ND9000® INTELLIGENT VALVE

CONTROLLER
Neles ND9000 is a top class intelligent valve
controller designed to operate on every control
valve actuator and in all industry areas. It
guarantees the end product quality in all
operating conditions with unique diagnostics and
incomparable performance features. ND9000 is
a reliable and future-proof investment with Neles
FieldCare™ life-time support

KEY FEATURES
□ Benchmark control performance on rotary and lin-
ear valves
□ Reliable and robust design
□ Easy commissioning and operation
□ Language selection: English, German and French
□ Local / remote operation
□ Expandable architecture
□ Advanced device diagnostics including
□ Self-diagnostics
□ Online diagnostics
□ Performance diagnostics
□ Communication diagnostics
□ Extended off-line tests
□ Intelligent Valve Diamond

Options
□ Interchangeable communication options:
□ HART
□ FOUNDATION fieldbus
□ Profibus PA
□ Limit switches
□ Position transmitter (in HART only)
□ Full stainless steel enclosure
□ Exhaust adapter
□ Flush mounting capability to avoid tubing and
Total cost of ownership mounting parts
□ Low power comsumption enables installation to all
□ Low energy and air consumption
common control systems
□ Future proof design allows further options at a
reduced cost Open solution
□ Optimized spares program minimizes spare part
□ Metso is committed to delivering products that
inventory
freely interface with software and hardware from a
□ Retro-fit to existing installations (Neles or 3rd party
variety of manufacturers; ND9000 is no exception.
valves)
This open architecture allows the ND9000 to be
Minimised process variability integrated with other field devices to give an
unprecedented level of controllability.
□ Linearisation of the valve flow characteristics
□ FDT and EDD based multi-vendor support configu-
□ Excellent dynamic and static control performance
ration
□ Fast response to control signal change
□ Support files for ND9000 are available from our
7 ND90 20 EN • 11/2009

□ Accurate internal measurements


internet page, at www.metso.com/ND9000
Easy installation and configuration
□ Same device can be used for linear and rotary
valves, double and single-acting actuators
□ Simple calibration and configuration
□ using Local User Interface (LUI)
□ using FieldCare software in a remote location
□ using Distributed Control System (DCS) asset
management tools
METSO 7 ND90 20EN

Neles ND9000 in fieldbus networks TECHNICAL DESCRIPTION


□ Approved interoperability The ND9000 is a 4–20 mA or fieldbus powered microcontrol-
□ Host interoperability ensured ler-based intelligent valve controller. The device contains a
□ FOUNDATION fieldbus ITK version 5.01 certified Local User Interface (LUI) enabling local configuration. A PC
□ Profibus PA profile version 3.0 PNO certified with FieldCare software can be connected to the ND9000
□ Easy to upgrade; can be done by replacing the HART itself or to the control loop.
communication board to fieldbus communication board
□ Excellent maintainability with firmware download feature The powerful 32-bit microcontroller controls the valve posi-
□ Advanced communication diagnostics tion. The measurements include:
□ Digital communication via the fieldbus includes not only □ Input signal
the set point, but also the position feedback signal from □ Valve position with contactless sensor
the position sensor. No special supplementary modules □ Actuator pressures, 2 independent measurements
for analog or digital position feedback are needed when □ Supply pressure
using the fieldbus valve controller. □ Spool valve position
□ Back up LAS functionality available in FOUNDATION field- □ Device temperature
bus enviroment
□ Input selector and output splitter blocks available in FOUN- Advanced self-diagnostics guarantees that all measure-
DATION fieldbus devices allowing advanced distributed ments operate correctly. After connections of electric signal
control and pneumatic supply the micro controller (μC) reads the
□ Standard function blocks enables the freedom to use input signal, position sensor (α), pressure sensors (Ps, P1,
ND9000 intelligent valve controller either in continuous or P2) and spool position sensor (SPS). A difference between
on-off control applications input signal and position sensor (α) measurement is
□ Open and close information is directly available via the detected by control algorithm inside the μC. The μC calcu-
fieldbus lates a new value for prestage (PR) coil current based on the
□ Open and close detection is based on either position information from the input signal and from the sensors.
measurement (soft limit switch) or mechanical limit switch Changed current to the PR changes the pilot pressure to the
information spool valve. Reduced pilot pressure moves the spool and the
actuator pressures change accordingly. The spool opens the
ND9000 mounting on actuators and valves flow to the driving side of the double diaphragm actuator and
□ Mounted on single and double acting actuators opens the flow out from the other side of the actuator. The
□ Both rotary and linear valves increasing pressure will move the diaphragm piston. The
□ Flush mounting capability actuator and feedback shaft rotate. The position sensor (α)
□ Ability to attach options to electronics and mechanics later measures the rotation for the μC. The μC using control algo-
□ 1-point calibration feature enables mounting without dis- rithm modulates the PR-current from the steady state value
turbing the process until a new position of the actuator according to the input sig-
nal is reached.
Product reliability
□ Designed to operate in harsh environmental conditions
□ Rugged modular design
□ Excellent temperature characteristics
□ Vibration and impact tolerant
□ IP66 enclosure
□ Stainless steel enclosure as an option
□ Protected against humidity
□ Maintenance free operation
□ Resistant to dirty air
□ Wear resistant and sealed components
□ Contactless position measurement

