Professional Documents
Culture Documents
PII: S2451-9049(16)30023-3
DOI: http://dx.doi.org/10.1016/j.tsep.2017.02.002
Reference: TSEP 2
Please cite this article as: A.G. Devecioğlu, V. Oruç, An analysis on the comparison of low-GWP refrigerants to
alternatively use in mobile air-conditioning systems, Thermal Science and Engineering Progress (2017), doi: http://
dx.doi.org/10.1016/j.tsep.2017.02.002
This is a PDF file of an unedited manuscript that has been accepted for publication. As a service to our customers
we are providing this early version of the manuscript. The manuscript will undergo copyediting, typesetting, and
review of the resulting proof before it is published in its final form. Please note that during the production process
errors may be discovered which could affect the content, and all legal disclaimers that apply to the journal pertain.
An analysis on the comparison of low-GWP refrigerants to alternatively use in mobile air-
conditioning systems
Abstract
The results of an analysis are discussed in this paper considering R1234yf, R444A and R445A
refrigerants having low Global Warming Potential (GWP) which can be used in the mobile air
conditioning systems. The evaporation temperatures of −5°C and +5°C while condenser
temperatures of 30°C and 60°C were taken for the evaluations of thermodynamic properties
of the refrigerants. In the study, electrical power consumption of the system and COP values
were calculated considering thermodynamic properties determined for the points in the cycle
depending on the assumed system parameters. The system was considered to operate in a
steady-state cycle. The pressure loss through evaporator and condenser, and heat transfer
amounts through connecting tubes, expansion valve and compressor were neglected for the
computations. The computations have pointed out that while cooling capacity of R444A and
R445A were higher; their COP values were smaller compared to R1234yf because of their
R1234yf, it may be suggested that R444A can be utilized in air-conditioning systems of heavy
vehicles such as busses, trucks, and trains due to its decreased flammability risk by mixture
content.
1
Nomenclature
h enthalpy, kJ·kg-1
P pressure, kPa
Q cooling capacity, kW
T temperature, °C
volumetric flow rate at suction, m3·s-1
Subscripts
C compressor
con condenser
ev evaporator
in inlet
out outlet
1. Introduction
According to the instructions of EU F-Gas and mobile air conditioning (MAC), the
refrigerants with global warming potential (GWP) value less than 150 should be used
2
mandatorily in the automotive air-conditioning systems [1,2]. The number of refrigerants with
low GWP developed for using in automotive air conditioners has been increased in the several
decades. Along with this increase, it would be important to select the refrigerants with better
energy performances. The major problem of HFC based low GWP refrigerants produced as a
substitute for R134a is that they are flammable. Although low-GWP refrigerants are in the
high flammability class, they have proper values in terms of satisfying the gas regulations.
The common properties of some natural refrigerants of very low-GWP (such as CO2 and
ammonia) and hydrocarbon derivative refrigerants (e.g., propane and isobutane) are that they
have high flammability and toxic effect [3]. Hence, their application fields are limited to small
refrigeration systems only. Although recently developed HFO refrigerants have lower GWP
values, their flammability risk restricts using of these new refrigerants. The HFO/HFC
derived refrigerants are classified as flammable and non-flammable with respect to cases of
GWP<700 and GWP>700, respectively. ASHRAE has introduced mildly flammable gases
class and 2L code for these refrigerating fluids. Despite R1234yf has been passed through
previous safety tests, some of the vehicle manufactures do not prefer that refrigerant because
of its flammability risk. The investigations on R1234yf which is a HFO derived refrigerant
remarkably increase in recent years [4-6]. Most of the studies include experimental
comparison of R134a and R1234yf for different operating conditions. The common results of
the published papers suggest that both cooling capacity and COP decrease when R1234yf is
used in the system [4-10]. The similar conclusions were also obtained by experimental
investigations on R134a and R1234yf for MAC systems [11-15]. Prior to the experimental
study R134a and its alternatives were theoretically compared in order to estimate the proper
conditions and physical behavior [16,17]. Mota-Babiloni et al. [17] compared R134a and its
alternatives, they expressed according to the results that R444A had higher cooling capacity
than R134a. It is seen that most of the previous investigations were carried on alternative
3
refrigerants those may be used instead of R134a. Comparing and obtaining the related
information about low GWP refrigerants, which are inevitably used, should be very useful for
air conditioning applications. In this paper, some thermodynamic properties and energy
performances under different conditions were compared for the refrigerants of HFO based
The mixing ratios by mass for the refrigerants used in the study are given in Table 1. R444A
blend consists of R1234ze(E), R152a and R32 refrigerants which are accepted as flammable
favorably such that there are HFC derived non-flammable R134a and carbon dioxide (R744)
R1234yf 100%
R445A 85% 9% 6%
Some basic characteristics for the considered refrigerants are indicated in Table 2. As it can
be noted GWP values are less than 150 and all three refrigerants are in flammable class. It is
clear that R445A has higher critical temperature than R1234yf 10.5% and its critical pressure
is greater than the other ones as well. Some of the thermodynamic and transport
4
characteristics of the refrigerants shown in the tables and figures of this study were obtained
refrigerants are shown in Fig. 1 for a temperature range of -40°C to 60°C. Although the
observed pressure behavior is similar for the refrigerants, the pressure of R445A at -15°C and
35°C is higher than that of R1234yf about 90% and 47%, respectively. Since it is expected the
higher saturation pressure in evaporator should be related to better results for some energy
parameters, R445A may be said to be more advantageous among the investigated refrigerants.
