Solutions for Maintenance and Operation of

Photovoltaic Power Station

Uni-Trend Technology (China) Co., Ltd.


(Stock Code: 688628)
Contents

 Structure of Photovoltaic Power Station

 The Application of Meters in Photovoltaic Power


政策背景

Structure of Photovoltaic Power Station


Structure of Concentrated Photovoltaic Power Station
Structure of Decentralized Solar Power Plant
政策背景

The Applications of Meters in


Photovoltaic Power
Solutions of Photovoltaic Power
Remote diagnosis and
analysis
Station operation
On-line O&M

statistics
Failure warning and
Service System of O&M of Decentralized PV Power Station

locating
Equipment operation
O&M service

monitoring
The service system ensures safe and reliable operation of photovoltaic power station for a long term.

Operational
O&M (Operation & Maintenance) service system

clearing
Special
Off-line O&M

inspection
Deficiency
elimination
Routine inspection
Station data
Management system
management
O&M documents
O&M management output
Routine management
system

O&M management
Platform team
Technology team
O&M team
政策背景

Solar Array Detection


FAQ: Hot Spots

1. What problems usually occur with components/strings:


Hot spots, array aging, etc.

2. Causes:
Array cracking or fissuring; poor soldering; shading, acid rain, droppings, or dust on array
surface; ambient or air pollution, etc.

3. Effects:
Affect output power, lifespan, generating efficiency, or even pose safety risk.

4. Reason for using IR thermal imaginer to detect hot spot: Hot spot on array
It’s difficult to identify hot spot through eye, clear shading or dark spot can be
identified fast using IR thermal imaginer.

5. Identification standard:
The temperature of the array should be roughly uniform with no obvious temperature
difference. If the local temperature is 6.5°C higher than the adjacent temperature, it is
considered a hot spot.

Normal array
Detect hot spot
5. Troubleshooting process:
Scan arrays/strings by using UAV thermal imaginer, if hot spots are found, please detect local area using handheld thermal
imaginer.

Advantages of UTi740H thermal imager: Manual focus, 4.3’’ display screen, 384x288 IR resolution, clear imaging, easy
operation and visible temperature variation facilitate identifying hot spot accurately, leading to maintenance in time and
improving generating efficiency.

 Manual focus: Identify hot spot clearly and intuitively.


 Auto-tracking for high temperature: Identify highest temperature spot rapidly
for evaluation and analysis.
 Manual Isotherm: User-defined temperature display for visibly locating area
with abnormal temperature.
 App: Generate report as reliable data for maintenance evaluation.

 Low price  Clear imaging

 Unclear
imaging  High price

Recommended model: UTi740H


UTi712S UTi640D
FAQ: Grounding issue
1. Issue:
Increased resistance or open circuit caused by poor contact of grounding
wire between arrays.
The array mounting is not grounded well: Earth resistance is greater than 4Ω.

2. Causes:
Under the effect of soil corrosion, moisture content, salt content and high
temperature, the grounding installation is corroded (this causes crack,
loosening, and deteriorated soldering) or is exposed after raining, thus
leading to increased earth resistance and open circuit.

3. Effects:
Solar arrays/strings are mainly installed in open areas, fields, hillsides and
other places with poor grounding. Lightning during thunderstorms directly
or indirectly hits the solar battery panels, which may cause the grounding
device to catch fire or other safety accidents, affecting solar energy. The
overall operating efficiency of the power plant.

