Additional characteristics Tripping curves

Compact NS400 to 630


Protection of distribution systems

STR23 and STR53 electronic trip units


STR23SE / STR23SV STR53UE / STR53SV

10 000
DB115281

10 000

DB115282
5 000 5 000

2 000 2 000
Ir = 0.4 1 x In Ir = 0.4 1 x In
1 000 1 000
500 500

200 200
100 100
50 50 tr = 0.5 16 s

20 20
Ii = 1.5 11 x In
10 10
5 5
t(s) t(s) Isd = 1.5 10 x Ir
2 2
l 2 t OFF
Isd = 2 10 x Ir 1
1
.5 .5
0.3
.2 .2
0.2
.1 .1 2
l t OFF 0.1
.05 .05
0
.02 .02
.01 Reflex tripping : .01
t < 10 ms
.005 .005 Reflex tripping :
t < 10 ms
.002 I = 11 x In .002
.001 .001
.5 .7 1 2 3 4 5 7 10 20 30 50 70 100 200 300 .5 .7 1 2 3 4 5 7 10 20 5 7 10 20 30 50

I / Ir I / Ir I / In

Options for STR53UE


Earth-fault protection
DB115283

10 000
5 000

2 000
Ig = 0.2 1 x In
1 000
500

200
100
50

20
10
I2t ON
5
t(s)
2
1
.5 0.4
0.3
.2 0.2

.1 I2t OFF 0.1

.05

.02
.01
.005

.002
.001
.05 .07 .1 .2 .3 .4 .5 .7 1 2 3 5 7 10 20 30
I / In