Single Universal

Cooling Only

MFL67986330

Region : Saudi Arabia


Printed in Apr. 1, 2022
Single Universal General Information
Up
Line
Model
1.
1. Model Line Up
Model Name Combination Indoor Unit
Product
Sales Sales
Universal AUUQ21GT6 ABNQ21GM1T6
Universal AUUQ21GT6 ATNQ21GPLT6
Universal AUUQ28GT6 ABNQ28GM1T6
Universal AUUQ28GT6 ATNQ28GPLT6
Universal AUUQ34GT6 ABNQ34GM3T6
Universal AUUQ34GT6 ATNQ34GNLT6
Universal AUUQ40GT6 ABNQ40GM3T6
Universal AUUQ40GT6 ATNQ40GNLT6
Universal AUUQ55GT6 ABNQ55GM3T6
Universal AUUQ55GT6 APNQ55GT3E6
Universal AUUQ55GT6 APNQ55GT3M6
Universal AUUQ55GT6 ATNQ55GMLT6
Universal AUUQ60GT6 ABNQ60GM3T6
Universal AUUQ60LT6 ABNQ60LM3T6

2
Single Universal

1. AUUQ21GT6 + ABNQ21GM1T6
2. AUUQ21GT6 + ATNQ21GPLT6
3. AUUQ28GT6 + ABNQ28GM1T6
4. AUUQ28GT6 + ATNQ28GPLT6
5. AUUQ34GT6 + ABNQ34GM3T6
6. AUUQ34GT6 + ATNQ34GNLT6
7. AUUQ40GT6 + ABNQ40GM3T6
8. AUUQ40GT6 + ATNQ40GNLT6
9. AUUQ55GT6 + ABNQ55GM3T6
10. AUUQ55GT6 + APNQ55GT3E6
11. AUUQ55GT6 + APNQ55GT3M6
12. AUUQ55GT6 + ATNQ55GMLT6
13. AUUQ60GT6 + ABNQ60GM3T6
14. AUUQ60LT6 + ABNQ60LM3T6
Single Universal Product Data
ABNQ21GM1T6
+
AUUQ21GT6
1.
1. AUUQ21GT6 + ABNQ21GM1T6

1.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 4.74
Rated(T1)
Btu/h 16,200
kW 4.35
Rated(T3)
Btu/h 14,800
Cooling Capacity
kW 4.12
Sensible Heat
Btu/h 14,070
kW 1.47~5.86
Min ~ Max
Btu/h 5,000~20,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 1.31
Power Input(Cooling) Rated, T3 kW 1.71
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 10
Running Current(Cooling) Rated, T1 A 5.7
Rated, T3 A 7.5
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 10
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 0.40
Type - R410A
Precharged Amount kg 1.200
Additional Charging amount g/m 20
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 2.505
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ6.35 (1/4)
Connecting Pipe
Gas mm(inch) Φ12.7 (1/2)
Piping Length IDU - ODU(Rated / Max / Min) m 5/30/5
Maximum Height Difference IDU - ODU(Max) m 20
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 49.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 13.1

4
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 15
Electrical Characteristic Comp_Rated Load Amperes (Max) A 9.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.25
Outdoor Unit Specification
Chassis - U18A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 28 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 43 x 1
Type - Twin Rotary
Model x No. - GAT156MAD x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - RB68A
Oil Charging amount cc x No. 400 x 1
Rows x Columns x FPI - 2 x 24 x 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 770 x 545 x 288
Dimensions
Shipping(W x H x D) mm 920 x 585 x 388
Net kg 31.8
Weight
Shipping kg 34.3
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

5
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

6
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6

1.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation X
Wiring Error Check X
Peak Control X
Convenience Mode Lock X
Forced Cooling Operation (Outdoor Unit) X
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function X

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

7
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6

1.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type X
AC EZ touch PACEZA000 Small / Touch type X
AC Smart IV PACS4B000 Touch type X
AC Smart 5 PACS5A000 Touch type X
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - X
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated X
ODU PI485 PMNFP14A1 For 16-room (3 series) X
ACP BACnet PQNFB17C0 - X
Gateway
ACP Lonwork PLNWKB000 - X
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) X
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port X
PDI Premium PQNUD1S40 Power distributor 8port X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

8
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6

1.4 Dimensions
1.4.1 Product
DWG No. : TBW35446501_Rev01
Chassis code : U18A

9
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6
1.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

10
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6

1.5 Piping Diagrams


1.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

11
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6

1.6 Wiring Diagrams

12
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6

1.7 Capacity Tables


1.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 2.78 2.77 0.53 3.62 3.32 0.67 4.26 3.85 0.77 4.74 4.12 0.85 4.90 4.10 0.86 5.22 4.05 0.87 5.59 3.99 0.88

25 2.78 2.77 0.63 3.62 3.32 0.79 4.26 3.85 0.91 4.74 4.12 1.00 4.90 4.10 1.01 5.22 4.05 1.03 5.59 3.99 1.04

32 2.78 2.77 0.76 3.62 3.32 0.95 4.26 3.85 1.11 4.74 4.12 1.21 4.90 4.10 1.22 5.22 4.05 1.25 5.59 3.99 1.26

35 2.78 2.77 0.82 3.62 3.32 1.03 4.26 3.85 1.19 4.74 4.12 1.31 4.90 4.10 1.32 5.22 4.05 1.34 5.59 3.99 1.35

40 2.78 2.77 0.82 3.62 3.32 1.03 4.26 3.85 1.20 4.74 4.12 1.31 4.90 4.10 1.32 5.22 4.05 1.35 5.59 3.99 1.36

43 2.78 2.77 0.83 3.62 3.32 1.04 4.26 3.85 1.20 4.64 4.08 1.32 4.80 4.05 1.33 5.12 3.99 1.36 5.48 3.94 1.37

46 2.78 2.77 0.83 3.62 3.32 1.04 4.26 3.85 1.21 4.35 3.87 1.71 4.50 3.84 1.73 4.79 3.77 1.76 5.13 3.71 1.77

48 2.78 2.77 0.83 3.62 3.32 1.05 4.01 3.66 1.21 4.09 3.66 1.58 4.21 3.61 1.60 4.44 3.52 1.63 4.71 3.42 1.64

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

13
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6

1.8 Capacity Correction Factor


1.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 - - - - - - - - - - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

14
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6

1.9 Operation Limits


1.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

15
Single Universal Product Data

1. AUUQ21GT6 + ABNQ21GM1T6

1.10 Sound Levels


1.10.1 Pressure Levels

80
■ Cooling
75

70
Octave Band Sound Pressure Level (dB = 20μPa )

65
NC-65
60
NC-60
55
NC-55
50
NC-50
45
NC-45
40
NC-40
35
NC-35
30
NC-30
25

20 NC-25

Approximate
Hearing NC-20
15

NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 49.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.

16
Single Universal Product Data
ATNQ21GPLT6
+
AUUQ21GT6
2.
2. AUUQ21GT6 + ATNQ21GPLT6

2.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 4.98
Rated(T1)
Btu/h 17,000
kW 4.38
Rated(T3)
Btu/h 14,900
Cooling Capacity
kW 4.88
Sensible Heat
Btu/h 16,660
kW 1.47~6.15
Min ~ Max
Btu/h 5,000~21,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 1.37
Power Input(Cooling) Rated, T3 kW 1.72
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 10
Running Current(Cooling) Rated, T1 A 6
Rated, T3 A 7.5
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 10
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 1.30
Type - R410A
Precharged Amount kg 1.200
Additional Charging amount g/m 20
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 2.505
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ6.35 (1/4)
Connecting Pipe
Gas mm(inch) Φ12.7 (1/2)
Piping Length IDU - ODU(Rated / Max / Min) m 5/30/5
Maximum Height Difference IDU - ODU(Max) m 20
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 49.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 13.4

17
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 15
Electrical Characteristic Comp_Rated Load Amperes (Max) A 10.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.25
Outdoor Unit Specification
Chassis - U18A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 28 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 43 x 1
Type - Twin Rotary
Model x No. - GAT156MAD x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - RB68A
Oil Charging amount cc x No. 400 x 1
Rows x Columns x FPI - 2 x 24 x 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 770 x 545 x 288
Dimensions
Shipping(W x H x D) mm 920 x 585 x 388
Net kg 31.8
Weight
Shipping kg 34.3
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

18
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

19
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6

2.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation X
Wiring Error Check X
Peak Control X
Convenience Mode Lock X
Forced Cooling Operation (Outdoor Unit) X
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function X

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

20
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6

2.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type X
AC EZ touch PACEZA000 Small / Touch type X
AC Smart IV PACS4B000 Touch type X
AC Smart 5 PACS5A000 Touch type X
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - X
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated X
ODU PI485 PMNFP14A1 For 16-room (3 series) X
ACP BACnet PQNFB17C0 - X
Gateway
ACP Lonwork PLNWKB000 - X
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) X
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port X
PDI Premium PQNUD1S40 Power distributor 8port X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

21
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6

2.4 Dimensions
2.4.1 Product
DWG No. : TBW35446501_Rev01
Chassis code : U18A

22
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6
2.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

23
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6

2.5 Piping Diagrams


2.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

24
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6

2.6 Wiring Diagrams

25
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6

2.7 Capacity Tables


2.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 2.92 2.91 0.56 3.80 3.78 0.70 4.47 4.45 0.81 4.98 4.88 0.89 5.15 4.85 0.90 5.49 4.79 0.92 5.88 4.73 0.92