Predictive maintenance
□ Easy access to collected data with Neles FieldCare soft-
ware
□ Intelligent Valve Diamond to visualise control valve per-
formance & diagnostics
□ Logical trend and histogram collection
□ Information collected during process uptime
□ Extensive set of off-line tests with accurate key figure cal-
culations
□ Fast notifications with on-line alarms
□ Condition monitoring tool available

2 TECHNICAL BULLETIN 11/09


7 ND90 20EN ND9000F ® I N T E L L I G E N T VA LV E C O N T RO L L E R

TECHNICAL SPECIFICATIONS
ND9000 INTELLIGENT VALVE CONTROLLER

General Electronics
Loop powered, no external power supply required. HART
Suitable for rotary and linear valves. Supply power: Loop powered, 4–20 mA
Actuator connections in accordance with VDI/VDE 3845 and Minimum signal: 3.6 mA
IEC 60534-6 standards. Current max : 120 mA
Flush mounting on selected actuators Load voltage: up to 9.5 VDC/20 mA
Action: Double or single acting (corresponding 475 Ω)
Travel range: Linear; 10–120 mm / 0.4-4.7 in Voltage: max. 30 VDC
rotary; 45–95 degrees. Measurement Polarity protection: -30 VDC
range 110° with freely rotating Over current protection: active over 35 mA
feedback shaft. EEx ia IIC T6: Ui ≤ 28 V
Ii ≤ 120 mA
Environmental influence Pi ≤ 1 W
Standard temperature range: Ci = 22 nF
-40° – +85 °C / -40° – +185 °F Li = 53 μH
Influence of temperature on valve position:
0.5 % /10 °K Profibus PA and FOUNDATION fieldbus
Influence of vibration on valve position: Supply power: voltage 9–32 VDC, reverse polarity
< 1 % under 2g 5–150 Hz, protection
1g 150–300 Hz, 0.5g 300–2000 Hz Max basic current 17.2 mA
Fault current (FDE) 3.9 mA
Enclosure
Material: Anodized aluminium alloy and FOUNDATION fieldbus function block
polymer composite (ND9100) or execution times
tempered glass (ND9200) AO 20 ms
Protection class: IP66, Nema 4x PID 25 ms
Pneumatic ports: G 1/4 (ND9100) DO 15 ms
NPT (ND9200) DI 15 ms
Cable gland thread: M20x1.5 (ND9000) IS 15 ms
1/2 NPT (ND9200 E2) OS 20 ms
Weight: 1.8 kg / 4.0 lbs (ND9100)
3.4 kg / 6.5 lbs (ND9200) Performance with moderate constant-load
Mechanical and digital position indicator visible through actuators EC05-EC10 in ambient temperature
main cover, not applicable ND9200 E2.
Dead band acc. to IEC 61514:≤0.1 %
Special corrosion resistance design or stainless steel hous-
Hysteresis acc. to IEC 61514:<0.5 %
ing available as an option for demanging environment.

