Professional Documents
Culture Documents
Manuale Descrizione Funzionale RXL
Manuale Descrizione Funzionale RXL
Supplementary documents
CM110785en_06
17 Sep 2010 Building Automation
Contents
1 Introduction ...................................................................................................5
1.1 Validity of the documentation..........................................................................5
1.2 Revision history ..............................................................................................5
1.3 Copyright ........................................................................................................6
1.4 Quality assurance ...........................................................................................6
1.5 Document use / request to the reader ............................................................6
1.6 Target audience, prerequisites .......................................................................7
1.7 Bus supply for RXL controllers........................................................................7
1.8 RXL controller communications ......................................................................7
1.9 Integration of the RXL controllers into DESIGO..............................................7
1.10 Use of the RXL controllers with Synco ...........................................................7
2 Definitions / Tools.........................................................................................8
2.1 Signals and parameters (presentation)...........................................................8
2.2 Supported tools...............................................................................................8
2.3 Parameterization in ACS ................................................................................9
2.4 Parameterization using the HandyTool...........................................................9
2.4.1 Operation of the HandyTool functions ..........................................................10
2.4.2 "Limited" parameterization using room unit QAX34.3...................................10
2.4.3 "Extended" parameterization using room unit QAX34.3 ...............................12
2.4.4 Selection of the device address using room unit QAX34.3...........................12
2.5 Upload/download parameters using room unit QAX34.3..............................13
2.6 Test the periphery using room unit QAX34.3................................................14
2/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Contents 17 Sep 2010
5.5 Determining the room operating mode without a bus (stand-alone) ........... 42
5.5.1 Local control of room operating mode via the window contact input ............ 43
5.5.2 Local control of room operating mode via a presence detector ................... 43
5.5.3 Local control of room operating mode with a room unit ............................... 44
5.5.4 Stand-alone Example ................................................................................... 45
10 Master/slave ................................................................................................ 82
10.1 Description.................................................................................................... 82
10.2 Peripheral functions...................................................................................... 84
3/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Contents 17 Sep 2010
11.1 Digital inputs .................................................................................................86
11.2 Temporary Comfort mode.............................................................................86
11.3 Presence detector switch-on and switch-off delay........................................86
11.4 Heating and cooling demand ........................................................................87
11.5 Special functions...........................................................................................87
11.6 Boost heating (Morning Warmup) .................................................................88
11.7 Night purge (Night Purge), (FNC10, FNC12)................................................88
11.8 Pre-cooling (Precool) ....................................................................................89
11.9 Emergency heating (Emergency Heat).........................................................89
11.10 Rapid ventilation (Fan only) ..........................................................................90
11.11 Free cooling (Freecool).................................................................................90
11.12 Alarm.............................................................................................................91
11.12.1 With DESIGO................................................................................................91
11.12.2 With Synco....................................................................................................92
11.13 Resetting the setpoint shift ...........................................................................92
11.14 Software version ...........................................................................................93
11.15 Device state ..................................................................................................93
14 FAQs ..........................................................................................................104
4/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Contents 17 Sep 2010
1 Introduction
1.1 Validity of the documentation
5/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Introduction 17 Sep 2010
1.3 Copyright
This document may be duplicated and distributed only with the express permission
of Siemens, and may be passed only to authorized persons or companies with the
required technical knowledge.
Support address:
Siemens Switzerland Ltd.
Building Technologies Group
International Headquarters
Field Support 5500
Gubelstrasse 22
6301 Zug, Switzerland
Tel. +41 41 724 5500
Fax. +41 41 724 5501
E-mail: fieldsupport-zug.ch.sbt@siemens.com
Before using our products, it is important that you read the documents supplied with or
ordered at the same time as the products (equipment, applications, tools etc.) carefully
and in full.
More information on the products and applications (e.g. system descriptions etc.) is
available on the Internet/intranet at
https://intranet10.sbt.siemens.com/business/building_comfort/systems/desigo/ra/.
We assume that the users of these products and documents have the appropriate
authorization and training, and that they are in possession of the technical knowledge
necessary to use the products in accordance with their intended application.
If, despite this, there is a lack of clarity or other problems associated with the use of the
documentation, please do not hesitate to contact the Product Manager at your nearest
branch office, or write directly to the support team at our Swiss headquarters.
E-mail: fieldsupport-zug.ch.sbt@siemens.com.
Please note that without prejudice to your statutory rights, Siemens accepts no liability
for any losses resulting from non-observance or improper observance of the points
referred to above.
6/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Introduction 17 Sep 2010
1.6 Target audience, prerequisites
This document assumes that users of the RXL controllers are familiar with the tools
Synco ACS and able to use them.
RXL controllers can work without bus supply if the following conditions are adhered to:
Parameterize only using the HandyTool (not with ACS).
No integration in a building automation and control system (e.g. DESIGO, Synco).
No changeover mode (sensor signal via bus).
No master/slave combinations.
Otherwise, the bus, used by the RXL room controller for communication, requires a bus
supply.
Each controller consumes 5 mA. The supply has to be selected according to the
number of controllers. We recommend the following products:
The RXL controllers are integrated into DESIGO using a proprietary Individual
addressing procedure.
See CM1Y9776, RXB / RXL Integration – Individual Addressing.
The RXL controllers can be used in conjunction with Synco. The interface is designed
to communicate with Synco 700 controllers.
7/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Introduction 17 Sep 2010
2 Definitions / Tools
2.1 Signals and parameters (presentation)
Room unit Parameters identified by this symbol are influenced by the room unit.
ACS Service Parameters identified by this symbol are set with the ACS Service tool.
HandyTool Parameters identified by this symbol are set with the HandyTool tool.
The left margin contains the symbol for the HandyTool next to a table containing the
parameter number, short name and basic setting.
The number has syntax *xxx, with xxx being a three-digit number.
Note A list of the parameters by number and in alphabetical order is located in sections 13.5
and 13.6.
A table of parameters with enumerations fort he HandyTool is shown in Section 13.7.
The RXL controllers can be commissioned either with the Synco ACS Service too or
the HandyTool.
STOP Note! Be careful when using different tools. The following rule applies:
Last one's right!
If you use OCI700 as an interface, it is connected to the service plug of the controller
or of the room unit.
As long as the OCI700 is connected to the service plug, it must be supplied by
the computer via the USB interface. Otherwise the LCD display of the room unit
will turn dark and the controller will switch to addressing mode.
8/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Definitions / Tools 17 Sep 2010
2.3 Parameterization in ACS
ACS Service This manual does not describe how the physical address is defined.
This information can be found in the ACS description.
In the ACS Service program, select Plant, Open to open the plant.
To start the parameterization, select Applications, Parameterizations:
HandyTool Tthe QAX34.3 room unit contains the function "HandyTool" allowing you to
parameterize the RXL room controllers.
Parameter
Physical address
Zones
QAX34.3 room unit In addition to its room unit functionality, this device also allows for parameterizing the
room controllers.
Parameters The parameter numbers and the functions are described in the sections below.
9/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Definitions / Tools 17 Sep 2010
2.4.1 Operation of the HandyTool functions
10385Z70
Display Parameter position e.g. P006
Value to be adjusted e.g. 22.5 (a temperature)
or 250 (e.g. a particular actuator type)
Restart after important After modification of certain parameters (e.g. *063 actuator type), the controller will
parameter changes perform a restart.
2 = Display mode:
The parameters are displayed with prefix "d" (e.g. d015).
+/– allows for finding the number and pressing < (Enter) confirms it.
The corresponding value is displayed.
Press < (Enter) or > (Escape) to return to the list.
3 = Parameterization mode
Some parameters (see below) can be set.
They are displayed with prefix "P"
+/– allows for finding the number and pressing < (Enter) confirms it.
The corresponding value is displayed.
+/– allows for modifying the value and pressing < (Enter) confirms it.
> (Escape) returns to list without changing anything.
Pressing Escape one more time opens the list with the modes.
Pressing Escape a third time returns to the normal mode (room unit).
Note The parameter numbers are located in sections 13.5 and 13.6 as well as in the sections
where the functions are described.
A table of parameters with enumerations fort he HandyTool is shown in Section 13.7.
10/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Definitions / Tools 17 Sep 2010
Adjustable parameters P001 Physical address (Area)
(Parameter mode) P002 Physical address (Line)
P003 Physical address (Device address)
P008 Geographical zone (Apartment)
P009 Geographical zone (Room)
P010 Geographical zone (Subzone)
P011 Timeswitch zone (Apartment)
P012 Timeswitch zone (Room)
P013 Timeswitch zone (Subzone)
P014 Heat distr. zone heating coil
P015 Refr. distr. zone cooling coil
P016 Heat distr. zone heating surface
P018 Outside air temp zone
P021 Master/Slave
P023 Master/Slave zone (group)
11/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Definitions / Tools 17 Sep 2010
2.4.3 "Extended" parameterization using room unit QAX34.3
STOP Caution This parameterization also allows for adjusting critical values.
In the worst case, this may destroy a device (controller / fan coil / actuator or
other plant parts).
Note The parameter numbers are located in sections 13.5 and 13.6 as well as in the sections
where the functions are described.
A table of parameters with enumerations fort he HandyTool is shown in Section 13.7.
12/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Definitions / Tools 17 Sep 2010
2.5 Upload/download parameters using room
unit QAX34.3
Download If the parameter set does not match the connected controller, error
message "Err" is displayed.
Press > (Escape) to return to the storage number and select a different number.
If the parameter set matches the connected controller, start download (display
flashes).
If connected successfully, "P1" is displayed (see 2.4.2).
13/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Definitions / Tools 17 Sep 2010
2.6 Test the periphery using room unit QAX34.3
The HandyTool allows you to test the connected field devices (sensors, actuators).
This works only for the controller with the connected HandyTool; it does not work in
master/slave mode.
1)
Considering the configuration means:
– For thermal actuators, the output is clocked 1:1 during the first 400 s, then as per
the % entry.
– Motorized actuators open at 100% 1.5 times the runtime, and close at 0% 1.5
times the runtime.
14/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Definitions / Tools 17 Sep 2010
2)
T21 and T22 have the same effect in changeover applications.
3)
Only for RXL22.1/FC-12
If a digital input is used by a safety thermostat, the thermostat is considered.
4)
Only for RXL21.1/FC-11
7)
Only the I/Os of the controller and no bus actuators are controlled in test mode.
8)
For FNC20, the different damper runtimes for heatin/cooling are not considered; for
test mode, the sum of the times are halfed.
9)
Values are correct when read, but will not automatically be updated.
Exit test modeTo exit test mode, press >- (Escape) 2 - 3 times (depending on the
situation).
15/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Definitions / Tools 17 Sep 2010
3 Select communication mode
As stated in section 1, the RXL room controllers can be integrated in DESIGO or
operated inc conjunction with Synco.
Note The factory setting of all controllers and the basic setting of the tools is 0 (for Desigo).
This minimizes the bus load.
Exception: ACS Service changes the setting immediately to 1 (for Synco).
ACS Service In a Synco network the ACS Service tool is used. It will automatically choose the
appropriate communication.
In cases where RXL controllers are used in conjunction with Synco, zone addresses
need to be allocated. These must be defined together with the Synco devices at the
planning stage.
Timeswitch zone This zone has the same structure as the geographical
(Apartment . Room Subzone)
zone. It indicates the source of the time schedule for
Apartment = ---, 1...126 the RXL controllers.
Room = ---, 0...63 The same zone must also contain a device (e.g. a
Subzone =---, 0...15
Synco RMx7xx or RMB795) to deliver the time
schedule.
16/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Select communication mode 17 Sep 2010
Heat distribution zone Information related specifically to the hot water system
heating coil in heating coils (heating registers) is exchanged within
Zone = ---, 1...31
this zone. The zone also includes a Synco device to
process the information (e.g. RMH7xx or RMU7xx with
changeover).