25 2.92 2.91 0.66 3.80 3.78 0.83 4.47 4.45 0.96 4.98 4.88 1.05 5.15 4.85 1.06 5.49 4.79 1.08 5.88 4.73 1.09

32 2.92 2.91 0.80 3.80 3.78 1.00 4.47 4.45 1.16 4.98 4.88 1.27 5.15 4.85 1.28 5.49 4.79 1.31 5.88 4.73 1.32

35 2.92 2.91 0.86 3.80 3.78 1.08 4.47 4.45 1.25 4.98 4.88 1.37 5.15 4.85 1.38 5.49 4.79 1.41 5.88 4.73 1.42

40 2.92 2.91 0.93 3.80 3.78 1.17 4.47 4.45 1.36 4.98 4.88 1.49 5.15 4.85 1.50 5.49 4.79 1.53 5.88 4.73 1.54

43 2.92 2.91 0.98 3.80 3.78 1.23 4.47 4.45 1.42 4.98 4.88 1.56 5.15 4.85 1.58 5.49 4.79 1.61 5.88 4.73 1.62

46 2.92 2.91 1.03 3.80 3.78 1.29 4.29 4.27 1.49 4.38 4.34 1.72 4.53 4.31 1.74 4.83 4.25 1.77 5.17 4.19 1.78

48 2.92 2.91 1.08 3.80 3.78 1.35 4.20 4.17 1.56 4.28 4.26 1.64 4.40 4.21 1.66 4.64 4.10 1.69 4.91 4.00 1.70

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

26
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6

2.8 Capacity Correction Factor


2.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 - - - - - - - - - - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

27
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6

2.9 Operation Limits


2.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

28
Single Universal Product Data

2. AUUQ21GT6 + ATNQ21GPLT6

2.10 Sound Levels


2.10.1 Pressure Levels

80
■ Cooling
75

70
Octave Band Sound Pressure Level (dB = 20μPa )

65
NC-65
60
NC-60
55
NC-55
50
NC-50
45
NC-45
40
NC-40
35
NC-35
30
NC-30
25

20 NC-25

Approximate
Hearing NC-20
15

NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 49.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.

29
Single Universal Product Data
ABNQ28GM1T6
+
AUUQ28GT6
3.
3. AUUQ28GT6 + ABNQ28GM1T6

3.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 6.27
Rated(T1)
Btu/h 21,400
kW 5.73
Rated(T3)
Btu/h 19,600
Cooling Capacity
kW 5.58
Sensible Heat
Btu/h 19,050
kW 1.83~8.20
Min ~ Max
Btu/h 6,200~28,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 1.73
Power Input(Cooling) Rated, T3 kW 2.26
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 7.6
Rated, T3 A 9.9
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 1.60
Type - R410A
Precharged Amount kg 1.500
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 3.131
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 50.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 23.7

30
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 12.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.33
Outdoor Unit Specification
Chassis - U24A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 50 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 85 x 1
Type - Twin Rotary
Model x No. - GKT208MAB x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 670 x 1
Rows x Columns x FPI - 2 x 28 x 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 870 x 650 x 330
Dimensions
Shipping(W x H x D) mm 1,026 x 693 x 446
Net kg 43.0
Weight
Shipping kg 47.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

31
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

32
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6

3.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function X

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

33
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6

3.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated X
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port X
PDI Premium PQNUD1S40 Power distributor 8port X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

34
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6

3.4 Dimensions
3.4.1 Product
DWG No. : TBW35646501_Rev01
Chassis code : U24A

35
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6
3.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

36
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6

3.5 Piping Diagrams


3.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

37
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6

3.6 Wiring Diagrams

38
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6

3.7 Capacity Tables


3.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 3.68 3.66 0.70 4.79 4.49 0.88 5.63 5.22 1.02 6.27 5.58 1.12 6.48 5.55 1.13 6.91 5.48 1.15 7.40 5.41 1.16

25 3.68 3.66 0.83 4.79 4.49 1.04 5.63 5.22 1.21 6.27 5.58 1.32 6.48 5.55 1.33 6.91 5.48 1.36 7.40 5.41 1.37

32 3.68 3.66 1.01 4.79 4.49 1.26 5.63 5.22 1.46 6.27 5.58 1.60 6.48 5.55 1.62 6.91 5.48 1.65 7.40 5.41 1.66

35 3.68 3.66 1.08 4.79 4.49 1.36 5.63 5.22 1.57 6.27 5.58 1.73 6.48 5.55 1.75 6.91 5.48 1.78 7.40 5.41 1.79

40 3.68 3.66 1.22 4.79 4.49 1.53 5.63 5.22 1.77 6.27 5.58 1.94 6.48 5.55 1.96 6.91 5.48 2.00 7.40 5.41 2.01

43 3.68 3.66 1.30 4.79 4.49 1.63 5.63 5.22 1.89 6.27 5.58 2.07 6.48 5.55 2.09 6.91 5.48 2.13 7.40 5.41 2.14

46 3.68 3.66 1.38 4.79 4.49 1.74 5.63 5.22 2.01 5.73 5.16 2.26 5.93 5.12 2.28 6.32 5.05 2.32 6.76 4.97 2.34

48 3.68 3.66 1.48 4.79 4.49 1.85 5.36 5.01 2.12 5.47 4.96 2.17 5.63 4.90 2.19 5.94 4.77 2.23 6.29 4.65 2.24

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

39
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6

3.8 Capacity Correction Factor


3.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 94.4 91.1 89.8 88.4 - - - - - - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

40
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6

3.9 Operation Limits


3.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

41
Single Universal Product Data

3. AUUQ28GT6 + ABNQ28GM1T6

3.10 Sound Levels


3.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 50.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.

42
Single Universal Product Data
ATNQ28GPLT6
+
AUUQ28GT6
4.
4. AUUQ28GT6 + ATNQ28GPLT6

4.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 6.45
Rated(T1)
Btu/h 22,000
kW 5.85
Rated(T3)
Btu/h 20,000
Cooling Capacity
kW 5.74
Sensible Heat
Btu/h 19,600
kW 1.92~8.20
Min ~ Max
Btu/h 6,600~28,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 1.77
Power Input(Cooling) Rated, T3 kW 2.26
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.85
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 7.8
Rated, T3 A 9.9
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 2.40
Type - R410A
Precharged Amount kg 1.500
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 3.131
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 50.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 22.4

43
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 12.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.33
Outdoor Unit Specification
Chassis - U24A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 50 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 85 x 1
Type - Twin Rotary
Model x No. - GKT208MAB x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 670 x 1
Rows x Columns x FPI - 2 x 28 x 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 870 x 650 x 330
Dimensions
Shipping(W x H x D) mm 1,026 x 693 x 446
Net kg 43.0
Weight
Shipping kg 47.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

44
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

45
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6

4.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function X

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

46
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6

4.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated X
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port X
PDI Premium PQNUD1S40 Power distributor 8port X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

47
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6

4.4 Dimensions
4.4.1 Product
DWG No. : TBW35646501_Rev01
Chassis code : U24A

48
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6
4.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

49
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6

4.5 Piping Diagrams


4.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

50
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6

4.6 Wiring Diagrams

51
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6

4.7 Capacity Tables


4.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 3.79 3.77 0.72 4.93 4.62 0.91 5.79 5.37 1.05 6.45 5.74 1.15 6.67 5.70 1.16 7.11 5.63 1.19 7.61 5.56 1.19

25 3.79 3.77 0.85 4.93 4.62 1.07 5.79 5.37 1.24 6.45 5.74 1.36 6.67 5.70 1.37 7.11 5.63 1.40 7.61 5.56 1.41

32 3.79 3.77 1.03 4.93 4.62 1.30 5.79 5.37 1.50 6.45 5.74 1.65 6.67 5.70 1.67 7.11 5.63 1.70 7.61 5.56 1.71

35 3.79 3.77 1.11 4.93 4.62 1.39 5.79 5.37 1.62 6.45 5.74 1.77 6.67 5.70 1.79 7.11 5.63 1.83 7.61 5.56 1.84

40 3.79 3.77 1.22 4.93 4.62 1.53 5.79 5.37 1.77 6.45 5.74 1.94 6.67 5.70 1.96 7.11 5.63 2.00 7.61 5.56 2.01

43 3.79 3.77 1.28 4.93 4.62 1.61 5.79 5.37 1.86 6.45 5.74 2.04 6.67 5.70 2.06 7.11 5.63 2.10 7.61 5.56 2.11

46 3.79 3.77 1.34 4.93 4.62 1.69 5.79 5.37 1.96 5.85 5.26 2.26 6.05 5.22 2.28 6.45 5.15 2.33 6.90 5.08 2.34

48 3.79 3.77 1.41 4.93 4.62 1.78 5.48 5.13 2.06 5.60 5.07 2.17 5.76 5.01 2.19 6.07 4.88 2.23 6.43 4.75 2.25

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

52
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6

4.8 Capacity Correction Factor


4.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 94.4 91.1 89.8 88.4 - - - - - - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

53
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6

4.9 Operation Limits


4.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

54
Single Universal Product Data

4. AUUQ28GT6 + ATNQ28GPLT6

4.10 Sound Levels


4.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 50.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.