4. Earth resistance standard:


The lightning-proof earth resistance of solar array shall be less than 4Ω
(the lower the better). Poor grounding
The conduction resistance (conductivity) shall be not greater than 0.4Ω.
Grounding detection

Advantages: The UT278D grounding clamp meter has functions such as clamp grounding
resistance measurement, 3-wire or 4-wire measurement, and voltage/current  Single-clamp
measurement. It can realize flexible application on multiple occasions, help operation and measurement
maintenance inspectors to judge whether the grounding resistance meets the
requirements, and carry out maintenance and rectification according to the test results, so
 Without
as to protect the normal operation of the power station. grounding-pole
measurement
UT273+
Recommended model: UT278D

 Earth resistance measurement


 2/3/4-wire earth
 Leakage current measurement resistance
measurements
 Soil resistivity measurement  Not easy to carry

 PC software analysis
UT572
FAQ: Insulation issue

1. Issues:
Damaged, aged or corroded array frames; poor insulation between grounding and positive/negative pole of array.

2. Causes:
Exposed in open area for a long time, sunlight, rain, wind and others cause cables, connectors and other equipment to age, thus
worsening the insulation performance.

3. Effects:
 Shortening equipment lifespan
 Safety risk: Cause equipment failure or fire
 Risk of violating regulation: Not in conformance to electrical regulations and
safety standards, thus causing penalty.
Insulation testing standards

Please refer to IEC62446:2016 standard.


Measure resistance between grounding and positive/negative pole of string by using insulation resistance tester, the measured
resistance is greater than 1MΩ at range of 500V (the higher the resistance, the better the insulation performance).
Note: For testing array with power of 10kWp (kilowatt-hour), please short-circuit the positive/negative pole to measure earth
insulation resistance for safety and high efficiency.
Insulation resistance of array with power within 10kWp: the higher the resistance, the better the insulation performance.

System voltage Testing voltage Insulation resistance

<120V 250V > 0.5MΩ

120V~150V 500V > 1MΩ

>500V 1000V > 1MΩ


FAQ: Insulation resistance detection
Advantages of UT513A:
UT513A Insulation Resistance Tester has multiple functions such as auto-discharging, absorption ratio, polarization index, USB
data and more. It is portable and easy to use. Featuring one-button operation, the tester improves work efficiency and ensures
operation safety.

Recommended model: UT513A

 One-button operation: Improve efficiency


 Auto-discharge: Ensure operation safety
 Polarization index/absorption ratio measurement:
Enable fast identification of insulation status
 USB data transfer: Data readout/analysis and report
generation
FAQ: Detect open-circuit voltage of array
Standard requirement: Under condition of consistent irradiation intensity, the deviation of open-circuit voltage of measured
array/string shall not be over 5%.
Testing method: Measure open-circuit voltage between grounding and positive/negative pole of array/string by using multi-
meter at DC voltage range.
For example: A string consists of 20 pieces of panels, the open-circuit voltage of each panel is 50V, so the total open-circuit voltage is
1000V. Under normal situation, the voltage between grounding and positive/negative pole of string is 500V.

Advantages of UT196 Photovoltaic Multi-meter: UT196 is designed in accordance with IP65 protection rating and 1700V
DC voltage measurement. It can be applied to measure voltage of solar array system. UT196 has cETL/EMC and other safety
certificates, ensuring operation safety and testing efficiency.
(Solar system voltage is up to 1500V currently, tending to be over 1500V or more in future)

Recommended model: UT196

 Voltage measurement: It can be used to measure voltage up to 1700V DC,


satisfying measurement of solar system voltage.
 LPF: The ability to intercept frequency of 1 kHz, making the measurement more
accurate.
 AC current extension: Allow for measuring current of 3000A by using flexible
current clamp.
 Certificates: cETLus/EMC (CE+UKCA)/LVD (CE+UKCA)/REACH/ROHS.
 IP65 protection rating: Waterproof, dustproof, drop-proof (2M), rugged.
政策背景

Inverter Detection
FAQ:

The role of inverter: Solar inverter converts the DC current generated by solar array to sine-wave AC current, and connects
to load or power grid in parallel.
1. Issues:
Abnormal voltage/current, aged cable insulation, leakage; heating failure; non-compliant power quality, etc.

2. Causes:
 Corroded connector, low-quality equipment
 Poor contact of cable
 Over-high harmonic, low power factor, unbalanced three phases, etc.