Heat distribution zone Information related specifically to the hot water system
heating surface (radiator) of a radiator is exchanged within this zone (e.g. heating
Zone = ---, 1...31
demand). This zone also includes a Synco device to
process the information (e.g. RMH7xx or RMB7xx).
Outside air temperature The outside air temperature (all Synco devices of series
zone 700) is exchanged in this zone.
Zone = ---, 1...31
17/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Select communication mode 17 Sep 2010
ACS Professional The zones are defined under Communication.
Reduce bus load Individual zones can also be disabled via command if they are not being used. This has
the advantage of reducing the load on the bus.
18/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Select communication mode 17 Sep 2010
3.2 Geographical zone and time switch zone
application example RXL with RMB795
To explain the philosophy of the room group, we use the following example.
10385Z02
User requirements / Each of the 2 companies wants to operate its room groups according to different
operating modes operating modes, that is, with own
– time programs
– setpoints
– fire and smoke extraction functions
Floor plan of floor 3 The following floor plan shows usage of the rooms on the third floor by Logistics Ltd
and Sport Ltd:
D: 113 D: 107
G: 2.4.1 G: 3.5.1
Sport Ltd
305
Office
Office
308
Office Office
D: 112 307 306 D: 108
G: 2.3.1 G: 3.6.1
10385Z03en
19/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Select communication mode 17 Sep 2010
Sport Ltd uses 2 For implementation of the application example, we focus on the floor plan of Sport Ltd.
room groups Due to company needs, a subdivision into 2 room groups or 2 “geographical zones
(apartment)” is made:
– Conference room (room group 1)
– All the other rooms are offices (room group 2)
The fan coils, all of which are equipped with RXL room controllers, are already shown
on the floor plan, and the appropriate assignments by means of addresses have been
made:
x x x x x x x x
SA EA
Conference Enable
Setpoint prio
Room group 1 Relay
1 2
Q Q
Conference
room
D: 114
G: 1.1.1
RMB795
309
D: 113
G: 2.4.1
Sport Ltd
308
Office
Office
D: 112 307
G: 2.3.1
10385Z04en
D: 111 D: 110
G: 2.2.1 G: 2.1.1
x x x x x x x x
SA EA
Office Enable
Setpoint prio
Raumgruppe 2 2
Room group
Relay
1 2
Q Q
Definition of The combination of several groups to 1 room group is made on the bus by addressing
room group the "Geographical zone". This address consists of 3 components:
Geographical zone: Apartment.Room.Subzone (e.g. 2.1.1)
All devices which, together, shall form one room group must be assigned the same
apartment number.
20/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Select communication mode 17 Sep 2010
Settings on the On the RMB795 central control unit, only the room group, that is, the "Geographical
central control unit zone (apartment)" can be set.
The room and the subzone use a fixed assignment (Room = 1, Subzone = 1).
This means that for setting a room group on the central control unit, following applies:
Room group = geographical zone (apartment.1.1).
Settings on the The RXL room controllers offer the following setting choices:
room controllers – Geographical zone (apartment)
– Geographical zone (room)
– Geographical zone (subzone)
On HVAC applications using RXL… room controllers, it is only the "Geographical zone
(apartment)" and the "Geographical zone (room)" that should be used.
Extension of addressing by the “Geographical zone (room) " leads to room control with
RXL room controllers. This offers individual operational interventions (from an operator
unit or the central control unit via bus), such as room setpoint readjustments from any
of the rooms or devices.
Significance of subzone The "Geographical zone (room)“ can be subdivided; for that, the RXL room controller
offers the "Geographical zone (subzone).
This subzone could be for use in plant where lighting conditions shall be taken into
consideration if, for example, a "Geographical zone (room)" shall be divided into the 2
subzones “Lighting window side” and “Lighting corridor side”.
For HVAC applications, the preset subzone = 1 should be left unchanged.
Significance of suffixes Suffixes (apartment), (room) and (subzone) are pre-defined, whereby (apartment) has
nothing to do with a living space or an apartment in the proper sense.
The device address Each bus user requires an individual device address – on the floor plan of the
preceding page shown as D:11x.
The device addresses in our example were assigned in accordance with the bus’
topology.
21/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Select communication mode 17 Sep 2010
3.3 Implementation of application example
Procedure for Using the "C3127_Planning and Commissioning Report, Communication Synco 700",
engineering the plant and the required communication settings can be represented in an easy-to-
understand way.
Proceed as follows:
1. Enter general information, such as plant name, device names, device types,
applications, etc.
2. Transfer the device addresses of all bus users and the basic settings of
communication from the floor plan.
3. Enter the "Geographical zone addresses" in agreement with the group formations
made.
Example Sport Ltd The following illustration shows the completed report for the plant of Sport Ltd:
1 Device type
RMU RMH,
7.. RMZ
RMK
OZW RMB
771... 795
RXB
....
QAW
740
RMB795 RXB.. RMB795 [2] RXB.. RXB.. RXB.. RXB..
Implementation with In agreement with the list created, the settings of the data points with the same names
commissioning are to be made on the devices during commissioning.
22/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Select communication mode 17 Sep 2010
3.4 Heating and cooling demand zone
The building described above is equipped with Synco control equipment on the
generation side.
Bus (TP1)
10785Z05en
Controller 1 Controller 2 Controller 3 Controller 4 Controller 5 Controller 6
2
T
T T
1
Heat source DHW heating Heating circuit Fan coil Fan coil Fan coil
fan coil room A room B room C
Heat demand
Heat demand
Heat requistion
Heat requistion
Heat demand
Heat distr zone 2 Heat distr zone 2 Heat distr zone 2 Heat distr zone 2
Setting values
Controller 1 Controller 2 Controller 3 Controller 4 Controller 5 Controller 6
Explanation relating to In the case of a typical application, the individual RXL room controllers - when used
the illustration with the RMB central control unit - signal their heat demand directly to the primary
controller (in the above example to the RMH760).
(1) and (2) designate the numbers of the distribution zone.
23/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Select communication mode 17 Sep 2010
4 Applications, parameters
4.1 Application selection
Most of the RXL controllers store a number of software applications (e.g. RXL22.1/FC-
12 with FNC03 and FNC05).
4.2 Parameterizations
24/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Applications, parameters 17 Sep 2010
5 Room operating modes
5.1 Description
The room operating modes available with DESIGO RXL are Comfort, Precomfort,
Economy and Protection. In addition, there is a frost protection limit, at which, for
example, an alarm can be triggered. Each room operating mode has separately
adjustable heating and cooling setpoints.
Heating Cooling
Y [%]
100
10385D01
0 TR
Comfort
Precomfort
Economy
Protection
Frost limit
Comfort Comfort is the room operating mode in an occupied room. In this mode, the room
temperature is within the comfort range. The room controller operates in the heating or
cooling sequence with the resulting Comfort setpoints.
Precomfort In Precomfort mode (in a vacant room), the controller operates with setpoints slightly
below the Comfort setpoint in heating mode, and slightly above the Comfort setpoint in
cooling mode.
Economy In rooms that are unoccupied for any significant length of time (e.g. night setback based
on a time scheduler, see pages 28, 37), the supply of energy to the room can be
reduced substantially. In Economy mode, the controller operates with a setpoint slightly
below the Precomfort setpoint in heating mode, and slightly above the Precomfort
setpoint in cooling mode.
Protection If the building is unoccupied over a long period of time (e.g. holidays) the temperature
setpoints can be reduced (or, in the case of cooling, raised) so that only sufficient
heating or cooling energy is provided to protect the building fabric and its contents.
Frost limit If the room temperature or return air temperature falls below the Frost limit, an alarm is
initiated for further processing in the building automation and control system.
The room controller will continue to operate at the relevant setpoint (e.g. Protection,
Economy, etc.).
The alarm threshold in the controller is a fixed 5°C. In the case of applications
incorporating an outside air damper, the value can be preset in the range 2 … 10°C.
25/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
26/114
Siemens
Building Technologies
Section 5.3 Section 5.4 Section 5.5
Central (ACS)
DI 1. DI 1. DI 1.
1.
Bus 2. Bus 2.
Protection
Room operating
Occupancy mode
Bus 3. Bus 3.
Presence detector
Presence detector Presence detector
DI DI 3. DI 3.
10784Z54en
17 Sep 2010
CM110785en_06
5.3 Determining the room operating mode
in DESIGO
The effective room operating mode of the room controller depends on the central Use
and Occupancy time schedules and/or on local influences such as window contacts,
presence detectors or a room unit.
The diagram below shows the priority of these influences and how they are processed
by the room controller:
Central Local
Controller
DI 1.
Use
Bus 2.
Occupancy
Bus 3.
Presence detector
DI
Room unit
10785Z55en
PPS2 3.
STOP Note! The effects of Priority 1 and Priority 2 are similar in nature to continuous states
The Priority 3 influences are treated as events.
The key factor is the moment at which the state changes (trigger edge).
If the mode is later changed by another source of priority 3, the last change
applies.
27/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
5.3.1 Local control of room operating mode via
a window contact
Central Local
Controller Whenever a window is opened, the room controller
Prio
DI 1.
always switches to the Protection room operating
mode, i.e. the heating or cooling output is reduced to a
2. minimum. If a window is opened outside the "building-
in-use" period it is also possible, for example, to
3. arrange for this to trip an alarm in the building
automation and control system.
DI
PPS2 3.
Effective The table below shows the effective room operating mode as a function of the Window
room operating mode contact input.
The window contact is connected directly to a digital input on the room controller (see
page 86).
28/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
Effective The table below shows the three possible occupancy states and the resulting effective
room operating mode room operating mode.
Central Local
Controller The effective occupancy is determined by the
Prio
DI 1.
Occupancy time schedule and the presence
detector.
2. It controls the room operating mode of a room
controller throughout the period when the building is
3. in use.
DI
PPS2 3.
Occupancy The central time schedule transmits the anticipated occupancy of a room or group of
time schedule rooms. It controls the room operating mode of a room controller throughout the period
when the building is in use. Outside the building-in-use period, the time schedule is
disabled.
The time schedule can be used, for example, by a building tenant to specify the
occupancy times applicable to that tenant’s own rooms.
29/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
The Occupancy scheduler has three possible states:
State Description
Occupied Occupants expected
The room controller switches to Comfort
Standby Occupancy is probable; the room must be ready for use shortly
(Comfort temperature)
The room controller switches to Precomfort
Unoccupied No occupants expected
The room controller switches to Economy
It controls the room operating mode of a room controller throughout the period when
the building is in use. Outside the building-in-use period, it is disabled.
State Description
Occupied The room is occupied
The room controller switches to Comfort
Unoccupied The room is not occupied
The room controller switches to Economy or Precomfort.
Effective occupancy The table below shows Effective occupancy as a function of the Occupancy time
schedule and the presence detector.
Principle: "Occupied" takes precedence over “Unoccupied“. If either the time schedule
or the presence detector transmits Occupied then the room is Occupied.
30/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
Effective The effective room operating mode can be changed by the effective occupancy only
room operating mode during the building-in-use period (defined by the Use time schedule)
The change in the effective room operating mode is event-driven, the key factor
being the moment at which the effective occupancy changes.
The room unit or Temporary Comfort mode (both Priority 3) can cause the effective
room operating mode to change again the last command always applies.
The presence detector is connected directly to a digital input on the room controller
(see page 86.
This type of time schedule is not supported in DESIGO. If it is nevertheless used, this
can cause room controller errors.
Room unit
Central Local
Controller The /Auto button on the room unit can be used like
Prio
DI 1.
an occupancy button.