55
Single Universal Product Data
ABNQ34GM3T6
+
AUUQ34GT6
5.
5. AUUQ34GT6 + ABNQ34GM3T6

5.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 7.75
Rated(T1)
Btu/h 26,400
kW 6.99
Rated(T3)
Btu/h 23,800
Cooling Capacity
kW 7.60
Sensible Heat
Btu/h 25,950
kW 2.34~9.96
Min ~ Max
Btu/h 8,000~34,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 2.13
Power Input(Cooling) Rated, T3 kW 2.74
Min ~ Max kW ~
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 9.3
Rated, T3 A 12
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 1.90
Type - R410A
Precharged Amount kg 1.500
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 3.131
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 50.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 X 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 23.7

56
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 12.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.33
Outdoor Unit Specification
Chassis - U24A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 50 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 85 x 1
Type - Twin Rotary
Model x No. - GKT208MAB x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 670 X 1
Rows x Columns x FPI - 2 X 28 X 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 870 x 650 x 330
Dimensions
Shipping(W x H x D) mm 1,026 x 693 x 446
Net kg 43.0
Weight
Shipping kg 47.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 X 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

57
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

58
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6

5.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function X

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

59
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6

5.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated X
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port X
PDI Premium PQNUD1S40 Power distributor 8port X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

60
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6

5.4 Dimensions
5.4.1 Product
DWG No. : TBW35646501_Rev01
Chassis code : U24A

61
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6
5.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

62
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6

5.5 Piping Diagrams


5.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

63
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6

5.6 Wiring Diagrams

64
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6

5.7 Capacity Tables


5.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 4.55 4.53 0.87 5.92 5.89 1.09 6.96 6.92 1.26 7.75 7.60 1.38 8.01 7.55 1.40 8.54 7.45 1.43 9.14 7.36 1.43

25 4.55 4.53 1.02 5.92 5.89 1.28 6.96 6.92 1.49 7.75 7.60 1.63 8.01 7.55 1.65 8.54 7.45 1.68 9.14 7.36 1.69

32 4.55 4.53 1.24 5.92 5.89 1.56 6.96 6.92 1.81 7.75 7.60 1.98 8.01 7.55 2.00 8.54 7.45 2.04 9.14 7.36 2.05

35 4.55 4.53 1.34 5.92 5.89 1.68 6.96 6.92 1.94 7.75 7.60 2.13 8.01 7.55 2.15 8.54 7.45 2.19 9.14 7.36 2.21

40 4.55 4.53 1.34 5.92 5.89 1.69 6.96 6.92 1.96 7.75 7.60 2.15 8.01 7.55 2.17 8.54 7.45 2.21 9.14 7.36 2.22

43 4.55 4.53 1.35 5.92 5.89 1.70 6.96 6.92 1.96 7.56 7.49 2.15 7.82 7.44 2.17 8.33 7.33 2.22 8.92 7.22 2.23

46 4.55 4.53 1.36 5.92 5.89 1.70 6.96 6.92 1.97 6.99 6.96 2.74 7.23 6.92 2.77 7.70 6.83 2.82 8.25 6.72 2.83

48 4.55 4.53 1.36 5.92 5.89 1.71 6.47 6.43 1.98 6.60 6.57 2.55 6.79 6.51 2.57 7.16 6.39 2.62 7.60 6.22 2.64

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

65
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6

5.8 Capacity Correction Factor


5.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.6 99.3 97.9 96.6 95.2 93.8 92.4 91.1 89.8 88.4 - - - - - - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

66
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6

5.9 Operation Limits


5.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

67
Single Universal Product Data

5. AUUQ34GT6 + ABNQ34GM3T6

5.10 Sound Levels


5.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 50.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.

68
Single Universal Product Data
ATNQ34GNLT6
+
AUUQ34GT6
6.
6. AUUQ34GT6 + ATNQ34GNLT6

6.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 7.35
Rated(T1)
Btu/h 25,000
kW 6.50
Rated(T3)
Btu/h 22,200
Cooling Capacity
kW 6.69
Sensible Heat
Btu/h 22,840
kW 2.16~9.38
Min ~ Max
Btu/h 7,400~32,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 2.02
Power Input(Cooling) Rated, T3 kW 2.55
Min ~ Max kW ~
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 8.9
Rated, T3 A 11.2
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 2.50
Type - R410A
Precharged Amount kg 1.500
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 3.131
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 50.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 23.2

69
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 12.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.33
Outdoor Unit Specification
Chassis - U24A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 50 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 85 x 1
Type - Twin Rotary
Model x No. - GKT208MAB x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 670 x 1
Rows x Columns x FPI - 2 X 28 X 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 870 x 650 x 330
Dimensions
Shipping(W x H x D) mm 1,026 x 693 x 466
Net kg 43.0
Weight
Shipping kg 47.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

70
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

71
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6

6.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function X

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

72
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6

6.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated X
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port X
PDI Premium PQNUD1S40 Power distributor 8port X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

73
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6

6.4 Dimensions
6.4.1 Product
DWG No. : TBW35646501_Rev01
Chassis code : U24A

74
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6
6.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

75
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6

6.5 Piping Diagrams


6.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

76
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6

6.6 Wiring Diagrams

77
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6

6.7 Capacity Tables


6.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 4.31 4.29 0.82 5.61 5.38 1.03 6.60 6.25 1.19 7.35 6.69 1.31 7.60 6.65 1.32 8.10 6.56 1.35 8.67 6.48 1.36

25 4.31 4.29 0.97 5.61 5.38 1.22 6.60 6.25 1.41 7.35 6.69 1.54 7.60 6.65 1.56 8.10 6.56 1.59 8.67 6.48 1.60

32 4.31 4.29 1.18 5.61 5.38 1.48 6.60 6.25 1.71 7.35 6.69 1.87 7.60 6.65 1.89 8.10 6.56 1.93 8.67 6.48 1.94

35 4.31 4.29 1.26 5.61 5.38 1.59 6.60 6.25 1.84 7.35 6.69 2.02 7.60 6.65 2.04 8.10 6.56 2.08 8.67 6.48 2.09

40 4.31 4.29 1.40 5.61 5.38 1.75 6.60 6.25 2.03 7.35 6.69 2.23 7.60 6.65 2.25 8.10 6.56 2.30 8.67 6.48 2.31

43 4.31 4.29 1.48 5.61 5.38 1.86 6.60 6.25 2.15 7.35 6.69 2.36 7.60 6.65 2.38 8.10 6.56 2.43 8.67 6.48 2.44

46 4.31 4.29 1.56 5.61 5.38 1.96 6.37 6.08 2.27 6.50 5.98 2.55 6.72 5.94 2.58 7.16 5.85 2.63 7.67 5.77 2.64

48 4.31 4.29 1.65 5.61 5.38 2.08 6.04 5.76 2.39 6.16 5.71 2.44 6.33 5.64 2.47 6.68 5.49 2.52 7.09 5.36 2.53

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

78
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6

6.8 Capacity Correction Factor


6.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.6 99.3 97.9 96.6 95.2 93.8 92.4 91.1 89.8 88.4 - - - - - - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

79
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6

6.9 Operation Limits


6.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

80
Single Universal Product Data

6. AUUQ34GT6 + ATNQ34GNLT6

6.10 Sound Levels


6.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 50.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.

81
Single Universal Product Data
ABNQ40GM3T6
+
AUUQ40GT6
7.
7. AUUQ40GT6 + ABNQ40GM3T6

7.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 9.95
Rated(T1)
Btu/h 34,000
kW 8.50
Rated(T3)
Btu/h 29,000
Cooling Capacity
kW 8.26
Sensible Heat
Btu/h 28,200
kW 2.82~11.25
Min ~ Max
Btu/h 9,600~38,400
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 2.74
Power Input(Cooling) Rated, T3 kW 3.33
Min ~ Max kW ~
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 12
Rated, T3 A 14.6
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 1.90
Type - R410A
Precharged Amount kg 2.200
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 4.593
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 51.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 23.7

82
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 17.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.58
Outdoor Unit Specification
Chassis - U36A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 X 1
Type - Twin Rotary
Model x No. - GJT240MAA X 1
Motor Type - BLDC
Compressor
Motor Output W x No. 2137 X 1
Oil Type - FW68D
Oil Charging amount cc x No. 900 X 1
Rows x Columns x FPI - 2 X 38 X 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 834 x 330
Dimensions
Shipping(W x H x D) mm 1,065 x 918 x 461
Net kg 56.5
Weight
Shipping kg 61.3
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 X 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

83
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

84
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6

7.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function X

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

85
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6

7.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated X
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port X
PDI Premium PQNUD1S40 Power distributor 8port X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

86
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6

7.4 Dimensions
7.4.1 Product
DWG No. : TBW35046501_rev01
Chassis code : U36A

87
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6
7.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

88
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6

7.5 Piping Diagrams


7.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

89
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6

7.6 Wiring Diagrams

90
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6

7.7 Capacity Tables


7.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 5.84 5.57 1.12 7.60 6.64 1.40 8.93 7.72 1.62 9.95 8.26 1.78 10.29 8.21 1.80 10.97 8.10 1.83 11.74 8.00 1.85

25 5.84 5.57 1.32 7.60 6.64 1.65 8.93 7.72 1.92 9.95 8.26 2.10 10.29 8.21 2.12 10.97 8.10 2.16 11.74 8.00 2.18

32 5.84 5.57 1.60 7.60 6.64 2.01 8.93 7.72 2.32 9.95 8.26 2.55 10.29 8.21 2.58 10.97 8.10 2.63 11.74 8.00 2.64

35 5.84 5.57 1.72 7.60 6.64 2.16 8.93 7.72 2.50 9.95 8.26 2.74 10.29 8.21 2.77 10.97 8.10 2.82 11.74 8.00 2.84

40 5.84 5.57 1.77 7.60 6.64 2.23 8.93 7.72 2.58 9.95 8.26 2.83 10.29 8.21 2.86 10.97 8.10 2.91 11.74 8.00 2.93

43 5.84 5.57 1.80 7.60 6.64 2.27 8.93 7.72 2.62 9.95 8.26 2.88 10.29 8.21 2.91 10.97 8.10 2.97 11.74 8.00 2.98

46 5.84 5.57 1.84 7.60 6.64 2.31 8.33 7.25 2.67 8.50 7.13 3.33 8.79 7.08 3.36 9.37 6.98 3.43 10.03 6.88 3.45

48 5.84 5.57 1.87 7.60 6.64 2.35 7.83 6.81 2.72 7.99 6.76 3.15 8.22 6.67 3.18 8.68 6.50 3.25 9.20 6.34 3.26

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

91
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6

7.8 Capacity Correction Factor


7.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.6 99.3 97.9 96.6 95.2 93.8 92.4 91.1 89.8 88.4 - - - - - - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

92
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6

7.9 Operation Limits


7.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

93
Single Universal Product Data

7. AUUQ40GT6 + ABNQ40GM3T6

7.10 Sound Levels


7.10.1 Pressure Levels
80
Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 51.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.

