N4 AMCS
Base Software Package
Release Notes
printed in Germany
© 2018 NORIS Automation GmbH
This publication including any and all of its parts is copyrighted. Any exploitation or utilization of the text shall require prior
written approval by NORIS Automation GmbH. This provision applies in particular to the reproduction, distribution, editing,
translation, storage and / or processing of the material in electronic systems, including data bases and online services.
Changes reserved.
NORIMOS 4 AMCS NAR-PD-0139-102-en
2.0.1.a-001 - 04/05/18
Base Software Package page 2 / 117
Release Notes
Document
[NAR-PD-0139-102-en_N4_AMCS_BaseSoftwarePackage_ReleaseNotes_020000g.docx]
Revision Overview
Version Doc. Date Author Changes
1.1.0a 001 05.10.2016 Asc/Mre Initial document for N4 IAMCS Base Software 1.1.0.a
1.1.0a 002 05.10.2016 Mre rev. PC image, build date, comments
1.1.0a 003 10.10.2016 Mre rev. Visu Version
1.1.0a 004 01.11.2016 Mre final Visu version corr.
1.1.0a 005 02.11.2016 Mre add. Information about task control file
1.1.0b 001 15.11.2016 Mre rev. Trend module
1.1.0c 001 02.12.2016 Mre rev. PLC AES lib, bug fixes in PC Trend module
1.1.0.c 002 08.12.2016 Mre rev. acc. Bug fixes counting duty stations
1.1.0d 001 02.12.2016 Mre rev. AES duty handling an time setting at AES
1.1.0d 002 08.12.2016 Mre rev. changelog entries
1.1.0e 001 09.12.2016 Mre bug fixes in Trend library; NMEA Protocol VBW; Cfg. File
1.1.1.a 001 30.12.2016 Mre bug fixes ALA.lib, VMP70; new alarming bridge
1.1.1.b 001 24.04.2017 Mre New ALA.lib, new COMxs integration, rev. Visu
1.1.1.c 001 04.05.2017 Mre New ALA.lib
1.1.1.c 002 15.05.2017 Mre Rev. Notes
1.1.2.a 001 30.02.2017 Mre new Visu base w. rev. menu, twin-VMP
1.1.2.a 002 31.03.2017 Mre Corr. Ioeco FW, hint for CODESYS versions
1.1.2.b 001 19.04.2017 Mre Corr. In ALA lib for PLC
1.1.3.a 001 31.05.2017 Mre New PLC RTS and ALA Lib for now COMxs impl.
1.1.4.a 001 22.06.2017 Mre Rev. Visu Trend & Templates; New Visu Journaling
1.1.4.b 001 27.06.2017 Mre New Visu
1.1.4.c 001 04.07.2017 Mre Corr. in Visu Trend
1.1.4.d 001 24.07.2017 Mre Corr. in Visu
2.0.0pre 001 04.08.2017 Mre New Visu + Multi-VMP Support
2.0.0pre 002 09.08.2017 Mre Rev. Config macro, new AES lib, rev. Visu
2.0.0.pre 003 11.08.2017 Mre Rev. in PH_Tool, Config, PLC, Visu, Visu-Controls
2.0.0.pre 004 01.09.2017 Mre Rev. ALA_Lib, AES_Lib, Corr. Visu
2.0.0.pre 005 18.09.2017 Mre Rev. ALA_Lib, AES_Lib, Com_N4Com, Corr. Visu
2.0.0.pre 006 20.10.2017 Mre Rev. Visu
2.0.0.pre 007 10.11.2017 Mre Rev. Visu
2.0.0.pre 008 13.11.2017 MRe Rev. Config
2.0.0.pre 009 21.11.2017 Mre Rev. Visu
2.0.0.a 001 24.01.2018 Mre Final 2.0.0 release
2.0.0.a 002 26.01.2018 Mre Rev. Config; Rev. ALA lib for MB-Req.
2.0.0.b 001 13.02.2018 Mre Rev. PLC Pro template, ALA lib, Visu, AES, PH Tool
2.0.0.c 001 19.02.2018 Mre Rev. PH Tool, corr. in MODBUS (FC6)
2.0.0.d 001 08.03.2018 Mre Rev. Config “VisuCh”, Corr. Visu
2.0.0.e 001 17.03.2018 Mre Rev. ALA lib, Visu, Config
2.0.0.f 001 23.03.2018 Mre Rev. Config, Visu
2.0.0.g 001 12.04.2018 Mre Rev. PH_Tool, PLC Pro Template, Visu
2.0.1.a 001 04.05.2018 MRe Visu
Contents
Revision Overview ............................................................................................................................... 2
Contents ................................................................................................................................................. 3
1 Type of Product ............................................................................................................................. 6
2 Revision 2.0.1.a ............................................................................................................................ 6
2.1 Information ............................................................................................................................. 6
2.2 System Requirements .......................................................................................................... 7
2.3 Components............................................................................................................................ 7
3 Revision 2.0.0.g ............................................................................................................................ 9
3.1 Information ............................................................................................................................. 9
3.2 System Requirements ........................................................................................................ 10
3.3 Components.......................................................................................................................... 10
4 Revision 2.0.0.f ........................................................................................................................... 12
4.1 Information ........................................................................................................................... 12
4.2 System Requirements ........................................................................................................ 13
4.3 Components.......................................................................................................................... 13
5 Revision 2.0.0.e .......................................................................................................................... 15
5.1 Information ........................................................................................................................... 15
5.2 System Requirements ........................................................................................................ 16
5.3 Components.......................................................................................................................... 16
6 Revision 2.0.0.d .......................................................................................................................... 18
6.1 Information ........................................................................................................................... 18
6.2 System Requirements ........................................................................................................ 19
6.3 Components.......................................................................................................................... 19
7 Revision 2.0.0.c .......................................................................................................................... 21
7.1 Information ........................................................................................................................... 21
7.2 System Requirements ........................................................................................................ 22
7.3 Components.......................................................................................................................... 22
8 Revision 2.0.0.b .......................................................................................................................... 24
8.1 Information ........................................................................................................................... 24
8.2 System Requirements ........................................................................................................ 25
8.3 Components.......................................................................................................................... 25
