24 deg C, and a relative humidity not exceeding 60%, a sensible heat load of 132 KW
and 84 Kg/hr of moisture has to be removed. Air is supplied to the auditorium at 15 deg C
a) How many kg of air per hour must be supplied?
b) What is the dew point temperature of supply air and what is its relative humidity?
c) How much latent heat is picked up in the auditorium?
d) What is the sensible heat factor?
e) What is the Apparatus Dew Point of the coil and its By-Pass Factor?
Cooling
Coil
Be sure when making schematic 15 deg C supply air
diagram, you can identify 1
how many state occurs supply air when added with sensible an
2 the resulting condition will be room con
132 KW (sensible)
24 deg C DB 84 kg/hr (moisture)
60% RH
State 1 2
DB ᵒC 15 24 Since there are 2 conditions already present,
WB ᵒC 18.6 by plotting to Psychrometric chart, all other conditions
RH % 60 can be found. (see red)
h KJ/kg d.a 52.73
w Kgw/kg da 0.01123
v m3/kg da 0.857
Since, 84kg/hr moisture is to be removed from the room, meaning 84kg/hr is also
being added to room, which is a latent heat:
QL = 2501 (0.0233)
QL = 58.36 KW (answer for letter c)
SHF = Qs/Qt
SHF = 132/190.36
SHF = 0.6934 (answer for letter d)
SHF (sensible heat factor is a line that connects supply air and room conditions)
the slope of SHF can be found using psychrometric chart
this is the slope of SHF = 0.6934 if this is your psychart, use the inner part
if this the found in you psychart, use
the lower half
Since we know that the supply air dry bulb temperature is 15 deg C
then we connect the SHF line to room condition (state 2) and intersect it to the dry bult of 15 deg C
the intersection is the condition of the supply air (state 1)
2
1
since, state 1 is now plotted in the psychart, all other conditions can also be found.
State 1 2
DB ᵒC 15 24
WB ᵒC 14.1 18.6
RH % 91.2 60
h KJ/kg d.a 39.7 52.73
w Kgw/kg da 0.0097 0.01123
v m3/kg da 0.829 0.857
(ma) = Qt = 190.36
(h2 - h1) (52.73 - 39.7)
2
1
State 1 is the resultant of mixture of state 2 and ADP (apparatus dew point)
when 2 points are being mixed, the psychart will just connect it with a straight line.
therefore, state 1 which is the resultant is a point in line connecting state 2 and ADP.
ADP is always lying on the saturation line. Thus, ADP is located when the line connecting
1 and 2, is extended until saturation line.
The by-pass factor (BPF) is the percentage of how many of the air that pass through
cooling coil did not touch the surface of the cooling coil.
BPF = 15 - 12.5
24 - 12.5
BPF = 0.2173 or 21.73% of the air did not touch the surface of the cooling coil
tip:
SHR is a line connecting the room condition and supply air
supply air is the resultant of ADP and state 2 (these 3 points are on same line)
state 2 is resultant of 1 and 4 (these 3 points are on same line)
answer:
a) DB = 15.12 deg C
WB = 14 deg C
b) DB = 28.25 deg C
WB = 21.25 deg C
c) ADP = 12 deg C
BPF = 0.192
d) 0.2168 kg/min
when added with sensible and latent heat of the room,
ting condition will be room condition
er conditions
11.1 KW (sensible)
3.9 KW (latent)