The central position of the


The central position of the
The center of the knife
knife hole
knife protuberance

The central position of the


Knife hole
The central
protuberance position
of the of the
sword base
Central location
The central position of the knife protuberance of the sword base

hole

Cross-section of the knife


base hole

Knife base thickness 0.8 or more


The location of the protrusion
Code Clips

Knives of the voltage pole Knives of the reference potential side pole (W)

Gently plunge outwards.


Budo 7 3-pole jammed plug and outlet (continued)
c) 20A 480V~20A 600V
Plagh Unit:mm

Outlet stall location


The central position of the knife
hole

 3.0 (Gather outwards.)

Concents

Cross-section of the

Knife stop position Knife base center position


Budo 7 3-pole jammed plug and outlet (continued)
d) 32A 480V~32A 600V
Unit:mm
Plagh

Outlet stall location The central position of the knife

hole

Gather outwards.

Concents
Cross-section of the
knife base hole

Knife stop position


Knife base center position
Displacement 8 3-pole jammed plug and outlet (grounding type)
a) 20A 480V~20A 600V
Unit:mm
Plagh

 3.0 (Gather outwards.)

Concents

Cross-section of the knife


base hole

The location of the

protrusion

Knife stop position


Displacement 8 3-pole jammed plug and outlet (grounding type) (continued)
b) 32A 480V~32A 600V
Plagh Unit:mm

Outlet stall location

The central position of the knife

hole

Gather outwards.

Concents

Cross-section of the
knife base hole

Knife stop position Knife base center position


Adapter for default 9 plug
16A 250V

Unit:mm

Knife Hole

(30)

Knife base (shape represents view.)

knife
(29)

Knife tip enlargement

Note (29) When the polarity is not attached, the knife butterfly is set to 6.3±0.3mm.
(30) Tolerance of molded products +0.3 mm, tolerance of magnetic or rubber materials +0.5 mm
Note 1. The appearance of the plug adapter may be in the form of a flat plug.
Dimensions of the default 10 smoke-type outlet
For one switch box
(The shape represents the view.) Unit:mm
a) For oval square
bosses

(38)

Note (38) One outlet may be attached to 60.5±0.4mm.


Note 1. The shape of the boss, including two or three of the same dimensions
(Hereinafter shown in this figure.)
2. If the attachment frame and plate are integrated and prefabricated, the dimensions of the screws do not apply.

b) For diagonal bosses


Unit:mm

Note: If the attachment frame and the plate are integrated and assembled, the dimensions of the screws do not
apply.
Dimensions of the default 10 smoke-type outlet (continued)
For small switch boxes
(The shape represents the view.)

Unit:mm

The shape and dimensions of the outlet boss


In the case of an oval In the case of an angular In the case of a diagonal

If it is diagonal (for 3 holes)


Default 11 Code Protector Bending Test Device

Fixed parts

Test Articles

movable plate

The center of the

movable plate

Shake stop

pendulum
a) Home

Unit:mm
The outer diameter of the d 3 3.5 4 4.5 5 6
screw (designation)
The diameter of the head D 6.5±0.3 7.5±0.3 8.5±0.3 10.5±0.5 11.5±0.5 13.0±0.5
The height of the head H 1.6 2.0 2.4 3.0 3.6 3.7
Butterflies in the groove a 0.8 1.0 1.0 1.2 1.2 1.2
The depth of the groove b 0.8 1.0 1.2 1.6 2.0 2.0
The length of the head L 4, 5, 6 5, 6, 7 6, 7, 8 8, 9, 10 8, 10, 12 11, 12, 13
The pitch of the screw P 0.5 0.6 0.7 0.75 0.8 1.0
Remarks and screws comply with KS B 0211.