The room user can use it to decrease or increase the
2. room temperature control.
3.
DI
PPS2 3.
The room unit is connected to the PPS2 interface on the room controller.
It displays the effective room operating mode in a simplified form, and can also be used
to change it:
State Description
Auto Effective room operating mode is Comfort
Reduced mode in the room, depending on the Priority 1, 2 and 3
influences:
The effective room operating mode is Precomfort, Economy or
Protection. (3rd priority: "last one wins ").
31/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
Effective The effective room operating mode can be changed via the room unit only during the
room operating mode building-in-use period (defined by the Use time schedule)
The change in the effective room operating mode is event-driven, the key factor
being the moment when the button on the room unit is pressed.
The Effective occupancy or Temporary Comfort mode (both Priority 3) can cause the
effective room operating mode to change again the last command always applies.
The table below shows the effect of the /Auto button on the effective room operating
mode of the room controller.
1) Comfort mode is operative for the pre-defined Temporary Comfort period (see page
86). The room controller then reverts to Economy.
32/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
5.3.6 DESIGO examples
The following are examples of two typical applications of time schedules in conjunction
with local control of the room operating mode.
10385D02
06:00 22:00
Time schedule Building in use
Use
Building not in use
Building protection
Time schedule
08:00 12:00 13:00 17:00
Occupancy Occupied
Rooms 1 … 3
Standby
Unoccupied
Window contact
Room 3
Window open
1) 1)
Window closed
Effective room
operating mode
Room 3
Comfort
Precomfort
Economy
2)
Protection mode
The operating mode in Rooms 1 and 2 of a building is determined centrally by the Use
and Occupancy time schedules. The Occupancy time schedule defines the period
during which both rooms are required to be available (Standby).
Comfort mode is then initiated locally via the room unit (Room 1) or presence detector
(Room 2).
33/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
The following conditions are specified:
Overall, the building is in use from 06.00 to 22.00 (Building use time schedule).
Rooms 1 and 2 must be available from 08.00 to 18.00 (Occupancy time schedule:
Standby)
The occupants of Room 1 continue working in the evening beyond the programmed
occupancy period. At the end of the programmed period of occupancy, the room
operating mode changes to Economy, even if the room unit is set to Auto (1).
Comfort mode can now be re-activated with the Auto switch on the room unit (2).
Comfort remains active for the pre-defined Temporary Comfort period (see page 86).
However, at the end of the "building-in-use" period the Temporary Comfort period is
also overridden and the room operating mode reverts to Economy mode (3).
In Room 2, in the evening, there are still people in the room beyond the "building-in-
use" period (4). However, at the end of the building-in-use period the room operating
mode still changes to Economy mode. An alarm can also be tripped, if required.
10385D03
06:00 22:00
Use Building in use
time
schedule Building not in use
Building protection
Occupancy Occupied
time 08:00 18:00
schedule Standby
Room 1 and 2
Unoccupied
Effective Comfort
room op. mode
Room 1 Precomfort
1) 2) 3)
Economy
Protection mode
Presence Occupied
detector 4)
Room 2 Unoccupied
Comfort
Effective 4)
room op. mode Precomfort
Room 2
Economy
Protection mode
34/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
5.4 Determining the room operating mode
with Synco
The effective room operating mode of the room controller depends on the central Room
operating mode time schedule and/or on local influences such as window contacts,
presence detectors or room units.
The diagram below shows how these influences are processed by the room controller,
and their priority:
Central (ACS)
10784Z57en
Central Local Controller
(Synco controller)
Prio
Window contact 0.
DI 1.
1.
Enable Comfort
Protection
Bus 2.
Room operating
mode
Bus 3.
Presence detector
DI 3.
Room unit
PPS2 3.
STOP Note! If the room operating mode in the ACS (operating booklet) is AUTO, the priorities
1 to 3 apply.
If the room operating mode in the ACS (operating booklet) is Comfort, Precomfort,
Economy or Protection, these modes have absolute priority ("Prio 0").
The effects of Priority 1 and Priority 2 are similar in nature to states, which apply
continuously
The Priority 3 influences are treated as events.
The key factor is the moment at which the state changes (trigger edge).
If the mode is later changed by another source of priority 3, the last change
applies.
35/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
5.4.1 Local control of room operating mode via the
window contact input
DI 1.
1.
2.
3.
DI 3.
PPS2 3.
Effective The table below shows the effective room operating mode as a function of the window
room operating mode contact input.
The window contact is connected directly to a digital input of the room controller (see
page 86).
PPS2 3.
36/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
The states are
State Description
Enabled Influences of priority 3 (input Room operating mode,
presence detector, room unit) are enabled.
Disabled Influences of priority 3 are disabled.
The effective room operating mode is Economy.
Comfort and Precomfort are enabled locally in the controller with the following
parameter in the Room unit menu, page 93:
Local
Central (ACS)
Controller
Synco controllers can command the RXL controllers
Prio via Room operating mode
Central 0.
(Synco controller)
DI 1.
1.
2.
3.
DI 3.
PPS2 3.
Priorities For the room controller, the room operating modes Comfort, Precomfort and
Economy are Priority 3 and can therefore be changed later by a presence detector or
room unit.
The room operating mode Protection has first priority, and the presence detector and
room units are therefore disabled.
37/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
5.4.4 Local control of room operating mode via
presence detector
DI 1.
1.
2.
3.
DI 3.
PPS2 3.
The presence detector is connected directly to a digital input of the room controller (see
page 86).
Effective The table below shows the two possible occupancy states and the resulting effective
room operating mode room operating mode.
38/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
5.4.5 Local control of room operating mode with a room unit
2.
3.
DI 3.
PPS2 3.
The room unit is connected to the PPS2 interface on the room controller.
It displays the effective room operating mode in a simplified form, and can also be used
to change it.
State Description
Auto Effective room operating mode is Comfort
Reduced mode in the room, depending on the Priority 1, 2 and 3
influences:
Effective room operating mode is Precomfort, Economy or Protection.
Effective The change in the effective room operating mode is event-driven, the key factor
room operating mode being the moment when the button on the room unit is pressed.
The Effective occupancy can cause the effective room operating mode to change
again the last command always applies.
The table below shows the effect of the /Auto button on the effective room operating
mode of the room controller.
1) Comfort mode is operative for the pre-defined Temporary Comfort period (see
page 86). The room controller then reverts to Economy.
39/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
5.4.6 Synco Examples
The following examples show two typical applications of the time schedule in
conjunction with local control of the room operating mode.
10385D04
06:00 08:00 12:00 13:00 17:00 20:00
Time schedule Comfort
Room operating
mode Precomfort
Economy
Protection
Economy
Protection
The room operating mode in Rooms 1 and 2 of a building is determined centrally by the
Room operating mode time schedule.
Comfort mode is then initiated locally via the room unit (Room 1) or presence detector
(Room 2).
40/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
The occupant(s) of Room 1 are working overtime. At 18.00 hours the room operating
mode changes to Economy, even if the room unit is set to Auto (1).
Comfort mode can now be re-activated with the Auto switch on the room unit (2).
Comfort remains active for the pre-defined Temporary Comfort mode period (see
page 86).
In Protection mode however, the Temporary Comfort period is also overridden and
the room operating mode changes to Protection (3).
In Room 2, in the evening, there are still people in the room beyond the "building-in-
use" period (4). However, at the end of the building-in-use period the room operating
mode still changes to Protection. An alarm can also be tripped, if required.
10385D05
06:00 08:00 18:00 20:00
Time schedule Comfort
Room operating
mode Precomfort
Economy
Protection
Effective Comfort
Room operating
mode Precomfort
1) 2) 3)
Room 1
Economy
Protection
Comfort
Effective 4)
Room op. mode Precomfort
Room 2
Economy
Protection
41/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
5.5 Determining the room operating mode
without a bus (stand-alone)
If no bus is connected, the effective room operating mode of the room controller
depends on local influences such as window contacts, presence detectors or room
units.
The diagram below shows how these influences are processed by the room controller,
and their priority:
Local Controller
DI 1.
Presence detector
DI 3.
Room unit
10785Z58en
PPS2 3.
STOP Note! The effects of Priority 1 and Priority 2 are similar in nature to the states, which
apply continuously
The Priority 3 influences are treated as events.
The key point in time is the moment at which the state changes (trigger edge).
If the mode is later changed by another source of priority 3, the last change
applies.
Note If there is no bus connection, the controller assumes the following defaults:
Use = Building in use
Occupancy = Occupied
42/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
5.5.1 Local control of room operating mode via the
window contact input
Prio
Whenever a window is opened, the room controller always
DI 1.
switches to the Protection room operating mode, i.e. the
heating or cooling output is reduced to a minimum.
DI 3.
PPS2 3.
The window contact is connected directly to a digital input of the room controller (see
page 86).
Effective The table below shows the effective room operating mode as a function of the window
room operating mode contact input.
Prio
A presence detector detects the presence of people in the
DI 1.
room and controls the room operating mode of a room
controller.
DI 3.
PPS2 3.
The presence detector is connected directly to a digital input of the room controller (see
page 86).
43/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
Effective The change in the effective room operating mode is event-driven, the key factor
room operating mode being the point at which the effective occupancy changes.
The room unit (which is also Priority 3) can cause the effective room operating mode
to change again the last command always applies.
Prio
The /Auto button on the room unit can be used like an
DI 1.
occupancy button.
The room user can use it to switch the HVAC system "on" or
"off".
DI 3.
PPS2 3.
The room unit is connected to the PPS2 interface on the room controller.
It displays the effective room operating mode in a simplified form, and can also be used
to change it.
State Description
Auto Effective room operating mode is Comfort
Reduced mode in the room, depending on the Priority 1 or 3 influences:
Effective room operating mode is Precomfort, Economy or Protection.
Effective The change in the effective room operating mode is event-driven, the key factor
room operating mode being the moment when the button on the room unit is pressed.
The presence detector (which is also Priority 3) can cause the effective room
operating mode to change again the last command always applies.
44/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
The table below shows the effect of the /Auto button on the effective room operating
mode of the room controller.
1) Comfort mode is operative for the pre-defined Temporary Comfort period (see page
86). The room controller then reverts to Economy.
The example below shows how local influences interact to affect the room operating
mode.
Room 3: In order to force the basic room operation mode to be Economy, one of the
open Digital inputs is parameterized as Occupied = Contact closed (see page 86),
thus simulating a presence detector in state "unoccupied.
Starting from Economy, the timer (Temporary Comfort period: see page 86) is
available.
The room has a room unit with the timer enabled. It can be used to set the room
operating mode to Comfort (2). It reverts to Economy when the window is opened,
(3) when the timer period expires (4), or when the /Auto switch is pressed again
(5).
45/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
10385D70
Economy
Protection
10385D71
Window contact Window open 1) 1)
Room 2 Window closed
Auto
/ Auto button 2) 2)
on room unit
Room 2
Economy
Protection
10385D72
Economy
Protection
46/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room operating modes 17 Sep 2010
6 Setpoint calculation
6.1 Description
The setpoints
– are defined in the tool during engineering.
– runtime-adjusted by the communication objects (DESIGO, Synco)
This does not apply to the Protection setpoints and the frost setpoint (page 25).
The effective room operating mode selects one setpoint each for heating and
cooling from the 8 setpoints.
These are the effective setpoints to which the controller executes control.
Define Shift
Tool 6.2 Runtime 6.3 Centrally 6.4 Locally 6.5
BUS
PPS2 BUS
10785Z40en
Comfort heating setpoint
Comfort cooling setpoint BUS
8 present setpoints
Frost setpoint
H C
BUS
Effective
PPS2 room operating mode
DI
47/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Setpoint calculation 17 Sep 2010
6.2 Setting the setpoints with the tool
A tool is used to set the temperature setpoints for the various room operating modes in
each room controller.