94
Single Universal Product Data
ATNQ40GNLT6
+
AUUQ40GT6
8.
8. AUUQ40GT6 + ATNQ40GNLT6

8.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 9.40
Rated(T1)
Btu/h 32,000
kW 8.20
Rated(T3)
Btu/h 28,000
Cooling Capacity
kW 7.90
Sensible Heat
Btu/h 26,970
kW 2.76~10.56
Min ~ Max
Btu/h 9,400~36,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 2.58
Power Input(Cooling) Rated, T3 kW 3.22
Min ~ Max kW ~
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 11.3
Rated, T3 A 14.1
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 2.50
Type - R410A
Precharged Amount kg 2.200
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 4.593
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 51.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 23.2

95
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 17.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.58
Outdoor Unit Specification
Chassis - U36A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 x 1
Type - Twin Rotary
Model x No. - GJT240MAA X 1
Motor Type - BLDC
Compressor
Motor Output W x No. 2137 X 1
Oil Type - FW68D
Oil Charging amount cc x No. 900 X 1
Rows x Columns x FPI - 2 X 38 X 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 834 x 330
Dimensions
Shipping(W x H x D) mm 1,065 x 918 x 461
Net kg 56.5
Weight
Shipping kg 61.3
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

96
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

97
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6

8.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function X

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

98
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6

8.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated X
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port X
PDI Premium PQNUD1S40 Power distributor 8port X

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

99
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6

8.4 Dimensions
8.4.1 Product
DWG No. : TBW35046501_rev01
Chassis code : U36A

100
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6
8.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

101
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6

8.5 Piping Diagrams


8.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

102
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6

8.6 Wiring Diagrams

103
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6

8.7 Capacity Tables


8.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 5.52 5.32 1.05 7.18 6.35 1.32 8.44 7.38 1.53 9.40 7.90 1.68 9.72 7.85 1.70 10.36 7.75 1.73 11.09 7.65 1.74

25 5.52 5.32 1.24 7.18 6.35 1.56 8.44 7.38 1.80 9.40 7.90 1.98 9.72 7.85 2.00 10.36 7.75 2.04 11.09 7.65 2.05

32 5.52 5.32 1.50 7.18 6.35 1.89 8.44 7.38 2.19 9.40 7.90 2.40 9.72 7.85 2.42 10.36 7.75 2.47 11.09 7.65 2.49

35 5.52 5.32 1.62 7.18 6.35 2.03 8.44 7.38 2.35 9.40 7.90 2.58 9.72 7.85 2.61 10.36 7.75 2.66 11.09 7.65 2.67

40 5.52 5.32 1.77 7.18 6.35 2.22 8.44 7.38 2.57 9.40 7.90 2.82 9.72 7.85 2.85 10.36 7.75 2.91 11.09 7.65 2.92

43 5.52 5.32 1.86 7.18 6.35 2.33 8.44 7.38 2.70 9.40 7.90 2.97 9.72 7.85 3.00 10.36 7.75 3.06 11.09 7.65 3.07

46 5.52 5.32 1.96 7.18 6.35 2.45 8.04 7.08 2.84 8.20 6.96 3.22 8.48 6.91 3.25 9.04 6.81 3.32 9.67 6.72 3.34

48 5.52 5.32 2.06 7.18 6.35 2.58 7.52 6.62 2.97 7.68 6.57 3.03 7.90 6.49 3.06 8.34 6.32 3.12 8.84 6.17 3.14

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

104
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6

8.8 Capacity Correction Factor


8.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.6 99.3 97.9 96.6 95.2 93.8 92.4 91.1 89.8 88.4 - - - - - - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

105
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6

8.9 Operation Limits


8.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

106
Single Universal Product Data

8. AUUQ40GT6 + ATNQ40GNLT6

8.10 Sound Levels


8.10.1 Pressure Levels
80
Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 51.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.

107
Single Universal Product Data
ABNQ55GM3T6
+
AUUQ55GT6
9.
9. AUUQ55GT6 + ABNQ55GM3T6

9.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 13.75
Rated(T1)
Btu/h 47,000
kW 11.70
Rated(T3)
Btu/h 40,000
Cooling Capacity
kW 11.14
Sensible Heat
Btu/h 38,040
kW 4.62~16.41
Min ~ Max
Btu/h 15,800~56,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 3.79
Power Input(Cooling) Rated, T3 kW 4.60
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 16.6
Rated, T3 A 20.2
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.50
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 35.7

108
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Comp_Rated Load Amperes (Max) A 25.6
Outdoor Fan Motor_Full Load Amperes (FLA) A 1.16
Outdoor Unit Specification
Chassis - U60A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60 x 2
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 x 2
Type - Twin Rotary
Model x No. - GPT442MAB X 1
Motor Type - BLDC
Compressor
Motor Output W x No. 4000 X 1
Oil Type - FW68D
Oil Charging amount cc x No. 1300 X 1
Rows x Columns x FPI - 2 X 32 X 14
No. - 2
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 1,380 x 330
Dimensions
Shipping(W x H x D) mm 1,140 x 1,462 x 461
Net kg 88.5
Weight
Shipping kg 97.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

109
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

110
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6

9.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function O(On/off Contorl)

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

111
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6

9.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated O
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port O
PDI Premium PQNUD1S40 Power distributor 8port O

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

112
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6

9.4 Dimensions
9.4.1 Product
Gravity point

159

541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A

113
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6
9.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

114
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6

9.5 Piping Diagrams


9.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

115
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6

9.6 Wiring Diagrams

116
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6

9.7 Capacity Tables


9.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 8.07 7.51 1.54 10.50 8.96 1.94 12.35 10.41 2.24 13.75 11.14 2.46 14.22 11.07 2.49 15.15 10.93 2.54 16.22 10.79 2.55

25 8.07 7.51 1.82 10.50 8.96 2.29 12.35 10.41 2.65 13.75 11.14 2.90 14.22 11.07 2.93 15.15 10.93 2.99 16.22 10.79 3.01

32 8.07 7.51 2.21 10.50 8.96 2.77 12.35 10.41 3.21 13.75 11.14 3.52 14.22 11.07 3.56 15.15 10.93 3.63 16.22 10.79 3.65

35 8.07 7.51 2.38 10.50 8.96 2.98 12.35 10.41 3.46 13.75 11.14 3.79 14.22 11.07 3.83 15.15 10.93 3.90 16.22 10.79 3.93

40 8.07 7.51 2.48 10.50 8.96 3.11 12.35 10.41 3.61 13.75 11.14 3.96 14.22 11.07 4.00 15.15 10.93 4.08 16.22 10.79 4.10

43 8.07 7.51 2.54 10.50 8.96 3.19 12.35 10.41 3.70 13.75 11.14 4.06 14.22 11.07 4.10 15.15 10.93 4.18 16.22 10.79 4.21

46 8.07 7.51 2.61 10.50 8.96 3.28 11.47 9.73 3.80 11.70 9.58 4.60 12.10 9.51 4.65 12.89 9.38 4.74 13.80 9.24 4.77

48 8.07 7.51 2.68 10.50 8.96 3.36 11.13 9.45 3.89 11.35 9.37 4.35 11.67 9.24 4.39 12.30 8.99 4.48 13.03 8.76 4.51

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

117
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6

9.8 Capacity Correction Factor


9.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 94.4 91.1 89.8 88.4 87.1 85.7 84.4 83.0 81.6 - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

118
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6

9.9 Operation Limits


9.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

119
Single Universal Product Data

9. AUUQ55GT6 + ABNQ55GM3T6

9.10 Sound Levels


9.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 55.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

120
Single Universal Product Data
APNQ55GT3E6
+
AUUQ55GT6
10.
10. AUUQ55GT6 + APNQ55GT3E6

10.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 14.05
Rated(T1)
Btu/h 48,000
kW 12.60
Rated(T3)
Btu/h 43,000
Cooling Capacity
kW 10.54
Sensible Heat
Btu/h 35,990
kW 4.44~16.12
Min ~ Max
Btu/h 15,200~55,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 3.87
Power Input(Cooling) Rated, T3 kW 4.94
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 17
Rated, T3 A 21.7
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.90
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 34.3