Pneumatics Local User Interface (LUI) functions


Supply pressure: 1.4–8 bar / 20–115 psi □ Local control of the valve
Effect of supply pressure on valve position: □ Monitoring of valve position, target position, input signal,
< 0.1 % at 10 % difference in inlet temperature, supply and actuator pressure difference
pressure □ Guided-startup function
Air quality: Acc. to ISO 8573-1 □ LUI may be locked remotely to prevent unauthorised
Solid particles: Class 5 (3 – 5 μm access
filtration is recommended) □ Calibration: Automatic / Manual with or without tuning
Humidity: Class 1 (dew point 10 °C/ □ 1-point calibration
18 °F below minimum temperature □ Control configuration: aggressive, fast, optimum, stable,
is recommended) maximum stability
Oil class: 3 ( or < 1 ppm) □ Configuration of the control valve
Capacity with 4 bar / 60 psi supply: □ Rotation: valve rotation clockwise or counter-clockwise
5.5 Nm3/h / 3.3 scfm (spool valve 2) to close
12 Nm3/h / 7.1 scfm (spool valve 3) □ Dead Angle
38 Nm3 /h /22,4 scfm (spool valve 6) □ Low cut-off, cut-off safety range (default 2 %)
Consumtion with 4 bar / 60 psi supply in steady state position: □ Positioner fail action, open/close
<0.6 Nm3 /h /0.35 scfm □ Signal direction: Direct/reverse acting
(spool valve 2 & 3) □ Actuator type, double/single acting
<1.0 Nm3/h / 0.6 scfm (spool valve 6) □ Valve type, rotary/linear
□ Language selection: English, German and French

TECHNICAL BULLETIN 11/09 3


METSO 7 ND90 20EN

Position transmitter (optional) CSA


Output signal: 4–20 mA (galvanic isolation; Class 1, Div 1 Groups B, C, D
600 VDC) Class 2, Div.1 Groups E, F, G, Class III T4 ...T6, Ex d IIC T4 ... T6
Supply voltage: 12–30 VDC DIP A21 Ta 100°C IP 66
Resolution: 16 bit / 0.244 μA
Linearity: <0.05 % FS CE Marking
Temperature effect: <0.35 % FS 89/336/EEC
External load: max 0–780 Ω Electromagnetic compatibility 94/9/EC
max 0–690 Ω for intrinsically safe ATEX (when applicable)
Ex ia IIC T6 Ui ≤28 V
Ii ≤120 mA
PROXIMITY SENSORS AND LIMIT SWITCHES
Rx =0–690 Ω
(OPTIONAL WITH EXTENSION MODULE)
Pi ≤1 W Code I02 P+F NJ2-12GK-SN, 2 sensors
Ci = 22 nF Code I09 P+F; NCB2-12GM35-N0
Li = 53 μH Code I56 IFC 2002-ARKG/UP, 2 sensors
Code K05 Omron D2VW-5, micro switch, 2 sensors
APPROVALS ND9100 Code K06 Omron D2VW-01 gold plated, micro switch
Intrinsically safe and non incendive Code B06 Omron D2VW-01 gold plated, micro switch, 2 sen-
ATEX sors. (Bus powered, no external power and cabling needed).
EC-Directive 94/9/EC;
II 1 G, Ex ia IIC T4/T5/T6 Ga
II 1 D, Ex tD A20 T 90 °C
II 2 G, Ex ia IIC T4/T5/T6 Ga
II 2 D, Ex tD A21 T 90 °C
II 3 G, Ex nA IIC T4/T5/T6
II 3 D, Ex tD A22 T90 °C
II 3 G, Ex nL IIC T4/T5/T6
II 3 D, Ex tD A22 T90 °C
(EN 60079, EN 60070, EN 61241)

CSA
CAN/CSA-C22.2-0,-142, -157;
CAN/CSA-E60079-0,-11, -15
IS Class I, Div. 1, Groups A, B, C, D T4...T6
IS Class I, Zone 0, Ex ia IIC T4...T6
NI Class I, Div. 2, Groups A, B, C, D T4...T6
NI Class I, Zone 2, Ex nA IIC T4...T6.