ACS Service The setpoints can be modified under Room temp setpoints:
48/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Setpoint calculation 17 Sep 2010
HandyTool: If setpoints are irrelevant for the application (e.g. heating setpoints for
chilled ceiling), they are hidden, and they are set equal to the Protection setpoints
internally.
STOP Note! The setpoints are stored in the EEPROM so that they are retained when the controller
is reset. If a value different from a previous value is received on the communication
EEPROM service
objects setpoints for heating and setpoints for cooling, a write process is triggered
life
in the EEPROM.
The service life of the EEPROM depends on the number of Write cycles.
STOP Note! Setpoints that have been changed by a tool (e.g. HandyTool) are overwritten by
PX-KNX during start-up of the room controller!
Management station The Comfort, Economy and Precomfort setpoints can be adjusted centrally for heating
and cooling via the building automation and control system.
Summer/winter Central setpoint shifts in particular are used for summer/winter compensation, for
compensation example. The summer/winter compensation feature causes a gradual increase in room
temperature as a function of the outdoor temperature. This prevents too great a
difference between the indoor and outdoor temperature in summer and increases
overall comfort in winter.
Internal correction by The room controller corrects the setpoints resulting from central shift by applying the
controller following rules
Comfort setpoints:
The value for the spacing must not be below the original value A .
Precomfort setpoints:
The value for the spacing to Comfort setpoints must not be below the original values
B .
49/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Setpoint calculation 17 Sep 2010
Winter compensation Original Summer compensation
values
Setpoints Sp [°C]
Protection cooling
Economy cooling
Precomfort cooling
B
Comfort cooling
A
Comfort heating
Precomfort heating
Economy heating
10385D107
Protection heating
TOA
If setpoints are shifted locally and corrected by the controller, local shift is applied.
If multiple sources command local setpoint shift, "last one wins" applies.
Function Comfort:
– The Comfort setpoints for heating and cooling are shifted in parallel A .
– The original spacing heating – cooling is maintained.
Internal correction by The room controller corrects the setpoints as follows following a local shift:
controller Precomfort::
– The values are shifted in parallel to the Comfort values B .
– The cooling setpoint cannot be lowered following central shift C .
– The heating setpoint cannot be increased following central shift C .
Economy:
– The cooling setpoint cannot be lowered following central shift C .
– The heating setpoint cannot be increased following central shift C .
– The value is shifted together with the Precomfort value D .
Protection:
– Protection values are absolute E .
– A minimum spacing between Comfort heating and Comfort cooling of 0.5 K is
maintained F .
50/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Setpoint calculation 17 Sep 2010
Setpoints Sp [°C] E
Protection cooling
D
Comfort cooling A
Comfort heating
F
Precomfort heating 0.5 K C
Economy heating
10385D108
D
Protection heating
Offset [K]
- 0 +
Local setpoint shift
Note Upon a change from Comfort and Precomfort to Economy or Protection, the setpoint
shift can be reset (see page 92).
51/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Setpoint calculation 17 Sep 2010
7 Temperature measurement
7.1 Room temperature measurement
Sources The value valid for temperature control can originate in various sources:
– A room unit via PPS2 7.1.1
– An analog sensor via B1 7.1.2
– Mean value of several sensors 7.1.3
Invalid temperature If none of these sources supplies a valid room temperature, the following will happen:
the controller uses the mean value from the effective heating and cooling setpoints
for control until a valid measured value is again received
the controller issues an alarm "Room temp. sensor error"
if slaves are connected, they receive an invalid temperatur (327.67°C)
if a room unit is connected to a slave, the slave uses the temperature value of its
room unit when two heartbeat periods have elapsed.
RXL...
10785Z12
RXL...
10785Z13
52/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Temperature measurement 17 Sep 2010
The sensors connected to terminal B1 can be tasked with different functions:
Parameterization Description
Room Room indoor air sensor (can also be used for
averaging, see below).
Return air Return air sensor
(refer also to Section 9.2.4, "Periodic fan kick")
Only measured value Not supported.
acquisition
Supply air (cascade) Supply air temperature for cascade control.
The sensor is automatically configured as a supply
air sensor if application FNC08 is selected.
No sensor No sensor connected
(basic setting, except for FNC08)
Note The sensor is parameterized under fan control for tool architectural reasons:
ACS Service Select Fan control, Temperature sensor B1 (see page 79).
53/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Temperature measurement 17 Sep 2010
7.1.3 Averaging analog input & PPS2 interface
In large spaces it can be useful to measure the room temperature in two locations and
to determine an average value. If both a QAX3… room unit and a QAA24 LG-Ni1000
sensor are connected to a controller, the measured room temperature is automatically
based on the average value from both sensors. The automatic detection feature
prevents miscalculation.
A QAX34 / QAX84 will display this average value.
10785Z14
QAA24 QAX3...
B1 PPS2 (CP+, CP-)
RXL...
Notes In order to determine the average value, the sensor must be configured as a room
temperature sensor
Return air temperature In fan coils with a return air sensor (at B1), the controller must be configured
accordingly (see page 80).
– The temperature sensor in the room unit is ignored in this process (the signal is not
averaged).
– A QAX34.1 room unit displays the value of B1.
The value of the local sensors (PPS2 and B1) can be corrected in the tools
(see page 94).
For the FNC10, FNC12, and FNC18 applications, the outside air temperature must be
available as a bus information.
In conjunction with Synco, the outside air temperature is sent in a special zone.
54/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Temperature measurement 17 Sep 2010
8 Control sequences
8.1 Fan coils with valve control
8.1.1 Four-pipe fan coils - With valve control
The applications for 4-pipe fan coils each have a proportional heating and proportional
cooling sequence. The controllers operate with a PI algorithm optimized for thermal or
motorized valve actuators. (For simplicity, the diagrams below only show the P-control
action).
10385S01
YC
YH
Q1
T
B1
The control sequences come into operation at the effective setpoints for heating and
cooling (see page 47).
Y [%] Y Output signal
H C TR Room temperature
100
SpH Effective heating setpoint
SpC Effective cooling setpoint
YH YC
H Heating sequence
10385D08
C Cooling sequence
YH Heating valve
0 YC Cooling valve
SpH SpC TR [°C] B1 Return air sensor
Q1 Fan
Actuator type Different applications support different valve actuators, and these do not all require the
same number of outputs on the controller. The tool displays the actuators suitable for
the selected application. Selection occurs at the engineering stage (see page 58).
55/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.1.2 Two-pipe fan coils - With valve control
Two-pipe fan coils have only one proportional control sequence. This may be
configured for heating, cooling or changeover operation, as required. The controllers
operate with a PI algorithm optimized for thermal or motorized valve actuators. (For
simplicity, the diagrams below only show the P-control action).
10385S02
YHC
Q1
T
B1
The control sequence comes into operation at the effective setpoint for heating or
cooling (see page 47).
Y [%]
Heating only
H
100
10385D09
YHC
0
SpH TR [°C]
Y [%]
Cooling only
C
100
10385D10
YHC
0
SpC TR [°C]
Y [%]
Changeover Change-over
(heating or H C
100
cooling) Y Output signal
TR Room temperature
10385D11
Selecting the control The control sequence must be selected when the controller is engineered:
sequence Heating only, Cooling only or Changeover.
56/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
ACS Service Select sequences under Parameterizations.
Actuator type Different applications support different valve actuators, and these do not all require the
same number of outputs on the controller. The tool displays the actuators suitable for
the selected application. The valve type must be selected at the engineering stage (see
page 58).
Changeover Changeover is only possible if the control sequence parameter is set to changeover.
In this case, a changeover command (heating or cooling) is essential. In the absence of
the required information (e.g. due to problems with data communication), the controller
operates as follows:
– After a reset, the controller operates in heating mode until another changeover
command is received.
– If the transfer of data is interrupted, the controller remains in the last valid room
operating mode.
57/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.1.3 Actuator type selection
STOP Note! All actuators have threads suitable for fitting to both normally-closed (push to open) and
normally-open (pull-to-open) valves. However, the RX applications do not support
inverse control, which means that only actuators with a pulling action can be used with
"pull-to-open" valves and only actuators with a pushing action can be used with "push-
to-open" valves. This is why, in RX applications, valves with mounted actuators are
always closed when de-energized.
Directly connected Different applications support different valve actuators, and these do not all require the
valve actuators same number of outputs on the controller.
Thermal and electromechanic actuators thus require one output, motorized actuators
two.
80262
(motorized) RXL21.1 Y1
M Heating
Y2
Y3
M Cooling
Y4
Electro- RXL21.1
Y1 M Heating
mechanic
Y3 M Cooling
(ON / OFF)
RXL22.1
Y1 M Heating
Y2 M Cooling
80263
Two-pipe fan coil (thermal) RXL21.1
Y1 Heating or cooling
RXL22.1
80264
(motorized) RXL21.1 Y1
M Heating or cooling
RXL22.1 Y2
Electro- RXL21.1
mechanic RXL22.1 Y1 M Heating or cooling
(ON / OFF)
58/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
Thermal valve actuators It is not possible to ensure exact parallel running of more than one thermal valve
actuator. If several fan coils are driven by the same controller, preference should be
given to motorized actuators.
If thermal actuators must nevertheless be controlled in parallel, third-party thermal
must be parameterized regardless of manufacture. This applies also if an external
power amplifier is used to drive the actuators.
Thermal actuators operate at a raised temperature. To ensure a fast response, these
actuators are constantly preheated to a slightly higher temperature (5% – 1 s ON /
19 s OFF). They therefore continue to receive pulses from the controller even when
closed.
Thermal third party Möhlenhoff actuators have been tested successfully in our HVAC laboratory.
devices
Electromechanic third- Electromechanic third-party devices often have different runtimes for opening and
party devices closing. For optimal control, the longer of the two running times must be parameterized.
Synchronize When switching on the controller, after parameterization, after switching from test mode
to normal mode and for valve protection (unblocking, see page 62), the actuators are
synchronized:
Thermal heating and cooling valve actuators are controlled with "Open" for 5 minutes
(50% – 1 sec ON/ 1 sec OFF), then again for 5 minutes with "Close" (5% – 1 sec
ON/ 19 sec OFF).
Motorized actuators are first opened (110% of the runtime) and then closed (110%
of the runtime).
Parameterization The actuator type used must be defined at the engineering stage:
59/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
HandyTool Parameter Short name Basic setting
*060 Actuator type heating / cooling valve STP72E (FNC08: SSB81)
Settings
STE71 1 SSA81 10 Electromech. third-party devices 252
STE72 2 SSB81 11 Thermal third-party devices 253
STA71 3 SQS81 12 Motorized third-party devices 254
STP71 4 SSC81 13
STA72E 5 SSP81 14
STP72E 6
With motorized actuators (conventional and bus actuators), third-party devices can
also be connected. The actuator running time can be adapted and an offset set
accordingly.
The offset considers the time between the electric pulse and the actual mechanic
movement of the actuator. This is especially important for fast running actuators.
For fast actuators, select valve type "Motoric 3rd party devices ".
60/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
HandyTool See Parameters in the last column of the table below
Motorized and electromechanic valves.
1) In the case of 2-pipe applications (changeover), the parameter *62 (Running time
cooling valve) is visible in the HandyTool, but has no effect.
Notes For FNC: 10, 12, 18, electromechanic actuators are not allowed for load reasons.
Also, thermal valves do not have parallel operation of Y1 / Y2 and Y3 / Y4.
Reduce bus load The bus load should be reduced by disabling the bus outputs.
61/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
ACS Service Select Sequences.
To prevent valves from seizing after long periods of inactivity (e.g. cooling valves in
winter) the valves are operated from time to time. The valve actuators are operated in
such a way as to waste as little heating or cooling energy as possible.