121
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6


Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Comp_Rated Load Amperes (Max) A 25.6
Outdoor Fan Motor_Full Load Amperes (FLA) A 1.02
Outdoor Unit Specification
Chassis - U3
Classification
Cooling / Heating - -
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60×2
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 x 2
Type - Twin Rotary
Model x No. - GPT442MAB X 1
Motor Type - BLDC
Compressor
Motor Output W x No. 4000 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 1300 X 1
Rows x Columns x FPI - 2x32x14
No. - 2
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 1,380 x 330
Dimensions
Shipping(W x H x D) mm 1,140 x 1,462 x 461
Net kg 88.5
Weight
Shipping kg 97.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

122
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6


■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

123
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6

10.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function O(On/off Contorl)

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

124
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6

10.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated O
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port O
PDI Premium PQNUD1S40 Power distributor 8port O

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

125
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6

10.4 Dimensions
10.4.1 Product
Gravity point

159

541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A

126
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6


10.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

127
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6

10.5 Piping Diagrams


10.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

128
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6

10.6 Wiring Diagrams

129
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6

10.7 Capacity Tables


10.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 8.25 7.10 1.58 10.73 8.48 1.98 12.62 9.85 2.29 14.05 10.54 2.51 14.53 10.47 2.54 15.48 10.34 2.59 16.58 10.21 2.60

25 8.25 7.10 1.86 10.73 8.48 2.33 12.62 9.85 2.70 14.05 10.54 2.97 14.53 10.47 3.00 15.48 10.34 3.06 16.58 10.21 3.07

32 8.25 7.10 2.26 10.73 8.48 2.83 12.62 9.85 3.28 14.05 10.54 3.60 14.53 10.47 3.64 15.48 10.34 3.71 16.58 10.21 3.73

35 8.25 7.10 2.43 10.73 8.48 3.05 12.62 9.85 3.53 14.05 10.54 3.87 14.53 10.47 3.91 15.48 10.34 3.99 16.58 10.21 4.01

40 8.25 7.10 2.68 10.73 8.48 3.37 12.62 9.85 3.90 14.05 10.54 4.28 14.53 10.47 4.32 15.48 10.34 4.41 16.58 10.21 4.44

43 8.25 7.10 2.84 10.73 8.48 3.56 12.62 9.85 4.13 14.05 10.54 4.53 14.53 10.47 4.57 15.48 10.34 4.66 16.58 10.21 4.69

46 8.25 7.10 3.00 10.73 8.48 3.77 12.35 9.71 4.37 12.60 9.55 4.94 13.03 9.48 4.99 13.89 9.35 5.09 14.86 9.21 5.12

48 8.25 7.10 3.17 10.73 8.48 3.99 11.67 9.17 4.54 11.91 9.10 4.63 12.25 8.98 4.68 12.92 8.75 4.77 13.71 8.53 4.80

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

130
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6

10.8 Capacity Correction Factor


10.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 94.4 91.1 89.8 88.4 87.1 85.7 84.4 83.0 81.6 - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

131
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6

10.9 Operation Limits


10.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

132
Single Universal Product Data

10. AUUQ55GT6 + APNQ55GT3E6

10.10 Sound Levels


10.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 55.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

133
Single Universal Product Data
APNQ55GT3M6
+
AUUQ55GT6
11.
11. AUUQ55GT6 + APNQ55GT3M6

11.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 14.05
Rated(T1)
Btu/h 48,000
kW 12.60
Rated(T3)
Btu/h 43,000
Cooling Capacity
kW 10.54
Sensible Heat
Btu/h 35,990
kW 4.44~16.12
Min ~ Max
Btu/h 15,200~55,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 3.87
Power Input(Cooling) Rated, T3 kW 4.94
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 17
Rated, T3 A 21.7
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.90
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 34.3

134
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6


Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Comp_Rated Load Amperes (Max) A 25.6
Outdoor Fan Motor_Full Load Amperes (FLA) A 1.02
Outdoor Unit Specification
Chassis - U60A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60 x 2
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 x 2
Type - Twin Rotary
Model x No. - GPT442MAB X 1
Motor Type - BLDC
Compressor
Motor Output W x No. 4000 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 1300 X 1
Rows x Columns x FPI - 2x32x14
No. - 2
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 1,380 x 330
Dimensions
Shipping(W x H x D) mm 1,140 x 1,462 x 461
Net kg 88.5
Weight
Shipping kg 97.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

135
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6


■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

136
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6

11.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function O(On/off Contorl)

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

137
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6

11.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated O
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port O
PDI Premium PQNUD1S40 Power distributor 8port O

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

138
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6

11.4 Dimensions
11.4.1 Product
Gravity point

159

541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A

139
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6


11.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

140
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6

11.5 Piping Diagrams


11.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

141
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6

11.6 Wiring Diagrams

142
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6

11.7 Capacity Tables


11.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 8.25 7.10 1.58 10.73 8.48 1.98 12.62 9.85 2.29 14.05 10.54 2.51 14.53 10.47 2.54 15.48 10.34 2.59 16.58 10.21 2.60

25 8.25 7.10 1.86 10.73 8.48 2.33 12.62 9.85 2.70 14.05 10.54 2.97 14.53 10.47 3.00 15.48 10.34 3.06 16.58 10.21 3.07

32 8.25 7.10 2.26 10.73 8.48 2.83 12.62 9.85 3.28 14.05 10.54 3.60 14.53 10.47 3.64 15.48 10.34 3.71 16.58 10.21 3.73

35 8.25 7.10 2.43 10.73 8.48 3.05 12.62 9.85 3.53 14.05 10.54 3.87 14.53 10.47 3.91 15.48 10.34 3.99 16.58 10.21 4.01

40 8.25 7.10 2.68 10.73 8.48 3.37 12.62 9.85 3.90 14.05 10.54 4.28 14.53 10.47 4.32 15.48 10.34 4.41 16.58 10.21 4.44

43 8.25 7.10 2.84 10.73 8.48 3.56 12.62 9.85 4.13 14.05 10.54 4.53 14.53 10.47 4.57 15.48 10.34 4.66 16.58 10.21 4.69

46 8.25 7.10 3.00 10.73 8.48 3.77 12.35 9.71 4.37 12.60 9.55 4.94 13.03 9.48 4.99 13.89 9.35 5.09 14.86 9.21 5.12

48 8.25 7.10 3.17 10.73 8.48 3.99 11.67 9.17 4.54 11.91 9.10 4.63 12.25 8.98 4.68 12.92 8.75 4.77 13.71 8.53 4.80

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

143
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6

11.8 Capacity Correction Factor


11.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 94.4 91.1 89.8 88.4 87.1 85.7 84.4 83.0 81.6 - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

144
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6

11.9 Operation Limits


11.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

145
Single Universal Product Data

11. AUUQ55GT6 + APNQ55GT3M6

11.10 Sound Levels


11.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 55.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

146
Single Universal Product Data
ATNQ55GMLT6
+
AUUQ55GT6
12.
12. AUUQ55GT6 + ATNQ55GMLT6

12.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 13.50
Rated(T1)
Btu/h 46,000
kW 11.45
Rated(T3)
Btu/h 39,000
Cooling Capacity
kW 10.40
Sensible Heat
Btu/h 35,510
kW 4.11~15.24
Min ~ Max
Btu/h 14,000~52,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 3.71
Power Input(Cooling) Rated, T3 kW 4.49
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 16.3
Rated, T3 A 19.7
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 5.20
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 34.3

147
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6


Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Comp_Rated Load Amperes (Max) A 25.6
Outdoor Fan Motor_Full Load Amperes (FLA) A 1.02
Outdoor Unit Specification
Chassis - U60A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60 x 2
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 x 2
Type - Twin Rotary
Model x No. - GPT442MAB X 1
Motor Type - BLDC
Compressor
Motor Output W x No. 4000 X 1
Oil Type - FW68D
Oil Charging amount cc x No. 1300 X 1
Rows x Columns x FPI - 2x32x14
No. - 2
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 1,380 x 330
Dimensions
Shipping(W x H x D) mm 1,140 x 1,462 x 461
Net kg 88.5
Weight
Shipping kg 97.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

148
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6


■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

149
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6

12.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function O(On/off Contorl)

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

150
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6

12.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated O
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port O
PDI Premium PQNUD1S40 Power distributor 8port O

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

151
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6

12.4 Dimensions
12.4.1 Product
Gravity point

159

541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A

152
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6


12.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

153
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6

12.5 Piping Diagrams


12.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

154
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6

12.6 Wiring Diagrams

155
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6

12.7 Capacity Tables


12.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 7.92 7.01 1.51 10.31 8.36 1.90 12.12 9.72 2.20 13.50 10.40 2.41 13.96 10.33 2.43 14.88 10.20 2.48 15.93 10.07 2.50

25 7.92 7.01 1.78 10.31 8.36 2.24 12.12 9.72 2.59 13.50 10.40 2.84 13.96 10.33 2.87 14.88 10.20 2.93 15.93 10.07 2.95

32 7.92 7.01 2.16 10.31 8.36 2.71 12.12 9.72 3.15 13.50 10.40 3.45 13.96 10.33 3.48 14.88 10.20 3.55 15.93 10.07 3.57

35 7.92 7.01 2.33 10.31 8.36 2.92 12.12 9.72 3.38 13.50 10.40 3.71 13.96 10.33 3.75 14.88 10.20 3.82 15.93 10.07 3.84

40 7.92 7.01 2.49 10.31 8.36 3.12 12.12 9.72 3.61 13.50 10.40 3.97 13.96 10.33 4.01 14.88 10.20 4.08 15.93 10.07 4.11

43 7.92 7.01 2.58 10.31 8.36 3.24 12.12 9.72 3.75 13.50 10.40 4.12 13.96 10.33 4.16 14.88 10.20 4.24 15.93 10.07 4.27

