kV=10)
H-110-RP-0262
.5 1 5 10 50 100 500 1K 5K 10K
1K 1K
OCR
500 500
100 100
50 50
10 10
5 5
H-110-RP-0262 - P
Seconds
Seconds
OC1
GE Multilin
750/760
CT Ratio 300:5
IEC - B
Pickup = 1.6 (0.05 - 20 xCT Sec)
Time Dial = 0.5
1 3x = 3.38 s, 5x = 1.69 s, 8x = 0.964 s 1
Inst = 8 (0.05 - 20 xCT Sec)
.5 .5
.1 .1
.05 .05
.01 .01
.5 1 5 10 50 100 500 1K 5K 10K
Amps X 10 H-110-PDC-026 (Nom. kV=10, Plot Ref. kV=10) ETAP Star 16.0.0C