The valve exercise function is triggered if the valve has been closed for ca. 91 hours
without interruption.
62/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.2 Fan coils with damper control
In FNC20, a single damper actuator is used for control of both heating and cooling.
In application FNC20, which uses a damper instead of a valve for modulating control of
the room temperature, a constant volume of water flows through the two heat
exchangers. Depending on the demand, the air flow is guided either through the
heating coil or through the cooling coil, causing a change in the resulting mixed air
temperature.
Y [%]
H N C
100
Y Damper position
TR Room temperature
YM SpH Effective heating setpoint
SpC Effective cooling setpoint
10385D12
H Heating sequence
N Dead band (recirculated air)
C Cooling sequence
0 YM Damper actuator
SpH SpC TR [°C]
The heat-exchanger configuration may call for asymmetric runtimes for heating and
cooling; these can be set individually. At the mid-point where the air flow switches from
heating to cooling, the time period associated with the mechanical dead band can also
be preset.
63/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
HandyTool See Parameters in the last column of the table below
64/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.3 Fan coils with an electric heating coil
In addition to controlling heating and/or cooling valves, some applications also provide
an output for the control of an electric heating coil. This is then operated as a reheater,
i.e. it only comes into operation when the heating valve is fully open.
Notes With motorized actuators, the electric reheater is only enabled when the heating
valve is fully open.
In the case of thermal actuators, the electric reheater is not enabled until the thermal
actuator has been operated at maximum flow (100%) for at least 2 minutes.
YR D3
Y Output signal
TR Room temperature
YC SpC Effective cooling setpoint
SpH Effective heating setpoint
H Heating sequence
C Cooling sequence
YH
YH Heating valve
Q1 YC Cooling valve
YR Electric reheater
D3 Safety thermostat
T
B1 Return air sensor
B1 Q1 Fan
1-step Modulating
Y YR YR, Y
1K
H H
100% ON 100%
10385D54
YR
10385D55
YH
YR
YH YC YC
0% OFF 0%
TR [°C] TR [°C]
SpH SpC SpH SpC
65/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.4.2 2-pipe fan coils with electric reheater
10385S23
YR D3
YHC
Selection of the control The control mode must be selected at the engineering stage:
mode heating only, cooling only or changeover
Electric reheater with The electric reheater also operates with "Cooling only" and "Change-over" in cooling
cooling-only or mode. In this case, the heating setpoint (SpH) is used for control.
changeover applications
1-step Modulating
Y YR YR, Y
Heating only 1K
or c/o = Heating H H
100% ON 100%
10385D56
YR
YHC
10385D57
YR YHC
0% OFF 0%
TR [°C] TR [°C]
SpH SpH
Y YR YR, Y
Cooling only 1K
H C H C
or c/o = Cooling 100% ON 100%
10358D58
YR
YHC YR YHC
10385D59
0% OFF 0%
TR [°C] TR [°C]
SpH SpC SpH SpC
Y YR Change-over YR, Y
Changeover 1K
Change-over
H C H C
100% ON 100%
10785D61
YR
10785D62
YR
YHC YHC
0% OFF 0%
TR [°C] TR [°C]
SpH SpC SpH SpC
66/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.4.3 The electric reheater
Controller output In the case of the RXL22.1 room controller, the electric reheater is switched directly via
output Q44 (max. 1.8 kW resistive).
Safety thermostat The controller output of the electric reheater can be disabled locally via a safety
thermostat connected to one of the hardware inputs. The alarm input and the way in
which it operates can be configured with the tool (see "Digital inputs", page 86).
When the safety thermostat trips, an alarm is generated, which is output via the
communication object Alarm (see page 91).
Desired output The "position" of the electrical reheater is assumed by the integration station after
integration in DESIGO; the same applies to Synco.
Bus load reduction If the LTE bus information no longer is required, it can be switched off.
Type of electric heater Single-stage or modulating control can be selected in the tool for the electric heater
battery.
67/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
HandyTool See Parameters in the last column of the table below
Power demand If an electric reheater is used, the controller makes the present power demand
available on the bus.
In order for this to happen, the capacity of the heater battery must be written to the
controller via the tool.
68/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.5 Fan coils with LTHW radiator (FNC18)
The radiator sequence can also be used for other heating types, e.g. floor heating.
However, the control parameters are not optimized for this.
The heater battery of the fan coil operates in a cascade with the radiator.
The control sequences come into operation at the effective heating setpoint.
B1
10385S08
T
D3 YHC
T
Q1
B1 T
YH
Y [%] Change-over
H C Y Output signal
100 TR Room temperature
SpH Effective heating setpoint
H Heating sequence
10385D16
69/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.5.1 Configuration and parameterization
The radiator as an additional heating sequence has its own settings for the valve
actuator and runtime. The principles are described in section 8.1.3.
ACS Service Select Sequences, Sequences, Act type heating surf valve:
70/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.5.2 Position values for radiator valve actuators
The position value of the valve actuator is assumed by the integration station after
integration in DESIGO; the same applies to Synco.
Bus load reduction If the LTE bus information no longer is required, it can be switched off.
This application can have two different heat demand signals; one from the air-to-air
heat exchanger and one from the radiator. With Synco, the demand signals are
mapped as 2 bus signals (see 11.4, Heating and cooling demand).
In situations where (owing to large internal heat gains) there is no heating demand from
the room despite a low outdoor temperature (supplied via the bus), large window
surfaces can impair indoor comfort (through radiated cold and the downward flow of
cold air).
Function A radiator located under the window can be used to “brake” the downward flow of cold
air and compensate for cold radiation.
To achieve this, the radiator is switched on whenever the outdoor temperature drops
below a predefined value (the Outdoor temp. 0% valve position).
The maximum heating output (set under Max. Valve Position) is reached at the "coldest
outdoor temperature" (which can be set under Outdoor temp. max. valve position).
Heating output
10385D17en_01
100%
Max. valve position
0% TOA
71/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
Note The controller adds the values representing the valve position for downdraft
compensation and the valve position for the heating sequence.
– If the room temperature rises as a result of the downdraft compensation feature, the
heating sequence reduces the opening of the associated valve, so correcting the
room temperature.
– When the sequence reaches zero, the room temperature is increased by the residual
heat from the downdraft compensation feature.
Controller output The heat output calculated by the controller is achieved as follows:
LTHW radiators with The valve is opened to the heat output value [%].
motorized valve actuators
LTHW radiators with The minimum heat output is 25% (LED08: 10%):
thermal valve actuators 400 seconds "OPEN" (1s On, 1 s Off) 1200 s "CLOSE" (1s On, 19 s Off)
Heat output 50%:
400 seconds "OPEN" (1s On, 1 s Off) 400 s "CLOSE" (1s On, 19 s Off)
Heat output 80%:
1600 seconds "OPEN" (1s On, 1 s Off) 400 s "CLOSE" (1s On, 19 s Off)
The long cycle time ensures that the valves are fully opened and closed.
In a network containing several room controllers, the opening of the Siemens thermic
actuators is staggered to prevent the heating load from fluctuating.
Note In fan coils with parallel operation of a thermal radiator valve actuator and a thermal
heating/cooling valve actuator, the valve actuators are driven alternately by the
controller.
72/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
Enabling the function The following conditions must be fulfilled:
The outside air damper mainly serves to provide the room with fresh outside air. In
addition, the outside air can be used to cool the room.
The outside air damper is always operated in Comfort and Precomfort modes.
In Economy mode, it is operated only in conjunction with the following special functions
(see page 87 ff. for a description):
Pre-Cool, Free Cool, Night Purge and Fan-Only.
Control sequence, The damper is controlled through a stroke model calculated from the runtime of the
damper actuator actuator.
The Economizer setpoint Outside air temp. min. damper pos. defines at which outside
temperature the outside air damper is opened to an adjustable minimum position.
This minimum position ensures a constant air supply below the outside air temperature.
The Outside air temp. min. damper pos. setpoint should be selected to ensure that
there is at least a difference of 4 K between this value and the cooling setpoint and that,
at the same time, no draught is caused by the inflow of cold outside air.
The Economizer setpoint should not be much lower than the Comfort heating setpoint,
otherwise too much cool air would come into the room during the heating sequence.
Above the Outside air temp. min. damper pos. setpoint, the damper is opened
beyond the minimum position if:
– the outside temperature is below the room temperature and
– either the room controller is in Comfort or Precomfort room operating mode
or
one of the special functions "Pre-Cool", "Free Cool", "Night Purge" or "Fan-Only" is
active
Y [%]
73/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.6.1 Configuration and parameterization
Outside air temperature The outside temperature is transmitted to the room controller via the bus.
See "Outside temperature via bus (FNC10, FNC12, FNC18)", page 54.
Basic HandyTool
Parameter outside air supply setting Range Resolution parameter
Outdoor temp. min. damper pos. 16°C 10 °C...40°C *) 0,5°C *073
Outside air damper runtime 150s 0 ... 360s 1s *074
Min. damper position 0% 0 ... 100% 1% *075
The use of the outside-air damper can only be implemented in conjunction with the
RXL21.1 controller. In this case, the AC 24 V 3-position damper actuator is connected
to the outputs Y3 and Y4.
74/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
8.7 Room supply air cascade control (FNC08)
Room supply air cascade control makes it possible to reach the required room
temperature very quickly. On the basis of the measured room temperature, the
controller calculates a setpoint for the temperature at the air outlet of the fan coil.
A limit value can be applied to this temperature to prevent the introduction of
uncomfortably cold / warm air into the room.
This function is not available for electric heaters, as these cannot be controlled well
enough with RXL controllers.
Discharge air
T Room sensor
sensor T
Fancoil H
Room
Max. disch. air
Min. disch. air
10385z121en
signals
Room controller FNC08
STOP Note! This function is possible in conjunction with motorized valve actuators only.
See also sections 8.1.1 through 8.1.5.
75/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
HandyTool See Parameters in the last column of the table below
Controller inputs The supply air temperature sensor is connected to input B1 of the controller.
The room temperature must be measured with the room sensor installed in the room
unit.
B1
temperature
Room temperature
CP+, CP– T
76/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Control sequences 17 Sep 2010
9 Fan control
9.1 Description
Room unit Certain room units allow the user to select the fan speeds MANUALLY (in Comfort
mode only).
The symbol " " does not mean “Fan Off”, but "automatic operation at reduced
setpoints", e.g. Precomfort mode.
In the reduced room operating modes, the fan speeds CANNOT be selected
manually.
Automatic mode In automatic mode, the fan speeds are controlled in accordance with the response of a
PI controller to the control deviation.
The relays are operated in alternation. Example: When the controller switches from
Speed 1 to Speed 2, first the relay for Speed 1 switches off (A), and then, after a delay
of 1 s, the relay for Speed 2 switches on (B). The same applies in reverse when
switching down.
Y Q 10385D19
Single-speed (relay Q14)
100% Valve sequence
Fan
H C
Q14
TR [°C]
SpH SpC
10385D20
2-speed (relays Q14, Q24) Y Q H C
a a Relays switch alternately
100%
Example:
(A) Speed 1 relay OFF
(B)
Q24
(B) Speed 2 relay ON
Q14 (A) after delay of 1 s
TR [°C]
SpH SpC
10285D21
Three-speed (relays Y Q
H C
Q14, Q24 and Q34) a a
100% Y Output signal
TR Room temperature
Q34 SpH Effective heating setpoint
SpC Effective cooling setpoint
Q24 H Heating sequence
C Cooling sequence
Q14 Q14 1. Fan speed 3
Q24 2. Fan speed 3
TR [°C] Q34 3. Fan speed 3
SpH SpC
77/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Fan control 17 Sep 2010
The fan runs at fan speed 1 for as long as the heating/cooling valve remains partly
open, or in the case of an electric heater, while the heater is in operation.