FM
FM Class 3600, 3610, 3611, 3810:
Fig. 1. Local User Interface (LUI) enables real time aware-
IS Class I, Div. 1, Groups A, B, C, D T4...T6
ness of control parameters in the device at a glance.
IS Class I, Zone 0, AEx ia IIC T4...T6
NI Class I, Div. 2, Groups A, B, C, D T4...T6
NI Class I, Zone 2, Ex nA IIC T4...T6

Electromagnetic Protection
Electromagnetic compatibility
Emission acc. to EN 61000-6-4 (2001)
and FCC 47 CFR PART 15,
SUBPART B, CLASS B (1994)
Immunity acc. to EN 61000-6-2 (2001)

APPROVALS ND9200
Flameproof and explosion proof
ATEX
EC-Directive 94/9/EC;
II 2 G Ex d IIC T4...T6 (EN 60079-0:2006, EN 60079-1:2004)
II 2 D Ex tD A21 IP66 T 100 °C (EN 61241-0:2006, EN 61241-
1:2004)
Certificate KEMA 04ATEX2098 X Fig. 2. Trend collection enables fast and easy predictive
maintenance. The need for maintenance is reduced and
FM increased plant and process availability are realised.
Explosion proof Class I, II and III,
Division 1 and 2, Groups A, B, C, D, E, F

