Single Universal Product Data
ABNQ21GM1T6
+
AUUQ21GT6
1.
1. AUUQ21GT6 + ABNQ21GM1T6
1.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 4.74
Rated(T1)
Btu/h 16,200
kW 4.35
Rated(T3)
Btu/h 14,800
Cooling Capacity
kW 4.12
Sensible Heat
Btu/h 14,070
kW 1.47~5.86
Min ~ Max
Btu/h 5,000~20,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 1.31
Power Input(Cooling) Rated, T3 kW 1.71
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 10
Running Current(Cooling) Rated, T1 A 5.7
Rated, T3 A 7.5
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 10
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 0.40
Type - R410A
Precharged Amount kg 1.200
Additional Charging amount g/m 20
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 2.505
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ6.35 (1/4)
Connecting Pipe
Gas mm(inch) Φ12.7 (1/2)
Piping Length IDU - ODU(Rated / Max / Min) m 5/30/5
Maximum Height Difference IDU - ODU(Max) m 20
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 49.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
4
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 15
Electrical Characteristic Comp_Rated Load Amperes (Max) A 9.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.25
Outdoor Unit Specification
Chassis - U18A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 28 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 43 x 1
Type - Twin Rotary
Model x No. - GAT156MAD x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - RB68A
Oil Charging amount cc x No. 400 x 1
Rows x Columns x FPI - 2 x 24 x 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 770 x 545 x 288
Dimensions
Shipping(W x H x D) mm 920 x 585 x 388
Net kg 31.8
Weight
Shipping kg 34.3
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
5
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
6
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
7
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
8
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
1.4 Dimensions
1.4.1 Product
DWG No. : TBW35446501_Rev01
Chassis code : U18A
9
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
1.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
10
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
11
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
12
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
20 2.78 2.77 0.53 3.62 3.32 0.67 4.26 3.85 0.77 4.74 4.12 0.85 4.90 4.10 0.86 5.22 4.05 0.87 5.59 3.99 0.88
25 2.78 2.77 0.63 3.62 3.32 0.79 4.26 3.85 0.91 4.74 4.12 1.00 4.90 4.10 1.01 5.22 4.05 1.03 5.59 3.99 1.04
32 2.78 2.77 0.76 3.62 3.32 0.95 4.26 3.85 1.11 4.74 4.12 1.21 4.90 4.10 1.22 5.22 4.05 1.25 5.59 3.99 1.26
35 2.78 2.77 0.82 3.62 3.32 1.03 4.26 3.85 1.19 4.74 4.12 1.31 4.90 4.10 1.32 5.22 4.05 1.34 5.59 3.99 1.35
40 2.78 2.77 0.82 3.62 3.32 1.03 4.26 3.85 1.20 4.74 4.12 1.31 4.90 4.10 1.32 5.22 4.05 1.35 5.59 3.99 1.36
43 2.78 2.77 0.83 3.62 3.32 1.04 4.26 3.85 1.20 4.64 4.08 1.32 4.80 4.05 1.33 5.12 3.99 1.36 5.48 3.94 1.37
46 2.78 2.77 0.83 3.62 3.32 1.04 4.26 3.85 1.21 4.35 3.87 1.71 4.50 3.84 1.73 4.79 3.77 1.76 5.13 3.71 1.77
48 2.78 2.77 0.83 3.62 3.32 1.05 4.01 3.66 1.21 4.09 3.66 1.58 4.21 3.61 1.60 4.44 3.52 1.63 4.71 3.42 1.64
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
13
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
14
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
15
Single Universal Product Data
1. AUUQ21GT6 + ABNQ21GM1T6
80
■ Cooling
75
70
Octave Band Sound Pressure Level (dB = 20μPa )
65
NC-65
60
NC-60
55
NC-55
50
NC-50
45
NC-45
40
NC-40
35
NC-35
30
NC-30
25
20 NC-25
Approximate
Hearing NC-20
15
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.
16
Single Universal Product Data
ATNQ21GPLT6
+
AUUQ21GT6
2.
2. AUUQ21GT6 + ATNQ21GPLT6
2.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 4.98
Rated(T1)
Btu/h 17,000
kW 4.38
Rated(T3)
Btu/h 14,900
Cooling Capacity
kW 4.88
Sensible Heat
Btu/h 16,660
kW 1.47~6.15
Min ~ Max
Btu/h 5,000~21,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 1.37
Power Input(Cooling) Rated, T3 kW 1.72
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 10
Running Current(Cooling) Rated, T1 A 6
Rated, T3 A 7.5
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 10
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 1.30
Type - R410A
Precharged Amount kg 1.200
Additional Charging amount g/m 20
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 2.505
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ6.35 (1/4)
Connecting Pipe
Gas mm(inch) Φ12.7 (1/2)
Piping Length IDU - ODU(Rated / Max / Min) m 5/30/5
Maximum Height Difference IDU - ODU(Max) m 20
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 49.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
17
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 15
Electrical Characteristic Comp_Rated Load Amperes (Max) A 10.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.25
Outdoor Unit Specification
Chassis - U18A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 28 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 43 x 1
Type - Twin Rotary
Model x No. - GAT156MAD x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - RB68A
Oil Charging amount cc x No. 400 x 1
Rows x Columns x FPI - 2 x 24 x 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 770 x 545 x 288
Dimensions
Shipping(W x H x D) mm 920 x 585 x 388
Net kg 31.8
Weight
Shipping kg 34.3
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ6.35 (1/4)
Gas mm(inch) Φ12.7 (1/2)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
18
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
19
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
20
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
21
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
2.4 Dimensions
2.4.1 Product
DWG No. : TBW35446501_Rev01
Chassis code : U18A
22
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
2.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
23
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
24
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
25
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
20 2.92 2.91 0.56 3.80 3.78 0.70 4.47 4.45 0.81 4.98 4.88 0.89 5.15 4.85 0.90 5.49 4.79 0.92 5.88 4.73 0.92
25 2.92 2.91 0.66 3.80 3.78 0.83 4.47 4.45 0.96 4.98 4.88 1.05 5.15 4.85 1.06 5.49 4.79 1.08 5.88 4.73 1.09
32 2.92 2.91 0.80 3.80 3.78 1.00 4.47 4.45 1.16 4.98 4.88 1.27 5.15 4.85 1.28 5.49 4.79 1.31 5.88 4.73 1.32
35 2.92 2.91 0.86 3.80 3.78 1.08 4.47 4.45 1.25 4.98 4.88 1.37 5.15 4.85 1.38 5.49 4.79 1.41 5.88 4.73 1.42
40 2.92 2.91 0.93 3.80 3.78 1.17 4.47 4.45 1.36 4.98 4.88 1.49 5.15 4.85 1.50 5.49 4.79 1.53 5.88 4.73 1.54
43 2.92 2.91 0.98 3.80 3.78 1.23 4.47 4.45 1.42 4.98 4.88 1.56 5.15 4.85 1.58 5.49 4.79 1.61 5.88 4.73 1.62
46 2.92 2.91 1.03 3.80 3.78 1.29 4.29 4.27 1.49 4.38 4.34 1.72 4.53 4.31 1.74 4.83 4.25 1.77 5.17 4.19 1.78
48 2.92 2.91 1.08 3.80 3.78 1.35 4.20 4.17 1.56 4.28 4.26 1.64 4.40 4.21 1.66 4.64 4.10 1.69 4.91 4.00 1.70
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
26
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
27
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
28
Single Universal Product Data
2. AUUQ21GT6 + ATNQ21GPLT6
80
■ Cooling
75
70
Octave Band Sound Pressure Level (dB = 20μPa )
65
NC-65
60
NC-60
55
NC-55
50
NC-50
45
NC-45
40
NC-40
35
NC-35
30
NC-30
25
20 NC-25
Approximate
Hearing NC-20
15
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.
29
Single Universal Product Data
ABNQ28GM1T6
+
AUUQ28GT6
3.