3. Effects:
 The solar generating system cannot operate normally, affecting generating
efficiency and investment return, more severely, damaging the inverter and thus
causing fire.
 Low power factor leads to penalty by power supply department.
Common testing items and standards

4. Common testing items


 Insulation impedance and cable leakage
 Equipment grounding
 Circuit voltage and current
 Connectors and cables heat
 Power quality

5. Standards
Insulation impedance: At 1000V range, the resistance, between phase and phase or between phase and grounding, shall be
greater than 250MΩ (the higher the resistance, the better the insulation).
Circuit voltage: Under the condition of consistent irradiation intensity, the deviation of the operating current of the same
inverter connected by string shall be not greater than 10%.
Temperature: The maximum surface temperature of connector and cable shall be not over 70°C; the maximum temperature
difference of same type of connectors, cables and three-phase wires shall be not greater than 15°C.
FAQ: Circuit current (DC) detection

Measurement method: To check whether the array has any fault on power generation, please make the clamp head
approach circuits to measure current, if large deviation occurs, please disconnect the corresponding array, and check each
array in order, then replace the faulty array.

Advantages of UT256 60A AC/DC Fork Meter: Without the need to open and close clamp head frequently, UT256 can
measure current by approaching circuits, facilitating easy and fast measurement.

 No need to open and  Multifunctional


close clamp head
frequently

 Not easy to
 Compact and portable
operate

UT256 UT203+
Circuit current measurement
FAQ: Voltage (AC) and Current (AC) measurement
Advantages of UT219PV:
UT219PV Photovoltaic Clamp Meter can measure voltage up to 1700V DC and is applicable to measure voltage of solar array
system. It has multiple functions including Bluetooth transfer, real-time data logging and analyzing, report generation and more,
facilitating measuring circuit voltage and current fast, improving operation and maintenance efficiency, and ensuring solar
station operates normally. (Solar system voltage is up to 1500V currently, tending to be over 1500V or more in future)

Recommended model: UT219PV

 Current measurement: Narrow clamp head (35mm) facilitates measuring concentrated cables and
copper bus bars of inverter/combiner box.
 Voltage measurement: Measure DC and AV voltages up to 1700V and 1500V respectively.
 LPF: Intercept frequency over 1kHz, making output measurement more accurate.
 DC power detection: 1700kVA measurement of DC power of inverter.
 Bluetooth data transfer: Achieve real-time data logging and analyzing, and report generation.
 Category rating: CAT III 1500V / CAT IV 600V
 Certificates: CE, cETLus, RoHS, REACH, FCC
FAQ: Cable insulation detection
Measuring cable insulation resistance: In power outage state, set the tester to 1000V range, then, measure the
insulation resistance between phase and phase or between phase and grounding, the measured resistance shall be
greater than 250MΩ (ambient temperature is 20°C, the higher the resistance, the better the insulation).
Advantages of UT513A Insulation Resistance Tester: UT513A has multiple functions such as auto-discharging, absorption
ratio, polarization index, USB data and more. It is portable and easy to use. Characterized by one-button operation, the tester
improves work efficiency and ensures operation safety.

Recommended model: UT513A


 One-button operation: Improve efficiency
 Auto-discharge: Ensure operation safety
 Polarization index/absorption ratio measurement: Enable fast
identification of insulation status
 Compare function: Make testing easier and improve work
efficiency
 USB data transfer: Data readout/analysis and report generation
FAQ: Inverter temperature measurement
Measurement method: Measure inverter temperature by using thermal imager, if large temperature variation occurs, it indicates
that electrical equipment may be faulty.

Advantages of UTi740H thermal imager: 4.3’’ display screen, 384x288 IR


resolution, clear imaging, easy operation and visible temperature variation
facilitate accurate identification on whether the inverter is faulty, prolonging
inverter lifespan substantially.

 Manual focus: Identify fault clearly and intuitively.


