You are on page 1of 1

Copyright 2014 National Fire Protection Association (NFPA).

Licensed, by agreement, for individual use and single download on February 18, 2014 to Northern NY Chapter of NECA for designated user Martin
Sullivan. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact licensing@nfpa.org.

ARTICLE 220 — BRANCH-CIRCUIT, FEEDER, AND SERVICE CALCULATIONS 220.83

(C) Prohibited Reductions. There shall be no reduction of (C) Heating and Air-Conditioning Load. The largest of
the neutral or grounded conductor capacity applied to the the following six selections (load in kVA) shall be included:
amount in 220.61(C)(1), or portion of the amount in (C)(2), (1) 100 percent of the nameplate rating(s) of the air condi-
from that determined by the basic calculation: tioning and cooling.
(1) Any portion of a 3-wire circuit consisting of 2 un- (2) 100 percent of the nameplate rating(s) of the heat pump
grounded conductors and the neutral conductor of a when the heat pump is used without any supplemental
4-wire, 3-phase, wye-connected system electric heating.
(2) That portion consisting of nonlinear loads supplied (3) 100 percent of the nameplate rating(s) of the heat pump
from a 4-wire, wye-connected, 3-phase system compressor and 65 percent of the supplemental electric

Informational Note: A 3-phase, 4-wire, wye-connected heating for central electric space-heating systems. If the
power system used to supply power to nonlinear loads may heat pump compressor is prevented from operating at
necessitate that the power system design allow for the pos- the same time as the supplementary heat, it does not
sibility of high harmonic neutral conductor currents.
need to be added to the supplementary heat for the total
central space heating load.
IV. Optional Feeder and Service Load Calculations (4) 65 percent of the nameplate rating(s) of electric space
220.80 General. Optional feeder and service load calcula- heating if less than four separately controlled units.
tions shall be permitted in accordance with Part IV. (5) 40 percent of the nameplate rating(s) of electric space
heating if four or more separately controlled units.
220.82 Dwelling Unit.
(6) 100 percent of the nameplate ratings of electric thermal
(A) Feeder and Service Load. This section applies to a storage and other heating systems where the usual load
dwelling unit having the total connected load served by a is expected to be continuous at the full nameplate
single 120/240-volt or 208Y/120-volt set of 3-wire service value. Systems qualifying under this selection shall not
or feeder conductors with an ampacity of 100 or greater. It be calculated under any other selection in 220.82(C).
shall be permissible to calculate the feeder and service
loads in accordance with this section instead of the method 220.83 Existing Dwelling Unit. This section shall be per-
specified in Part III of this article. The calculated load shall mitted to be used to determine if the existing service or
be the result of adding the loads from 220.82(B) and (C). feeder is of sufficient capacity to serve additional loads.
Feeder and service-entrance conductors whose calculated Where the dwelling unit is served by a 120/240-volt or
load is determined by this optional calculation shall be per- 208Y/120-volt, 3-wire service, it shall be permissible to cal-
mitted to have the neutral load determined by 220.61. culate the total load in accordance with 220.83(A) or (B).
(B) General Loads. The general calculated load shall be (A) Where Additional Air-Conditioning Equipment or
not less than 100 percent of the first 10 kVA plus 40 percent Electric Space-Heating Equipment Is Not to Be In-
of the remainder of the following loads: stalled. The following percentages shall be used for exist-
(1) 33 volt-amperes/m2 or 3 volt-amperes/ft2 for general ing and additional new loads.
lighting and general-use receptacles. The floor area for
each floor shall be calculated from the outside dimen- Load (kVA) Percent of Load
sions of the dwelling unit. The calculated floor area
shall not include open porches, garages, or unused or First 8 kVA of load at 100
Remainder of load at 40
unfinished spaces not adaptable for future use.
(2) 1500 volt-amperes for each 2-wire, 20-ampere small-
appliance branch circuit and each laundry branch cir-
cuit covered in 210.11(C)(1) and (C)(2).
(3) The nameplate rating of the following: Load calculations shall include the following:
(1) General lighting and general-use receptacles at 33 volt-
a. All appliances that are fastened in place, permanently
amperes/m2 or 3 volt-amperes/ft2 as determined by
connected, or located to be on a specific circuit
220.12
b. Ranges, wall-mounted ovens, counter-mounted cook-
ing units (2) 1500 volt-amperes for each 2-wire, 20-ampere small-
c. Clothes dryers that are not connected to the laundry appliance branch circuit and each laundry branch cir-
branch circuit specified in item (2) cuit covered in 210.11(C)(1) and (C)(2)
d. Water heaters (3) The nameplate rating of the following:
(4) The nameplate ampere or kVA rating of all perma- a. All appliances that are fastened in place, permanently
nently connected motors not included in item (3). connected, or located to be on a specific circuit

2014 Edition NATIONAL ELECTRICAL CODE 70–73

You might also like