3. AUUQ28GT6 + ABNQ28GM1T6
3.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 6.27
Rated(T1)
Btu/h 21,400
kW 5.73
Rated(T3)
Btu/h 19,600
Cooling Capacity
kW 5.58
Sensible Heat
Btu/h 19,050
kW 1.83~8.20
Min ~ Max
Btu/h 6,200~28,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 1.73
Power Input(Cooling) Rated, T3 kW 2.26
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 7.6
Rated, T3 A 9.9
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 1.60
Type - R410A
Precharged Amount kg 1.500
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 3.131
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 50.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
30
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 12.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.33
Outdoor Unit Specification
Chassis - U24A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 50 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 85 x 1
Type - Twin Rotary
Model x No. - GKT208MAB x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 670 x 1
Rows x Columns x FPI - 2 x 28 x 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 870 x 650 x 330
Dimensions
Shipping(W x H x D) mm 1,026 x 693 x 446
Net kg 43.0
Weight
Shipping kg 47.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
31
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
32
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
33
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
34
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
3.4 Dimensions
3.4.1 Product
DWG No. : TBW35646501_Rev01
Chassis code : U24A
35
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
3.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
36
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
37
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
38
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
20 3.68 3.66 0.70 4.79 4.49 0.88 5.63 5.22 1.02 6.27 5.58 1.12 6.48 5.55 1.13 6.91 5.48 1.15 7.40 5.41 1.16
25 3.68 3.66 0.83 4.79 4.49 1.04 5.63 5.22 1.21 6.27 5.58 1.32 6.48 5.55 1.33 6.91 5.48 1.36 7.40 5.41 1.37
32 3.68 3.66 1.01 4.79 4.49 1.26 5.63 5.22 1.46 6.27 5.58 1.60 6.48 5.55 1.62 6.91 5.48 1.65 7.40 5.41 1.66
35 3.68 3.66 1.08 4.79 4.49 1.36 5.63 5.22 1.57 6.27 5.58 1.73 6.48 5.55 1.75 6.91 5.48 1.78 7.40 5.41 1.79
40 3.68 3.66 1.22 4.79 4.49 1.53 5.63 5.22 1.77 6.27 5.58 1.94 6.48 5.55 1.96 6.91 5.48 2.00 7.40 5.41 2.01
43 3.68 3.66 1.30 4.79 4.49 1.63 5.63 5.22 1.89 6.27 5.58 2.07 6.48 5.55 2.09 6.91 5.48 2.13 7.40 5.41 2.14
46 3.68 3.66 1.38 4.79 4.49 1.74 5.63 5.22 2.01 5.73 5.16 2.26 5.93 5.12 2.28 6.32 5.05 2.32 6.76 4.97 2.34
48 3.68 3.66 1.48 4.79 4.49 1.85 5.36 5.01 2.12 5.47 4.96 2.17 5.63 4.90 2.19 5.94 4.77 2.23 6.29 4.65 2.24
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
39
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
40
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
41
Single Universal Product Data
3. AUUQ28GT6 + ABNQ28GM1T6
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.
42
Single Universal Product Data
ATNQ28GPLT6
+
AUUQ28GT6
4.
4. AUUQ28GT6 + ATNQ28GPLT6
4.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 6.45
Rated(T1)
Btu/h 22,000
kW 5.85
Rated(T3)
Btu/h 20,000
Cooling Capacity
kW 5.74
Sensible Heat
Btu/h 19,600
kW 1.92~8.20
Min ~ Max
Btu/h 6,600~28,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 1.77
Power Input(Cooling) Rated, T3 kW 2.26
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.85
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 7.8
Rated, T3 A 9.9
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 2.40
Type - R410A
Precharged Amount kg 1.500
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 3.131
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 50.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
43
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 12.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.33
Outdoor Unit Specification
Chassis - U24A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 50 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 85 x 1
Type - Twin Rotary
Model x No. - GKT208MAB x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 670 x 1
Rows x Columns x FPI - 2 x 28 x 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 870 x 650 x 330
Dimensions
Shipping(W x H x D) mm 1,026 x 693 x 446
Net kg 43.0
Weight
Shipping kg 47.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
44
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
45
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
46
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
47
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
4.4 Dimensions
4.4.1 Product
DWG No. : TBW35646501_Rev01
Chassis code : U24A
48
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
4.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
49
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
50
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
51
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
20 3.79 3.77 0.72 4.93 4.62 0.91 5.79 5.37 1.05 6.45 5.74 1.15 6.67 5.70 1.16 7.11 5.63 1.19 7.61 5.56 1.19
25 3.79 3.77 0.85 4.93 4.62 1.07 5.79 5.37 1.24 6.45 5.74 1.36 6.67 5.70 1.37 7.11 5.63 1.40 7.61 5.56 1.41
32 3.79 3.77 1.03 4.93 4.62 1.30 5.79 5.37 1.50 6.45 5.74 1.65 6.67 5.70 1.67 7.11 5.63 1.70 7.61 5.56 1.71
35 3.79 3.77 1.11 4.93 4.62 1.39 5.79 5.37 1.62 6.45 5.74 1.77 6.67 5.70 1.79 7.11 5.63 1.83 7.61 5.56 1.84
40 3.79 3.77 1.22 4.93 4.62 1.53 5.79 5.37 1.77 6.45 5.74 1.94 6.67 5.70 1.96 7.11 5.63 2.00 7.61 5.56 2.01
43 3.79 3.77 1.28 4.93 4.62 1.61 5.79 5.37 1.86 6.45 5.74 2.04 6.67 5.70 2.06 7.11 5.63 2.10 7.61 5.56 2.11
46 3.79 3.77 1.34 4.93 4.62 1.69 5.79 5.37 1.96 5.85 5.26 2.26 6.05 5.22 2.28 6.45 5.15 2.33 6.90 5.08 2.34
48 3.79 3.77 1.41 4.93 4.62 1.78 5.48 5.13 2.06 5.60 5.07 2.17 5.76 5.01 2.19 6.07 4.88 2.23 6.43 4.75 2.25
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
52
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
53
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
54
Single Universal Product Data
4. AUUQ28GT6 + ATNQ28GPLT6
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.
55
Single Universal Product Data
ABNQ34GM3T6
+
AUUQ34GT6
5.
5. AUUQ34GT6 + ABNQ34GM3T6
5.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 7.75
Rated(T1)
Btu/h 26,400
kW 6.99
Rated(T3)
Btu/h 23,800
Cooling Capacity
kW 7.60
Sensible Heat
Btu/h 25,950
kW 2.34~9.96
Min ~ Max
Btu/h 8,000~34,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 2.13
Power Input(Cooling) Rated, T3 kW 2.74
Min ~ Max kW ~
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 9.3
Rated, T3 A 12
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 1.90
Type - R410A
Precharged Amount kg 1.500
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 3.131
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 50.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 X 3C
56
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 12.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.33
Outdoor Unit Specification
Chassis - U24A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 50 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 85 x 1
Type - Twin Rotary
Model x No. - GKT208MAB x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 670 X 1
Rows x Columns x FPI - 2 X 28 X 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 870 x 650 x 330
Dimensions
Shipping(W x H x D) mm 1,026 x 693 x 446
Net kg 43.0
Weight
Shipping kg 47.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 X 3C
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
57
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
58
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
59
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
60
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
5.4 Dimensions
5.4.1 Product
DWG No. : TBW35646501_Rev01
Chassis code : U24A
61
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
5.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
62
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
63
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
64
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
20 4.55 4.53 0.87 5.92 5.89 1.09 6.96 6.92 1.26 7.75 7.60 1.38 8.01 7.55 1.40 8.54 7.45 1.43 9.14 7.36 1.43
25 4.55 4.53 1.02 5.92 5.89 1.28 6.96 6.92 1.49 7.75 7.60 1.63 8.01 7.55 1.65 8.54 7.45 1.68 9.14 7.36 1.69
32 4.55 4.53 1.24 5.92 5.89 1.56 6.96 6.92 1.81 7.75 7.60 1.98 8.01 7.55 2.00 8.54 7.45 2.04 9.14 7.36 2.05
35 4.55 4.53 1.34 5.92 5.89 1.68 6.96 6.92 1.94 7.75 7.60 2.13 8.01 7.55 2.15 8.54 7.45 2.19 9.14 7.36 2.21
40 4.55 4.53 1.34 5.92 5.89 1.69 6.96 6.92 1.96 7.75 7.60 2.15 8.01 7.55 2.17 8.54 7.45 2.21 9.14 7.36 2.22
43 4.55 4.53 1.35 5.92 5.89 1.70 6.96 6.92 1.96 7.56 7.49 2.15 7.82 7.44 2.17 8.33 7.33 2.22 8.92 7.22 2.23
46 4.55 4.53 1.36 5.92 5.89 1.70 6.96 6.92 1.97 6.99 6.96 2.74 7.23 6.92 2.77 7.70 6.83 2.82 8.25 6.72 2.83
48 4.55 4.53 1.36 5.92 5.89 1.71 6.47 6.43 1.98 6.60 6.57 2.55 6.79 6.51 2.57 7.16 6.39 2.62 7.60 6.22 2.64
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
65
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
66
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
67
Single Universal Product Data
5. AUUQ34GT6 + ABNQ34GM3T6
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.