46 7.92 7.01 2.68 10.31 8.36 3.37 11.22 9.06 3.90 11.45 8.91 4.49 11.84 8.85 4.54 12.62 8.72 4.63 13.51 8.60 4.65

48 7.92 7.01 2.78 10.31 8.36 3.50 10.90 8.79 4.05 11.12 8.72 4.30 11.43 8.60 4.34 12.05 8.37 4.43 12.76 8.16 4.46

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

156
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6

12.8 Capacity Correction Factor


12.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 94.4 91.1 89.8 88.4 87.1 85.7 84.4 83.0 81.6 - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

157
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6

12.9 Operation Limits


12.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

158
Single Universal Product Data

12. AUUQ55GT6 + ATNQ55GMLT6

12.10 Sound Levels


12.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 55.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

159
Single Universal Product Data
ABNQ60GM3T6
+
AUUQ60GT6
13.
13. AUUQ60GT6 + ABNQ60GM3T6

13.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 15.25
Rated(T1)
Btu/h 52,000
kW 13.05
Rated(T3)
Btu/h 44,600
Cooling Capacity
kW 12.81
Sensible Heat
Btu/h 43,740
kW 5.62~15.80
Min ~ Max
Btu/h 19,200~54,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 4.19
Power Input(Cooling) Rated, T3 kW 5.12
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 18.4
Rated, T3 A 22.5
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.00
Type - R410A
Precharged Amount kg 3.800
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.933
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6 X 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 34.3

160
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6


Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Comp_Rated Load Amperes (Max) A 25.6
Outdoor Fan Motor_Full Load Amperes (FLA) A 1.02
Outdoor Unit Specification
Chassis - U60A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60×2
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124.2 x 2
Type - Scroll
Model x No. - RJA036MAA x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 3,198 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 1000 X 1
Rows x Columns x FPI - 2 x 32 x 16
No. - 2
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 1,380 x 330
Dimensions
Shipping(W x H x D) mm 1,140 x 1,462 x 461
Net kg 84.3
Weight
Shipping kg 93.1
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

161
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6


■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

162
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6

13.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function O(On/off Contorl)

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

163
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6

13.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated O
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port O
PDI Premium PQNUD1S40 Power distributor 8port O

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

164
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6

13.4 Dimensions
13.4.1 Product
Gravity point

159

541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A

165
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6


13.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

166
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6

13.5 Piping Diagrams


13.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

167
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6

13.6 Wiring Diagrams

168
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6

13.7 Capacity Tables


13.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 8.95 8.63 1.71 11.65 10.30 2.14 13.69 11.97 2.48 15.25 12.81 2.72 15.77 12.73 2.75 16.81 12.57 2.80 17.99 12.41 2.82

25 8.95 8.63 2.01 11.65 10.30 2.53 13.69 11.97 2.93 15.25 12.81 3.21 15.77 12.73 3.24 16.81 12.57 3.31 17.99 12.41 3.33

32 8.95 8.63 2.44 11.65 10.30 3.07 13.69 11.97 3.55 15.25 12.81 3.90 15.77 12.73 3.94 16.81 12.57 4.01 17.99 12.41 4.04

35 8.95 8.63 2.63 11.65 10.30 3.30 13.69 11.97 3.82 15.25 12.81 4.19 15.77 12.73 4.23 16.81 12.57 4.32 17.99 12.41 4.34

40 8.95 8.63 2.87 11.65 10.30 3.60 13.69 11.97 4.17 15.25 12.81 4.58 15.77 12.73 4.63 16.81 12.57 4.72 17.99 12.41 4.74

43 8.95 8.63 3.02 11.65 10.30 3.79 13.69 11.97 4.39 14.70 12.48 4.81 15.20 12.39 4.86 16.20 12.21 4.96 17.34 12.04 4.99

46 8.95 8.63 3.17 11.65 10.30 3.98 12.79 11.26 4.61 13.05 11.20 5.12 13.49 11.11 5.17 14.38 10.93 5.27 15.40 10.76 5.30

48 8.95 8.63 3.33 11.65 10.30 4.18 12.02 10.58 4.82 12.27 10.61 4.92 12.62 10.47 4.97 13.31 10.18 5.07 14.12 9.91 5.10

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

169
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6

13.8 Capacity Correction Factor


13.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 94.4 91.1 89.8 88.4 87.1 85.7 84.4 83.0 81.6 - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

170
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6

13.9 Operation Limits


13.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

171
Single Universal Product Data

13. AUUQ60GT6 + ABNQ60GM3T6

13.10 Sound Levels


13.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 55.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

172
Single Universal Product Data
ABNQ60LM3T6
+
AUUQ60LT6
14.
14. AUUQ60LT6 + ABNQ60LM3T6

14.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 380-400-415, 3, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 342-456
Limit Range of Voltage(#2) V -
kW 15.25
Rated(T1)
Btu/h 52,000
kW 13.40
Rated(T3)
Btu/h 45,800
Cooling Capacity
kW 12.81
Sensible Heat
Btu/h 43,740
kW 6.33~16.70
Min ~ Max
Btu/h 21,600~58,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 4.19
Power Input(Cooling) Rated, T3 kW 5.26
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 10
Running Current(Cooling) Rated, T1 A 6.5
Rated, T3 A 8.1
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 10
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.00
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Electrical Characteristic Minimium Circuit Amperes (MCA) A 15.4

173
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6


Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 20
Electrical Characteristic Comp_Rated Load Amperes (Max) A 10.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 1.02
Outdoor Unit Specification
Chassis - U60A
Classification
Cooling / Heating - C/O
#1 - 380-400-415, 3, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 342-456
Limit Range of Voltage(#2) V -
Type - Axial Fan
m³/min x No. 60X2
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 x 2
Type - Twin Rotary
Model x No. - GPT442MAB
Motor Type - BLDC
Compressor
Motor Output W x No. 4000 X 1
Oil Type - FW68D
Oil Charging amount cc x No. 1300 X 1
Rows x Columns x FPI - 2 X 32 X 16
No. - 2
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 1,380 x 330
Dimensions
Shipping(W x H x D) mm 1,140 x 1,462 x 461
Net kg 89.5
Weight
Shipping kg 100.6
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C

Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.

174
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6


■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].

■ Performances are based on the following conditions :


- Applicable standard according to indoor type : Non Ducted - ISO 5151 / Ducted - ISO 13253
- Cooling(T1) : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Cooling(T3) : Indoor Ambient Temp. 29°CDB / 19°CWB, Outdoor Ambient Temp. 46°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe is standard length and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.

175
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6

14.2 List of Functions


Category Functions Value
Defrost / Deicing X
High Pressure Switch X
Low Pressure Switch X
Reliability Phase Protection X
Restart Delay (3-minutes) O
Self Diagnosis O
Soft Start O
Night Low Noise Operation O
Wiring Error Check X
Peak Control X
Convenience Mode Lock O
Forced Cooling Operation (Outdoor Unit) O
SLC(Smart Load Control) X
Auto Detecting Mode O
Special Functions ODU Dry Contact Function O(On/off Contorl)

Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.

176
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6

14.3 Accessory Compatibility List


Category Accessory Name Model Name Description Value
AC EZ PQCSZ250S0 Small type O
AC EZ touch PACEZA000 Small / Touch type O
AC Smart IV PACS4B000 Touch type O
AC Smart 5 PACS5A000 Touch type O
Central Controller
ACP IV PACP4B000 - O
ACP 5 PACP5A000 - O
AC Manager IV PACM4B000 Integrated O
AC Manager 5 PACM5A000 Integrated O
ODU PI485 PMNFP14A1 For 16-room (3 series) O
ACP BACnet PQNFB17C0 - O
Gateway
ACP Lonwork PLNWKB000 - O
Cloud Gateway PWFMDB200 - X
PAHCMR000 For AHU Control (Multi V / Single ODU Communication) O
AHU comm. kit
PAHCMS000 For AHU Control (Multi V / Single ODU Communication) X
PAHCMC000 For AHU Control (Communication Module) X
Integration Device AHU Controller Module
PAHCMM000 For AHU Control (Main Module) X
PDI Stadnard PPWRDB000 Power distributor 2port O
PDI Premium PQNUD1S40 Power distributor 8port O

Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.

177
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6

14.4 Dimensions
14.4.1 Product
Gravity point

159

541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A

178
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6


14.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side

To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.

To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft

Case 1 Case 2 Case 1 Case 2


To ≥ 1,000(39-3/8) Ft ≥ 500(19-11/16) Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,000(39-3/8)
Tr ≤ 500(19-11/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)

Obstacle on the Suction and Discharge side


Ld >H (Ls should be lower H.)
※ Close the bottom of the installation frame Re Re
to prevent the discharged Bw
air from being bypassed
To
Ft Front Front Front
Front Tr
Ft Ft
Ld

Re Re
H

Case 1 Case 2 Case 1 Case 2


Ls

Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls

Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld

To ≥ 1,000(39-3/8) ※ In case of series installation (2 Units or more)


Front Front
Tf ≤ 500(19-11/16) for 2 Fan models, Ld should be lower than H/2.

Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)

Ft Rb Fb Re
Ft Rb Fb Re
Ls

Multiple Columns
H

Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)

Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.