5
2500
R1234yf
2000 R444A
R445A
Pressure (kPa)
1500
1000
500
0
-40 -15 10 35 60
Temperature (°C)
Fig. 1. The behavior of saturation pressure versus temperature for the studied refrigerants
The mass flow rate of the refrigerant which circulates in the evaporator is one of the important
parameters affecting the cooling capacity. The amount of refrigerant that would be charged
into the system decreases significantly with lower liquid density of refrigerating fluid [19].
As expected liquid density decreases with higher temperatures since volume is larger at a
greater temperature for a given mass causing lower density. It is obvious that R1234yf and
R444A gases exhibit nearly the same density versus pressure distribution, but R445A has
greater the density values by 4.3 to 6.4% compared to R1234yf. Hence, using R444A or
R445A refrigerant should lead to less gas charging to the system because of their smaller
6
1400
R1234yf
1300 R444A
Liquid density (kg/m3)
R445A
1200
1100
1000
900
-40 -15 10 35 60
Temperature (°C)
The higher liquid thermal conductivity, which is one of the transport properties of the gases,
causes more amount of heat transfer, thereby using smaller or more compact heat exchanger
directly corresponding to lower initial investment cost. The relationship between liquid
thermal conductivity and temperature for the studied refrigerants is presented in Fig. 3. First
of all, liquid thermal conductivity values of R444A and R445A refrigerants are close to each
other and evidently greater than those of R1234yf. This consequence expresses that utilizing
R444A and R445A may enable using smaller size of heat exchangers in the new designed air
conditioning systems. Note also that increasing temperature reduces thermal conductivity
7
120
80
60
40
-40 -15 10 35 60
Temperature (°C)
Fig 3. Variation of liquid thermal conductivity with temperature for studied refrigerants
The cooling capacity of gases changes depending on saturation pressure of the refrigerant.
The saturation curves for the refrigerants are plotted on pressure-enthalpy, P-h diagram in
Fig.4 which schematically includes operation principle for a simple cycle as well. It is seen
for the same saturation pressure from P-h chart that evaporation heat (i.e., the cooling
capacity) of R1234yf is less about 26% and 28% compared to R444A and R445A,
respectively.
Fig. 4. Pressure-enthalpy diagram for the gases and basic components of the system
8
3. The parameters and methods for the analysis
The analysis was conducted for a single stage vapor compression refrigeration cycle. The
evaporation temperatures (Tev) were selected as -5, 0 and +5 °C while condenser temperatures
(Tcon) were assessed as 35, 45 and 55°C which are typical values for a mobile air conditioner.
Furthermore, some considered assumptions for the system analysis were as follows:
• the pressure loss through evaporator and condenser, and heat transfer through
• the energy consumed by the fans evaporator and condenser is not taken into account,
• Sub-cooling is 3°C,
coefficient of performance, COP which can be determined by the ratio of cooling capacity to
( , ,)
COP =
(1)
where is the mass flow rate in kg/s, hout,ev and hin,ev are the enthalpy values of fluid leaving
and entering to the evaporator, respectively in kJ/kg, and Wel is the electrical power input to
the system in kW. Note that the numerator in Eq.(1) indicates cooling capacity (extracted
9
heat) of the refrigerant through evaporator in kW. The actual consumed energy Wel in
compressor may be evaluated by means of isentropic efficiency, ηis [20] defined as:
( , , ) ( , , )
= = ( , ,)
=( (2)
!"#,$ ,)
where Ws is the energy consumed for constant entropy in kW; h ’out,C is the enthalpy of
refrigerant at compressor discharge for constant entropy (i.e., isentropic) case; hout,C and hin,C
are the enthalpy values of refrigerant at outlet and inlet of compressor, respectively. The
Point 1: Refers to low pressure and suction temperature regarding superheat value as
well.