68
Single Universal Product Data
ATNQ34GNLT6
+
AUUQ34GT6
6.
6. AUUQ34GT6 + ATNQ34GNLT6
6.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 7.35
Rated(T1)
Btu/h 25,000
kW 6.50
Rated(T3)
Btu/h 22,200
Cooling Capacity
kW 6.69
Sensible Heat
Btu/h 22,840
kW 2.16~9.38
Min ~ Max
Btu/h 7,400~32,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 2.02
Power Input(Cooling) Rated, T3 kW 2.55
Min ~ Max kW ~
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 8.9
Rated, T3 A 11.2
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 2.50
Type - R410A
Precharged Amount kg 1.500
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 3.131
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 50.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
69
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 12.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.33
Outdoor Unit Specification
Chassis - U24A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 50 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 85 x 1
Type - Twin Rotary
Model x No. - GKT208MAB x 1
Motor Type - BLDC
Compressor
Motor Output W x No. 1500 x 1
Oil Type - FW68D
Oil Charging amount cc x No. 670 x 1
Rows x Columns x FPI - 2 X 28 X 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 870 x 650 x 330
Dimensions
Shipping(W x H x D) mm 1,026 x 693 x 466
Net kg 43.0
Weight
Shipping kg 47.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
70
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
71
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
72
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
73
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
6.4 Dimensions
6.4.1 Product
DWG No. : TBW35646501_Rev01
Chassis code : U24A
74
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
6.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
75
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
76
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
77
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
20 4.31 4.29 0.82 5.61 5.38 1.03 6.60 6.25 1.19 7.35 6.69 1.31 7.60 6.65 1.32 8.10 6.56 1.35 8.67 6.48 1.36
25 4.31 4.29 0.97 5.61 5.38 1.22 6.60 6.25 1.41 7.35 6.69 1.54 7.60 6.65 1.56 8.10 6.56 1.59 8.67 6.48 1.60
32 4.31 4.29 1.18 5.61 5.38 1.48 6.60 6.25 1.71 7.35 6.69 1.87 7.60 6.65 1.89 8.10 6.56 1.93 8.67 6.48 1.94
35 4.31 4.29 1.26 5.61 5.38 1.59 6.60 6.25 1.84 7.35 6.69 2.02 7.60 6.65 2.04 8.10 6.56 2.08 8.67 6.48 2.09
40 4.31 4.29 1.40 5.61 5.38 1.75 6.60 6.25 2.03 7.35 6.69 2.23 7.60 6.65 2.25 8.10 6.56 2.30 8.67 6.48 2.31
43 4.31 4.29 1.48 5.61 5.38 1.86 6.60 6.25 2.15 7.35 6.69 2.36 7.60 6.65 2.38 8.10 6.56 2.43 8.67 6.48 2.44
46 4.31 4.29 1.56 5.61 5.38 1.96 6.37 6.08 2.27 6.50 5.98 2.55 6.72 5.94 2.58 7.16 5.85 2.63 7.67 5.77 2.64
48 4.31 4.29 1.65 5.61 5.38 2.08 6.04 5.76 2.39 6.16 5.71 2.44 6.33 5.64 2.47 6.68 5.49 2.52 7.09 5.36 2.53
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
78
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
79
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
80
Single Universal Product Data
6. AUUQ34GT6 + ATNQ34GNLT6
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.
81
Single Universal Product Data
ABNQ40GM3T6
+
AUUQ40GT6
7.
7. AUUQ40GT6 + ABNQ40GM3T6
7.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 9.95
Rated(T1)
Btu/h 34,000
kW 8.50
Rated(T3)
Btu/h 29,000
Cooling Capacity
kW 8.26
Sensible Heat
Btu/h 28,200
kW 2.82~11.25
Min ~ Max
Btu/h 9,600~38,400
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 2.74
Power Input(Cooling) Rated, T3 kW 3.33
Min ~ Max kW ~
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 12
Rated, T3 A 14.6
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 1.90
Type - R410A
Precharged Amount kg 2.200
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 4.593
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 51.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
82
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 17.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.58
Outdoor Unit Specification
Chassis - U36A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 X 1
Type - Twin Rotary
Model x No. - GJT240MAA X 1
Motor Type - BLDC
Compressor
Motor Output W x No. 2137 X 1
Oil Type - FW68D
Oil Charging amount cc x No. 900 X 1
Rows x Columns x FPI - 2 X 38 X 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 834 x 330
Dimensions
Shipping(W x H x D) mm 1,065 x 918 x 461
Net kg 56.5
Weight
Shipping kg 61.3
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 X 3C
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
83
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
84
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
85
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
86
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
7.4 Dimensions
7.4.1 Product
DWG No. : TBW35046501_rev01
Chassis code : U36A
87
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
7.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
88
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
89
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
90
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
20 5.84 5.57 1.12 7.60 6.64 1.40 8.93 7.72 1.62 9.95 8.26 1.78 10.29 8.21 1.80 10.97 8.10 1.83 11.74 8.00 1.85
25 5.84 5.57 1.32 7.60 6.64 1.65 8.93 7.72 1.92 9.95 8.26 2.10 10.29 8.21 2.12 10.97 8.10 2.16 11.74 8.00 2.18
32 5.84 5.57 1.60 7.60 6.64 2.01 8.93 7.72 2.32 9.95 8.26 2.55 10.29 8.21 2.58 10.97 8.10 2.63 11.74 8.00 2.64
35 5.84 5.57 1.72 7.60 6.64 2.16 8.93 7.72 2.50 9.95 8.26 2.74 10.29 8.21 2.77 10.97 8.10 2.82 11.74 8.00 2.84
40 5.84 5.57 1.77 7.60 6.64 2.23 8.93 7.72 2.58 9.95 8.26 2.83 10.29 8.21 2.86 10.97 8.10 2.91 11.74 8.00 2.93
43 5.84 5.57 1.80 7.60 6.64 2.27 8.93 7.72 2.62 9.95 8.26 2.88 10.29 8.21 2.91 10.97 8.10 2.97 11.74 8.00 2.98
46 5.84 5.57 1.84 7.60 6.64 2.31 8.33 7.25 2.67 8.50 7.13 3.33 8.79 7.08 3.36 9.37 6.98 3.43 10.03 6.88 3.45
48 5.84 5.57 1.87 7.60 6.64 2.35 7.83 6.81 2.72 7.99 6.76 3.15 8.22 6.67 3.18 8.68 6.50 3.25 9.20 6.34 3.26
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
91
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
92
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
93
Single Universal Product Data
7. AUUQ40GT6 + ABNQ40GM3T6
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.
94
Single Universal Product Data
ATNQ40GNLT6
+
AUUQ40GT6
8.