9 Revision 2.0.0.a .......................................................................................................................... 27
9.1 Information ........................................................................................................................... 27
9.2 System Requirements ........................................................................................................ 28
9.3 Components.......................................................................................................................... 28
10 Revision 2.0.0.pre -009 ......................................................................................................... 31
10.1 Information ..................................................................................................................... 31
10.2 System Requirements ................................................................................................... 32
10.3 Components .................................................................................................................... 32
11 Revision 2.0.0.pre -008 ......................................................................................................... 34
11.1 Information ..................................................................................................................... 34
11.2 System Requirements ................................................................................................... 35
11.3 Components .................................................................................................................... 35
12 Revision 2.0.0.pre -007 ......................................................................................................... 37
12.1 Information ..................................................................................................................... 37
12.2 System Requirements ................................................................................................... 38
12.3 Components .................................................................................................................... 38
13 Revision 2.0.0.pre -006 ......................................................................................................... 40
13.1 Information ..................................................................................................................... 40
13.2 System Requirements ................................................................................................... 41
1 Type of Product
Field Device / Signal Processing Device
Software application for display and monitoring
Project specific software application
2 Revision 2.0.1.a
2.1 Information
Scope of revision
Product software package 2.0.1.a
Release Date 2018-05-04
Test Date 2018-05-04
Build Date 2018-05-04
Requested by NAR R&D Division
Global Enhancements
Notes
Store the archive extract files in your project folder, if asked by CODESYS during open visualization
archive. PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
Visu does not work on PLC runtime, running on intel Atom driven machines!
For updating an existing project, the files “CODESYSControl.cfg” and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration worksheet “group assign.”), because it will be enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assign.” has to be set to a
value > as for entry “BusTout” in worksheet “Modbus” normally: “timeout” = “BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.53
N4 CPU RTS V120a
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP12 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.10
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
UltraVnc 1.2.1.6
2.3 Components
N4 CPU Files
PLC.pro V1.5.0.e
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.e
N4_ALA.lib V1.3.2.f
N4_kBus.lib V1.2.1.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.1.1.c
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.1.0.9 Bug Fixes
NAR_NoriVis_Communication
NAR_NoriVis_CSV_Handling
NAR_NoriVis_Data_Source
NAR_NoriVis_DataManager
NAR_NoriVis_Interfaces
NAR_NoriVis_Journal
NAR_NoriVis_Lists
NAR_NoriVis_Menu
NAR_NoriVis_Mimic_Templates
NAR_NoriVis_Performance_Monitor
NAR_NoriVis_Symbol
NAR_NoriVis_System
NAR_NoriVis_Toolbox
NAR_NoriVis_Trend
NAR_NoriVis_Update
VMP Visu
NORIVIS_VMP-AES V2.0.1.2
N4 Config
Version 2.0.12
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.1
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.2
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.2
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.3.1.3
3 Revision 2.0.0.g
3.1 Information
Scope of revision
Product software package 2.0.0.g
Release Date 2018-04-12
Test Date 2018-04-12
Build Date 2018-04-12
Requested by NAR R&D Division
Global Enhancements
Visu : User def. message indication option at logo area
PLC : Rev. TankControl_2 with calc. of fpCalc_h without gravity constants in uiMode_hp = 1
and accepting density in kg/m³; New connection routine Control_1_Connection_3
PH-Tool: ZIP files in Release folder enforces long delay times for creating new releases
Docs : AA55 and AA57 lists old versions of CODESYS and outdated PCs
Notes
Store the archive extract files in your project folder, if asked by CODESYS during open visualization
archive. PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files “CODESYSControl.cfg” and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration worksheet “group assign.”), because it will be enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assign.” has to be set to a
value > as for entry “BusTout” in worksheet “Modbus” normally: “timeout” = “BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.53
N4 CPU RTS V120a
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP12 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.10
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
UltraVnc 1.2.1.6
3.3 Components
N4 CPU Files
PLC.pro V1.5.0.e New control_1_connection_3
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.e
N4_ALA.lib V1.3.2.f
N4_kBus.lib V1.2.1.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.1.1.c Rev. TankControl_2
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.2.6 Redundancy; Bug fixes
NAR_NoriVis_Communication 2.0.1.9
NAR_NoriVis_CSV_Handling 2.0.1.9
NAR_NoriVis_Data_Source 2.0.1.7
NAR_NoriVis_DataManager 2.0.1.9
NAR_NoriVis_Interfaces 2.0.1.7
NAR_NoriVis_Journal 2.0.2.24
NAR_NoriVis_Lists 2.0.1.10
NAR_NoriVis_Menu 2.0.1.7
NAR_NoriVis_Mimic_Templates 3.0.1.5
NAR_NoriVis_Performance_Monitor 2.0.1.2
NAR_NoriVis_Symbol 1.0.1.2
NAR_NoriVis_System 2.0.1.8
NAR_NoriVis_Toolbox 2.0.0.27
NAR_NoriVis_Trend 2.1.0.32
NAR_NoriVis_Update 2.0.1.7
VMP Visu
NORIVIS_VMP-AES V2.0.1.2
N4 Config
Version 2.0.12
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.1
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.2
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.2
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.3.1.3 Excl. ZIP files in get-release
4 Revision 2.0.0.f
4.1 Information
Scope of revision
Product software package 2.0.0.f
Release Date 2018-03-23
Test Date 2018-03-23
Build Date 2018-03-23
Requested by NAR R&D Division
Global Enhancements
Visu : Last position in lists will be on hold if page is changed. Special template library
“NAR_NoriVis_Templates_SpecialDesign.compiled-library” now part of base release in
folder “NoriVis_Templates_Special”.