179
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6

14.5 Piping Diagrams


14.5.1 Normal
Outdoor Unit
Inlet Air
Refrigerant Flow Temperature
Thermistor

Condensing
Temperature
Thermistor

Flare Connection M

Electronic
Expansion Strainer
Valve

Flare Connection
Discharge
Temperature
Thermistor

Accumulator Inverter
Compressor

180
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6

14.6 Wiring Diagrams

181
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6

14.7 Capacity Tables


14.7.1 Cooling
Indoor Air Temp. (°C, DB/WB)
Outdoor
Air Temp. 20.0 / 14.0 22.0 / 16.0 25.0 / 18.0 27.0 / 19.0 28.0 / 20.0 30.0 / 22.0 32.0 / 24.0
(°C,DB)
TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

20 8.95 8.63 1.71 11.65 10.30 2.15 13.69 11.97 2.49 15.25 12.81 2.73 15.77 12.73 2.76 16.81 12.57 2.81 17.99 12.41 2.83

25 8.95 8.63 2.02 11.65 10.30 2.53 13.69 11.97 2.93 15.25 12.81 3.22 15.77 12.73 3.25 16.81 12.57 3.32 17.99 12.41 3.33

32 8.95 8.63 2.45 11.65 10.30 3.07 13.69 11.97 3.56 15.25 12.81 3.91 15.77 12.73 3.95 16.81 12.57 4.02 17.99 12.41 4.05

35 8.95 8.63 2.63 11.65 10.30 3.30 13.69 11.97 3.83 15.25 12.81 4.20 15.77 12.73 4.24 16.81 12.57 4.33 17.99 12.41 4.35

40 8.95 8.63 2.88 11.65 10.30 3.61 13.69 11.97 4.18 15.25 12.81 4.59 15.77 12.73 4.64 16.81 12.57 4.73 17.99 12.41 4.76

43 8.95 8.63 3.02 11.65 10.30 3.80 13.69 11.97 4.40 14.79 12.55 4.82 15.29 12.46 4.87 16.30 12.29 4.97 17.45 12.11 5.00

46 8.95 8.63 3.18 11.65 10.30 3.99 13.13 11.56 4.62 13.40 11.50 5.26 13.86 11.41 5.31 14.77 11.22 5.42 15.81 11.04 5.45

48 8.95 8.63 3.34 11.65 10.30 4.19 12.28 10.81 4.86 12.53 10.83 5.03 12.89 10.69 5.08 13.60 10.40 5.18 14.43 10.13 5.21

Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.

182
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6

14.8 Capacity Correction Factor


14.8.1 Cooling
Capacity correction factor (%) by equivalent pipe length (m)
5 7.5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
100.0 99.9 99.8 99.3 98.8 98.3 97.8 94.4 91.1 89.8 88.4 87.1 85.7 84.4 83.0 81.6 - - - -

Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping

183
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6

14.9 Operation Limits


14.9.1 Cooling
55
54
50

45

40

35
Outdoor Temperature [℃ DB]

30

25
Continuous
20 Operation
15

10

-5

-10

-15

-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]

184
Single Universal Product Data

14. AUUQ60LT6 + ABNQ60LM3T6

14.10 Sound Levels


14.10.1 Pressure Levels
80

Cooling

70
Octave Band Sound Pressure Level (0dB = 20μPa)

NC-65
60
NC-60

NC-55
50
NC-50

NC-45
40
NC-40

NC-35
30
NC-30

NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)

Sound level [ dB(A), @ Standard condition ]


Cooling / Heating (@ 1.5m height) 55.0 / -

Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.

185
SINGLE

Installation of Outdoor Units


1.Information for Refrigerant
2.Select the Best Location
3.Foundation for Installation
4.Refrigerant Piping System
5.Electrical Wiring
6.Field Wiring
7.Special guide for installation at the Seaside
SINGLE Installation of Outdoor Units

1. Information for Refrigerant


1.1 Alternative Refrigerant R410A
• The refrigerant R410A has the property of higher operating pressure in comparison with R22. Therefore, all
materials have the characteristics of higher resisting pressure than ones of R22 and this characteristic should
also be considered during the installation.
• R410A is an azeotrope of R32 and R125 mixed at 50:50, so the ozone depletion potential (ODP) of R410A is 0.

CAUTION
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed
pressure 3.8MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.

2
SINGLE Installation of Outdoor Units

1. Information for Refrigerant

1.2 Caution For Refrigerant Leaks


The installer and system specialist shall secure safety against leakage according to local regulations or standards.
The following standards may be applicable if local regulations are not available.

1.2.1 Concentration limit


Concentration limit is the limit of Freon gas concentration where immediate measures can be taken without
hurting human body when refrigerant leaks in the air. The concentration limit shall be described in the unit of
kg/m3 (Freon gas weight per unit air volume) for facilitating calculation.
Concentration limit : 0.44kg/m3(R410A)

Outdoor unit Flow of


(No.1 system) refrigerant

Indoor unit Room where refrigerant leaks


(Refrigerant of the whole No.1
system flows out.)

1.2.2 Checking procedure of limiting concentration


Check concentration limit along following steps and take appropriate measure depending on the situation.

■ Calculate refrigerant concentration


1. Calculate amount of all the replenished refrigerant (kg) per each refrigerant system.
Amount of pre-charged Amount of additional Total amount of refrigerant
R d
refrigerant per single replenished refrigerant in the system
system (kg)

Amount of replenished Amount of additionally Note : In case one refrigerant facility is


refrigerant at factory shipment replenished refrigerant divided into 2 or more refrigerant
depending on piping systems and each system is
length or piping independent, amount of replenished
diameter by customer refrigerant of each system shall be
adopted.

2. Calculate the volume of the room where indoor unit is installed as single room or the smallest room.

With partition but opened which With partition and without opening
Without partition serve passage of air to adjoining which serve as passage of air to
room adjoining room

Outdoor unit Outdoor unit


Outdoor unit

Indoor unit Indoor unit In the case of opening Indoor unit


without door , or 0.15
Opening % or more openings Smallest
(to floor space) both room
Partition above and below door)

3
SINGLE Installation of Outdoor Units

1. Information for Refrigerant


3. Calculate the volume of the room where indoor unit is installed as single room or the smallest room.
Total amount of refrigerant
Maximum concentration In case the result of calculation exceeds
system (kg)
limit the concentration limit, perform the
Volume of smallest room where (kg/m
indoor unit is installed (m same calculations by shifting to the
(R410A) second smallest, and the third smallest
rooms until at last the result is below the
concentration limit.

■ In case the concentration exceeds the limit


When the concentration exceeds the limit, change original plan or take one of the counter measure shown below:
• Counter measure 1
Provide opening for ventilation.
Provide 0.15% or more size of opening to floor space both above and below door, or provide opening without
door.
• Counter measure 2
Provide gas leak alarm linked with mechanical ventilator.
• Counter measure 3
Reducing the system’s refrigerant quantity by deviding into smaller separate system.
Gas leak alarm
Countermeasure 2
Mechanical ventilator

Indoor unit

Countermeasure 1 Opening effective to ventilation

CAUTION
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant
is heavier than air.

4
SINGLE Installation of Outdoor Units

2. Select the Best Location


Select space for installing outdoor unit, which will meet the following conditions:
• No direct thermal radiation from other heat sources.
• No possibility of annoying neighbors due to noise of unit.
• No exposition to strong wind.
• Place with strength which bears weight of unit.
• Note that drain flows out of unit when heating mode operation (except for Cooling only model).
• Because of the possibility of fire, do not install unit to the space where generation, inflow, stagnation, and
leakage of combustible gas is expected.
• Avoid unit installation in a place where acidic solution and spray (sulfur) are often used.
• Do not use unit under any special environment where oil, steam and sulfuric gas exist.
• It is recommended to fence round the outdoor unit in order to prevent any person or animal from accessing the
outdoor unit.
• If installation site is area of heavy snowfall, then the following directions should be observed.
– Make the foundation as high as possible.
– Fit a snow protection hood.
• Select installation location considering following conditions to avoid bad condition when additionally performing
defrost operation.
– Install the outdoor unit at a place well ventilated and having a lot of sunshine in case of installing the product
at a place with a high humidity in winter (near beach, coast, lake, etc).
(Ex) Rooftop where sunshine always shines.
– Performance of heating will be reduced and pre-heat time of the indoor unit may be lengthened in case of
installing the outdoor unit in winter at following location:
» Shade position with a narrow space.
» Location with much moisture in neighboring floor.
» Location with much humidity around.
It is recommended to install the outdoor unit at a place with a lot of sunshine as possible as.
» Location where liquid gathers since the floor is not even.
» When installing the outdoor unit in a place that is constantly exposed to a strong wind like a coast or on a
high story of a building, secure a normal fan operation by using a duct or a wind shield.
 Cautions corresponding to strong/seasonal wind
• When the“Outdoor unit of Side Discharge Type” is installed in a place that is constantly exposed to a strong wind
like a coast or on a high story of a building, secure a normal fan operation by using a duct or a wind shield.
– Don't install the suction hole and discharge hole of the Outdoor unit facing the seasonal wind.
– Install the unit so that its discharge port faces to the wall of the building.
Keep a distance 500mm or more between the unit and the wall surface.
– Supposing the wind direction during the operation season of the air conditioner, install the unit so that the
discharge port is set at right angle to the wind direction.
 Cautions in winter
• Sufficient measures are required in a snow area or severe cold area in winter so that product can be operated
well.
• Get ready for seasonal wind or snow in winter even in other areas.
• Install a suction and discharge duct not to let in snow or rain.
• Install the outdoor unit not to come in contact with snow directly. If snow piles up and freezes on the air suction
hole, the system may malfunction. If it is installed at snowy area, attach the hood to the system.
• Where snow accumulated on the upper part of the Outdoor Unit, always remove snow for operation.
• If width of the frame is wider than that of the product, snow may accumulate. So, its width shall not exceed the
width of the product.