b) Slotted + hole

Unit:mm

The outer diameter of the d 3 3.5 4 4.5 5 6


screw (designation)
The diameter of the head D 6.5±0.3 7.5±0.3 8.5±0.3 10.5±0.5 11.5±0.5 13.0±0.5
The height of the head H 1.9 2.2 2.5 3.0 3.6 3.7
Butterflies in the groove a 0.8 1.0 1.0 1.2 1.2 1.2
The depth of the groove b 0.8 1.0 1.2 1.6 2.0 2.0
1
Number of +Hole ( ) 2 2 2 2 2 3
The length of the + shaped M 3.6 3.9 4.2 4.6 4.9 6.2
hole (maximum)
+Depth of the hole (2) Q 1.01~1.53 1.30~1.83 1.60~2.13 1.99~2.53 2.29~2.83 2.31~2.86
The length of the head L 4, 5, 6 5, 6, 7 6, 7, 8 8, 9, 10 8, 10, 12 11, 12, 13
The pitch of the screw P 0.5 0.6 0.7 0.75 0.8 1.0
Note ( ) The number of the + hole is in accordance with KS B 3009.
1

(2) Q indicates the gauge depth of the +-shaped hole.


Remarks and screws comply with KS B 0211.
Note Figure 1 Binding Small Screw

Unit:mm
The outer diameter of the d 3.5 4 4.5 5 6
screw (designation)
Diameter of the head (bottom) B1 7.2 8.5 9.9 11.2 12.7
Diameter of the head (phase) B2 6.4 7.5 8.7 9.8 11.1
Maximum diameter of the head C1 7.5±0.3 8.8±0.3 10.2±0.3 11.5±0.3 13.0±0.3
(bottom)
Maximum diameter of the head C2 7.2 8.5 9.9 11.2 12.7
(phase)
The height of the head H 2.0 2.4 3.0 3.6 3.7
Butterflies in the groove a 1.0 1.0 1.2 1.2 1.2
The depth of the groove b 1.0 1.2 1.6 2.0 2.0
The length of the head L 5, 6, 7 6, 7, 8 8, 9, 10 8, 10, 12 11, 12, 13
The pitch of the screw P 0.6 0.7 0.75 0.8 1.0
Note 1. The head is colored green.
2. The direction of the groove is arbitrary.
3. The screws comply with KS B 0211.

Note Figure 2 Grooved small screws (for ground terminals)


Unit:mm
The outer diameter of the d 3.5 4 4.5 5 6
screw (designation)
Cross distance (bottom) B1 7.2 8.5 9.9 11.2 12.7
Opposite distance (top) B2 6.4 7.5 8.7 9.8 11.1
Maximum diameter of the head C1 7.5±0.3 8.8±0.3 10.2±0.3 10.2±0.3 13.0±0.3
(bottom)
Maximum diameter of the head C2 7.2 8.5 9.9 11.2 12.7
(phase)
The height of the head H 2.2 2.5 3.0 3.6 3.7
Butterflies in the groove a 1.0 1.0 1.2 1.2 1.2
The depth of the groove b 1.0 1.2 1.6 2.0 2.0
3
Number of +Hole ( ) 2 2 2 2 3
The length of the + shaped hole M 3.9 4.2 4.6 4.9 6.2
(maximum)
+Depth of the hole (4) Q 1.30~1.83 1.60~2.13 1.99~2.53 2.29~2.83 2.31~2.86
The length of the head L 5, 6, 7 6, 7, 8 8, 9, 10 8, 10, 12 11, 12, 13
The pitch of the screw P 0.6 0.7 0.75 0.8 1.0
Note ( ) The number of the + hole is in accordance with KS B 3009.
3

(4) Q indicates the gauge depth of the +-shaped hole.


Note 1. The head is colored green.
2. The direction of the groove is arbitrary.
3. The screws comply with KS B 0211.

Note Figure 2 Grooved small screws (for ground terminals) (continued)


Budo 12 round recessed outlet
a) For 1 hole

Unit:mm

b) For 2
holes

Note 1. The position of the pinrest hole is arbitrary.