8. AUUQ40GT6 + ATNQ40GNLT6
8.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 9.40
Rated(T1)
Btu/h 32,000
kW 8.20
Rated(T3)
Btu/h 28,000
Cooling Capacity
kW 7.90
Sensible Heat
Btu/h 26,970
kW 2.76~10.56
Min ~ Max
Btu/h 9,400~36,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 2.58
Power Input(Cooling) Rated, T3 kW 3.22
Min ~ Max kW ~
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 19
Running Current(Cooling) Rated, T1 A 11.3
Rated, T3 A 14.1
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 19
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 2.50
Type - R410A
Precharged Amount kg 2.200
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 4.593
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ15.88 (5/8)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 51.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
95
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 25
Electrical Characteristic Comp_Rated Load Amperes (Max) A 17.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 0.58
Outdoor Unit Specification
Chassis - U36A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60 x 1
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 x 1
Type - Twin Rotary
Model x No. - GJT240MAA X 1
Motor Type - BLDC
Compressor
Motor Output W x No. 2137 X 1
Oil Type - FW68D
Oil Charging amount cc x No. 900 X 1
Rows x Columns x FPI - 2 X 38 X 14
No. - 1
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 834 x 330
Dimensions
Shipping(W x H x D) mm 1,065 x 918 x 461
Net kg 56.5
Weight
Shipping kg 61.3
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ15.88 (5/8)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 2.5 x 3C
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
96
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
97
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
98
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
99
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
8.4 Dimensions
8.4.1 Product
DWG No. : TBW35046501_rev01
Chassis code : U36A
100
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
8.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
101
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
102
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
103
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
20 5.52 5.32 1.05 7.18 6.35 1.32 8.44 7.38 1.53 9.40 7.90 1.68 9.72 7.85 1.70 10.36 7.75 1.73 11.09 7.65 1.74
25 5.52 5.32 1.24 7.18 6.35 1.56 8.44 7.38 1.80 9.40 7.90 1.98 9.72 7.85 2.00 10.36 7.75 2.04 11.09 7.65 2.05
32 5.52 5.32 1.50 7.18 6.35 1.89 8.44 7.38 2.19 9.40 7.90 2.40 9.72 7.85 2.42 10.36 7.75 2.47 11.09 7.65 2.49
35 5.52 5.32 1.62 7.18 6.35 2.03 8.44 7.38 2.35 9.40 7.90 2.58 9.72 7.85 2.61 10.36 7.75 2.66 11.09 7.65 2.67
40 5.52 5.32 1.77 7.18 6.35 2.22 8.44 7.38 2.57 9.40 7.90 2.82 9.72 7.85 2.85 10.36 7.75 2.91 11.09 7.65 2.92
43 5.52 5.32 1.86 7.18 6.35 2.33 8.44 7.38 2.70 9.40 7.90 2.97 9.72 7.85 3.00 10.36 7.75 3.06 11.09 7.65 3.07
46 5.52 5.32 1.96 7.18 6.35 2.45 8.04 7.08 2.84 8.20 6.96 3.22 8.48 6.91 3.25 9.04 6.81 3.32 9.67 6.72 3.34
48 5.52 5.32 2.06 7.18 6.35 2.58 7.52 6.62 2.97 7.68 6.57 3.03 7.90 6.49 3.06 8.34 6.32 3.12 8.84 6.17 3.14
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
104
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
105
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
106
Single Universal Product Data
8. AUUQ40GT6 + ATNQ40GNLT6
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition. Refer to the model specifications for nominal coditions.(Power source and Ambient temperature, etc)
■ Reference accoustic pressure 0dB = 20μPa.
■ Sound levels can be increased in accordance with installation and operating conditions. (Operating conditions include some functional condition like Static
pressure mode, air guide use, Room target temperature setting, etc and these functions are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 Standard.
Therefore, these values can be increased owing to ambient conditions during operation.
107
Single Universal Product Data
ABNQ55GM3T6
+
AUUQ55GT6
9.
9. AUUQ55GT6 + ABNQ55GM3T6
9.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 13.75
Rated(T1)
Btu/h 47,000
kW 11.70
Rated(T3)
Btu/h 40,000
Cooling Capacity
kW 11.14
Sensible Heat
Btu/h 38,040
kW 4.62~16.41
Min ~ Max
Btu/h 15,800~56,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 3.79
Power Input(Cooling) Rated, T3 kW 4.60
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 16.6
Rated, T3 A 20.2
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.50
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C
108
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
Category
Unit Value
Major Minor
Maximum Fuse Amperes (MFA) A 40
Electrical Characteristic Comp_Rated Load Amperes (Max) A 25.6
Outdoor Fan Motor_Full Load Amperes (FLA) A 1.16
Outdoor Unit Specification
Chassis - U60A
Classification
Cooling / Heating - C/O
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
Type - Axial
m³/min x No. 60 x 2
Air Flow Rate(Max)
Outdoor Fan ft³/min x No. -
RPM(Cooling, Min~Max) RPM -
Max. External Static Pressure Pa -
Type - BLDC
Outdoor Fan Motor Drive - -
Output W x No. 124 x 2
Type - Twin Rotary
Model x No. - GPT442MAB X 1
Motor Type - BLDC
Compressor
Motor Output W x No. 4000 X 1
Oil Type - FW68D
Oil Charging amount cc x No. 1300 X 1
Rows x Columns x FPI - 2 X 32 X 14
No. - 2
Fin Type - Wide Louver Plus
Heat Exchanger
Corrosion Protection (Coating) - -
Material (Tube / Fin) - -
Face Area m² -
Net(W x H x D) mm 950 x 1,380 x 330
Dimensions
Shipping(W x H x D) mm 1,140 x 1,462 x 461
Net kg 88.5
Weight
Shipping kg 97.0
Color - Warm Gray
Exterior
RAL (Classic) - RAL 7044
High Pressure Prevention - -
Frost Prevention - -
Protection Device
Discharge Tempreature Control - -
Inverter Protection - -
Type - R410A
Refrigerant
Control Type - EEV
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Pipe Connecting Socket
Connection Type(Liquid) - Flare
Connection Type(Gas) - Flare
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
109
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
■ Voltage supplied to the unit terminals should be within the minimum and maximum range.
■ Maximum allowable voltage unbalance between phase is 2%.
■ MSC means the Max. current during the starting of compressor.
■ MSC and RLA are measured as the compressor only test condition.
■ OFM and IFM are measured as the outdoor unit test condition.
■ Select the wire size based on MCA.
■ MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
110
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
111
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
112
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
9.4 Dimensions
9.4.1 Product
Gravity point
159
541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A
113
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
9.4.2 Install Space
For Side Discharge (capacity < 28.0 kW)
※ Case 1 : No obstacle on top side [Unit : mm(inch)]
Obstacle on the Suction side Case 2 : Obstacle on top side
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
114
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
115
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
116
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
20 8.07 7.51 1.54 10.50 8.96 1.94 12.35 10.41 2.24 13.75 11.14 2.46 14.22 11.07 2.49 15.15 10.93 2.54 16.22 10.79 2.55
25 8.07 7.51 1.82 10.50 8.96 2.29 12.35 10.41 2.65 13.75 11.14 2.90 14.22 11.07 2.93 15.15 10.93 2.99 16.22 10.79 3.01
32 8.07 7.51 2.21 10.50 8.96 2.77 12.35 10.41 3.21 13.75 11.14 3.52 14.22 11.07 3.56 15.15 10.93 3.63 16.22 10.79 3.65
35 8.07 7.51 2.38 10.50 8.96 2.98 12.35 10.41 3.46 13.75 11.14 3.79 14.22 11.07 3.83 15.15 10.93 3.90 16.22 10.79 3.93
40 8.07 7.51 2.48 10.50 8.96 3.11 12.35 10.41 3.61 13.75 11.14 3.96 14.22 11.07 4.00 15.15 10.93 4.08 16.22 10.79 4.10
43 8.07 7.51 2.54 10.50 8.96 3.19 12.35 10.41 3.70 13.75 11.14 4.06 14.22 11.07 4.10 15.15 10.93 4.18 16.22 10.79 4.21
46 8.07 7.51 2.61 10.50 8.96 3.28 11.47 9.73 3.80 11.70 9.58 4.60 12.10 9.51 4.65 12.89 9.38 4.74 13.80 9.24 4.77
48 8.07 7.51 2.68 10.50 8.96 3.36 11.13 9.45 3.89 11.35 9.37 4.35 11.67 9.24 4.39 12.30 8.99 4.48 13.03 8.76 4.51
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
117
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
118
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
119
Single Universal Product Data
9. AUUQ55GT6 + ABNQ55GM3T6
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
120
Single Universal Product Data
APNQ55GT3E6
+
AUUQ55GT6
10.
