Simply Modbus TCP Client 1.4
Modbus TCP Client Software
About
Enron System Requirements:
MODBUS
Windows NT, 95, 2000, XP. (not recommended for Windows 7 or Vista )

RTU Master display resolution: 800 x 600 minimum

RTU Slave

TCP Client Installation - Simply Modbus TCP Client 1.4 (1.65 MB) :
manual1
manual7
Click to download SimplyModbusTCPclient1.4.zip
manual8
Unzip the compressed files into a common folder on your hard drive.

Download Simply Modbus TCP Client 1.4.exe - the program


Read me TCP Client 1.4.txt - documentation
Read me for Windows7.txt - documentation
Purchase

Contact
Known Issues with version 1.4: Two instances normally appears in the taskbar while the program is running, the runtime
engine and the program itself, Sometimes the runtime engine does not quit when the program is closed, although it is not
consistent and behaves differently on different PCs. It is more likely to happen when the program is opened and closed
within a few seconds. Waiting longer or sending a request before closing may help it quit properly. It may quit by itself after
a few minutes on some Windows 7 and systems. Although it's okay on others.

Work Arounds: It can be forced to quit by right clicking on the taskbar item and selecting close. Using Alt-F4 to quit the
program also works better in some cases.

Simply Modbus TCP Client 7.1.2 looks and runs exactly like Simply Modbus TCP Client 1.4 but was created using a
newer compiler. It is a significantly larger download and has an install program. It appears to be more stable with the newer
Windows versions. see.....manual7

Simply Modbus TCP Client 7.1.2 will automatically use a license for Simply Modbus TCP Client if already installed on
the PC.

Starting the program

Double-click on Simply Modbus TCP Client 1.4.exe.

You will see the demonstration startup window.

https://www.simplymodbus.ca/TCPmanual.htm 1/9
17/11/2020 TCP Client Manual 1 | Simply Modbus Software

The progress bar will take approximately 15 seconds to load the demonstration version.
During this time, you can press the ENTER KEY and see

After purchasing and receiving a license key by email, enter the key and press OK.

The licensed program


- goes immediately to the main Simply Modbus Read window and bypasses the Loading Demo startup window.
- allows unlimited reads and writes.

The demo version


- offers full functionality
- requires a program restart to send more than six read requests or two write commands.

The Simply Modbus TCP Client Read Window

https://www.simplymodbus.ca/TCPmanual.htm 2/9
17/11/2020 TCP Client Manual 1 | Simply Modbus Software

Controls (inputs) that can be changed by the user are shown in yellow.
Indicators (outputs) shown in blue cannot be changed.

Set the controls to build the Request string.

Select TCP or RTU-over-TCP mode. more info...

Select the IP Address of the Server (Slave device) that you wish to connect to.

Select the Server's Port to connect to.

Press the Connect button and the program will attempt to connect to the Modbus Server.
Each 6 second attempt will count up on the button after the word CONNECTING.
The program will keep trying to connect until a connection is made or the button is pressed again.
The connection status is displayed as CONNECTED or NOT CONNECTED.

When in TCP Mode, The first 7 bytes in the Request is the MBAP header. The 7th byte is the Slave ID.
When in RTU-over-TCP Mode, the first six bytes of the MBAP header are not present. The Request starts with the Slave ID.

The 7th byte in the Request string in TCP Mode (The 1st byte in RTU-over-TCP mode)
The unit address of the Server (Slave) device to get data from. normal range: 1 to 247 more info...

Setting a Slave ID over 255 will automatically check this box and allow Slave IDs up to 65535. more
info...

https://www.simplymodbus.ca/TCPmanual.htm 3/9
17/11/2020 TCP Client Manual 1 | Simply Modbus Software
Remains on for all addresses until the Slave ID is lowered below 256 and the box manually unchecked.

The 8th byte in the Request string in TCP Mode (The 7th byte in RTU-over-TCP mode
Can be automatically set more info...
Used to select which table to read from. more info...
Read Window supports Function codes 01, 02, 03 & 04

The 9th & 10th bytes in the Request string in TCP Mode (The 3rd & 4th bytes in RTU-over-TCP mode)
The coil or register number at the start of the block to read. more info...