2. A dotted line that is not a solid line can be made in any form.
Buoy 1 Citation Standard

KS C IEC 60050-151 : International electrotechnical terminology – Part 151. Electrical and magnetic
devices
IEC 60050-442: International electrotechnical terminology – Part 442. Electrical splices
IEC 60050-826: International electrotechnical terminology – Part 826. Electrical installations
IEC 60068-2-30: Environmental test methods - Part 2, Test DBs and Guidelines: Temperature and
humidity cycles
IEC 60068-2-32: Environmental test methods - Part 2,, Test ed: Free fall
KS C IEC 60112 : Test method for comparative tracking index and internal tracking index of solid
electrical insulating materials under wet conditions
IEC 60212 : Standard conditions for use before and during tests for solid electrical insulating materials
IEC 60228: Conductors in insulated cables
KS C 3328 : 450/750V heat-resistant vinyl insulated wire (HIV)
K 60227-1, -4, -5, -7 : Polyvinyl chloride insulated cable with rated voltage of 450/750V or less
KS C IEC 60227-2 : Vinyl chloride insulated cables with rated voltage 450/750V or less - Part 2: Test
method
KS C IEC 60227-3 : Vinyl chloride insulated cables with rated voltage of 450/750V or less - Part 3:
Insulated wires for wiring
KS C IEC 60227-6 : Vinyl chloride insulated cables with rated voltage 450/750 V or less - Part 4: Vinyl
lift cables
K 60245-1, -2, -3, -6, -8 : rubber-insulated cables with rated voltages of 450/750 V or less
KS C IEC 60245-4 : Rubber insulated cables with rated voltage of 450/750V or less - Part 4: Cords
and flexible cables
KS C IEC 60245-5 : Rubber insulated cables with rated voltage of 450/750 V or less - Part 5: Lift
cables
KS C IEC 60245-7 : Rubber insulated cables with rated voltage 450/750V or less
- Part 7: Heat-resistant ethylene vinyl acetape rubber insulated cable
KS C 0262: Electrical magnetic compatibility (EMC) - Measurement general
IEC 60364-5-52: Electrical installations in buildings – Part 5-52: Wiring systems
IEC 60364-5-54: Electrical installations in construction – Part 5-54: Grounding and protective
conductors
IEC 60417: Graph symbols for instruments
IEC 60423 : Wire conductor pipe systems – Outer diameter of conductor pipes for electrical installations
and threads for conductor pipes and fittings
KS C IEC 60529 : Classification of enclosures on the perimeter (IP code)
IEC 60695-2-10 : Fire hazard testing - General test procedures for glow wire devices
IEC 60695-2-11 : Fire hazard testing - Flammability test of glow wire in final results
IEC 60670-1 : Accessaries for fixed wiring for household and similar applications
General requirements for boxes and enclosures
IEC 60719 : For circular copper conductor cables with rated voltages of 450/750 V or less
Calculating the upper and lower limits of the average outer diameter dimension
KS C 8111: Test methods for wiring fixtures
KS C IEC 60884-1, -2-1, -2-2, -2-3, -2-5, -2-6 : Plugs and outlets for household and similar
applications
KS C IEC 60999-1 : Connection mechanisms - Safety requirements for threaded and plugged-in wire
connectors for copper wires
IEC 61032 : Protection of human body and equipment by enclosures - Verification probes
IEC 61140 : Protection against electric shock - General for installations and equipment
ISO 1456 : Metal plating - Electroplating of copper+nickel+chromium and nickel+chromium
ISO 2039-2 : Plastics - Determination of hardness - Part 2 : Rockwell hardness
ISO 2081: Metal plating, galvanizing iron or steel
ISO 2093: Specification and test methods for metal plating, tin electroplating
KS B 0211: Allowable limits dimensions and tolerances of metric ordinary screws
KS B 3009: Ruler screwdriver
KS D 5201: Plates and bands of copper and copper alloys
KS D 5506: Phosphorus bronze and white plates and strips
KS D 8304: Electro-galvanized
KS M 3340: Phenolic resin molding materials
KS M 3341: Urea resin molding materials
Commentary

This explanation is an explanation of the matters specified in the text and subsection and related
matters, and is not part of the standard.

1. Outline
1.1 Purpose of the amendment

In July 2000, the type approval system under the type approval system for electrical appliances was
changed to the safety certification system for electrical appliances. As a result, the contents of the
related test standards have also been changed from the technical standards for electrical appliances
used in Japan ("former" standards for type approval) to the safety standards for electrical appliances
("K" standards for safety certification), which are translations of the IEC standard, which is an
international standard.