It is enabled as soon as the controller specifies a valve position or an electric
heating output greater than 0.
It is disabled when the controller specifies a valve position or electric heating output
equal to 0 and the minimum fan switch-on time has elapsed.
When the valve is fully open or the electric heater is operating at 100% (in the range
marked "a"), a sequence controller enables fan speeds 2 and 3.
In addition to the control deviation, an integrator also comes into operation in the
range marked "a". This ensures that the fan switches to speed 2 (and later to speed 3)
if the control deviation has remained >0 for a period of time, even if the room
temperature has not reached the switching point for fan speed 2.
The fan does not switch back down to speed 2 and later to speed 1 until there has been
no control deviation for a period of time.
If the room operating mode changes (Comfort, Economy etc.), the sequence
controller is reinitialized by the application. This produces the following response: If the
room temperature is within the dead band after the change of room operating mode,
the controller specifies valve positions of 0%, or in the case of electric heaters, these
are disabled, and the fan is switched off. However, any delay time (minimum switch-on
time, switch-off delay in conjunction with electric heating coil / reheater or periodic fan
kick)) is allowed to expire first.
78/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Fan control 17 Sep 2010
9.2 Fan parameterization
9.2.1
9.2.2
7.1.2
9.2.4
9.2.3
Note: For other operating states but Comfort, the fan is enabled by
the fan algorithm.
Warning! With FNC03 (electric re-heater) the fan must not be
switched off while the re-heater is active, and a fan overrun must be
assured, in order to avoid overheating.
1-speed Single-speed fan control with relay Q14. 1
2-speed Two-speed fan control with relays Q14 and Q24. 2
3-speed Three-speed fan control with relays Q14, Q24 and Q34. 3
79/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Fan control 17 Sep 2010
Fan control *093
Auto Fan speeds are changed over automatically 1
(by the room controller). Manual fan speed presetting is possible only
in operating state Comfort.
Manual No automatic fan control. For example, the fan is operated manually 0
on the fan coil itself and can be enabled via relay Q14 (relay Q14 is
ON in Comfort mode).
Fan startup behavior The motors of some fans do not have a sufficiently powerful torque to set the fan in
motion at the lowest speed. Multi-speed fans are, therefore, always started at the
highest speed and then switched back to fan speed 1.
Note This feature also applies to manual fan-speed control via the room unit.
Each fan speed remains on for a pre-defined minimum period before switching to the
next higher speed. This enables the controller to adjust to the fan speed
When switching off an electric reheater (FNC03, FNC05), it is essential to ensure that
the residual heat from the electric heater battery is dissipated.
For this reason, the fan is switched off only after a delay. The overrun time can be
defined.
Return air sensor If the room temperature is measured with a return air sensor in the fan coil (connected
to input B1 at the room controller, see Section 7), the fan must be switched on to
ensure that the effective room temperature is measured correctly.
From version V2.36, a reduced functionality (without time values for Comfort and
Economy) is available even if no return air sensor is parameterized.
Note! For tool architecture reasons, those time values are visible and settable in ACS
and in the HandyTool although not supported by the controller.
80/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Fan control 17 Sep 2010
Function The fan can be enabled at the lowest speed at regular intervals. While the room
temperature remains between the effective setpoints SpH and SpC, fan speed 1 is
always on for the predefined minimum runtime after expiry of the duty cycle.
Y 10385D22en
Q14
0
t [h:mm]
From V2.36, this function no longer depends on the sensor selection, i.e. is available
not just at the return air sensor.
With a setting of 90 min. (or 360 min), the display changes to "Off".
This indicates that the function is disabled.
When the measured temperature moves outside the dead band, i.e. above or below
the effective heating/cooling setpoint, the fan switches on before the periodic fan kick
has expired.
When the room operating mode switches from Economy to Precomfort or between
Precomfort and Comfort, fan speed 1 is enabled for the minimum runtime and the
periodic fan kick starts.
81/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Fan control 17 Sep 2010
10 Master/slave
10.1 Description
T A B B
10785Z17
Room 321 Room 322 Room 323
Controller A is configured as the master controller and controls the room temperature.
Controllers B are configured as slaves and operate in parallel with Controller A.
STOP Note! A slave controller may be controlled by one master controller only. A master,
however, can control any number of slaves, subject to the limits of the bus system
(topology, bus load etc.).
Parallel operation of thermal valves among other factors primarily depends on the
supplied voltage. We recommend to parameterize "3rd Party Thermic" for thermal
valves regardless of make.
Master/slave bindings are only possible between controllers with the same version
(ASN) and featuring the same applications and settings.
Parameter Description
Master Normal control.
Slave The slave controller is controlled by a master controller via the bus.
The master and slave controllers operate in parallel.
The room temperature is measured only by the master.
Master-Slave with zones For master-slave operation the controllers must be parameterized accordingly and the
master / slave zones must be set correctly.
Example M S S
Rooum 321 322 323
Geogr. zone 5.1.1 5.2.1 5.3.1
Master / Slave Master Slave Slave
M/S zone 5.1.1 5.1.1 5.1.1
Note Geogr. zone und M/S zone need not bet he same. However, every day work is easier
because you see directly to which master a slave belongs.
82/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Master/slave 17 Sep 2010
ACS Service Select Master/Slave:
Notes The master/slave function requires that all 3 M/S zones have the same name
If the master/slave function is not required, the M/S zone should be disabled (to limit
the load on the bus).
83/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Master/slave 17 Sep 2010
10.2 Peripheral functions
Room units in master / The room controllers and room units can be configured as master or slave devices. A
slave configurations number of rules must be adhered to in this process.
When more than one room unit is used in a master/slave configuration, all such room
units must be of the type with a button for setpoint adjustment. In the case of room units
with a mechanical setpoint adjuster, only one room unit may be connected. (Room
units with mechanical setpoint adjusters and those with pushbuttons for setpoint
adjustment must not be combined.)
Bus
Permissible combinations Room units with
10785Z23_01
pushbutton setpoint
adjustment (more than Master RXL... Slave RXL...
one of this type allowed)
QAX34.1
QAX34.1
Bus
Room units with a
10785Z24_01
mechanical setpoint
adjustment (only one unit Master RXL... Slave RXL...
of this type allowed)
Auto
- +
QAX31.1,
QAX33.1
STOP Caution Room units with a mechanical setpoint adjuster must NOT be used in configurations
where the room unit is connected via the room controller to a building automation
system and controlled via bus by Setpoint shift for heating / cooling (see pages 49,50).
Bus
Prohibited combinations Do not use more than one
room unit with a
10785Z25_01
Auto Auto
- + - +
QAX33.1 QAX33.1
Bus
Do not combine room
10785Z26_01
- +
QAX33.1 QAX34.1
84/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Master/slave 17 Sep 2010
11 General or central functions
ACS Service The following functions are enabled or configured under General or Central functions.
11.1
11.2
11.3
*)
11.13
*) Room number and Device name do not influence the application; they are used only
for plant documentation purposes. We recommend to use this feature.
HandyTool The general and central functions are set with parameters 117 – 137. For detailed
information, refer to the individual sections.
85/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies General or central functions 17 Sep 2010
11.1 Digital inputs
The following volt-free contacts can be connected to digital inputs D1 and D2:
Presence detector or window contact (details of this function see Section 5).
Safety thermostat electric heating coil / reheater (for details of this function, see page
65).
Safety thermostat outdoor temperature (for details of this function, see page 71).
Note Do not connect the same type of sensor/functions to both digital inputs.
The controller would ignore the second input.
If the room controller is set to Economy mode and the associated room unit is switched
to Auto (Comfort), the controller maintains Comfort mode for the period defined by the
temporary occupancy override time (veto) and then switches to Economy.
This function is only available if the room unit concerned has a /Auto switch (see also
pages 31 and 39).
Basic
Parameter setting Range Resolution HandyTool
Temporary Comfort mode 60 min 0 ... 360 min 1 min *117
A switch-on or switch-off delay can be applied to the presence detector function. The
room controller only switches to Comfort or to Precomfort or Economy mode when the
delay time has expired.
Basic
Parameter setting Range Resolution HandyTool
On delay Occupancy detector 5 min 0 ... 90 min 1 min *119
Off delay Occupancy detector 5 min 0 ... 90 min 1 min *120
86/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies General or central functions 17 Sep 2010
11.4 Heating and cooling demand
To provide the required heating or cooling energy, the heating and/or cooling demand
from each room is transmitted to the building automation and control system.
Refer to the application example in section 3.4 for more detailed information on
heating/cooling demand.
Note In the case of changeover applications the real demand is transmitted, independent
from the state of the changeover input (therefore it might be that a controller demands
heat, if c/o = cooling and room temp < SpH).
The special functions described in sections 11.6 ff are triggered by the DESIGO
integration station or by the RMB795 Synco controller.
Disable special Triggering the special functions by the building automation and control system can be
functions disabled in each room controller via tool.
HandyTool Parameter for disabling: See last column in the above table.
87/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies General or central functions 17 Sep 2010
11.6 Boost heating (Morning Warmup)
This function is used to raise the temperature in a room as quickly as possible to the
Precomfort heating setpoint at the end of the night setback period.
100 Fan
Heating coil
10385D23en
0
SpHPcf SpCPcf TR
Initiating the function The function must be enabled via the building automation and control system
Terminating the function The function is disabled via the building automation and control system.
This function is used to cool rooms to the Comfort cooling setpoint, in readiness for
normal occupancy, using the outside air damper. Here, only the fan is active, not the
cooling coil.
100 Ventilator
10285D24
0
SpHCmf SpCCmf TR
Initiating the function The function must be enabled via the building automation and control system
Terminating the function – The function is disabled via the building automation and control system.
– When the outside air damper is disabled
88/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies General or central functions 17 Sep 2010
11.8 Pre-cooling (Precool)
This function is used to cool rooms to the Comfort cooling setpoint, in readiness for
normal occupancy. The fan and cooling coil are used here to precool the rooms.
Y [%]
100 Fan
Cooling coil
10385D25
0
SpHCmf SpCCmf TR
Initiating the function The function must be enabled via the building automation and control system.
Terminating the function The function is disabled via the building automation and control system.
This function is used for emergency heating when the room temperature or return air
temperature drops below the frost protection setpoint. The function is independent of
the effective room operating mode.
When using a radiator and a heated ceiling the valve opens 100 %.
An electric radiator is switched to the highest stage and remains there until the
temperature rises above the Protection heating setpoint again.
When the room temperature rises above the Protection setpoint, the controller reverts
to the original room operation mode (see 87).
Emergency Heat
10385D26
Normal operation
SpFr SpHPrt TR
Initiating the function The function must be enabled via the building automation and control system
89/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies General or central functions 17 Sep 2010
Terminating the function – The function is disabled via the building automation and control system
– If the room temperature rises above the Protection setpoint
This function (formerly Air flush) is only used in Precomfort and Economy room
operating modes.
The aim is to flush the building with as much outside air as possible to renew the room
air.
To achieve the maximum air change rate, the outside air damper (if available) is
opened fully (FNC10, FNC12).
Temperature control is switched off and the heating and cooling coils are disabled.
Outside air is only introduced if the room temperature is between the Economy heating
and Economy cooling setpoints.
Y [%]
0.5K
100 Fan
10385D27
0
SpHEco SpCEco TR
Initiating the function The function must be enabled via the building automation and control system.
This function is used to precool rooms to the Comfort cooling setpoint, in readiness for
normal occupancy. It uses both fan and cooling coil.
This function is meaningful only if low-tariff energy is available.