 Auto-tracking for high temperature: Identify highest temperature spot rapidly for
evaluation and analysis.
 Manual Isotherm: User-defined temperature display for visibly locating area with
abnormal temperature.
Temperature measurement  App: Generate report as reliable data for maintenance evaluation.

Over-high connector Unbalanced three Over-high cable


temperature phases temperature
FAQ: Power quality measurement
Use power quality analyze to measure the quality of power generated by solar station. The measured voltage deviation,
frequency deviation, harmonic content, distortion rate, unbalanced three phases, power factor and others shall meet
relevant power quality standards specified by national power grid.
Frequency: The rated frequency of power grid is 50Hz, the allowable frequency deviation of solar system shall be
± 0.5Hz.
Harmonic: The harmonic of each phase shall be less than 5%.
Power factor: Shall be ≥0.90 typically.
FAQ: Power quality measurement
Advantages of UT285C:
UT285C Power Quality Analyzer can analyze harmonic and power factor for power operation, and perform data acquisition and
monitoring for power grid for a long time. The equipped PC software can analyze the measurement data uploaded to computer
and generates test report, facilitating determining if the power quality meets requirements, achieving grid connection and
improving operation efficiency.

Recommended model: UT285C

 Real-time waveform display: Observe and record real-time voltage and


current waveforms or time trend.
 50th harmonic measurement: Over-high harmonic in circuit can cause high-
frequency interference to equipment.
 Power factor measurement: Power factor reflects the power usage
efficiency of equipment.
 Unbalanced three phases: Overheat equipment, reduce efficiency and
accelerate aging.
 PC software: Data can be downloaded via PC software for data analysis,
report generation, and report export.
Inverter power quality inspection
政策背景

AC Combiner Box Detection


FAQ:
The role of combiner box: Reducing the amount of connecting wires between grid-tie
inverter and grid-tie cabinet.

1. Issues:
Abnormal voltage/current, aged cable insulation, leakage; heating failure; non-compliant
power quality, etc.

2. Causes:
 Terminal connection: loose connection, nonstandard connection, cable
disconnection
 Cable aging, short circuit, low insulation performance
 Over-high current and voltage

3. Effects: The issues may cause combiner shutdown, fire, property damage, safety accidents,
etc.
AC Combiner box testing:

4. Common testing items


 Insulation impedance and cable leakage
 Equipment grounding
 Circuit voltage and current
 Connectors and cables heat
 Power quality

5. Standards
 Temperature: The maximum surface temperature of connector and cable shall be not over 70°C; the maximum
temperature difference of same type of connectors, cables and three-phase wires shall be not greater than 15°C.
 Leakage current: <300mA for inverter with rated output at ≤30kVA; 10mA/kVA for inverter with rated output at >30kVA
(action time: <0.3S); ≤30mA for residential users.
Temperature measurement

Measurement method: Measure inverter temperature by using thermal imager, if large temperature variation occurs, it
indicates that electrical equipment may be faulty.

Advantages of UTi740H thermal imager: 4.3’’ display screen,


384x288 IR resolution, clear imaging, easy operation and visible
temperature variation facilitate accurate identification on whether
the inverter is faulty, prolonging combiner lifespan substantially
and improving generating efficiency.

Recommended model: UTi740H


 Manual focus: Identify fault clearly and intuitively.
 Auto-tracking for high temperature: Identify high temperature spot
rapidly for evaluation and analysis.
 Manual Isotherm: User-defined temperature display for visibly
locating area with abnormal temperature.
Temperature measurement  App: Generate report as reliable data for maintenance evaluation.
Leakage current detection

Detection method: Clamp all output cables through leakage current meter, if the displayed current is large, that indicates severe
leakage, please troubleshoot the issue in time.

Advantages of UT253A Leakage Current Tester: Single-clamp measurement facilitates identifying leakage rapidly and clearly and
troubleshooting failure in time.