efficiency (Eq. 2), then point 2 represents the high pressure and determined enthalpy values.
was determined
represent the refrigerant’s adaptation for the compressor in the system.
by dividing mass flow rate to the density of fluid at suction state. Then obtained distribution
for the considered refrigerants is demonstrated in Fig. 5 with two evaporation temperature
cases of +5°C and −5°C. It is clear that volumetric flow rate values at suction are nearly same
10
(roughly 35% for
regardless of Tev for R444A and R445A having greater magnitudes of
,
both temperatures) compared to R1234yf which may be preferred due to its smaller
remarkably
hence leading to lower electricity consumption potential. Furthermore,
16
Tev=-5 °C
Tev=5 °C
12
Vsuc x 104 (m3/s)
.
4
0
R1234yf R444A R445A
The energy performances for the investigated refrigerants are discussed in Fig. 6 with
assumed evaporation and condenser temperatures. Fig. 6(a) demonstrates the cooling capacity
of the refrigerants obtained in the evaporator, Qev. It is evident that R444A and R445A
provide nearly same magnitude of Qev which is higher approximately 27% by comparison that
obtained using R1234yf refrigerant, namely R444A and R445A have a greater heat extraction
potential in the evaporator. Moreover, evaporation and condenser temperatures (i.e., Tev and
Tcon, respectively) have significant effect on Qev results such that the largest cooling capacity
could be obtained for Tev=5°C and Tcon=30°C regardless of refrigerant type. Similarly, the
lowest Qev is seen for Tev=−5°C and Tcon=60°C for all refrigerants. Nevertheless, it is not easy
11
to make a generalization on refrigerant type and/or the temperature effect without referring
the COP analysis which requires electrical power supplied to the system as well as Qev.
Thus, electrical power consumption using three types of refrigerants is investigated in Fig.
6(b). Obviously, R1234yf needs the lowest electrical energy among the refrigerants. R444A
and R445A have nearly same characteristic in terms of Wel. Note also that the effect of
temperature has different influence in contrast to Fig. 6(a). In summary, R1234yf for
Tev=+5°C and Tcon=30°C condition seems to offer most advantageous result among the
COP values are calculated for the covered cases and the results are demonstrated in Fig. 6(c).
Among the refrigerants R1234yf may be preferred in general due to its higher COP at the
considered temperatures. Especially, it has also noticeable greater COP value for Tev=+5°C
and Tcon=30°C case at which COP of R1234yf is larger about 40% than that of R444A.
Interestingly, COP is almost same for Tev=−5°C and Tcon=60°C whatever the refrigerant type.
Although COP values of R444A and R445A are in the same order, R444A seems better
compared to R445A. It is useful to address the effect of temperature in Fig. 6(c) such that the
best result in terms of COP could be achieved for Tev=+5°C and Tcon=30°C. The next
preferable case may be suggested as Tev=−5°C and Tcon=30°C with R1234yf while the worst
case among the discussed refrigerants appears for Tev=−5°C and Tcon=60°C. Finally it may be
useful to simultaneously discuss plots in Fig. 6 such that although cooling capacity of
R1234yf is lower, its COP is markedly higher due to smaller electrical power consumption.
Hence it may be stated that Wel is dominant parameter on COP rather than Qev.
12
2500
(a)
2000 Tev=-5 °C
Tcon=30 °C
Tev=5 °C
Qev (W)
1500 Tcon=30 °C
Tev=-5 °C
Tcon=60 °C
1000
Tev=5 °C
Tcon=60 °C
500
0
R1234yf R444A R445A
1000
(b)
800
Tev=-5 °C
Tcon=30 °C
600 Tev=5 °C
Wel (W)
Tcon=30 °C
400 Tev=-5 °C
Tcon=60 °C
Tev=5 °C
200 Tcon=60 °C
0
R1234yf R444A R445A
8
(c)
Tev=-5 °C
6
Tcon=30 °C
Tev=5 °C
Tcon=30 °C
COP
4
Tev=-5 °C
Tcon=60 °C
Tev=5 °C
2 Tcon=60 °C
0
R1234yf R444A R445A
13
Fig. 6. Energy performances of the refrigerants for different evaporation and condenser
temperatures (a) cooling capacity, (b) power consumption in the compressor, (c) coefficient
of performance distribution
The relationship between COP and Tev/Tcon ratio (where temperatures are evaluated in Kelvin)
is plotted in Fig. 7 for the studied refrigerants. Obviously, greater Tev/Tcon (especially for
Tev/Tcon > 0.85) causes COP to increase for all refrigerants significantly. For example,
increasing Tev/Tcon from 0.83 to 0.88 for R444A causes an improvement in COP about 63%.