4 TECHNICAL BULLETIN 11/09


7 ND90 20EN ND9000F ® I N T E L L I G E N T VA LV E C O N T RO L L E R

HOW TO ORDER
INTELLIGENT VALVE CONTROLLER ND9000

1. 2. 3. 4. 5. 6. 7. 8. 9. 6. APPROVALS OF ND9100 VALVE CONTROLLER


ND 9 10 3 H X1 T ATEX certifications:
II 3 G, Ex nA IIC T4/T5/T6
II 3 D, Ex tD A22 T90C
1. PRODUCT GROUP (EN 60079, EN 60070, EN 61241)
No Zener Barrier needed.
ND Intelligent valve controller Not applicable to 3. sign "20".
ND91_HX3:
Ui ≤ 30 V, Pmax = device limits
2. SERIES CODE itself, Li = 53 μH, Ci = 22 nF.
X3 M20x1.5 conduit entry.
Series 9000 valve controller with universal shaft and attachment Temperature range: T4; -40 – +85 °C / -40 – +185 °F,
face according to standard VDI/VDE 3845, EC/EJ actuators and T5; < +75 °C / +167 °F, T6; < +60 °C / +140 °F.
9 Metso standard. Relevant shaft adapter included in mounting kits. ND91_FX3 and ND91_PX3:
When valve positioners are separate deliveries, shaft adapter kit is Ui ≤ 24 V, Ci < 5 nF, Li < 10 μH
supplied. M20x1.5 conduit entry.
Temperature range: T4; -40° – +85 °C / -40°– +185 °F,
T5; < +75 °C / +167 °F, T6; < +60 °C / +140 °F.
3. ENCLOSURE Not available with limit switches with 8. sign I or K
10 Standard IP66 / NEMA 4X enclosure ATEX certifications:
II 3 G, Ex nL IIC T4/T5/T6
20 Flameproof (Ex d) IP66 / NEMA 4X enclosure II 3 D, Ex tD A22 T90C
(EN 60079, EN 60070, EN 61241)
FNICO model:
PNEUMATIC CONNECTIONS Not applicable to 3. sign "20".
4. SPOOL VALVE ND91_HX4:
(S, C1, C2)
Ui ≤ 30 V, Pmax = device limits itself,
Low capacity. G 1/4 (ND9100) X4 Li = 53 μH, Ci = 22 nF, Ii = 152mA
2
Stroke volume of actuator < 1 dm3 1/4 NPT (ND9200) M20x1.5 conduit entry.
Medium capacity. G 1/4 (ND9100) Temperature range: T4; -40 – +85 °C / -40 – +185 °F,
3 T5; < +75 °C / +167 °F, T6; < +60 °C / +140 °F.
Stroke volume of actuator 1 - 3 dm3 1/4 NPT (ND9200)
ND91_FX4 and ND91_PX4:
High capacity. G 1/4 (ND9100) Ui ≤ 32 V, Ci ≤ 5 nF, Li ≤ 10 μH, Pi ≤ 5.32 W, Ii ≤ 380 mA
6
Stroke volume of actuator > 3 dm3 1/4 NPT (ND9200) M20x1.5 conduit entry.
Temperature range: T4; -40° – +85 °C / -40°– +185 °F,
T5; < +75 °C / +167 °F, T6; < +60 °C / +140 °F.
5. COMMUNICATION / INPUT SIGNAL RANGE
FM and CSA certifications:
4-20 mA, HART communication. IS Class I, Division 1, Groups A, B, C, D, T4...T6
H Supply voltage 30 V DC. Load voltage: up to 9.5 V DC at 20 mA IS Class I, Zone 0, AEx ia, IIC T4...T6
corresponding to 475 Ω (maximum voltage drop). Not applicable to 3. sign "20"
ND91_HU1: Ui ≤ 28 V, Ii ≤ 120 mA, Pi ≤ 1 W, Li = 53 μH, Ci = 22 nF.
F FOUNDATION fieldbus. M20 x 1.5 conduit entry.