Recommended model: UT253A


 Single-clamp measurement enables easy
operation
 0.01mA resolution allows for small current
detection
 Large clamp size (80x80mm) enable
clamping large cables or flat steel
 Data storage function, PC software for data
analysis and export
Leakage current detection
政策背景

Transformer Detection
FAQ:

The role of transformer: Transform is an equipment used to transform voltage.

1. Issues:
Over-high oil temperature, abnormal oil level, poor insulation and grounding, overvoltage, overload, sleeve failure, oil leakage,
etc.

2. Causes:
Damaged winding insulation, multi-point grounding, poor heat radiation condition, leakage flux, damped insulation, overload,
poor material, etc.

3. Effects:
The issues cause over-high temperature, insulation damage, transformer
aging/failure/damage, power outage.

4. Standards:
 The grounding current of transformer core shall be less than 0.1A during
normal operation.
 Oil temperature shall be 95°C (85°C to ensure optimal work state).
 Poor grounding: the grounding resistance shall be less than 4Ω.
Temperature measurement
Temperature measurement: The level of heat radiated by radiators of transform during normal operation shall be same
approximately, the temperature rises when one of the radiators fail, oil way clogs or radiator powers off. Thermal imaginer
displays temperature variation visibly, facilitating troubleshooting fault safely and efficiently.

Advantages of UTi740H thermal imager: 4.3’’ display screen, 384x288 IR resolution, clear imaging, easy operation and visible
temperature variation facilitate accurate identification on whether the inverter is faulty, prolonging combiner lifespan
substantially and improving generating efficiency.

Recommended model: UTi740H

 Manual focus: Identify fault clearly and intuitively.


 Auto-tracking for high temperature: Identify high temperature
spot rapidly for evaluation and analysis.
 Manual Isotherm: User-defined temperature display for visibly
locating area with abnormal temperature.
 App: Generate report as reliable data for maintenance evaluation.
Transformer temperature measurement
Grounding measurement
UT572 is for measuring earth resistance and soil resistivity. It can automatically check interface connection and
detect interference voltage/frequency, with data hold and indication functions. It can perform 2/3/4-wire measurements for
different on-site applications, such as power equipment wiring and lightning protection equipment.

Recommended model: UT572


Black Yellow
E P(S) Red  Large 4-digit LCD Display, 5s sampling time
Green C(H)
ES  2/3/4-wire earth resistance and soil resistivity
measurements
 Selectable test frequencies (94Hz/128Hz)
h  Disturbance voltage (Ust) and frequency (Fst)
measurement
d >5d >5d
 Earth resistance, RH and RS measurements
Grounding
conductor
Note: Please perform grounding measurements in a dry environment through a
grounding resistance tester (grounding pile type). Connect green and black cables with
the flat steel of the transformer, and pile yellow and red wires into the ground
respectively (distance: 5~10 meters).
Insulation resistance measurement
Measurement method: Measure insulation resistance of transformer under condition that the transformer powers off. Typically,
insulation resistances between high-voltage coil and casing, low-voltage coil and casing, and, high-voltage and low-voltage coil are
measured.
Standards: At 10kV or less, insulation resistance is greater than 300MΩ; At 35kV, insulation resistance is greater than 400MΩ (ambient
temperature is 20°C, the higher the resistance, the better the insulation performance).
Advantages of UT516B:
UT516B 12kV Insulation Resistance Tester: UT516B has multiple functions including auto-discharging, absorption ratio, polarization
index, USB data transfer and more. Characterized by one-button operation, the tester improves work efficiency and ensures operation
safety.

Recommended model: UT516B

 12kV voltage output;


 10TGΩ resistance range.
 Auto-discharging function ensures operation safety.
 PI/DAR measurement;
 USB data transfer function
Transformer insulation
resistance measurement
政策背景

Photovoltaic Monitoring
System Detection
FAQ:

The role of photovoltaic monitoring system: The system can perform real-time monitor and control on array, inverter,
combiner box, power distribution cabinet and other equipment in solar power station. The system displays data through
data acquisition software, facilitating better control on the station operation.