Implemented change requests: 55,56, 57, 91, 92, 94, 98, 105, 106
PLC : Revised reset timer settings for commands / buttons in control connection routines.
Notes
Store the archive extract files in your project folder, if asked by CODESYS during open visualization
archive. PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files “CODESYSControl.cfg” and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration worksheet “group assign.”), because it will be enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assign.” has to be set to a
value > as for entry “BusTout” in worksheet “Modbus” normally: “timeout” = “BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.53
N4 CPU RTS V120a
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP12 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.10
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
UltraVnc 1.2.1.6
4.3 Components
N4 CPU Files
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.e
N4_ALA.lib V1.3.2.f
N4_kBus.lib V1.2.1.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.1.1.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.2.5 Corr.
NAR_NoriVis_Communication 2.0.1.6
NAR_NoriVis_CSV_Handling 2.0.1.7
NAR_NoriVis_Data_Source 2.0.1.6
NAR_NoriVis_DataManager 2.0.1.7
NAR_NoriVis_Interfaces 2.0.1.6
NAR_NoriVis_Journal 2.0.2.23
NAR_NoriVis_Lists 2.0.1.9
NAR_NoriVis_Menu 2.0.1.6
NAR_NoriVis_Mimic_Templates 3.0.1.4
NAR_NoriVis_Performance_Monitor 2.0.1.2
NAR_NoriVis_Symbol 1.0.1.2
NAR_NoriVis_System 2.0.1.7
NAR_NoriVis_Toolbox 2.0.0.26
NAR_NoriVis_Trend 2.1.0.31
NAR_NoriVis_Update 2.0.1.6
VMP Visu
NORIVIS_VMP-AES V2.0.1.2
N4 Config
Version 2.0.12 Corr. comments
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.1
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.2
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.2
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.3.1.2
5 Revision 2.0.0.e
5.1 Information
Scope of revision
Product software package 2.0.0.e
Release Date 2018-03-17
Test Date 2018-03-17
Build Date 2018-03-17
Requested by NAR R&D Division
Global Enhancements
Config : Revised work sheet “VisuCh”.
PLC : change pulse to pulse with reset; reset output pulse on1 with on2 and off; reset output
pulse on2 with in1 and off; reset output pulse off with on1 and on2
Visu : Several Bug fixes (22, 54, 76, 79, 81, 83, 85, 87, 95, 96, 97, 99, 100, 101, 104).
Notes
Store the archive extract files in your project folder, if asked by CODESYS during open visualization
archive. PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files “CODESYSControl.cfg” and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration worksheet “group assign.”), because it will be enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assign.” has to be set to a
value > as for entry “BusTout” in worksheet “Modbus” normally: “timeout” = “BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.53
N4 CPU RTS V120a
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP12 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.10
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
UltraVnc 1.2.1.6
5.3 Components
N4 CPU Files
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.e
N4_ALA.lib V1.3.2.f Corr.
N4_kBus.lib V1.2.1.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.1.1.a Rev. control reset actions
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.2.4 Corr.
NAR_NoriVis_Communication 2.0.1.5
NAR_NoriVis_CSV_Handling 2.0.1.5
NAR_NoriVis_Data_Source 2.0.1.5
NAR_NoriVis_DataManager 2.0.1.5
NAR_NoriVis_Interfaces 2.0.1.5
NAR_NoriVis_Journal 2.0.2.21 New screenshot module; corr.
NAR_NoriVis_Lists 2.0.1.7
NAR_NoriVis_Menu 2.0.1.5
NAR_NoriVis_Mimic_Templates 3.0.1.3
NAR_NoriVis_Performance_Monitor 2.0.1.2
NAR_NoriVis_Symbol 1.0.1.2
NAR_NoriVis_System 2.0.1.5
NAR_NoriVis_Toolbox 2.0.0.24
VMP Visu
NORIVIS_VMP-AES V2.0.1.2
N4 Config
Version 2.0.11 Rev. VisuCh
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.1
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.2
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.2 Corr.
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.3.1.2
6 Revision 2.0.0.d
6.1 Information
Scope of revision
Product software package 2.0.0.d
Release Date 2018-03-08
Test Date 2018-03-08
Build Date 2018-03-08
Requested by NAR R&D Division
Global Enhancements
Config: Revised work sheet “VisuCh”.
Notes
Store the archive extract files in your project folder, if asked by CODESYS during open visualization
archive. PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files “CODESYSControl.cfg” and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration worksheet “group assign.”), because it will be enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assign.” has to be set to a
value > as for entry “BusTout” in worksheet “Modbus” normally: “timeout” = “BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.53
N4 CPU RTS V120a
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP12 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.10
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
UltraVnc 1.2.1.6
6.3 Components
N4 CPU Files
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.e
N4_ALA.lib V1.3.2.e
N4_kBus.lib V1.2.1.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.1.0.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.2.2 Bug fixes; New VisuCh.
NAR_NoriVis_Communication
NAR_NoriVis_CSV_Handling
NAR_NoriVis_Data_Source
NAR_NoriVis_DataManager
NAR_NoriVis_Interfaces
NAR_NoriVis_Journal
NAR_NoriVis_Lists
NAR_NoriVis_Menu
NAR_NoriVis_Mimic_Templates
NAR_NoriVis_Performance_Monitor
NAR_NoriVis_Symbol
NAR_NoriVis_System
NAR_NoriVis_Toolbox
NAR_NoriVis_Trend
NAR_NoriVis_Update
VMP Visu
NORIVIS_VMP-AES V2.0.1.2
N4 Config
Version 2.0.10 Rev. VisuCh
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.1
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.2
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.2 Rev. for better coloring sup.