Physical layer according to IEC 61158-2. Temperature range: T4; -40 – +80 °C / -40 – +176 °F,
Profibus PA. U1 T5; < +65 °C / +149 °F, T6; < +50 °C / +122 °F.
P Not available with any limit switches (8. sign I, K or B).
Physical layer according to IEC 61158-2.
ND91_FU1 and ND91_PU1: Ui ≤ 24 V, Ii ≤ 380 mA, Pi ≤ 5.32 W,
Ci < 5 nF, Li < 10 μH.
6. APPROVALS OF ND9100 VALVE CONTROLLER M20 x 1.5 conduit entry.
Temperature range: T4; -40 – +80 °C / -40 – +176 °F,
No approvals for hazardous areas. M20x1.5 conduit entry. T5; < +65 °C / +149 °F, T6; < +50 °C / +122 °F.
N Not applicable to 3. sign "20". Not available with any limit switches ( 8. sign I, K or B).
Temperature range -40 ... +85°C / -40 ... +185°F.
FM and CSA certifications:
ATEX certifications: NI Class I, Division 2, Groups A, B, C, D, T4...T6.
II 1 G, Ex ia IIC T4/T5/T6 Ga NI Class I, Zone 2, Ex nA IIC T4...T6.
II 1 D, Ex tD A20 T 90°C No Zener Barrier needed.
(EN 60079, EN 60070, EN 61241) Not applicable to 3. sign "20"
Not applicable to 3. sign "20". ND91_HU2: Ui ≤ 30 V, Pmax = device limits itself,
ND91_HX1: Li = 53 μH, Ci = 22 nF, external load resistance 0–780 Ω
Ui < 28 V, Ii < 120 mA, Pi < 1 W, Li = 53 μH, Ci = 22 nF. M20 x 1.5 conduit entry.
M20x1.5 conduit entry. U2 Temperature range: T4; -40 – +85 °C / -40 – +185 °F,
Temperature range: T4; -40 – +80 °C / -40 – +176 °F, T5; < +70 °C / +158 °F, T6; < +55 °C / +131 °F.
X1 T5; < +65 °C / < +149 °F, T6; < +50 °C / < +122 °F. Not available with any limit switches (8. sign I, K or B).
Not available with any limit switches (8. sign I, K or B) ND91_FU2 and ND91_PU2: Ui ≤ 24 V, Ii ≤ 380 mA, Pi ≤ 5.32 W,
ND91_FX1, ND91_PX1 Ci < 5 nF, Li < 10 μH.
Ui ≤ 24 V, Ii ≤ 380 mA, Pi ≤ 5.32 W, M20 x 1.5 conduit entry.
Ci < 5 nF, Li < 10 μH. Temperature range: T4; -40 – +85 °C / -40 – +185 °F,
M20x1.5 conduit entry. T5; < +75 °C / +167 °F, T6; < +60 °C / +140 °F.
Temperature range: T4; -40 – +80 °C / -40 – +176 °F, Not available with any limit switches ( 8. sign I, K or B).
T5; < +65 °C / +149 °F, T6; < +50 °C / +122 °F.
Not available with limit switches with 8. sign I or K
ATEX certifications:
II 2 G, Ex ia IIC T4/T5/T6 Ga
II 2 D, Ex tD A21 T 90°C
(EN 60079, EN 60070, EN 61241)
Not applicable to 3. sign "20"
ND91_HX2: Ui ≤ 28 V, Ii ≤ 120 mA, Pi ≤ 1 W, Li = 53 μH, Ci = 22 nF.
X2 M20x1.5 conduit entry.
Temperature range: T4; -40° – +80 °C / -40°– +176 °F,
T5; < +65 °C / +149 °F, T6; < +50 °C / +122 °F.
Only available with ATEX certified inductive limit switches (e.g. I02,
I09).
Without limit switches and with B_ switches, use X1 instead.