This value is subtracted from the First Register to give the data address used in the Request.

The 11th & 12th bytes in the Request string. in TCP Mode (The 5th & 6th bytes in RTU-over-TCP mode)
The quantity of registers or coils in the block to read.

check to automatically set the default values function code, offset and register size
when the value of First Register is changed.

The size of the registers in the block to be read.


This value should be set to 16 bit registers to read standard modbus registers.
and set to 1 bit coils to read standard modbus coils.
32 bit registers should be used for Enron modbus only. more info...

Events: This box is checked when reading Enron events from register 32 more info...

History: This box is checked when reading Enron historical records from register 701-799 more info...

TCP Mode RTU-over-TCP Mode

crc In RTU-over-TCP Mode, the last 2 bytes of the Request are the cyclic redundancy check. These are error detection
bytes.
They are not present in TCP Mode more info...

Auto Set values:

First Register function code minus offset register size


1 to 10000 1 1 1 bit coils
10001 to 10000 2 10001 1 bit coils
30001 to 40000 4 30001 16 bit registers
40001 & greater 3 40001 16 bit registers

Exceptions (for reading Enron modbus data):

First Register function code minus offset register size


32 (events) 3 0 32 bit registers
701 to 799 (history) 3 0 32 bit registers
1001 to 1999 1 0 1 bit coils
3001 to 3999 3 0 16 bit registers
5001 to 5999 3 0 32 bit registers
7001 to 7999 3 0 32 bit registers

Physical Connection

Before sending a message, the ethernet port needs to be physically connected to a network with Modbus servers.

Sending the Request

Press the SEND button. The program then monitors for incoming data and displays all bytes received in the Response
indicator. The SEND button is greyed out until a connection is established with the Modbus Server (Slave device).
https://www.simplymodbus.ca/TCPmanual.htm 4/9
17/11/2020 TCP Client Manual 1 | Simply Modbus Software

While receiving, the response time counts up with a progress bar.

Receiving stops when the expected response bytes are received or the time
reaches the fail in value entered.

The 'expected response bytes' indicator is calculated from the input settings.
The response timer stops when this many bytes are received.

Troubleshooting

Check the IP Address and Port in the Modbus Server (Slave device) to make sure it matches the settings in the TCP Client
program (Master device)

Reading the Response

The data bytes in the response are displayed in the bytes column of the response table.

Use the pull-down boxes in the first column to set the data type for each value. more info...
The copy down button sets all data types to match the setting for the first value.

The bytes and words can be swapped by toggling the High/Low check boxes.

The bytes are re-processed immediately as the settings are changed and the results are shown in the fourth column.
Sending another request for a new response is not required for a recalculation.

A notes column is provided to enter labels for the values.

Press the clear notes button to blank the whole notes column.

Byte History Log

All bytes sent and received are added to the byte history log with date/time stamps.

Displays a 'Save As..' dialog box to allow the log contents to be saved to a text file.

Empties the log contents.

Log Results

All data results received can be saved to a data log with date/time stamps.

Displays a 'Save As..' dialog box to create a tabbed-text data file for logging the results.

register# and notes are used as column headers in the file.

When data is received, a row is added to the file with date/time and the results.

https://www.simplymodbus.ca/TCPmanual.htm 5/9
17/11/2020 TCP Client Manual 1 | Simply Modbus Software
Pressing the button again will close the file and stop logging the results.

The data file can be loaded into just about any system or progam like Excel.

Send Continuously

Check this box to send back to back requests.

The seconds after the start of one send request until the start of the next send request.

Statistics

The seconds taken for the slave to respond to last message.


The number of message responses received (meeting the expected response bytes).
The number of message with an incomplete or absent response

The longest amount of seconds taken for a response (not including failed responses).
The average amount of seconds taken for a response (not including failed responses).
The shortest amount of seconds taken for a response (not including failed responses).
Sets all statistical values back to zero.

Save and Restore Configurations

Displays a 'Save As..' dialog box to allow saving the current settings and results to a text file.