90/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies General or central functions 17 Sep 2010
Y [%]
100 Fan
Cooling coil
10385D28
0
SpHCmf SpCCmf TR
Initiating the function The function must be enabled via the building automation and control system.
Terminating the function The function is disabled via the building automation and control system.
11.12 Alarm
Room temperature frost If the room temperature or return temperature in a fan coil
application drops below the fixed frost protection limit (5
°C or adjustable for outside air applications), an alarm is
generated.
Outside air temperature In applications with outside air damper, a safety thermo-
frost stat in the outside air duct can be connected to the digital
input.
When integrated in DESIGO, the above described alarms are bundled and provided as
a common alarm.
91/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies General or central functions 17 Sep 2010
11.12.2 With Synco
The device listens on the bus and sends an alarm when it has highest alarm priority.
This ensures that the management station does not miss any alarms.
For more information on the alarm concept, see "Communication on the bus, Synco700
& RXB", CE1P3127.
When the system changes from Comfort or Precomfort to Economy or Protection mode
(see page 50), the setpoint shift can be canceled. This function can be enabled and
disabled via Central functions.
STOP Note! The setpoint adjustment can only be cancelled with the QAX34.1 and QAX84.1 room
units, which have an LCD display. Enabling this function in room units with a
mechanical setpoint adjuster (potentiometer) will cause errors in data transmission.
92/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies General or central functions 17 Sep 2010
11.14 Software version
HandyTool
Parameter HandyTool
Application set *236 424 = RXB21.1/FC-10
425 = RXB21.1/FC-11
426 = RXB22.1/FC-12
427 = RXL21.1/FC-10
428 = RXL21.1/FC-11
429 = RXL22.1/FC-12
Application version *237 *)
Operating system version *238 *)
KNX interface version *239 *)
*) This information serves to identify the controller's software version. You can use it in
case of a service request.
HandyTool
Parameter HandyTool
Device state *240
Hinweis In Service mode the device state is always = 0 because the application is not running.
93/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies General or central functions 17 Sep 2010
12 Room unit
Sensor correction The measured value of the built-in temperature sensor can be recalibrated to
compensate for radiation from a cold wall, for example.
Note This correction is also valid for a sensor that is connected to the analog input B1.
Setpoint adjustment The maximum setpoint adjustment range is as follows (see also page 50).
range
Parameter Basic setting Range Resolution HandyTool
Setpoint adjustment range ±3K ± 0 ... 10 K 1K *103
94/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room unit 17 Sep 2010
Local comfort mode A management station can use the communication object Enable Comfort (see
(with Syncoe only) page 36) to prevent the room operating mode from being higher than Economy (energy
conservation). Local comfort mode can be ignored by setting the following parameter:
Room unit You can choose if the room unit is equipped with an LCD display. If so, the parameters
hereafter can also be set. The HandyTool has a fixed setting "With LCD".
Selecting the The room temperature can be displayed either in Celsius (°C) or Fahrenheit (°F). Note
temperature unit that this applies only to room units with an LCD display.
Temperature display in In room units with an LCD panel, it is also possible to select the temperature value
normal mode to be displayed.
(Normal mode = setpoint not shifted or setpoint shift canceled).
95/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room unit 17 Sep 2010
Temperature display in In room units with an LCD, it is possible to define what is to be displayed in the event of
the case of a setpoint a setpoint shift.
shift
If "Absolute setpoint adjustment" is selected, the LCD panel displays a scale which
illustrates the adjustment as it happens:
10385Z20
96/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Room unit 17 Sep 2010
13 Bus information
13.1 Reset and startup response
The application is restarted after every reset. Depending on the controller address, this
may take 1 ... 255 s.
Then, the bus connection is opened and all connected valve actuators are
synchronized. This takes the following time depending on application and actuator type:
– Typically 170 s for closing (runtime + 10%) for motorized actuators.
– 300 s ON and 300 s OFF (3rd party: 400 + 400 s) for thermal actuators.
The application is always placed in a safe state. Any outputs which cannot be
synchronized will not be operated (triac outputs = 0, and relay outputs = Open). Normal
operation is resumed after synchronization.
Note When the controller exist the test mode, only a soft reset is carried out:
– The valve actuators and dampers are synchronized.
– The control algorithm, but not the complete application, is restarted.
Each time the control sequence reaches 0% or 100%, a limit position
synchronization takes place.
– For motorized actuators close or open during (runtime + 10%).
– 300 s ON and 300 s OFF (3rd party: 400 s) for thermal actuators.
An LED is located at the controller's bottom right indicating the operating state by
various flashing patterns:
97/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Bus information 17 Sep 2010
13.3 Startup delay
After a reset, it takes up to 5 minutes for all the connected room controllers to restart.
This is designed to avoid overloading the mains power supply when restarting. At the
same time, it reduces the bus load, as not all controllers transmit data at the same time.
The delay is determined by the controller's device address.
In a large system, the bus load can be a problem, especially with central commands
which cause the controllers to send status information simultaneously. This can even
result in the loss of data telegrams.
If the recommended limits are respected (max. 45 RXL controllers per line and per
integration station), no problems should occur.)
98/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Bus information 17 Sep 2010
13.5 HandyTool parameters by number
S = Service (Mode 6)
Description on page
(Mode 2)
Parameter No
Name
FNC02
FNC04
FNC08
FNC20
FNC10
FNC12
FNC18
FNC03
FNC05
001 12 Physical address (area address) d P S X X X X X X X X X
002 12 Physical address (line address) d P S X X X X X X X X X
003 12 Physical address (device address) d P S X X X X X X X X X
005 24 Plant type d S X X X X X X X X X
006 16 Communication mode d S X X X X X X X X X
008 18 Geographical zone (apartment) d P S X X X X X X X X X
009 18 Geographical zone (room) d P S X X X X X X X X X
010 18 Geographical zone (subzone) d P S X X X X X X X X X
011 18 Time switch zone (apartment) d P S X X X X X X X X X
012 18 Time switch zone (room) d P S X X X X X X X X X
013 18 Time switch zone (subzone) d P S X X X X X X X X X
014 18 Heat distr zone heating coil d P S X X X X X X X X X
015 18 Refrig distr zone cooling coil d P S X X X X X X X X X
016 18 Heat distr zone heating surface d P S X X X
8) 8)
018 18 Outside temperature zone d P S X X X
021 83 Master/slave d P S X X X X X X X X X
022 83 Master/slave zone (apartment) d P S X X X X X X X X X
023 83 Master/slave zone (room) d S X X X X X X X X X
024 83 Master/slave zone (subzone) d S X X X X X X X X X
030 48 Protection cooling setpoint d S X X X X X X X X X
031 48 Economy cooling setpoint d P S X X X X X X X X X
032 48 Precomfort cooling setpoint d P S X X X X X X X X X
033 48 Comfort cooling setpoint d P S X X X X X X X X X
034 48 Comfort heating setpoint d P S X X X X X X X X X
035 48 Precomfort heating setpoint d P S X X X X X X X X X
036 48 Economy heating setpoint d P S X X X X X X X X X
037 48 Protection heating setpoint d S X X X X X X X X X
038 76 Minimum supply air temperature d P S X
039 76 Maximum supply air temperature d P S X
040 48 Risk of frost limit d S X X
050 57 Control sequence d S X X X X
056 68 Electric heater d S X X
057 68 Power consumption el heater d S X X
060 60 Actuator type H/C coil valve d S X X X X X X X X
061 61, 64 Running time damper heating d S X X X X X X X X X
1)
062 61, 64 Running time damper cooling d S X X X X X X X X X
8) 2) 8) 8) 8)
063 70 Actuator type heat surf valve d S X
064 70 Run time heating surface valve d S X
066 70 Offset heating surface valve d S X X
070 64 Switchover period H/C d S X
071 61 Offset heating valve d S X X
072 61 Offset cooling valve d S X X
073 74 Outside temp min damper pos d S X X
074 74 Running time outside air damper d S X X
075 74 Minimum damper position d S X X
99/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Bus information 17 Sep 2010
Visible FC-10 FC-11 FC-12
S = Service (Mode 6)
Description on page
(Mode 2)
Parameter No
Name
FNC02
FNC04
FNC08
FNC20
FNC10
FNC12
FNC18
FNC03
FNC05
078 72 Outside temp 0% valve pos d S X
079 72 Outside temp max valve pos d S X
080 72 Max valve position d S X
085 62 Heating outp bus valve d S X X X X X X X X
Heating coil outp bus valve X
086 71 Heating surface output bus valve d S X
actuator
087 62 Cooling outp bus valve, d S X X X X X X X X
Cooling coil outp bus valve 5) X
089 67 Heating outp bus el heating d S X X
092 53 Temperature sensor. d S X X X X X X X X X
9)
093 79 Fan control d S X X X X X X X X X
094 79 Fan speeds d S X X X X X X X X X
095 79 Minimum on time d S X X X X X X X X X
096 79 Periodic fan kick Comfort d S X X X X X X X X X
097 79 Periodic fan kick Eco d S X X X X X X X X X
098 79 Fan overrun time d S X X
101 94 Measured value correction d S X X X X X X X X X
103 94 Setpoint offset range d S X X X X X X X X X
105 37, Local Comfort mode d S X X X X X X X X X
94, 95
108 94, 95 Temperature unit d S X X X X X X X X X
109 94, 95 Standard display d S X X X X X X X X X
110 94, 96 Setpoint display d S X X X X X X X X X
113 86 Digital input 1 d S X X X X X X X X X
114 86 Digital input 2 d S X X X X X X X X X
117 86 Temporary Comfort mode d S X X X X X X X X X
119 86 On-delay occupancy detector d S X X X X X X X X X
120 86 Off-delay occupancy detector d S X X X X X X X X X
131 87 Heat demand signal d S X X X X X X X X X
132 87 Cooling demand signal d S X X X X X X X X X
134 87 Boost heating d S X X X X X X X X X
135 87 Preecooling (Precool), d S X X X X X X X X X
Free cooling (Freecool)
136 87 Rapid ventilation (earlier: air purge) d S X X X X X X X X X
137 92 Reset setpoint offset d S X X X X X X X X X
138 87 Night purge d S X X X X X X X X X
236 93 Application set d S X X X X X X X X X
237 93 Application version d S X X X X X X X X X
238 93 Operating system version d S X X X X X X X X X
239 93 KNX interface version d S X X X X X X X X X
240 93 Device state d P S X X X X X X X X X
100/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Bus information 17 Sep 2010
13.6 HandyTool parameters sorted alphabetically
S = Service (Mode 6)
Description on page
(Mode 2)
Parameter No
Name
FNC02
FNC04
FNC08
FNC20
FNC10
FNC12
FNC18
FNC03
FNC05
060 60 Actuator type H/C coil valve d S X X X X X X X X
063 70 Actuator type heat surf valve d S X
236 93 Application set d S X X X X X X X X X
237 93 Application version d S X X X X X X X X X
134 87 Boost heating d S X X X X X X X X X
033 48 Comfort cooling setpoint d P S X X X X X X X X X
034 48 Comfort heating setpoint d P S X X X X X X X X X
006 16 Communication mode d S X X X X X X X X X
050 57 Control sequence d S X X X X
132 87 Cooling demand signal d S X X X X X X X X X
087 62 Cooling outp bus valve, d S X X X X X X X X
Cooling coil outp bus valve 5) X
240 93 Device state d P S X X X X X X X X X
113 86 Digital input 1 d S X X X X X X X X X
114 86 Digital input 2 d S X X X X X X X X X
031 48 Economy cooling setpoint d P S X X X X X X X X X