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.3.1.2
7 Revision 2.0.0.c
7.1 Information
Scope of revision
Product software package 2.0.0.c
Release Date 2018-02-19
Test Date 2018-02-19
Build Date 2018-02-19
Requested by NAR R&D Division
Global Enhancements
PH-Tool: Configuration copy in export folder is not transferred to release and via FTP to device.
Notes
Store the archive extract files in your project folder, if asked by CODESYS during open visualization
archive. PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files “CODESYSControl.cfg” and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration worksheet “group assign.”), because it will be enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assign.” has to be set to a
value > as for entry “BusTout” in worksheet “Modbus” normally: “timeout” = “BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.53
N4 CPU RTS V120a
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP12 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.10
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
UltraVnc 1.2.1.6
7.3 Components
N4 CPU Files
Pro-Template v1.5.0.c Rev. error handling for
MODBUS/COMxs flags
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.e
N4_ALA.lib V1.3.2.e Corr. MODBUS FC06
N4_kBus.lib V1.2.1.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.1.0.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.2.1
NAR_NoriVis_Communication 2.0.1.2
NAR_NoriVis_CSV_Handling 2.0.1.2
NAR_NoriVis_Data_Source 2.0.1.3
NAR_NoriVis_DataManager 2.0.1.2
NAR_NoriVis_Interfaces 2.0.1.2
NAR_NoriVis_Journal 2.0.2.15
NAR_NoriVis_Lists 2.0.1.3
NAR_NoriVis_Menu 2.0.1.2
NAR_NoriVis_Mimic_Templates 3.0.1.2
NAR_NoriVis_Performance_Monitor 2.0.1.1
NAR_NoriVis_Symbol 1.0.1.2
NAR_NoriVis_System 2.0.1.2
NAR_NoriVis_Toolbox 2.0.0.16
NAR_NoriVis_Trend 2.1.0.23
NAR_NoriVis_Update 2.0.1.2
VMP Visu
NORIVIS_VMP-AES V2.0.1.2
N4 Config
Version 2.0.9
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.1
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.2
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.3.1.2 Corr. copy cfg. process
8 Revision 2.0.0.b
8.1 Information
Scope of revision
Product software package 2.0.0.b
Release Date 2018-02-14
Test Date 2018-02-13
Build Date 2018-02-13
Requested by NAR R&D Division
Global Enhancements
PLC: Revised example code in Dead-Man control with using wchannel variable for alarm channel.
Revised versioning of connection FBs for controls.
Visu: Incorrect CODESYS configuration files. Active debug mode enforces test data in trend.
Revised time zoom selection appearance.
Notes
Store the archive extract files in your project folder, if asked by CODESYS during open visualization
archive. PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files “CODESYSControl.cfg” and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration worksheet “group assign.”), because it will be enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assign.” has to be set to a
value > as for entry “BusTout” in worksheet “Modbus” normally: “timeout” = “BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.53
N4 CPU RTS V120a
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP12 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.10
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
UltraVnc 1.2.1.6
8.3 Components
N4 CPU Files
Pro-Template v1.5.0.b Corr. Dead-Man examples;
Rev. connection FBs for
controls
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.e
N4_ALA.lib V1.3.2.d Rev. UDP objects for int.com.
N4_kBus.lib V1.2.1.d Corr. duty key detect.
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.1.0.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.2.1 Disabled debug mode
NAR_NoriVis_Communication 2.0.1.2
NAR_NoriVis_CSV_Handling 2.0.1.2
NAR_NoriVis_Data_Source 2.0.1.3
NAR_NoriVis_DataManager 2.0.1.2
NAR_NoriVis_Interfaces 2.0.1.2
NAR_NoriVis_Journal 2.0.2.15 Corr.
NAR_NoriVis_Lists 2.0.1.3
NAR_NoriVis_Menu 2.0.1.2
NAR_NoriVis_Mimic_Templates 3.0.1.2
NAR_NoriVis_Performance_Monitor 2.0.1.1
NAR_NoriVis_Symbol 1.0.1.2
NAR_NoriVis_System 2.0.1.2
NAR_NoriVis_Toolbox 2.0.0.16 Corr.
NAR_NoriVis_Trend 2.1.0.23 Rev. time zoom; tooltips
NAR_NoriVis_Update 2.0.1.2
VMP Visu
NORIVIS_VMP-AES V2.0.1.2 Corr. duty key detect.
N4 Config
Version 2.0.9
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.1
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.2
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.3.1.1 Corr. Visu-Cfg Version check
9 Revision 2.0.0.a
9.1 Information
Scope of revision
Product software package 2.0.0.a
Release Date 2018-01-26
Test Date 2018-01-25
Build Date 2018-01-25
Requested by NAR R&D Division
Global Enhancements
Visu: Enhanced control template library with file browser and file open, revised gauge
template and indication channel text; integration of masking for non-alarm
channels in page alarm indicators.
PLC: Added MODBUS on-demand communication option; increased MODBUS requests to 750;
new readable NMEA data sets EVE, FIR, ALA; new Control_2 + TankCalc_2 in
NAR_Controls.lib; option for MODBUS frame end detection for temporary on-site
communication faults.
AES: New device VMP70-III; No-duty devices class; enforceable on-duty/off-duty, horn-off
(DSP), horn acknowledge (VMP) via User_PLC;
PH-Tool: User input option for selecting VMP70-I or III while creating release
AES: Indication of all alarms independent from configured base group for device.