10. AUUQ55GT6 + APNQ55GT3E6
10.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 14.05
Rated(T1)
Btu/h 48,000
kW 12.60
Rated(T3)
Btu/h 43,000
Cooling Capacity
kW 10.54
Sensible Heat
Btu/h 35,990
kW 4.44~16.12
Min ~ Max
Btu/h 15,200~55,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 3.87
Power Input(Cooling) Rated, T3 kW 4.94
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 17
Rated, T3 A 21.7
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.90
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C
121
Single Universal Product Data
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
122
Single Universal Product Data
123
Single Universal Product Data
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
124
Single Universal Product Data
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
125
Single Universal Product Data
10.4 Dimensions
10.4.1 Product
Gravity point
159
541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A
126
Single Universal Product Data
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
127
Single Universal Product Data
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
128
Single Universal Product Data
129
Single Universal Product Data
20 8.25 7.10 1.58 10.73 8.48 1.98 12.62 9.85 2.29 14.05 10.54 2.51 14.53 10.47 2.54 15.48 10.34 2.59 16.58 10.21 2.60
25 8.25 7.10 1.86 10.73 8.48 2.33 12.62 9.85 2.70 14.05 10.54 2.97 14.53 10.47 3.00 15.48 10.34 3.06 16.58 10.21 3.07
32 8.25 7.10 2.26 10.73 8.48 2.83 12.62 9.85 3.28 14.05 10.54 3.60 14.53 10.47 3.64 15.48 10.34 3.71 16.58 10.21 3.73
35 8.25 7.10 2.43 10.73 8.48 3.05 12.62 9.85 3.53 14.05 10.54 3.87 14.53 10.47 3.91 15.48 10.34 3.99 16.58 10.21 4.01
40 8.25 7.10 2.68 10.73 8.48 3.37 12.62 9.85 3.90 14.05 10.54 4.28 14.53 10.47 4.32 15.48 10.34 4.41 16.58 10.21 4.44
43 8.25 7.10 2.84 10.73 8.48 3.56 12.62 9.85 4.13 14.05 10.54 4.53 14.53 10.47 4.57 15.48 10.34 4.66 16.58 10.21 4.69
46 8.25 7.10 3.00 10.73 8.48 3.77 12.35 9.71 4.37 12.60 9.55 4.94 13.03 9.48 4.99 13.89 9.35 5.09 14.86 9.21 5.12
48 8.25 7.10 3.17 10.73 8.48 3.99 11.67 9.17 4.54 11.91 9.10 4.63 12.25 8.98 4.68 12.92 8.75 4.77 13.71 8.53 4.80
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
130
Single Universal Product Data
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
131
Single Universal Product Data
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
132
Single Universal Product Data
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
133
Single Universal Product Data
APNQ55GT3M6
+
AUUQ55GT6
11.
11. AUUQ55GT6 + APNQ55GT3M6
11.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 14.05
Rated(T1)
Btu/h 48,000
kW 12.60
Rated(T3)
Btu/h 43,000
Cooling Capacity
kW 10.54
Sensible Heat
Btu/h 35,990
kW 4.44~16.12
Min ~ Max
Btu/h 15,200~55,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 3.87
Power Input(Cooling) Rated, T3 kW 4.94
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 17
Rated, T3 A 21.7
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.90
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C
134
Single Universal Product Data
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
135
Single Universal Product Data
136
Single Universal Product Data
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
137
Single Universal Product Data
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
138
Single Universal Product Data
11.4 Dimensions
11.4.1 Product
Gravity point
159
541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A
139
Single Universal Product Data
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
140
Single Universal Product Data
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
141
Single Universal Product Data
142
Single Universal Product Data
20 8.25 7.10 1.58 10.73 8.48 1.98 12.62 9.85 2.29 14.05 10.54 2.51 14.53 10.47 2.54 15.48 10.34 2.59 16.58 10.21 2.60
25 8.25 7.10 1.86 10.73 8.48 2.33 12.62 9.85 2.70 14.05 10.54 2.97 14.53 10.47 3.00 15.48 10.34 3.06 16.58 10.21 3.07
32 8.25 7.10 2.26 10.73 8.48 2.83 12.62 9.85 3.28 14.05 10.54 3.60 14.53 10.47 3.64 15.48 10.34 3.71 16.58 10.21 3.73
35 8.25 7.10 2.43 10.73 8.48 3.05 12.62 9.85 3.53 14.05 10.54 3.87 14.53 10.47 3.91 15.48 10.34 3.99 16.58 10.21 4.01
40 8.25 7.10 2.68 10.73 8.48 3.37 12.62 9.85 3.90 14.05 10.54 4.28 14.53 10.47 4.32 15.48 10.34 4.41 16.58 10.21 4.44
43 8.25 7.10 2.84 10.73 8.48 3.56 12.62 9.85 4.13 14.05 10.54 4.53 14.53 10.47 4.57 15.48 10.34 4.66 16.58 10.21 4.69
46 8.25 7.10 3.00 10.73 8.48 3.77 12.35 9.71 4.37 12.60 9.55 4.94 13.03 9.48 4.99 13.89 9.35 5.09 14.86 9.21 5.12
48 8.25 7.10 3.17 10.73 8.48 3.99 11.67 9.17 4.54 11.91 9.10 4.63 12.25 8.98 4.68 12.92 8.75 4.77 13.71 8.53 4.80
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
143
Single Universal Product Data
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
144
Single Universal Product Data
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
145
Single Universal Product Data
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
146
Single Universal Product Data
ATNQ55GMLT6
+
AUUQ55GT6
12.
12. AUUQ55GT6 + ATNQ55GMLT6
12.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 13.50
Rated(T1)
Btu/h 46,000
kW 11.45
Rated(T3)
Btu/h 39,000
Cooling Capacity
kW 10.40
Sensible Heat
Btu/h 35,510
kW 4.11~15.24
Min ~ Max
Btu/h 14,000~52,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 3.71
Power Input(Cooling) Rated, T3 kW 4.49
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 16.3
Rated, T3 A 19.7
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 5.20
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C
147
Single Universal Product Data
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
148
Single Universal Product Data
149
Single Universal Product Data
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
150
Single Universal Product Data
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the BECON PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
151
Single Universal Product Data
12.4 Dimensions
12.4.1 Product
Gravity point
159
541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A
152
Single Universal Product Data
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
153
Single Universal Product Data
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
154
Single Universal Product Data
155
Single Universal Product Data
20 7.92 7.01 1.51 10.31 8.36 1.90 12.12 9.72 2.20 13.50 10.40 2.41 13.96 10.33 2.43 14.88 10.20 2.48 15.93 10.07 2.50
25 7.92 7.01 1.78 10.31 8.36 2.24 12.12 9.72 2.59 13.50 10.40 2.84 13.96 10.33 2.87 14.88 10.20 2.93 15.93 10.07 2.95
32 7.92 7.01 2.16 10.31 8.36 2.71 12.12 9.72 3.15 13.50 10.40 3.45 13.96 10.33 3.48 14.88 10.20 3.55 15.93 10.07 3.57
35 7.92 7.01 2.33 10.31 8.36 2.92 12.12 9.72 3.38 13.50 10.40 3.71 13.96 10.33 3.75 14.88 10.20 3.82 15.93 10.07 3.84
40 7.92 7.01 2.49 10.31 8.36 3.12 12.12 9.72 3.61 13.50 10.40 3.97 13.96 10.33 4.01 14.88 10.20 4.08 15.93 10.07 4.11
43 7.92 7.01 2.58 10.31 8.36 3.24 12.12 9.72 3.75 13.50 10.40 4.12 13.96 10.33 4.16 14.88 10.20 4.24 15.93 10.07 4.27
46 7.92 7.01 2.68 10.31 8.36 3.37 11.22 9.06 3.90 11.45 8.91 4.49 11.84 8.85 4.54 12.62 8.72 4.63 13.51 8.60 4.65
48 7.92 7.01 2.78 10.31 8.36 3.50 10.90 8.79 4.05 11.12 8.72 4.30 11.43 8.60 4.34 12.05 8.37 4.43 12.76 8.16 4.46
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
156
Single Universal Product Data
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
157
Single Universal Product Data
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
158
Single Universal Product Data
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
159
Single Universal Product Data
ABNQ60GM3T6
+
AUUQ60GT6
13.