5
SINGLE Installation of Outdoor Units

3. Foundation for Installation

Unit : mm
re
mo
a
c
or h)
m in c
0m

≥75
10 15/16
(3-

≥75

≥ 200
≥ 200
≥ 100
b
re
mo
or h)
m in c
0m
10 15/16
(3-

re
mo c
or h)
m inc
0m
10 15/16
(3-

re d
mo e
or h)
m inc
0m f
10 15/16
(3- Pallet(Wood Support)
- Remove before Installation
• Install where it can sufficiently support the weight of the outdoor unit.
If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake.
If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treatment(treatment of the
water flowing out of the outdoor unit in operation), and the passages of the pipe and wiring, when making the
ground support.
• Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet. The tube or pipe
may freeze and the water may not be drained.
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm under the Unit’s legs before being
fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
• Fix the unit tightly with bolts as shown so that unit will not fall down due to earthquake or gust.
a. The corner part must be fixed firmly. Otherwise, the support for the installation may be bent.
b. Get and use M10 Anchor bolt.
c. Noise and vibration may occur from the floor or wall since vibration is transferred through the
installation part depending on installation status. Thus, use anti-vibration materials (cushion pad)
fully.(The base pad shall be more than 200mm)
d. Space for pipes and wiring (Pipes and wiring for bottom side)
e. Use the H-beam support as a base support
f. Concrete support
• Be sure to remove the Pallet (Wood Support) of the bottom of the outdoor unit before fixing the bolt or welding.
It may cause the unstable state of the outdoor settlement, and may cause freezing of the heat exchanger
resulting in abnormal operations, hazard of fire during welding.

6
SINGLE Installation of Outdoor Units

4. Refrigerant Piping System


■ Piping System between outdoor unit and indoor unit

Indoor Unit
L
Outdoor Unit

H
Outdoor Unit
H

Indoor Unit

Notes Refer to the specifications of Outdoor Unit for Maximum. limit


L (m) : Piping Length (Outdoor Unit ~ Indoor Unt) These figures are representatibe. Actual appearance of unit may
H (m) : Height Difference (Outdoor Unit ~ Indoor Unit) be different but clearances will stay the same.

 Refrigerant additional charge calculation method


Additional Refrigerant = (L - A) x a
L (m) : Installed Piping Length (Outdoor Unit ~ Indoor Unit)
A (m) : Charge-less piping length
a (g/m) : Additional charging volume
* Refer to the specifications for detail information of A, a.
* If total additional charge value after calculation comes out to be negative, then do not consider additional charge.
 Caution
• Please check the product type. Piping installation and refrigerant charge varies depending on the type of
product. For more information, please refer to the installation manual.
• Capacity is based on standard length and maximum allowance length is on the basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.

7
SINGLE Installation of Outdoor Units

5. Electrical Wiring
■ General Instruction
Outdoor Unit Outdoor Unit
Indoor Indoor
Unit Unit Indoor Indoor
Unit Unit

Remote Remote
control control Remote Remote
control control
Outdoor Unit
Indoor
door Indoor
Unit Unit
Outdoor Unit Indoor Indoor
Unit Unit
Remote Remote
control control
Remote Remote
control control

Outdoor Unit Indoor Indoor


Unit
U Unit Outdoor Unit Indoor Indoor
Unit Unit

R
Remote Remote
ccontrol control Remote Remote
control control
Outdoor Unit oor
Indoor Indoor
Unit
nit Unit
Outdoor Unit Indoor
Unit
Remote Remote
control control
Remote
control
Outdoor Unit Indoor
Unit Outdoor Unit Indoor
or
Unitt

Remote
control
Remote
control
Outdoor Unit Indoor
Unit

Remote
control ※ This figure is representative. Actual appearance of outdoor unit may be different
by product type, but schematic diagram will stay the same.

• Follow ordinance of local regulation for technical standard related to electrical equipment, wiring regulations and
guidance of each electric power company.
• Be sure to provide designated grounding work to installed unit.
• Give some allowance to wiring for electrical part box of units, because the box is sometimes removed at the time
of service work.
• Only the communication line specified should be connected to the terminal block for unit communication.
 WARNING
• Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with
regulations and installation manual. If power supply circuit has a lack of capacity or electric work deficiency, it
may cause an electric shock or fire.
• Be sure to connect the installed unit to earth. Do not connect earth line to any gas pipe, liquid pipe, lightening
rod or telephone earth line. If earth is incomplete, it may cause an electric shock
 CAUTION
• Product which use 3-phase power source have reversed phase protection detector that only works when the
power is turned on. If there exists black out or the power goes on and off which the product is operating, attach

8
SINGLE Installation of Outdoor Units

5. Electrical Wiring
a reversed phase protection circuit locally. Running the product in reversed phase may break the compressor
and other parts.
• Install the communication line away from the power source wiring so that it is not affected by electric noise from
the power source. (Do not run it through the same conduit.) Never use them together with power cables.
• Never use multi-core cable. If communication lines of different systems are wired with the same multiplecore
cable, the resultant poor transmitting and receiving will cause erroneous operations.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate power factor
improvement effect, but also may cause capacitor abnormal heating. Therefore, never install a phase leading
capacitor.
• Make sure that the power unbalance ratio is not greater than 2%. If it is greater, the unit’s lifespan will be
reduced.
• Never connect the main power source to terminal block of communication line. If connected, electrical parts will
be burnt out.
• Introducing with a missing “N” phase or with a mistaken “N” phase will break the equipment.
When the power supply is applied to “N” phase by mistake, replace inverter PCB and transformer in control box.

■ Communication and Power Lines


• Communication cable
– Types : shielded cables
– Use wires of size : over 1.0 ~ 1.5 mm2
– Maximum allowable temperature of cabel : 60°C (140℉)
– Maximum allowable line length: under 1,000m
• Remote control cable
– Types : 3-core cable
• Central control cable
– Please check the model function table for compatibility with central controller.

Product type Wire type Diameter


ACP&AC Manager 2-core cables (shielded) 1.0 ~ 1.5 mm2
AC Smart 2-core cables (shielded) 1.0 ~ 1.5 mm2
Simple central controller 4-core cables (shielded) 1.0 ~ 1.5 mm2
AC Ez 4-core cables (shielded) 1.0 ~ 1.5 mm2
• Separation of communication and power lines
– If communication and power lines are installed alongside each other then there is a strong likelihood of
operational faults developing due to interference in the signal wiring caused by electrostatic and
electromagnetic coupling.
The tables below indicates our recommendation as to appropriate spacing of communication and power lines
where these are to be run side by side

Current capacity of power line Spacing


10A 300mm
50A 500mm
100V or more
100A 1,000mm
Exceed 100A 1,500mm

9
SINGLE Installation of Outdoor Units

5. Electrical Wiring
– The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m the
figures will have to be recalculated in direct proportion to the additional length of line involved.
– If the power supply waveform continues to exhibit some distortion the recommended spacing in the table
should be increased.
» If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits
» Power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
» In the same way, when grouping the lines power and signal lines should not be bunched together.
 CAUTION
• If apparatus is not properly earthed then there is always a risk of electric shock, the grounding of the apparatus
must be carried out by a qualified person.

10
SINGLE Installation of Outdoor Units

6. Field Wiring
■ Wiring of Main Power Supply
• Bear in mind ambient conditions (ambient temperature,direct sunlight, rain liquid,etc.) when proceeding with the
wiring and connections
• The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking
into account the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
• Specific wiring requirements should adhere to the wiring regulations of the region.
• Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed
flexible cord (design 60245 IEC57).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power
supply.

WARNING
• Make sure to use specified wires for connections so that no external force is imparted to terminal connections.
If connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may
include some amount of direct current.
• All Installation site must require attachment of an earth leakage breaker. If no earth leakage breaker is installed,
it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with
too large capacity may cause a malfunction of unit or fire.

 Schematic Diagram of system wiring

!! This System is representative Example.

Outdoor
Power Supply **
(Main Switch)
R S T N R S T L N
Switch Switch Switch

Fuse
Fuse Fuse
to Indoor Unit

**
Power Supply
T/B T/B

3 Phase 3 Phase 1 Phase


4 Wires 3 Wires 2 Wires
Power Line

: Power Line
: Communication Line

Indoor Unit

Communication Line

11
SINGLE Installation of Outdoor Units

7. Special guide for installation at the Seaside


■ CAUTION
• Air conditioners should not be installed in areas where corrosive gases, such as acid or alkaline gas, are
produced.
• Do not install the product where it could be exposed to sea wind (salty wind) directly. It can result corrosion on
the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunctionor
inefficient performance.
• If outdoor unit is installed close to the seaside, it should avoid direct exposure to the sea wind. Otherwise itneeds
additional anticorrosion treatment on the heat exchanger.

■ Selecting the location of Outdoor Units

Windbreak

Sea wind Sea wind Sea wind

※ This figure is representative. Actual appearance of outdoor unit may be different by product type.

• If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
• It should be strong enough like concrete to prevent the sea wind from the sea.
• The height and width should be more than 150% of the outdoor unit.
• It should be kept more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
• In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
• Select a well-drained place.
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.

12
Air Solution
LG Electronics Inc, 128, Yeoui-daero,
Yeongdeungpo-gu, Seoul, Korea
(07336)
http://partner.lge.com
http://sedc.lge.com

Copyright © 2022 LG Electronics Inc.


All Rights Reserved.

The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance
and ISO14001 certificate for environmental management system.
The specifications, designs, and information in this brochure are subject to change without notice.

You might also like