PH-Tool: FTP transfer deletes NwMasterId file; processing failure if configuration folder
does not exist in devices base folders
Notes
Store the archive extract files in your project folder, if asked by CODESYS during open visualization
archive. PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files “CODESYSControl.cfg” and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration worksheet “group assign.”), because it will be enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assign.” has to be set >
entry “BusTout” in worksheet “Modbus” normally: “timeout” = “BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.53
N4 CPU RTS V120a
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP12 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.10
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
UltraVnc 1.2.1.6
9.3 Components
N4 CPU Files
Pro-Template v1.5.0.a Rev. for NAR_Control_2
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.e base group; horn output
N4_ALA.lib V1.3.2.c NMEA; MODBUS
N4_kBus.lib V1.2.1.c base group; horn output
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.1.0.a NAR_Control_2, TankCalc_2
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.2.0 Corr. base group handling
NAR_NoriVis_Communication 2.0.1.2 Add. AES protocol
NAR_NoriVis_CSV_Handling 2.0.1.2 Add changed files
NAR_NoriVis_Data_Source 2.0.1.3 Rev.
NAR_NoriVis_DataManager 2.0.1.2 Corr.
NAR_NoriVis_Interfaces 2.0.1.2 Rev.
NAR_NoriVis_Journal 2.0.1.15 Rev.
NAR_NoriVis_Lists 2.0.1.3
NAR_NoriVis_Menu 2.0.1.2 Corr. indicator ctrl.
NAR_NoriVis_Mimic_Templates 3.0.1.2 New templates; Corr.
NAR_NoriVis_Performance_Monitor 2.0.1.1
NAR_NoriVis_Symbol 1.0.1.2 Rev.
NAR_NoriVis_System 2.0.1.2 Rev.
NAR_NoriVis_Toolbox 2.0.0.15 Rev.
NAR_NoriVis_Trend 2.1.0.22 Corr. restart routine
NAR_NoriVis_Update 2.0.1.2 Rev.
VMP Visu
NORIVIS_VMP-AES V2.0.1.1 base group; horn output
N4 Config
Version 2.0.9 Corr. macro
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.1 Sel. of control channel
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.2 EVE, FIR, ALA
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2 Protocol type 19
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1
VisuGroups V1.0.0
Project Helper
ph.exe V1.3.1.0 Corr. FTP delete; VMP70-III
Global Enhancements
Visu: Revised restart routine of trend module.
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files "CODESYSControl.cfg" and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119f
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP11 Patch 3
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
10.3 Components
N4 CPU Files
Pro-Template v1.4.0.d
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.c
N4_ALA.lib V1.3.1.f
N4_kBus.lib V1.2.1.b
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.1.2 Disabled debug mode
NAR_NoriVis_Communication 2.0.1.1
NAR_NoriVis_CSV_Handling 2.0.1.1
NAR_NoriVis_Data_Source 2.0.1.2
NAR_NoriVis_DataManager 2.0.1.1
NAR_NoriVis_DialogHandler 0.0.0.7
NAR_NoriVis_Interfaces 2.0.1.1
NAR_NoriVis_Journal 2.0.1.13
NAR_NoriVis_Lists 2.0.1.2
NAR_NoriVis_Menu 2.0.1.1
NAR_NoriVis_Mimic_Templates 3.0.1.1
NAR_NoriVis_Performance_Monitor 2.0.1.1
NAR_NoriVis_Symbol 2.0.1.1
NAR_NoriVis_System 2.0.1.1
NAR_NoriVis_Toolbox 2.0.0.13
NAR_NoriVis_Trend 2.1.0.20 Corr. restart routine
NAR_NoriVis_Update 2.0.1.1
VMP Visu
NORIVIS_VMP-AES V2.0.1.c Corr. horn output calc.
N4 Config
Version 2.0.5 Corr. macro for pages
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.0
IOeco V1.0.0 deleted empty lines
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.2.0.3
Global Enhancements
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files "CODESYSControl.cfg" and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119f
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP11 Patch 3
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
11.3 Components
N4 CPU Files
Pro-Template v1.4.0.d
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.c
N4_ALA.lib V1.3.1.f
N4_kBus.lib V1.2.1.b
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.1.1
NAR_NoriVis_Communication 2.0.1.1
NAR_NoriVis_CSV_Handling 2.0.1.1
NAR_NoriVis_Data_Source 2.0.1.2
NAR_NoriVis_DataManager 2.0.1.1
NAR_NoriVis_DialogHandler 0.0.0.7
NAR_NoriVis_Interfaces 2.0.1.1
NAR_NoriVis_Journal 2.0.1.13
NAR_NoriVis_Lists 2.0.1.2
NAR_NoriVis_Menu 2.0.1.1
NAR_NoriVis_Mimic_Templates 3.0.1.1
NAR_NoriVis_Performance_Monitor 2.0.1.1
NAR_NoriVis_Symbol 2.0.1.1
NAR_NoriVis_System 2.0.1.1
NAR_NoriVis_Toolbox 2.0.0.13
NAR_NoriVis_Trend 2.1.0.19
NAR_NoriVis_Update 2.0.1.1
VMP Visu
NORIVIS_VMP-AES V2.0.1.c Corr. horn output calc.
N4 Config
Version 2.0.5 Corr. macro for pages
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.0
IOeco V1.0.0 deleted empty lines
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.2.0.3
Global Enhancements
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files "CODESYSControl.cfg" and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119f
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP11 Patch 3
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
12.3 Components
N4 CPU Files
Pro-Template v1.4.0.d
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.c
N4_ALA.lib V1.3.1.f
N4_kBus.lib V1.2.1.b
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE 2.0.1.1 All new
NAR_NoriVis_Communication 2.0.1.1
NAR_NoriVis_CSV_Handling 2.0.1.1
NAR_NoriVis_Data_Source 2.0.1.2
NAR_NoriVis_DataManager 2.0.1.1
NAR_NoriVis_DialogHandler 0.0.0.7
NAR_NoriVis_Interfaces 2.0.1.1
NAR_NoriVis_Journal 2.0.1.13
NAR_NoriVis_Lists 2.0.1.2
NAR_NoriVis_Menu 2.0.1.1
NAR_NoriVis_Mimic_Templates 3.0.1.1
NAR_NoriVis_Performance_Monitor 2.0.1.1
NAR_NoriVis_Symbol 2.0.1.1
NAR_NoriVis_System 2.0.1.1
NAR_NoriVis_Toolbox 2.0.0.13
NAR_NoriVis_Trend 2.1.0.19
NAR_NoriVis_Update 2.0.1.1
VMP Visu
NORIVIS_VMP-AES V2.0.1.c Corr. horn output calc.