TECHNICAL BULLETIN 11/09 5


METSO 7 ND90 20EN

6. APPROVALS OF ND9200 VALVE CONTROLLER LIMIT SWITCH TYPE


8.
Not applicable to 3. sign "30"
Flameproof enclosure, M20 x 1.5 conduit entry.
ATEX certifications: Inductive proximity switches, 2 pcs.
II 2 G Ex d IIC T4...T6 (EN 60079-0:2006, EN 60079-1:2004) IP 66/ NEMA 4X enclosure.
II 2 D Ex tD A21 IP66 T 100 °C (EN 61241-0:2006, EN 61241- M20x1.5 conduit entry (2 pcs). Option E2: 1/2NPT conduit entry
1:2004) (2 pcs).
Not applicable to 3. sign "10". P+F; NJ2-12GK-SN, 2-wire type, DC; > 3 mA; < 1 mA.
E1 ND92_HE1: Ui ≤ 30 V Intrinsically safe according to ATEX II 2 G Ex ia IIC T6.
Temperature range: T4; -40° – +85 °C / -40° – +185 °F Temperature range -40...+85 °C / -40...+185 °F
T5; < +75 °C / < +167 °F, T6; < +60 °C / < +140 °F I02 Option of valve controller shall always be X2, X3 or X4 or E1 or E2
ND92_FE1 and ND92_PE1: Ui ≤32 V (6. sign).
Temperature range: T4; -40° – +85 °C / -40° – +185 °F Not applicable to 6. sign "X1" , "U1" and ”U2”.
T5; < +75 °C / < +167 °F, T6; < +60 °C / < +140 °F
P+F; NCB2-12GM35-N0, 2-wire type, DC; > 3 mA; < 1 mA.
Flameproof enclosure, 1/2 NPT conduit entry. Intrinsically safe according to ATEX II 2 G Ex ia IIC T6.
Temperature range: -40° – +85 °C / -40° – +185 °F. Temperature range -25...+85 °C / -13...+185 °F
I09 Option of valve controller shall always be X2, X3 or X4 or E1 or E2 (6.
FM certification:
Class I, Div 1. Groups A, B, C, D. Class II, Div 1, sign).
Groups E, F, G, Class III T4/T5/T6 Not applicable to 6. sign "X1" , "U1" and ”U2”.
Class I, Zone 1, AEx d IIC, T4/T5/T6, IP66/Type 4X ifm IFC2002-ARKG/UP, 2-wire type, DC; 150 mA, 10 - 36 V DC,
CSA certification: leakage current < 0.6 mA.
Class I, Div 1. Groups B, C, D, I56 Temperature range -20 ... +80 °C / -4 ... +176 °F.
E2 Class II, Div 1, Groups E, F, G, Class III T4/T5/T6 Not applicable to 6. sign "X1", "X2", "X3", "X4", "U1" and "U2".
Ex d IIC T4/T5/T6, DIP A21, Ta 100 °C, IP 66/NEMA 4X
Applicable to 3. sign “20” only. Mechanical micro switches, 2 pcs.
IP 66/ NEMA 4X enclosure.
ND92_HE2: Ui ≤ 30 V
Temperature range: T4; -40° – +85 °C / -40° – +185 °F M20x1.5 conduit entry (2 pcs). Option E2: 1/2NPT conduit entry
T5; < +75 °C / < +167 °F, T6; < +60 °C / < +140 °F (2 pcs).
ND92_FE2 and ND92_PE2: Ui ≤32 V OMRON D2VW-5; 3 A - 250 V AC, 0.4 A - 125 V DC, 5 A - 30 V DC.
Temperature range: T4; -40° – +85 °C / -40° – +185 °F K05 Temperature range -40° – +80 °C / -40° – +176 °F.
T5; < +75 °C / < +167 °F, T6; < +60 °C / < +140 °F Not applicable to 6. sign "X1", "X2", "X3", "U1" and "U2".
OMROND2VW-01;gold plated contacts,100mA -30VDC /125VAC.
K06 Temperature range -40° – +80 °C / -40° – +176 °F.
7. OPTIONS OF VALVE CONTROLLER Not applicable to 6. sign "X1", "X2", "X3", "U1" and "U2".
ND9_H_T only: Internal 2-wire (passive) position transmitter. Bus powered mechanical micro switches, 2 pcs.
Analog position feedback signal, output 4-20 mA, supply voltage Applicable with ND9000F and ND9000P only.
12 - 30 VDC,external load resistance 0 – 780 Ω. IP 66 / NEMA 4 and 4X enclosure. M20x1.5 conduit entry
ND91_HX1T, ND91_HX2T: Ui < 28 V, Ii < 120 mA, (ND9000), 1/2 NPT (ND9200 E2)
Pi < 1 W, Li = 53 μH, Ci = 22 nF, external load resistance 0 - 690 Ω. OMRON D2VW-01, gold plated contacts; Bus Powered, no external
ND91_HX3T, ND91_HX4T: Ui ≤ 30 V, Pmax = device limits itself, Li power and cabling needed.
= 53 μH, Ci = 22 nF, Ii = 152 mA, external load resistance 0 - 780 Ω. B06 Temperature range -40 – +80 °C / -40 – +176 °F.
T ND91_HU1T: Ui < 28 V, Ii < 120 mA, Pi < 1 W, Li = 53 μH, Ci = 22 Not applicable to 6. sign "U1” and ”U2".
nF, external load resistance 0 - 690 Ω.
ND91_HU2T: Ui ≤ 30 V, Pmax = device limits itself, Li = 53 μH, Ci =
22 nF, external load resistance 0 - 780 Ω. 9. OPTIONS OF LIMIT SWITCH
ND92_HE1T: Ui ≤ 30 V, Pmax = device limits itself, external
load resistance 0–780 Ω. Y Special construction, to be specified.
ND92_HE2T: ≤ 30 V, Pmax = device limits itself, external Note! Information regarding stainless steel flameproof ND9300 design,
load resistance 0–780 Ω. see bulletin 7 ND93 20.
Special corrosion resistant finish. External aluminium surfaces
protected by hard anodizing with PTFE. Coating thickness 20 μm.
M
Not painted.
Not available with 7. sign G.
Exhaust adapter. ND9100: 1 x 1/2 NPT thread, ND9200: 2 x 1/2 NPT
G thread.
Not available with 7. sign M.
Y Special construction, to be specified.