Displays a 'Open File' dialog box to allow selecting a previously saved settings file to load.

The configuration file is saved in tabbed text format (tab separated values) and appears like this in notepad.

The preset tabs in Notepad cause the cells with long labels to push the other columns over.
Sending it to, or opening it from, a spreadsheet program like Excel will use the tabs as column delimiters as shown here...

https://www.simplymodbus.ca/TCPmanual.htm 6/9
17/11/2020 TCP Client Manual 1 | Simply Modbus Software
1st column contains descriptions, 2nd column contains values

3rd column contains the data types 0 through 11 in the order shown in its pull down menu.

4th column is empty, 5th column contains the register numbers.

6th column contains the register values from the last poll, if any

------------------------------------------------------------------------------------

Writing Data

Displays the Simply Modbus TCP Client Write1.4 window

Controls (inputs) that can be changed by the user are shown in yellow.
Indicators (outputs) shown in blue cannot be changed.

Set the controls to build the Command string.

The mode setting is copied from the previous window and can also be changed here.

Select TCP or RTU-over-TCP mode. more info...

The IP Address and Port are copied from the previous window and cannot be changed here.

The 7th byte in the Command string. in TCP Mode (The 1st byte in RTU-over-TCP mode)
The unit address of the Slave device to get data from. normal range: 1 to 247 more info...

Setting a Slave ID over 255 will automatically check this box and allow Slave IDs up to 65535. more
info...
Remains on for all addresses until the Slave ID is lowered below 256 and the box manually unchecked.

https://www.simplymodbus.ca/TCPmanual.htm 7/9
17/11/2020 TCP Client Manual 1 | Simply Modbus Software

The 8th byte in the Command string. in TCP Mode (The 7th byte in RTU-over-TCP mode)
Can be automatically set more info...
Used to select which table to write to. more info...
Write Window supports Function codes 05, 06, 15 & 16

The 9th & 10th bytes in the Command string. in TCP Mode (The 3rd & 4th bytes in RTU-over-TCP mode)
The coil or register number at the start of the block to be written. more info...

This value is subtracted from the First Register to give the data address used in the Command.

The 11th & 12th bytes in the Command string. in TCP Mode (The 5th & 6th bytes in RTU-over-TCP mode)
The quantity of registers or coils in the block to be written.

Check to automatically set the default values for function code, offset and register size
when the value of First Register is changed.

The size of the registers in the block to be written.


This value should be set to 16 bit registers to write standard modbus registers.
and set to 1 bit coils to write standard modbus coils.
32 bit registers should be used for Enron modbus only. more info...

Auto Set values:

First Register function code minus offset register size


1 to 7000 5 1 1 bit coils
7001 to 7999 (Enron modbus) 16 0 32 bit registers
8000 to 10000 5 1 1 bit coils
10001 to 30000 5 10001 1 bit coils
30001 to 40000 6 30001 16 bit registers
40001 & greater 6 40001 16 bit registers

Data to Write

The values to write are entered in the table shown. The table size is automatically adjusted as the #values to write is
changed.

Use this pull-down box to set the data type for the whole table to be written.

The bytes and words can be swapped by toggling the High/Low check boxes.

Sending the Command

Press the SEND button. The program then monitors for incoming data and displays all bytes received in the Response
indicator.

While receiving, the response time counts up with a progress


bar.

Receiving stops when the expected response bytes are received


or the time reaches the fail in value entered.

The 'expected response bytes' indicator is calculated from the


input settings.
The response timer stops when this many bytes are received.

Reading the Response

The data bytes in the response are displayed in the bytes column of the response table.

https://www.simplymodbus.ca/TCPmanual.htm 8/9
17/11/2020 TCP Client Manual 1 | Simply Modbus Software
Byte History Log

All bytes sent and received are added to the byte history log with date/time stamps.

Displays a 'Save As..' dialog box to allow saving the log contents to a text file.

Empties the log contents

Save and Restore Configurations

Displays a 'Save As..' dialog box to allow saving the current settings to a text file.

Displays an 'Open File' dialog box to allow selecting a previously saved settings file to load.

Press the Close box in the top corner to Exit the Write program.