N4 Config
Version 2.0.3
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.0
IOeco V1.0.0 deleted empty lines
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.2.0.3
Global Enhancements
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files "CODESYSControl.cfg" and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119f
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 4
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
13.3 Components
N4 CPU Files
Pro-Template v1.4.0.d
Com_N4Com.lib V1.1.0.b
EcM_EcoModul.lib V1.1.0.b
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.c
N4_ALA.lib V1.3.1.f
N4_kBus.lib V1.2.1.b
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V2.0.0.27 All new
NAR_NoriVis_Communication V1.0.0.1
NAR_NoriVis_CSV_Handling V1.0.0.1
NAR_NoriVis_Data_Source V1.0.0.2
NAR_NoriVis_DataManager V1.0.0.1
NAR_NoriVis_DialogHandler V0.0.0.6
NAR_NoriVis_Interfaces V1.0.0.2
NAR_NoriVis_Journal V2.0.2.11
NAR_NoriVis_Lists V1.0.0.1
NAR_NoriVis_Menu V1.0.0.1
NAR_NoriVis_Mimic_Templates V3.0.0.5
NAR_NoriVis_Performance_Monitor V1.0.0.1
NAR_NoriVis_Symbol V1.0.0.1
NAR_NoriVis_System V1.0.0.1
NAR_NoriVis_Toolbox V2.0.0.11
NAR_NoriVis_Trend V2.1.0.17 corrections
NAR_NoriVis_Update V1.0.0.1
VMP Visu
NORIVIS_VMP-AES V2.0.1.c Corr. horn output calc.
N4 Config
Version 2.0.3
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.0
IOeco V1.0.0 deleted empty lines
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1
PLC V1.0.4
visu V1.0.1
AES V1.0.0
serial V1.0.1
ComXS V1.0.2
MB TcpInterf V1.0.0
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1
VisuGroups V1.0.0
DSP V1.0.3
DSP FctGrp V1.0.1
SSP V1.0.1
SSP channel V1.0.1
SSP assign. V1.0.1
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.2.0.3
Global Enhancements
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files "CODESYSControl.cfg" and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119f
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 4
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
14.3 Components
N4 CPU Files
Pro-Template v1.4.0.d Rev. AES assignments
Com_N4Com.lib V1.1.0.b Internal changes
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.c Rev. printer cue del.; horn
N4_ALA.lib V1.3.1.f Corr.
N4_kBus.lib V1.2.1.b Corr.
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V2.0.0.25 All new
NAR_NoriVis_Communication V1.0.0.1
NAR_NoriVis_CSV_Handling V1.0.0.1
NAR_NoriVis_Data_Source V1.0.0.2
NAR_NoriVis_DataManager V1.0.0.1
NAR_NoriVis_DialogHandler V0.0.0.6
NAR_NoriVis_Interfaces V1.0.0.2
NAR_NoriVis_Journal V2.0.2.11
NAR_NoriVis_Lists V1.0.0.1
NAR_NoriVis_Menu V1.0.0.1
NAR_NoriVis_Mimic_Templates V3.0.0.5
NAR_NoriVis_Performance_Monitor V1.0.0.1
NAR_NoriVis_Symbol V1.0.0.1
NAR_NoriVis_System V1.0.0.1
NAR_NoriVis_Toolbox V2.0.0.10
NAR_NoriVis_Trend V2.1.0.16
NAR_NoriVis_Update V1.0.0.1
VMP Visu
NORIVIS_VMP-AES V2.0.1.b Multi-VMP, Support for 3
languages
N4 Config
Version 2.0.0
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0 Inteface type TCP
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1 New master definitions
PLC V1.0.4 Master assignment
visu V1.0.1 Master assignment
AES V1.0.0 Master assignment + kBus
+ Printer
serial V1.0.1 No RTS control
ComXS V1.0.2
MB TcpInterf V1.0.0 New MODBUS-TCP cfg.
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1 Support for 3 languages
VisuGroups V1.0.0
DSP V1.0.3 New duty master, AES ID
DSP FctGrp V1.0.1
SSP V1.0.1 New AES ID
SSP channel V1.0.1 New AES ID
SSP assign. V1.0.1 New AES ID
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.2.0.3 Rev. for cfg. and Multi-VMP
Global Enhancements
Visu: minor feature updates
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files "CODESYSControl.cfg" and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119f
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 4
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
15.3 Components
N4 CPU Files
Pro-Template v1.4.0.c Rev. AES assignments
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.b Rev. VMP detection
N4_ALA.lib V1.3.1.c Corr. in tasks
N4_kBus.lib V1.2.1.b Rev. AES user PLC interface
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V2.0.0.20 All new
NAR_NoriVis_Communication V1.0.0.1
NAR_NoriVis_CSV_Handling V1.0.0.1
NAR_NoriVis_Data_Source V1.0.0.2
NAR_NoriVis_DataManager V1.0.0.1
NAR_NoriVis_DialogHandler V0.0.0.6
NAR_NoriVis_Interfaces V1.0.0.0
NAR_NoriVis_Journal V2.0.2.8
NAR_NoriVis_Lists V1.0.0.1
NAR_NoriVis_Menu V1.0.0.1
NAR_NoriVis_Mimic_Templates V3.0.0.3
NAR_NoriVis_Performance_Monitor V1.0.0.1
NAR_NoriVis_Symbol V1.0.0.1
NAR_NoriVis_System V1.0.0.1
NAR_NoriVis_Toolbox V2.0.0.7
NAR_NoriVis_Trend V2.1.0.13
NAR_NoriVis_Update V1.0.0.1
VMP Visu
NORIVIS_VMP-AES V2.0.1 Multi-VMP, Support for 3
languages
N4 Config
Version 2.0.0
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0 Inteface type TCP
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1 New master definitions
PLC V1.0.4 Master assignment
visu V1.0.1 Master assignment
AES V1.0.0 Master assignment + kBus
+ Printer
serial V1.0.1 No RTS control
ComXS V1.0.2
MB TcpInterf V1.0.0 New MODBUS-TCP cfg.
