FusionModule800 V100R001C00 Survey Report Template
FusionModule800 V100R001C00 Survey Report Template
V100R001C00
Survey Report Template
Issue
Sufficient water supply, stable and reliable electric power, convenient transportation and communications
environment
Basic A considerable distance from areas which generate dust, oil fume, harmful gas, or corrosive objects, or s
Requirements
A considerable distance from flood-prone areas
A considerable distance from sources of strong vibration, loud noises, and strong electromagnetic interfe
Distance
Requirements
GB50174-2008 Design IDS2000 V500R002C00勘
测报告 OFFE00016342_PMD46ZH A 秘密
Code for Electronic
Computer Room
Distance from arsenals ≥ 1600 meters ≥ 1600 meters
Distance
Requirements Distance from dangerous areas of
nuclear power plants ≥ 1600 meters ≥ 1600 meters
The equipment
room should not
Flood-prone areas be deployed. The equipment room should not be deployed.
The equipment
Areas near earthquake faults or room should not
landslide-prone areas be deployed. The equipment room should not be deployed.
The equipment
room should be far
away from airport
Airport runways runways. The equipment room should be far away from airp
The equipment
room should not
Areas with high crime rate be deployed. The equipment room should not be deployed.
1. The data center should not be close to air routes of a nearby airport.
Basic 2. The distance from railways or highways should be 800 m at least to lower the risk of chemical substan
Requirements
3. The distance from military bases should be greater than 800 m, and the distance from nuclear facilities
should be greater than 1600 m.
Precautions for Site Selection T3 Standard T4 Stand
Distance from an airport 1.8–48 km away from the airport 1.8–48 km away fr
Distance from major cities ≤ 48 km ≤ 48 k
IDS2000 V500R002C00勘
测报告 OFFE00016342_PMD46ZH A 秘密
electromagnetic interference
Remarks
ld not be deployed.
ld not be deployed.
ld not be deployed.
T4 Standard
≥ 800 meters
≥ 800 meters
Number of building
floors and the floor Record the number of building floors and the
3.3 Data Design
where the data floor where the data center is located.
center is located
Record the vertical distance between the
Equipment room spandrel girder on the ceiling board and the
3.4 Data Design
height floor, and the vertical distance between the
ceiling and the floor.
Measure the height between the completed
Equipment room net
3.5 floor and the lowest beam or suspended Data Design
height
ceiling.
Position, length, and
Measure the positions, lengths, and widths of
3.6 width of equipment Data and drawing Design
equipment room columns.
room columns
Usable area and
3.7 shape of the data Measure the usable area of the data center. Data and drawing Design
center
Bearing capacity of Measure the bearing capacity of the floor
the floor where the where the data center is located to determine
3.8 Building Data Design
data center is whether the floor is able to bear an equipment
condition located room.
Data center outdoor Mark the area for placing air conditioner
3.9 space and its outdoor units and the diesel generator (DG) on Data and drawing Design
bearing capacity the site survey plan.
Design and
5.2 Frequency range Record the AC frequency (Hz). Data
delivery
Grounding
IDS2000 V500R002C00勘
测报告 OFFE00016342_PMD46ZH A 秘密
Installation height
Measure the height difference if the outdoor
difference between
unit is placed higher than the indoor unit. Design and
8.2 the air conditioner Data
Air Measure the height difference if the outdoor delivery
indoor and outdoor
conditioner units unit is placed lower than the indoor unit.
outdoor unit
(air cooled Local property
chiller) manager's or house Work with the customer to communicate with
owner's agreement the local property manager or house owner,
on the installation describe the installation position, purpose, and Design and
8.3 Description
position and cable parameters of outdoor units, and obtain the delivery
routes for the air local property manager or house owner's
conditioner outdoor approval.
units
IDS2000 V500R002C00勘
测报告 OFFE00016342_PMD46ZH A 秘密
Corridor wall
10.7 Record the corridor wall materials. Description Design
materials
IDS2000 V500R002C00勘
测报告 OFFE00016342_PMD46ZH A 秘密
Remarks
Voltage range
IDS2000 V500R002C00勘
测报告 OFFE00016342_PMD46ZH A 秘密
The pipe routes refer to the routes that pipes will pass
through during construction, including items related to
the pipe design and construction, such as the
installation method, drilling holes or not, and passing
through the corridor or not.
The pipe routes refer to the routes that pipes will pass
through during construction, including items related to
the pipe design and construction, such as the
installation method, drilling holes or not, and passing
through the corridor or not.