1. Issues:
The system fails to supply power normally, the voltage of storage battery is low voltage; Abnormal communication, data
acquisition failure, etc.

2. Causes:
 Battery aging or failure
 Weak Bluetooth, WIFI or mobile signal causes failed reception and abnormal communication module.

3. Effects: The system fails to work normally and control station in real time, which affects the generating efficiency.
System measurement

4. Measurement items:
 Storage aging and failure
 Communication failure; data collection failure

5. Measurement standard:
The internal resistance of battery depends upon the battery standard. When storage battery ages and its
capacitance decreases, the internal resistance increases (the lower the resistance, the better the battery
performance).
For example: The internal resistance of 300Ah lead-acid storage battery is relatively low, typically at
around 0.78Ω.

6. Measurement method:
Connect red test lead of battery tester with positive pole of storage battery, and black with negative,
perform measurement continuously for several times. If the measured internal resistance is approximate,
that indicates a good consistence.
System measurement
Advantages of UT3550:
UT3550 Battery Tester can perform on-line measurement on storage battery automatically and in real time, ensuring accuracy
and stability. It can also be applied to measure lithium battery, lead-acid battery, button battery, hydrogen fuel battery and
various batteries, facilitating identifying battery quality rapidly, improving work efficiency, and ensuring normal operation of
monitoring system.

Recommended model: UT3550


 Voltage and resistance are shown on the same
display: Facilitating viewing voltage and
resistance rapidly.
 Data transfer: Exporting measurement data via
PC software
 Auxiliary display: Facilitate data reading and
match with hanging/shoulder strap, satisfying
more testing requirements.
 IP65 rating: Water proof, dust proof, drop proof
(2m), rugged
 Interface/protocol support: Supporting custom
development, remote control and data
acquisition. Battery measurement
政策背景

Power distribution cabinet temperature


measurement
FAQ:
The role of power distribution cabinet/room:
Power distribution cabinet is a power distribution unit that assembles and integrates switch, breaker, fuse, indicator light, meter,
cable and other protection parts to meet design function requirements.

1. Issues:
Low impedance or circuit leakage caused by cable aging; poor grounding; component overheat due to
overcurrent or overvoltage.

2. Causes:
 Leakage caused by poor impedance: cable aging or damage.
 Flat steel and connector are loose; lightning strike damages equipment.
 Switch and connector are loose; contactor, cable or others are oxidized or corroded.

3. Effects:
Equipment are damaged, short-circuited, or burnt, causing fire or property damage.
4. Standards:
 Grounding resistance: Less than 4Ω (the lower the better)
 Temperature: The maximum surface temperature of connector and cable shall be not over 70°C; the maximum
temperature difference of same type of connectors, cables and three-phase wires shall be not greater than 15°C.
(Temperature changes depending upon different level of current and heat)
Temperature measurement

Advantages of UTi740H:
UTi740H thermal imager: 4.3’’ display screen, 384x288 IR resolution, clear imaging, easy operation and visible temperature
variation facilitate accurate identification on whether the inverter is faulty, prolonging lifespan of power distribution cabinet
substantially and improving generating efficiency.

Recommended model: UTi740H


 Manual focus: Identify fault clearly and intuitively.
 Auto-tracking for high temperature: Identify high temperature
spot rapidly for evaluation and analysis.
 Manual Isotherm: User-defined temperature display for visibly
locating area with abnormal temperature.
 App: Generate report as reliable data for maintenance
evaluation.
Power distribution cabinet
temperature measurement
政策背景

Transmission Line Detection


Common issues
The role of transmission line: Connect power supply with electrical equipment to supply power to users; establish electric
connection between substations, so as to improve the reliability of supplying power by grid.

1. Issues:
Electric discharge caused by low insulator/circuit insulation performance due to lightning stroke, bird damage,
pollution flashover and the like.