In other words, higher Tev and/or lower Tcon creates a desirable condition as far as COP is
considered. This evidence, which could also be detected from Fig.6 (c), in fact clearly verifies
be larger among the refrigerants. Note additionally that R444A is better compared to R445A
8
R1234yf
7
R444A
6
R445A
5
COP
1
0.75 0.80 0.85 0.90 0.95
Tev/Tcon
14
5. Conclusions
The analysis on the energy performances of R1234yf, R444A and R445A with low-GWP
values those may be used in MAC systems have demonstrated that COP values of R444A and
R445A are less compared to R1234yf. However, R444A or R445A could be utilized in the
systems referring to their lower potential of flammability risk because of their content in the
mixture. Therefore, these may be considered as alternatives to R1234yf for the air
conditioning systems of large vehicles for which flammability is a major problem. Actually,
investigation presented that the cooling capacity of R444A or R445A were greater than that of
R1234yf, but their electricity consumption magnitudes were also higher which caused COP to
to be higher with respect to R1234yf, hence electricity consumption was lower for the latter
refrigerant). Furthermore, R444A or R445A can be used safely in the all refrigeration systems
operating with R134a as long as possible highest COP is not the essential object. As a further
designs may be considered and/or increased condenser surface area could be tested to obtain
References
[1] Official Journal of the European Union, Directive 2006/40/EC of the European Parliament
15
[2] Regulation (EU) No 517/2014 of the European Parliament and the Council of 16 April
2014 on fluorinated greenhouse gases and repealing Regulation (EC) No 842/2006. Off. J.
[3] Mohanraj, M., Jayaraj, S., Muraleedharan, C., 2009. Environment friendly alternatives to
[4]Navarro, E., Martinez-Galvan, I.O., Nohales, J., Gonzalvez-Macia, J., 2013. Comparative
experimental study of an open piston compressor working with R-1234yf, R-134a and R-290.
[5] Mota-Babiloni, A., Navarro-Esbri, J., Barragan, A., Moles, F., Peris, B., 2014. Drop-in
[7] Navarro-Esbri, J., Moles, F., Barragan-Cervera, A., 2013. Experimental analysis of the
internal heat exchanger influence on a vapour compression system performance working with
R1234yf as a drop-in replacement for R134a. Applied Thermal Engineering 59, 153-161.
16
[8] Zvonimir, J., Atienza, J.S., Suarez, J.A.M., 2015. Thermodynamic and heat transfer
analyses for R1234yf and R1234ze(E) as drop-in replacements for R134a in a small power
[9] Fukuda, S., Kondou, C., Takata, N., Koyama, S. 2014. Low GWP refrigerants R1234ze(E)
and R1234ze(Z) for high temperature heat pumps. International journal of Refrigeration, 40,
161-173.
[10] Minor, B., Spatz, M., 2008. HFO-1234yf low GWP Refrigerant Update. In: International
Refrigeration and Air Conditioning Conference at Purdue, West Lafayette, IN, USA, Paper
No. 2349.
[11] Qi, Z., 2013. Experimental study on evaporator performance in mobile air conditioning
system using HFO-1234yf as working fluid. Applied Thermal Engineering 53, 124-130.
[12] Cho, H., Lee, H., Park, C., 2013. Performance characteristics of an automobile air
conditioning system with internal heat exchanger using refrigerant R1234yf. Applied Thermal
[13] Qi, Z., 2015. Performance Improvement Potentials of R1234yf Mobile Air Conditioning
[14] Qi, Z., 2015. Quick and Empirical Correlations for Refrigerant Pressure Drop in Mobile
17
[15] Zilio, C., Brownb, J.S., Schiochet, G., Cavallini, A., 2011. The refrigerant R1234yf in air
[16] Moles, F., Navarro-Esbri, J., Peris, B., Mota-Babiloni, A., Barragan-Cervera, A., 2014.
[17] Mota-Babiloni, A., Navarro-Esbri, J., Barragan-Cervera, A., Moles, F., Peris, B., 2015.
[18] Lemmon, E.W., Huber, M.L., McLinden, M.O., 2013. NIST Standard Reference
9.1, National Institute of Standards and Technology, Standard Reference Data Program,
Gaithersburg.
[19] Mohanraj M., 2013. Energy performance assessment of R430A as a possible alternative
refrigerant to R134a in domestic refrigerators. Energy for Sustainable Development 17, 471–
476.
[20] Dinçer İ., Kanoğlu M., Refrigeration Systems and Applications, John Wiley and Sons
Ltd., 2010.
18