036 48 Economy heating setpoint d P S X X X X X X X X X
056 68 Electric heater d S X X
093 79 Fan control d S X X X X X X X X X
098 79 Fan overrun time d S X X
094 79 Fan speeds d S X X X X X X X X X
135 87 Free cooling (Freecool) , d S X X X X X X X X X
Preecooling (Precool)
040 48 Frost limit d S X X
008 18 Geographical zone (apartment) d P S X X X X X X X X X
009 18 Geographical zone (room) d P S X X X X X X X X X
010 18 Geographical zone (subzone) d P S X X X X X X X X X
131 87 Heat demand signal d S X X X X X X X X X
014 18 Heat distr zone heating coil d P S X X X X X X X X X
016 18 Heat distr zone heating surface d P S X X X
8) 8)
089 67 Heating outp bus el heating d S X X
085 62 Heating outp bus valve d S X X X X X X X X
Heating coil outp bus valve X
086 71 Heating surf. output bus valve actuator d S X
239 93 KNX interface version d S X X X X X X X X X
105 37, Local Comfort mode d S X X X X X X X X X
94, 95
021 83 Master/slave d P S X X X X X X X X X
022 83 Master/slave zone (apartment) d P S X X X X X X X X X
023 83 Master/slave zone (room) d S X X X X X X X X X
024 83 Master/slave zone (subzone) d S X X X X X X X X X
039 76 Maximum supply air temperature d P S X
080 72 Max valve position d S X
101 94 Measured value correction d S X X X X X X X X X
075 74 Minimum damper position d S X X
095 79 Minimum on time d S X X X X X X X X X
038 76 Minimum supply air temperature d P S X
101/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Bus information 17 Sep 2010
Visible FC-10 FC-11 FC-12
S = Service (Mode 6)
Description on page
(Mode 2)
Parameter No
Name
FNC02
FNC04
FNC08
FNC20
FNC10
FNC12
FNC18
FNC03
FNC05
138 Night purge
87 d S X X X X X X X X X
120 86
Off-delay occupancy detector d S X X X X X X X X X
072 61
Offset cooling valve d S X X
066 70
Offset heating surface valve d S X X
071 61
Offset heating valve d S X X
119 86
On-delay occupancy detector d S X X X X X X X X X
238 93
Operating system version d S X X X X X X X X X
018 18
Outside temperature zone d P S X X X
078 72
Outside temp 0% valve pos d S X
079 72
Outside temp max valve pos d S X
073 74
Outside temp min damper pos d S X X
096 79
Periodic fan kick Comfort d S X X X X X X X X X
097 79
Periodic fan kick Eco d S X X X X X X X X X
001 12
Physical address (area address) d P S X X X X X X X X X
003 12
Physical address (device address) d P S X X X X X X X X X
002 12
Physical address (line address) d P S X X X X X X X X X
005 24
Plant type d S X X X X X X X X X
057 68
Power consumption el heater d S X X
032 48
Precomfort cooling setpoint d P S X X X X X X X X X
035 48
Precomfort heating setpoint d P S X X X X X X X X X
135 Preecooling (Precool),
87 d S X X X X X X X X X
Free cooling (Freecool)
030 48 Protection cooling setpoint d S X X X X X X X X X
037 48 Protection heating setpoint d S X X X X X X X X X
136 87 Rapid ventilation (earlier: air purge) d S X X X X X X X X X
015 18 Refrig distr zone cooling coil d P S X X X X X X X X X
137 92 Reset setpoint offset d S X X X X X X X X X
040 48 Risk of frost limit d S X X
062 61, 64 Running time damper cooling d S X X X X X X X X X
8) 2) 8) 8) 8)
061 61, 64 Running time damper heating d S X X X X X X X X X
1)
074 74 Running time outside air damper d S X X
064 70 Run time heating surface valve d S X
110 94, 96 Setpoint display d S X X X X X X X X X
103 94 Setpoint offset range d S X X X X X X X X X
109 94, 95 Standard display d S X X X X X X X X X
070 64 Switchover period H/C d S X
092 53 Temperature sensor. d S X X X X X X X X X
9)
108 94, 95 Temperature unit d S X X X X X X X X X
117 86 Temporary Comfort mode d S X X X X X X X X X
011 18 Time switch zone (apartment) d P S X X X X X X X X X
012 18 Time switch zone (room) d P S X X X X X X X X X
013 18 Time switch zone (subzone) d P S X X X X X X X X X
1) HandyTool: In FNC20, runtime damper heating
2) HandyTool: In FNC20, runtime damper cooling
5) HandyTool: In FNC20, output bus damper actuator
7) HandyTool: Cannot be mapped
8) HandyTool: Visible, but not used by application
9) FNC08: always Supply air
102/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Bus information 17 Sep 2010
13.7 HandyTool enumerations
CLC / RAD
FNC
No. Parameter
103/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Bus information 17 Sep 2010
14 FAQs
Question: What happens if the parameter download process is interrupted? (power failure,
bus failure etc.)
Answer: The parameter set loaded into the controller will be incomplete. The controller will not
start up properly. For example, the fan may run but the valves do not open.
You will have to download the parameters again.
Question: Why does the controller fail to start after a parameter download?
(applies to HandyTool.)
Answer: The parameter download was probably interrupted or exposed to interference. Reload
the controller with the entire parameter set (with HandyTool or ACS).
Question: Why does the controller not start after adjusting certain parameters?
(applies to HandyTool.)
Question: Why does the HandyTool not display parameter 1 upon quick quit and restart of the
Display mode?
Answer : Other parameters have been changed so that the selected parameter became irrele-
vant. Just continue your work;. the problem will disappear when the parameterization is
started again.
Answer: Check to make shure that neither the operating booklet nor the plant image is active.
Both applications cause a lot of bus traffic and thus slow down reading back
parameters.
104/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies FAQs 17 Sep 2010
Question: ACS: Parameter download does not work, why?
Answer: Make sure that the parameter tree is expanded prior to download.
Wrong Right
Question: Why can I not parameterize the controller via HandyTool in service mode (n6)?
Question: Why does a controller with thermal valves not respond immediately when it is
enabled in the plant graphics in the ACS view and in the DESIGO graphics?
Answer: After start-up, the thermal valves are preheated first. This is not shown in the plant
graphics.
However, if the room temperature is outside the dead band during this period, the fan
switches to Speed 1.
Question: With master/slave configurations, why do the QAX34 room units not always show the
same temperature values?
105/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies FAQs 17 Sep 2010
Question: Why does the slave window contact/presence detector contact have no effect?
Answer: For the window/presence detector contact, the slave can only be integrated via the
CFC. Suitable compounds are available in the library: [WndStaDtr] and [OcStaDtr].
Question Why do the ACS plant graphics not always display all values (e.g. room operating
mode)?
Answer The controller is configured as a slave. These values are not available with slave
controllers.
Question Why doesn’t the ACS Operator Book show the current data?
Answer After a change of application (e.g. from FNC12 to FNC18) you first need to update the
reference data points.
106/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies FAQs 17 Sep 2010
15 Integration of RXL into DESIGO/Synco
Combinations of RXL controllers with Synco and a DESIGO integration are possible
and certainly make sense.
Key
Display
Time scheduler
Heating demand
10385D69
Cooling demand
Communication:
– between controllers via zones
– with ACS: Individual addressing
RXL display: ACS
Synco display: ACS
RXL time scheduler: from Synco
Energy demand: to Synco
ACS7..
Individual addressing
FLN
Konnex
Timeswitch zone
107/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Integration of RXL into DESIGO/Synco 17 Sep 2010
15.2 Case 2: Integration into DESIGO
Communication:
– with DESIGO: Individual addressing
RXL display: DESIGO
RXL time scheduler: from DESIGO
Energy demand: to DESIGO
DESIGO
INSIGHT
ALN
PXM20
Individual addressing
FLN
RXL
RXL
10785D63
RXL
108/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Integration of RXL into DESIGO/Synco 17 Sep 2010
15.3 Case 3: Display in DESIGO,
with shared Synco time scheduler
Communication:
– between controllers via zones
– with DESIGO: Individual addressing
RXL display: DESIGO
Synco display: DESIGO
RXL time scheduler: from Synco
Energy demand: to Synco
STOP Important note The DESIGO time scheduler must be disabled by a specialist. Reason: Integration
by means of individual addressing treats the time scheduler and display as one
package. They subsequently need to be separated.
DESIGO
INSIGHT
ALN
PXM20
Individual addressing
FLN
Geographical zone Konnex
RXL
RXL
Geographical zone
RXL
Timeswitch zone
109/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Integration of RXL into DESIGO/Synco 17 Sep 2010
15.4 Case 4: Display in DESIGO/Synco,
with shared Synco time scheduler
Communication:
– between controllers via zones
– with DESIGO: Individual addressing
– with ACS: Individual addressing
RXL display: DESIGO and ACS
Synco display: DESIGO and ACS
RXL time scheduler: from Synco
Energy demand: to Synco
STOP Important note The DESIGO time scheduler must be disabled by a specialist.
In theory simultaneous display via DESIGO and Synco is possible. However,
problems do arise with the manipulation of values (heartbeat, “last one rules”)
DESIGO
INSIGHT
ALN
ACS7...
PXC... PXC... PX KNX
PXM20
Individual addressing
FLN
Konnex
Timeswitch zone
110/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Integration of RXL into DESIGO/Synco 17 Sep 2010
15.5 Case 5: Display in DESIGO, and
separate time schedulers
Communication:
– between controllers via zones
– with DESIGO: Individual addressing
RXL display: DESIGO
Synco display: DESIGO
RXL time scheduler: from DESIGO
Energy demand: to Synco
STOP Important note The RXL controllers use the DESIGO time scheduler
The Synco controllers need a local Synco time schedule
The two schedules must be kept synchronous
DESIGO
INSIGHT
ALN
PXM20
Individual addressing
FLN
Konnex
Timeswitch zone
111/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Integration of RXL into DESIGO/Synco 17 Sep 2010
15.6 Case 6: Separate display, and
separate time schedulers
Communication:
– between controllers via zones
– with DESIGO: Individual addressing
– with ACS: Individual addressing
RXL display: DESIGO
Synco display: ACS
RXL time scheduler: from DESIGO
Energy demand: to Synco
STOP Important note The RXL controllers use the DESIGO time scheduler
The Synco controllers need a local Synco time schedule
The two schedules must be synchronous at all times
DESIGO
INSIGHT
ALN
ACS7..
PXC... PXC... PX KNX
PXM20
Individual addressing
FLN
Konnex
Timeswitch zone
112/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Integration of RXL into DESIGO/Synco 17 Sep 2010
15.7 Case 7: Separate display, and
shared Synco time scheduler
Communication:
– between controllers via zones
– with DESIGO: Individual addressing
– with ACS: Individual addressing
RXL display: DESIGO
Synco display: ACS
RXL time scheduler: from Synco
Energy demand: to Synco
STOP Important note The DESIGO time scheduler must be disabled by a specialist.
DESIGO
INSIGHT
ALN
ACS7..
PXC... PXC... PX KNX
PXM20
Individual addressing
FLN .
Konnex .
Geographical zone RXL .
Timeswitch zone
10785D68
Cooling demand zone
113/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Integration of RXL into DESIGO/Synco 17 Sep 2010
16 Working with different tools
It is possible to prepare the RXL controllers in the office by setting the parameters in
advance, so that only the physical address has to be entered on site. The HandyTool
contains a “limited” parameter-setting option which can be used for this purpose.
The preparatory work would then probably be carried out with ACS rather than with the
HandyTool.
Special caution is required (in relation to data consistency) when using more than one
tool.
Step 1 Step 2
HandyTool ACS Service
HandyTool () *
ACS
114/114
Siemens RXL application library FNC – Description of functions for FC-10, FC-11, FC-12 CM110785en_06
Building Technologies Working with different tools 17 Sep 2010