6 TECHNICAL BULLETIN 11/09


7 ND90 20EN ND9000F ® I N T E L L I G E N T VA LV E C O N T RO L L E R

ADDITIONAL ACCESSORIES

FILTER REGULATOR CONNECTION PLUGS FOR ND9100


Filter regulator for supply air. Not to be used together with conduit entry nipples (CE_) or
Filter size 5 μm. cableglands (CG_).
Pressure gauge, scale bar/psi/kPa, basic material brass, ND9100H (HART): Connection plug according to M20x1.5 / DIN
nickel plated, housing stainless steel, glycerine filled. P1H 43650A (ISO 4400). Not applicable with 5. sign "F" and "P"; 6. sign
K Temperature range -40 ºC...+82 ºC / -40 ºF... +180 ºF. "X1", "X2", "X3", "U1"and "U2".
K option includes a thread nipple 1/4"NPT to 1/4"NPT Valve controller and limit switch with connection plugs (1 + 1 pc)
which is suitable with ND9000 positioner options A3 ND9100H (HART): M20x1.5 / DIN 43650A (ISO 4400).
and A5 (1/4NPT AIR CONNECTION) ND9100/K00 or 2 wire ND9100/I00 limit switches only: Male
P4H
Filter regulator for supply air. M20x1.5 / M12.
Filter size 5 μm. Not applicable with 5.sign "F" and "P".
Pressure gauge, scale bar/psi/kPa, basic material brass,
nickel plated, housing stainless steel, glycerine filled. ND9100F (FOUNDATION fieldbus): Connection plug male eurofast,
K1 Temperature range -40 ºC...+82 ºC / -40 ºF... +180 ºF. Turck FSV49, M20x1.5 / M12.
P2F
P2 is not applicable with 5. sign "H"; 6. sign "X1", "X2", "X3", "U1"
K1 option includes a thread nipple 1/4"NPT to G1/4" and "U2".
which is suitable with ND9100 positioner and with option
A1 (G1/4 AIR CONNECTION). ND9100P (Profibus PA): Connection plug male, Weidmuller
842593, M20x1.5 / M12.
P2P P2 is not applicable with 5. sign "H"; 6. sign "X1", "X2", "X3", "U1"
CONDUIT ENTRY NIPPLES and "U2".
1/2 NPT conduit entry nipples ND9100F (FOUNDATION fieldbus): Connection plug male minifast,
CE07 Turck RSFV49, M20x1.5 / 7/8".
M20x1,5 / 1/2 NPT (ND9100) P3F P3 is not applicable with 5. sign "H"; 6. sign "X1", "X2", "X3", "U1"
R1/2 (PF1/2) conduit entry nipples and "U2".
CE08 M20x1,5 / R1/2 (ND9100)
ND9100P (Profibus PA): Connection plug male minifast, Turck
1/2 NPT conduit entry nipples RSFV48, M20x1.5 / 7/8".
CE09 M20x1,5 / 1/2 NPT Exd approved (ND9100 & ND9200) P3P
P3 is not applicable with 5. sign "H"; 6. sign "X1", "X2", "X3", "U1"
and "U2".
CABLE GLANDS FOR ND9100
Not to be used together with conduit entry nipples (CE_) or PNEUMATIC CONNECTION BLOCKS
connection plugs (P_). Pressure gauges, scale bar/psi/kPa, basic material brass, housing
CG5 M20x1.5 grey/plastic, IP66 nickel plated stainless steel, glycerine filled. Connections G1/4
A1
(S, C1, C2). Temperature range -40 °C...+85 °C /
CG6 M20x1.5 blue/plastic, IP66, EExe -40 °C...+185 °F.
Pressure gauges, scale bar/psi/kPa, basic material brass, housing
nickel plated stainless steel, glycerine filled.
A3
Connections 1/4 NPT (S, C1, C2).
Temperature range -40 °C...+85 °C / -40 °C...+185 °F.
Pneumatic connection block. Material AlSiMg, anodised
grey. Connections 1/4 NPT (S, C1, C2).
A5
Temperature range -40 °C...+85 °C / -40 °C...+185 °F.
Only for ND9100.

Subject to change without prior notice.

TECHNICAL BULLETIN 11/09 7


Metso Automation Inc.
Europe, Levytie 6, P.O. Box 310, 00811 Helsinki, Finland.
Tel. +358 20 483 150. Fax +358 20 483 151
North America, 44 Bowditch Drive, P.O. Box 8044, Shrewsbury, MA 01545, USA.
Tel. +1 508 852 0200. Fax +1 508 852 8172
South America, Av. Independéncia, 2500- Iporanga, 18087-101, Sorocaba-São Paulo, Brazil.
Tel. +55 15 2102 9700. Fax +55 15 2102 9748/49
Asia Pacific, 238A Thomson Road, #25-09 Novena Square Tower A, 307684 Singapore.
Tel. +65 6511 1011. Fax +65 6250 0830
China, 19/F, the Exchange Beijing, No. 118, Jianguo Lu Yi, Chaoyang Dist, 100022 Beijing, China.
Tel. +86-10-6566-6600. Fax +86-10-6566-2575
Middle East, Roundabout 8, Unit AB-07, P.O. Box 17175, Jebel Ali Freezone, Dubai,
United Arab Emirates. Tel. +971 4 883 6974. Fax +971 4 883 6836
www.metso.com/automation

You might also like