As the Harmonization period for using the "former" standard, which is a type approval standard, and
the K standard, which is a translation of the IEC standard, which is an international standard, ended in
June 2004, there were cases where only the K standard was used as a safety certification standard for
electrical appliances. In addition, it became necessary to change the KS standard, which is a test
standard used when selectively acquiring the KS standard a few months after obtaining the safety
certification, to the contents of the international standard.

In response to these demands, the KS standard related to the safety certification of electrical appliances
has been revised.

1.2 How the 2008 amendment was made

In 2007, following the standardization project in the field of wiring equipment, KS C 8305 standard was
also revised by adopting the numbering system and contents of KSCIEC60884-1 in cooperation with
related organizations after surveys, public hearings, and identification of related standards by the
manufacturer.

2. Major revisions
2.1 Classification of product ratings

The contents of 50A, which are classified as industrial use, were deleted, and the types that are not

produced and defaulted were deleted.

The rating expressions used in the type approval standard were 3A, 7A, 10A, 12A, 15A, 20A, and 30A,
but in the KS standard, which is revised according to the contents of the safety certification standard,
the rating expression was changed to 2.5A, 6A, 10A, 16A, 20A, 32A, and 50A

2.2 Nominal cross-sectional area of the wire used

The nominal cross-sectional area of the wire used in the type approval standard was 0.5 ㎟, 0.75 ㎟,
1.0 ㎟, 1.25 ㎟, 1.5 ㎟, 2.0 ㎟, and 3.5 ㎟, but in the KS standard, which is revised according to the
contents of the safety certification standard, the nominal cross-sectional area expression of the wire
was changed to 0.5 ㎟, 0.75 ㎟, 1.0 ㎟, 1.5 ㎟, 2.5 ㎟, and 4.0 ㎟

2.3 Definition and main content of terms

The expression of the terms used in the type approval standard has been changed to the same as the
K standard, which translates the terms used in the IEC standard in the KS standard, which is revised
according to the contents of the safety certification standard. For example, "corded plug plug" has
been changed to "cordless plug".
A new term was also enacted, such as the term "shutter" was coined in parallel with the "safety device"
of the outlet.
The main content correction omitted those that overlapped with those in the IEC standard, such as
structural insulators and markings.

2.4 Representation of waterproof class

The grade expression of waterproof products was divided only in Korean, but the same symbol notation
was used as the method expressed in the IEC standard. In other words, the product waterproof grade
indication such as "rainproof type" was changed to an expression such as "vertical drop (IPX1)" or
"spraying (IPX5)", clarifying the division of the waterproof grade mark.
2.5 Establishment of outlet and plug geometric dimensions

In response to the needs of increasing the capacity of household electrical equipment such as air
conditioners, "Budo 2-d: Two-pole outlet and plug for grounding (for 32A/50A 250VAC)" was newly
enacted.

2.6 Description of power polarity

In the default indicating the shape and dimensions of outlets and plugs, English characters were added
to the power polarity representation and modified to the power pole (L, Live), neutral pole (reference
potential pole, N, W, Neutral), and ground pole (E, Earth, Ground) so that understanding and
interpretation are clear.
2.7 Supplementing the explanation of the default

The explanation of the budo indicating the shape and dimensions of the outlet and plug was added or
supplemented explanatorily to make the understanding and interpretation clear, the recessed outlet that
had not been produced for many years was deleted, the horizontal length limit of the round recessed
outlet was removed, and the outer height of the outlet of the round outlet of the round outlet of the part
5 was changed from 8.5 to 8.0, which is the same as the foreign standard.

2.8 Display of the rated voltage of the product

In the rated voltage display method of the product, the symbol of the power supply type (AC indication
is "~" or "AC") is displayed to be the same as the safety certification standard.

2.9 Standards Cited

The contents of the standards cited in this KS C 8305 standard have been modified to the contents
of the standards currently published and used.

㉿ KS C 8305:2008
KSKSKS
SKSKS
KSKS
Credits
KSKS
SKSKS
KSKSKS
Plugs and socket-outlets for
domestic and similar purposes
ICS 29.120.30

Enacter: Director of Technology and Established: December 31, 1962


Standards Technical Standards Agency Notice No. 02-1853
Release: December 31, 2007
Collaborators on drafting the original draft: Electrical Division of the Industrial Standards Council