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1 Support for 3 languages
VisuGroups V1.0.0
DSP V1.0.3 New duty master, AES ID
DSP FctGrp V1.0.1
SSP V1.0.1 New AES ID
SSP channel V1.0.1 New AES ID
SSP assign. V1.0.1 New AES ID
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.2.0.3 Rev. for cfg. and Multi-VMP
Global Enhancements
Visu: minor feature updates
PH-Tool: Incorrect PLC numbering while update process. FTP access failure for uploading images.
Missing NwMasterId.csv at PCs.
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the files "CODESYSControl.cfg" and “CoDeSysHMI.cfg” in the path
„C:\NoriVis4\PlcLogic“ at the project PC(s) has to be replaced with the new files!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119f
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 4
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
16.3 Components
N4 CPU Files
Pro-Template v1.4.0.b Rev. AES assignments
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.a Rev. AES user PLC interface
N4_ALA.lib V1.3.1.e Corr. in serial itf. (stop bits)
N4_kBus.lib V1.2.1.b Rev. AES user PLC interface
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V2.0.0.18 All new
NAR_NoriVis_Communication V1.0.0.0
NAR_NoriVis_CSV_Handling V1.0.0.0
NAR_NoriVis_Data_Source V1.0.0.0
NAR_NoriVis_DataManager V1.0.0.0
NAR_NoriVis_DialogHandler V0.0.0.6
NAR_NoriVis_Interfaces V1.0.0.0
NAR_NoriVis_Journal V2.0.2.5
NAR_NoriVis_Lists V1.0.0.0
NAR_NoriVis_Menu V1.0.0.0
NAR_NoriVis_Mimic_Templates V3.0.0.4
NAR_NoriVis_Performance_Monitor V1.0.0.0
NAR_NoriVis_Symbol V1.0.0.1
NAR_NoriVis_System V1.0.0.0
NAR_NoriVis_Toolbox V2.0.0.4
NAR_NoriVis_Trend V2.1.0.10
NAR_NoriVis_Update V1.0.0.0
VMP Visu
NORIVIS_VMP-AES V2.0.1 Multi-VMP, Support for 3
languages
N4 Config
Version 2.0.0
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0 Inteface type TCP
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1 New master definitions
PLC V1.0.4 Master assignment
visu V1.0.1 Master assignment
AES V1.0.0 Master assignment + kBus
+ Printer
serial V1.0.1 No RTS control
ComXS V1.0.2
MB TcpInterf V1.0.0 New MODBUS-TCP cfg.
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1 Support for 3 languages
VisuGroups V1.0.0
DSP V1.0.3 New duty master, AES ID
DSP FctGrp V1.0.1
SSP V1.0.1 New AES ID
SSP channel V1.0.1 New AES ID
SSP assign. V1.0.1 New AES ID
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.2.0.3 Rev. for cfg. and Multi-VMP
Global Enhancements
Visu: minor feature updates
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
PC-Images: 01=PLC Dongle Version, 02=HMI Dongle Version
For updating an existing project, the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ at the project PC(s) has to be replaced with the new one!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119f
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 4
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
17.3 Components
N4 CPU Files
Pro-Template v1.4.0.b Rev. AES assignments
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.a Rev. AES user PLC interface
N4_ALA.lib V1.3.1.d Corr. in serial itf. (stop bits)
N4_kBus.lib V1.2.1.b Rev. AES user PLC interface
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V2.0.0.17 All new
NAR_NoriVis_Communication V1.0.0.0
NAR_NoriVis_CSV_Handling V1.0.0.0
NAR_NoriVis_Data_Source V1.0.0.0
NAR_NoriVis_DataManager V1.0.0.0
NAR_NoriVis_DialogHandler V0.0.0.6
NAR_NoriVis_Interfaces V1.0.0.0
NAR_NoriVis_Journal V2.0.2.5
NAR_NoriVis_Lists V1.0.0.0
NAR_NoriVis_Menu V1.0.0.0
NAR_NoriVis_Mimic_Templates V3.0.0.3
NAR_NoriVis_Performance_Monitor V1.0.0.0
NAR_NoriVis_Symbol V1.0.0.0
NAR_NoriVis_System V1.0.0.0
NAR_NoriVis_Toolbox V2.0.0.4
NAR_NoriVis_Trend V2.1.0.10
NAR_NoriVis_Update V1.0.0.0
VMP Visu
NORIVIS_VMP-AES V2.0.0 Multi-VMP support
N4 Config
Version 2.0.0
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0 Inteface type TCP
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1 New master definitions
PLC V1.0.4 Master assignment
visu V1.0.1 Master assignment
AES V1.0.0 Master assignment + kBus
+ Printer
serial V1.0.1 No RTS control
ComXS V1.0.2
MB TcpInterf V1.0.0 New MODBUS-TCP cfg.