13. AUUQ60GT6 + ABNQ60GM3T6
13.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 220-230-240, 1, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 187-276
Limit Range of Voltage(#2) V -
kW 15.25
Rated(T1)
Btu/h 52,000
kW 13.05
Rated(T3)
Btu/h 44,600
Cooling Capacity
kW 12.81
Sensible Heat
Btu/h 43,740
kW 5.62~15.80
Min ~ Max
Btu/h 19,200~54,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 4.19
Power Input(Cooling) Rated, T3 kW 5.12
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 29
Running Current(Cooling) Rated, T1 A 18.4
Rated, T3 A 22.5
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 29
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.00
Type - R410A
Precharged Amount kg 3.800
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.933
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6 X 3C
160
Single Universal Product Data
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
161
Single Universal Product Data
162
Single Universal Product Data
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
163
Single Universal Product Data
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
164
Single Universal Product Data
13.4 Dimensions
13.4.1 Product
Gravity point
159
541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A
165
Single Universal Product Data
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
166
Single Universal Product Data
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
167
Single Universal Product Data
168
Single Universal Product Data
20 8.95 8.63 1.71 11.65 10.30 2.14 13.69 11.97 2.48 15.25 12.81 2.72 15.77 12.73 2.75 16.81 12.57 2.80 17.99 12.41 2.82
25 8.95 8.63 2.01 11.65 10.30 2.53 13.69 11.97 2.93 15.25 12.81 3.21 15.77 12.73 3.24 16.81 12.57 3.31 17.99 12.41 3.33
32 8.95 8.63 2.44 11.65 10.30 3.07 13.69 11.97 3.55 15.25 12.81 3.90 15.77 12.73 3.94 16.81 12.57 4.01 17.99 12.41 4.04
35 8.95 8.63 2.63 11.65 10.30 3.30 13.69 11.97 3.82 15.25 12.81 4.19 15.77 12.73 4.23 16.81 12.57 4.32 17.99 12.41 4.34
40 8.95 8.63 2.87 11.65 10.30 3.60 13.69 11.97 4.17 15.25 12.81 4.58 15.77 12.73 4.63 16.81 12.57 4.72 17.99 12.41 4.74
43 8.95 8.63 3.02 11.65 10.30 3.79 13.69 11.97 4.39 14.70 12.48 4.81 15.20 12.39 4.86 16.20 12.21 4.96 17.34 12.04 4.99
46 8.95 8.63 3.17 11.65 10.30 3.98 12.79 11.26 4.61 13.05 11.20 5.12 13.49 11.11 5.17 14.38 10.93 5.27 15.40 10.76 5.30
48 8.95 8.63 3.33 11.65 10.30 4.18 12.02 10.58 4.82 12.27 10.61 4.92 12.62 10.47 4.97 13.31 10.18 5.07 14.12 9.91 5.10
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
169
Single Universal Product Data
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
170
Single Universal Product Data
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
171
Single Universal Product Data
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
172
Single Universal Product Data
ABNQ60LM3T6
+
AUUQ60LT6
14.
14. AUUQ60LT6 + ABNQ60LM3T6
14.1 Specifications
Category
Unit Value
Major Minor
Combinational Specification
#1 - 380-400-415, 3, 50/60
#2 - -
Power Supply
Limit Range of Voltage(#1) V 342-456
Limit Range of Voltage(#2) V -
kW 15.25
Rated(T1)
Btu/h 52,000
kW 13.40
Rated(T3)
Btu/h 45,800
Cooling Capacity
kW 12.81
Sensible Heat
Btu/h 43,740
kW 6.33~16.70
Min ~ Max
Btu/h 21,600~58,000
kW -
Rated(H1)
Btu/h -
Heating Capacity
kW -~-
Min ~ Max
Btu/h -~-
Rated, T1 kW 4.19
Power Input(Cooling) Rated, T3 kW 5.26
Min ~ Max kW -~-
Rated, H1 kW -
Power Input(Heating)
Min ~ Max kW -~-
EER (Btu/h)/W 12.40
Efficiency EER(T3) (Btu/h)/W 8.70
COP(H1) W/W -
Max A 10
Running Current(Cooling) Rated, T1 A 6.5
Rated, T3 A 8.1
Max A -
Running Current(Heating)
Rated, H1 A -
Running Current Maximum Running Current A 10
Power Factor(Cooling/Heating) Rated - 0.99/-
Dehumidification Rate - ℓ/h 4.00
Type - R410A
Precharged Amount kg 3.400
Additional Charging amount g/m 40
Refrigerant
GWP(Global Warming Potential) - 2,087.5
t-CO₂ eq. - 7.098
Chargeless-Pipe Length m 7.5
Liquid mm(inch) Φ9.52 (3/8)
Connecting Pipe
Gas mm(inch) Φ19.05 (3/4)
Piping Length IDU - ODU(Rated / Max / Min) m 5/50/5
Maximum Height Difference IDU - ODU(Max) m 30
Sound Pressure Level(Outdoor Unit) Cooling / Heating (@ 1.5m height) dB(A) 55.0 / -
Measurement Standard (Pressure Leve
- - ISO 3745
l)
Sound Power Level(Outdoor Unit) Cooling / Heating dB(A) -
Measurement Standard (Power Level) - - -
Connecting Cable Power Supply Cable(H07RN-F) mm² × cores 6.0 X 3C
173
Single Universal Product Data
Note
■ Due to our policy of innovation some specifications may be changed without notification.
■ Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■ Power factor could vary less than ±1% according to the operating conditions.
■ Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
■ This product contains Fluorinated greenhouse gases.
174
Single Universal Product Data
175
Single Universal Product Data
Note
■ O : Applied, X : Not applied
- Accessory : Ordered and purchased separately the accessory package referring to the model name provided and install at field.
- Accessory line-ups varies by region, so check your local catalogue or local sales material.
176
Single Universal Product Data
Note
■ O: Possible, X: Impossible, - : Unconfirmed or irrelevant
■ AC Manager requires ACP or AC Smart.
■ Compatibility of individual controller(wireless/wired remote controller) could be found with function list on Indoor Unit’s PDB.
■ If you need more detail, please refer to the Control(BECON) PDB or the manual of product.
(http://partner.lge.com/global : Home> Doc.Library> Product > Control(BECON)).
■ Accessory line-ups varies by region, so check your local catalogue or local sales material.
177
Single Universal Product Data
14.4 Dimensions
14.4.1 Product
Gravity point
159
541
550
DWG No. : TBA36228001_rev01
Chassis code : U60A
178
Single Universal Product Data
To Re Re Re
Tf
Lt Rt Lt Bw Rt
Re
Front Front Front
Front
Front
Case 1 Case 1 Case 2 Case 1 Case 2
To ≥ 1,000(39-3/8) Re ≥ 100(3-15/16) Re ≥ 100(3-15/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Tf ≤ 500(19-11/16) Lt ≥ 100(3-15/16) Lt ≥ 150(5-29/32) Lt ≥ 1,000(39-3/8) Lt ≥ 1,000(39-3/8)
Case 2
Rt ≥ 100(3-15/16) Rt ≥ 150(5-29/32) Rt ≥ 200(7-7/8) Rt ≥ 200(7-7/8)
Re ≥ 300(11-13/16) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Obstacle on the Discharge side ※ For Rear Piping / External SVC Valve type / Side-CBOX type
: Re,Lt ≥ 300(11-13/16) and Rt,Bw,Rb ≥ 600(23-5/8) for ALL CASE.