2. Causes:
 Bird nest on transmission line cause tower to discharge electricity and insulator to
break down.
 Dirt cause low insulation performance of insulator.
 Insulator or connector failure, poor or defective contact, oxidized connector, etc.

3. Effects:
Equipment damage, transmission line breakdown, power outage, etc.

4. Measurement items:
 Check if metal parts of tower are worn, corrode, or grounded well.
 Check if conductors are corroded, broken, burnt, and if overheat occurs caused by poor contact of conductors.
 Check if any damage or crack occurs at insulator, and if partial discharge occurs at the tip of insulator.
Grounding measurement
Advantages of UT572:
UT572 Advanced Earth Resistance Tester is for measuring earth resistance and soil resistivity. It can automatically check
interface connection and detect interference voltage/frequency, with data hold and indication functions. It can perform 2/3/4-
wire measurements for different on-site applications, such as power equipment wiring and lightning protection equipment.

Recommended model: UT572


 Large 4-digit LCD Display, 5s sampling time
 2/3/4-wire earth resistance and soil resistivity measurements
 Selectable test frequencies (94Hz/128Hz)
 Disturbance voltage (Ust) and frequency (Fst) measurement
 Earth resistance, RH and RS measurements
Measuring grounding
resistance of tower Black Yellow
Green E P(S) Red
C(H)
Note: Please perform grounding measurements in a dry ES
environment through a grounding resistance tester
(grounding pile type). Connect green and black cables with
the flat steel of the transformer, and pile yellow and red h
wires into the ground respectively (distance: 5~10 meters).
d >5d >5d
Grounding
conductor
Acoustic imaginer
Advantages of UT568A:
UT568A Acoustic Imaginer locates sound source and measures the amplitude of sound source according to phased array
principle, and displays the distribution of sound source in space in imagining mode. Users simply adjust frequency range and
dynamic range to satisfy most of testing requirements, facilitating rapid identification of partial discharge (electric charge caused
by poor insulation of insulator) and improvement of measurement efficiency.
Recommended model: UT568A
 Scanning overall, visibly and efficiently.
 62° field of view of ultrasonography; 25FPS refresh rate; real-time
imagining.
 128-channel MEMS digital microphone to collect sound source.
 Shooting and videoing enable recording data on site flexibly.
 PC software to analyze data and generate report.
 Adjustable frequency and equipped aperture to eliminate frequency.

Performance comparison:
Thermal Imaginer:
Heating fault becomes relatively severe when it is identified by
temperature screening
Acoustic Imaginer:
The ability to identify potential faults visibly and efficiently
Electric discharge occurs at the tip of insulator
Product List of Solutions
High-end portfolio: The products shown below are suited for large-scale photovoltaic power stations (have O&M teams) with generating capacity
at over 20 MW. This portfolio is suitable for third-party O&M institute. (Reference voltage: 110KV)

Designation Model Usage Role

Check if the insulation resistance of


Insulation Measure insulation resistance of
UT516B transformers, cables and other equipment
Resistance Tester various equipment
meet requirement.
Ground Pile Clamp Check if equipment grounding meets
UT278D Measure grounding resistance
Resistance Tester requirement.

Advanced Earth Measure grounding resistance of


UT572 Measure grounding resistance
Resistance Tester equipment.

Leakage Current Measure leakage current of Check the insulation variation of


UT253A
Clamp Meter equipment equipment.

IR Thermal Locate hot spot or abnormal Rapidly troubleshoot issues caused by


UTi740H
Imaginer temperature point rapidly abnormal temperature.

Power Quality Analyze power quality, i.e., harmonic,


UT285C Measure power quality
Analyzer power factor, and other parameters.
Product List of Solutions
High-end portfolio: The products shown below are suited for large-scale photovoltaic power stations (have O&M teams) with generating capacity at
over 20 MW. This portfolio is suitable for third-party O&M institute. (Reference voltage: 110KV)

Designation Model Usage Role

UT256 (60A AC/DC)


Clamp Meter UT219PV (1000A Measure current Measure circuit current.
AC/DC)

Measure voltage, continuity, Perform measurement of voltage and


Multi-meter UT196
resistance, etc. other basic parameters.