To Bw
Front Front Tr
Front Front Front
Ft Ft
Ft Ft
Re Re
H
Front
Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) * Ft ≥ 1,000(39-3/8) Ft ≥ 1,250(49-7/32)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
To ≥ 1,000(39-3/8) Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
Tf ≤ 500(19-11/16) * If Ls ≤ H/2,
Ft ≥ 750(29-17/32)
Ld ≤ H
To Case 1 Case 2 Case 1 Case 2
Tf Ft ≥ 500(19-11/16) Ft ≥ 1,000(39-3/8) Ft ≥ 1,500(59-1/16) Ft ≥ 1,500(59-1/16)
Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16) Re ≥ 300(11-13/16)
Ft Ft
Ls
Re Re Bw ≥ 100(3-15/16) Bw ≥ 100(3-15/16)
H
Ld
Collective/Continuous Installation Ft Rb Fb Re
1 Column
(Multiple Columns) Ft ≥ 1,000(39-3/8)
Rb ≥ 200(7-7/8)
Front Front Front Fb ≥ 2,000(78-3/4)
Front Front Front Re ≥ 100(3-15/16)
Ft Rb Fb Re
Ft Rb Fb Re
Ls
Multiple Columns
H
Ft ≥ 1,500(59-1/16)
Front Bw Front Front
Rb ≥ 600(23-5/8)
※ In case of Multiple columns/continuous installation, Fb ≥ 3,000(118-1/8)
Ls should be lower than H. Re ≥ 300(11-13/16)
Bw ≥ 100(3-15/16)
Note
■ If there is a concern about product performance degradation due to group installation or interference with obstacles, secure an additional separation distance.
■ Secure enough space for smooth service and maintenance.
■ According to product type, model line up, sales region..etc, applicability of each chassis could be different.
179
Single Universal Product Data
Condensing
Temperature
Thermistor
Flare Connection M
Electronic
Expansion Strainer
Valve
Flare Connection
Discharge
Temperature
Thermistor
Accumulator Inverter
Compressor
180
Single Universal Product Data
181
Single Universal Product Data
20 8.95 8.63 1.71 11.65 10.30 2.15 13.69 11.97 2.49 15.25 12.81 2.73 15.77 12.73 2.76 16.81 12.57 2.81 17.99 12.41 2.83
25 8.95 8.63 2.02 11.65 10.30 2.53 13.69 11.97 2.93 15.25 12.81 3.22 15.77 12.73 3.25 16.81 12.57 3.32 17.99 12.41 3.33
32 8.95 8.63 2.45 11.65 10.30 3.07 13.69 11.97 3.56 15.25 12.81 3.91 15.77 12.73 3.95 16.81 12.57 4.02 17.99 12.41 4.05
35 8.95 8.63 2.63 11.65 10.30 3.30 13.69 11.97 3.83 15.25 12.81 4.20 15.77 12.73 4.24 16.81 12.57 4.33 17.99 12.41 4.35
40 8.95 8.63 2.88 11.65 10.30 3.61 13.69 11.97 4.18 15.25 12.81 4.59 15.77 12.73 4.64 16.81 12.57 4.73 17.99 12.41 4.76
43 8.95 8.63 3.02 11.65 10.30 3.80 13.69 11.97 4.40 14.79 12.55 4.82 15.29 12.46 4.87 16.30 12.29 4.97 17.45 12.11 5.00
46 8.95 8.63 3.18 11.65 10.30 3.99 13.13 11.56 4.62 13.40 11.50 5.26 13.86 11.41 5.31 14.77 11.22 5.42 15.81 11.04 5.45
48 8.95 8.63 3.34 11.65 10.30 4.19 12.28 10.81 4.86 12.53 10.83 5.03 12.89 10.69 5.08 13.60 10.40 5.18 14.43 10.13 5.21
Note
■ DB : Dry bulb temperature(℃), WB : Wet bulb temperature(℃)
■ TC : Total Capacity(kW), SHC : Sensible Heat Capacity(kW)
■ PI : Power Input (kW, Compressor + indoor fan motor + outdoor fan motor)
■ All capacities are net. A deduction of capacity due to operating heat of indoor unit motor is reflected.
■ Direct interpolation is permissible. Do not extrapolate.
■ Rated capacities and power inputs are based on standard temperature and piping conditions, and it can be found on specifications table.
Except for rated value, the performance is not guaranteed.
■ In accordance with the test standard(or nations), the rating will vary slightly.
182
Single Universal Product Data
Note
In Order to estimate the actual system capacity, the influence of various installation conditions should be reflected.
Reflect the capacity correction factor effect of piping installation as below.
■ Qodu [from specification table] : Outdoor unit standard capacity.
■ Q(Ti, To) [from capacity table] : Outdoor unit capacity at Ti, To temperature.
■ F(Ti, To) = Q(Ti, To) / Qodu. : Outdoor unit capacity correction factor
■ Fpiping for piping length [from capacity correction factor table] : Piping correction factor
■ Indoor unit actual capacity : Qactual = Qodu x F(Ti, To) x Fpiping
183
Single Universal Product Data
45
40
35
Outdoor Temperature [℃ DB]
30
25
Continuous
20 Operation
15
10
-5
-10
-15
-20
-20 10 12 15 20 23 25 28
Indoor Temperature [℃ WB]
184
Single Universal Product Data
Cooling
70
Octave Band Sound Pressure Level (0dB = 20μPa)
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
NC-20
Hearing
Threshold
NC-15
10
63 125 250 500 1000 2000 4000 8000
Octave Band Center Frequency (Hz)
Note
■ Data is valid at diffuse field condition.
■ Data is valid at nominal operating condition.
■ Reference accoustic pressure 0dB = 20μPa.
■ Refer to the model specifications for nominal conditions. (Power source and Ambient temperature, etc)
■ Sound levels can be increased in accordance with installation and operating conditions.
(Operating conditions include some functional condition like Static pressure mode, air guide use, Room target temperature setting, etc and these functions
are different in accordance with each model.)
■ Sound level will vary depending on a range of factors such as the construction(acoustic absorption coefficient) of particular room in which the equipment
in installed.
■ Sound pressure level is measured on the rated condition in the anechoic rooms by ISO 3745 standard.
Therefore, these values can be increased owing to ambient conditions during operation.
185
SINGLE
CAUTION
• The wall thickness of the piping should comply with the relevant local and national regulations for the designed
pressure 3.8MPa
• Since R410A is a mixed refrigerant, the required additional refrigerant must be charged in its liquid state.
If the refrigerant is charged in its gaseous state, its composition changes and the system will not work properly.
• Do not place the refrigerant container under the direct rays of the sun to prevent it from exploding.
• For high-pressure refrigerant, any unapproved pipe must not be used.
• Do not heat pipes more than necessary to prevent them from softening.
• Be careful not to install wrongly to minimize economic loss because it is expensive in comparison with R22.
2
SINGLE Installation of Outdoor Units
2. Calculate the volume of the room where indoor unit is installed as single room or the smallest room.
With partition but opened which With partition and without opening
Without partition serve passage of air to adjoining which serve as passage of air to
room adjoining room
3
SINGLE Installation of Outdoor Units
Indoor unit
CAUTION
Pay a special attention to the place, such as a basement, etc. where refrigerant can stay, since refrigerant
is heavier than air.
4
SINGLE Installation of Outdoor Units
5
SINGLE Installation of Outdoor Units
Unit : mm
re
mo
a
c
or h)
m in c
0m
≥75
10 15/16
(3-
≥75
≥ 200
≥ 200
≥ 100
b
re
mo
or h)
m in c
0m
10 15/16
(3-
re
mo c
or h)
m inc
0m
10 15/16
(3-
re d
mo e
or h)
m inc
0m f
10 15/16
(3- Pallet(Wood Support)
- Remove before Installation
• Install where it can sufficiently support the weight of the outdoor unit.
If the support strength is not enough, the outdoor unit may drop and hurt people.
• Install where the outdoor unit may not fall in strong wind or earthquake.
If there is a fault in the supporting conditions, the outdoor unit may fall and hurt people.
• Please take extra cautions on the supporting strength of the ground, water outlet treatment(treatment of the
water flowing out of the outdoor unit in operation), and the passages of the pipe and wiring, when making the
ground support.
• Do not use tube or pipe for water outlet in the Base pan. Use drainage instead for water outlet. The tube or pipe
may freeze and the water may not be drained.
• Install at places where it can endure the weight and vibration/noise of the outdoor unit.
• The outdoor unit supports at the bottom shall have width of at least 100mm under the Unit’s legs before being
fixed.
• The outdoor unit supports should have minimum height of 200mm.
• Anchor bolts must be inserted at least 75mm.
• Fix the unit tightly with bolts as shown so that unit will not fall down due to earthquake or gust.
a. The corner part must be fixed firmly. Otherwise, the support for the installation may be bent.
b. Get and use M10 Anchor bolt.
c. Noise and vibration may occur from the floor or wall since vibration is transferred through the
installation part depending on installation status. Thus, use anti-vibration materials (cushion pad)
fully.(The base pad shall be more than 200mm)
d. Space for pipes and wiring (Pipes and wiring for bottom side)
e. Use the H-beam support as a base support
f. Concrete support
• Be sure to remove the Pallet (Wood Support) of the bottom of the outdoor unit before fixing the bolt or welding.
It may cause the unstable state of the outdoor settlement, and may cause freezing of the heat exchanger
resulting in abnormal operations, hazard of fire during welding.
6
SINGLE Installation of Outdoor Units
Indoor Unit
L
Outdoor Unit
H
Outdoor Unit
H
Indoor Unit
7
SINGLE Installation of Outdoor Units
5. Electrical Wiring
■ General Instruction
Outdoor Unit Outdoor Unit
Indoor Indoor
Unit Unit Indoor Indoor
Unit Unit
Remote Remote
control control Remote Remote
control control
Outdoor Unit
Indoor
door Indoor
Unit Unit
Outdoor Unit Indoor Indoor
Unit Unit
Remote Remote
control control
Remote Remote
control control
R
Remote Remote
ccontrol control Remote Remote
control control
Outdoor Unit oor
Indoor Indoor
Unit
nit Unit
Outdoor Unit Indoor
Unit
Remote Remote
control control
Remote
control
Outdoor Unit Indoor
Unit Outdoor Unit Indoor
or
Unitt
Remote
control
Remote
control
Outdoor Unit Indoor
Unit
Remote
control ※ This figure is representative. Actual appearance of outdoor unit may be different
by product type, but schematic diagram will stay the same.
• Follow ordinance of local regulation for technical standard related to electrical equipment, wiring regulations and
guidance of each electric power company.
• Be sure to provide designated grounding work to installed unit.
• Give some allowance to wiring for electrical part box of units, because the box is sometimes removed at the time
of service work.
• Only the communication line specified should be connected to the terminal block for unit communication.
WARNING
• Be sure to have authorized electrical engineers do the electric work using special circuits in accordance with
regulations and installation manual. If power supply circuit has a lack of capacity or electric work deficiency, it
may cause an electric shock or fire.
• Be sure to connect the installed unit to earth. Do not connect earth line to any gas pipe, liquid pipe, lightening
rod or telephone earth line. If earth is incomplete, it may cause an electric shock
CAUTION
• Product which use 3-phase power source have reversed phase protection detector that only works when the
power is turned on. If there exists black out or the power goes on and off which the product is operating, attach
8
SINGLE Installation of Outdoor Units
5. Electrical Wiring
a reversed phase protection circuit locally. Running the product in reversed phase may break the compressor
and other parts.
• Install the communication line away from the power source wiring so that it is not affected by electric noise from
the power source. (Do not run it through the same conduit.) Never use them together with power cables.
• Never use multi-core cable. If communication lines of different systems are wired with the same multiplecore
cable, the resultant poor transmitting and receiving will cause erroneous operations.
• The conductive shielding layer of cable should be grounded to the metal part of both units.
• As this unit is equipped with an inverter, to install a phase leading capacitor not only will deteriorate power factor
improvement effect, but also may cause capacitor abnormal heating. Therefore, never install a phase leading
capacitor.
• Make sure that the power unbalance ratio is not greater than 2%. If it is greater, the unit’s lifespan will be
reduced.
• Never connect the main power source to terminal block of communication line. If connected, electrical parts will
be burnt out.
• Introducing with a missing “N” phase or with a mistaken “N” phase will break the equipment.
When the power supply is applied to “N” phase by mistake, replace inverter PCB and transformer in control box.
9
SINGLE Installation of Outdoor Units
5. Electrical Wiring
– The figures are based on assumed length of parallel cabling up to 100m. For length in excess of 100m the
figures will have to be recalculated in direct proportion to the additional length of line involved.
– If the power supply waveform continues to exhibit some distortion the recommended spacing in the table
should be increased.
» If the lines are laid inside conduits then the following point must also be taken into account when grouping
various lines together for introduction into the conduits
» Power lines(including power supply to air conditioner) and signal lines must not be laid inside the same
» In the same way, when grouping the lines power and signal lines should not be bunched together.
CAUTION
• If apparatus is not properly earthed then there is always a risk of electric shock, the grounding of the apparatus
must be carried out by a qualified person.
10
SINGLE Installation of Outdoor Units
6. Field Wiring
■ Wiring of Main Power Supply
• Bear in mind ambient conditions (ambient temperature,direct sunlight, rain liquid,etc.) when proceeding with the
wiring and connections
• The wire size is the minimum value for metal conduit wiring. The power cord size should be 1 rank thicker taking
into account the line voltage drops. Make sure the power-supply voltage does not drop more than 10%.
• Specific wiring requirements should adhere to the wiring regulations of the region.
• Power supply cords of parts of appliances for outdoor use should not be lighter than polychloroprene sheathed
flexible cord (design 60245 IEC57).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the power
supply.
WARNING
• Make sure to use specified wires for connections so that no external force is imparted to terminal connections.
If connections are not fixed firmly, it may cause heating or fire.
• Make sure to use the appropriate type of overcurrent protection switch. Note that generated overcurrent may
include some amount of direct current.
• All Installation site must require attachment of an earth leakage breaker. If no earth leakage breaker is installed,
it may cause an electric shock.
• Do not use anything other than breaker and fuse with correct capacity. Using fuse and wire or copper wire with
too large capacity may cause a malfunction of unit or fire.
Outdoor
Power Supply **
(Main Switch)
R S T N R S T L N
Switch Switch Switch
Fuse
Fuse Fuse
to Indoor Unit
**
Power Supply
T/B T/B
: Power Line
: Communication Line
Indoor Unit
Communication Line
11
SINGLE Installation of Outdoor Units
Windbreak
※ This figure is representative. Actual appearance of outdoor unit may be different by product type.
• If the outdoor unit is to be installed close to the seaside, direct exposure to the sea wind should be avoided.
Install the outdoor unit on the opposite side of the sea wind direction.
• It should be strong enough like concrete to prevent the sea wind from the sea.
• The height and width should be more than 150% of the outdoor unit.
• It should be kept more than 70 cm of space between outdoor unit and the windbreak for easy air flow.
• In case, to install the outdoor unit on the seaside, set up a windbreak not to be exposed to the sea wind.
• Select a well-drained place.
• Periodic ( more than once/year ) cleaning of the dust or salt particles stuck on the heat exchanger by using water.
12
Air Solution
LG Electronics Inc, 128, Yeoui-daero,
Yeongdeungpo-gu, Seoul, Korea
(07336)
http://partner.lge.com
http://sedc.lge.com
The air conditioners manufactured by LG have received ISO9001 certificate for quality assurance
and ISO14001 certificate for environmental management system.
The specifications, designs, and information in this brochure are subject to change without notice.