Battery Internal Measure internal resistance of Determine battery status based on


UT3550
Resistance Tester battery internal resistance

Detect partial discharge of high- Detect partial discharge to reduce energy


Acoustic Imaginer UT568A
voltage equipment loss and safety risk.

Voltage Detector UT12E Identify live and neutral wires Identify live and neutral wires.

Measure phase sequence of power


Phase Detector UT262E Determine phase sequence.
distribution cabinet
Product List of Solutions
Mid-end portfolio: The products shown below are suited for on-site maintenance on equipment of medium-scale
photovoltaic power station with generating capacity at 1 to 20 MW. (Reference voltage: 10KV and 35KV)

Designation Model Usage Role

Insulation Measure insulation resistance of Ensure the insulation resistance of


UT513A
Resistance Tester various equipment equipment meets requirement.

Ground Pile
Check if equipment grounding meets
Clamp Resistance UT278D Measure grounding resistance
requirement.
Tester

Leakage Current Measure leakage current of Check the insulation variation of


UT253A
Clamp Meter equipment equipment.

IR Thermal Locate hot spot or abnormal Rapidly troubleshoot issues caused by


UTi740H
Imaginer temperature point rapidly abnormal temperature.

Power Quality Analyze power quality, i.e., harmonic,


UT285C Measure power quality
Analyzer power factor, and other parameters.
Product List of Solutions
Mid-end portfolio: The products shown below are suited for on-site maintenance on equipment of medium-scale
photovoltaic power station with generating capacity at 1 to 20 MW. (Reference voltage: 10KV and 35KV)

Designation Model Usage Role

UT256 (60A AC/DC)


Clamp Meter UT219PV (1000A Measure current Measure circuit current.
AC/DC)

Measure voltage, continuity, Perform measurement of voltage and


Multi-meter UT196
resistance, etc. other basic parameters.

Battery Internal Measure internal resistance of Determine battery status based on


UT3550
Resistance Tester battery internal resistance of battery.

Voltage Detector UT12E Identify live and neutral wires Identify live and neutral wires.

Measure phase sequence of power


Phase Detector UT262E Determine phase sequence.
distribution cabinet
Product List of Solutions
Economical portfolio: The products shown below are suited for small-scale photovoltaic power station with generating capacity at
≤1 MW. (Reference voltage: 220/380V, 10KV)

Designation Model Usage Role

Insulation Measure insulation resistance of Ensure the insulation resistance of


UT513A
Resistance Tester various equipment equipment meets requirement.

Ground Pile
Check if equipment grounding meets
Clamp Resistance UT278D Measure grounding resistance
requirement.
Tester

Leakage Current Measure leakage current of Check the insulation variation of


UT253A
Clamp Meter equipment equipment.

IR Thermal Locate hot spot or abnormal Rapidly troubleshoot issues caused by


UTi740H
Imaginer temperature point rapidly abnormal temperature.

Unit conversion: 104 kW = 10 MW; 1 MW = 1000 kW


Product List of Solutions
Economical portfolio: The products shown below are suited for small-scale photovoltaic power station with generating capacity at
≤1 MW. (Reference voltage: 220/380V, 10KV)

Designation Model Usage Role

Clamp
UT219P Measure power factor Measure power factor
Wattmeter

UT256 (60A AC/DC)


Clamp Meter UT219PV (1000A Measure current Measure circuit current.
AC/DC)

Measure voltage, continuity, Perform measurement of voltage and


Multi-meter UT196
resistance, etc. other basic parameters.

Voltage Detector UT12E Identify live and neutral wires Identify live and neutral wires.

Unit conversion: 104 kW = 10 MW; 1 MW = 1000 kW