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1 Support for 3 languages
VisuGroups V1.0.0
DSP V1.0.3 New duty master, AES ID
DSP FctGrp V1.0.1
SSP V1.0.1 New AES ID
SSP channel V1.0.1 New AES ID
SSP assign. V1.0.1 New AES ID
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.2.0.0 Rev. for cfg. and Multi-VMP
Global Enhancements
Visu: Lists, Communication
PLC: MODBUS-TCP
AES: Multi-VMP
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
For updating an existing project, the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ at the project PC(s) has to be replaced with the new one!
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119f
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 4
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
18.3 Components
N4 CPU Files
Pro-Template v1.4.0.a Rev. reg. cfg. changes
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.2.1.a Rev. reg. cfg. & Multi-VMP
N4_ALA.lib V1.3.1.c Rev. reg. cfg. & Multi-VMP
N4_kBus.lib V1.2.1.a Rev. reg. cfg. & Multi-VMP
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V2.0.0.0 All new
NAR_NoriVis_Communication V1.0.0.0
NAR_NoriVis_CSV_Handling V1.0.0.0
NAR_NoriVis_Data_Source V1.0.0.0
NAR_NoriVis_DataManager V1.0.0.0
NAR_NoriVis_DialogHandler V0.0.0.5
NAR_NoriVis_Interfaces V1.0.0.0
NAR_NoriVis_Journal V2.0.2.4
NAR_NoriVis_Lists V1.0.0.0
NAR_NoriVis_Menu V1.0.0.0
NAR_NoriVis_Mimic_Templates V3.0.0.1
NAR_NoriVis_Performance_Monitor V1.0.0.0
NAR_NoriVis_Symbol V1.0.0.0
NAR_NoriVis_System V1.0.0.0
NAR_NoriVis_Toolbox V2.0.0.3
NAR_NoriVis_Trend V2.1.0.9
NAR_NoriVis_Update V1.0.0.0
VMP Visu
NORIVIS_VMP-AES V2.0.0 Multi-VMP support
N4 Config
Version 2.0.0
N4 Config Files
Config macro template V2.0.0
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0 Inteface type TCP
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.1 New master definitions
PLC V1.0.4 Master assignment
visu V1.0.1 Master assignment
AES V1.0.0 Master assignment + kBus
+ Printer
serial V1.0.1 No RTS control
ComXS V1.0.2
MB TcpInterf V1.0.0 New MODBUS-TCP cfg.
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.1 Support for 3 languages
VisuGroups V1.0.0
DSP V1.0.3 New duty master, AES ID
DSP FctGrp V1.0.1
SSP V1.0.1 New AES ID
SSP channel V1.0.1 New AES ID
SSP assign. V1.0.1 New AES ID
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.2.0.0 Rev. reg. cfg. Changes and
Multi-VMP
19 Revision 1.1.4.g
19.1 Information
Scope of revision
Product software package 1.1.4.g
Release Date 2018-01-03
Test Date 2018-01-03
Build Date 2018-01-03
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
PLC: added NMEA sets (14=EVE read, 15=FIR read, 16=ALA read)
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
For updating an existing project, the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ at the project PC(s) has to be replaced with the new one!
Changes of the channel configuration requires a delete of the trend data base in path
“C:\Program Files (x86)\3S CODESYS\GatewayPLC\trend” at the project PC(s).
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image Winmate 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
N4 IOeco V1.1.0 FW-N4-IO-ECO-110.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119c
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
19.3 Components
N4 CPU Files
Pro-Template v1.3.0.a
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.d
N4_ALA.lib V1.2.2.a Add. NMEA sets
N4_kBus.lib V1.1.0.e
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.83
TEMPLATE_BASE VT_2.0.6-n
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.40.3
DialogHandler 0.0.0.5
JournalManager 0.0.0.6
ToolBox 0.0.0.5
VMP Visu
NORIVIS_VMP-AES #1 V1.0.31.1
NORIVIS_VMP-AES #2 V1.0.31.2
N4 Config
Version 1.2.4 Update
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.2 Add. NMEA sets
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.2
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.0
VisuGroups V1.0.0
DSP V1.0.2
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.1.0.0
20 Revision 1.1.4.f
20.1 Information
Scope of revision
Product software package 1.1.4.f
Release Date 2017-11-24
Test Date 2017-11-24
Build Date 2017-11-24
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
PLC: added NME-ID is empty for XDR write requests
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
For updating an existing project, the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ at the project PC(s) has to be replaced with the new one!
Changes of the channel configuration requires a delete of the trend data base in path
“C:\Program Files (x86)\3S CODESYS\GatewayPLC\trend” at the project PC(s).
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image Winmate 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
N4 IOeco V1.1.0 FW-N4-IO-ECO-110.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
20.3 Components
N4 CPU Files
Pro-Template v1.3.0.a
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.d
N4_ALA.lib V1.2.1.b Add. check if NMEA-ID is empty for XDR wr
N4_kBus.lib V1.1.0.e
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.83
TEMPLATE_BASE VT_2.0.6-n
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.40.3
DialogHandler 0.0.0.5
JournalManager 0.0.0.6
ToolBox 0.0.0.5
VMP Visu
NORIVIS_VMP-AES #1 V1.0.31.1
NORIVIS_VMP-AES #2 V1.0.31.2
N4 Config
Version 1.2.3 Update
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
Project Helper
ph.exe V1.1.0.0
21 Revision 1.1.4.e
21.1 Information
Scope of revision
Product software package 1.1.4.e
Release Date 2017-11-22
Test Date 2017-11-22
Build Date 2017-11-22
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
PLC: added NMEA data sets: HDT read, DPT read, GLL read, GGA read, MWV read,
XDR read, XDR write
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
For updating an existing project, the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ at the project PC(s) has to be replaced with the new one!
Changes of the channel configuration requires a delete of the trend data base in path
“C:\Program Files (x86)\3S CODESYS\GatewayPLC\trend” at the project PC(s).
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image Winmate 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
N4 IOeco V1.1.0 FW-N4-IO-ECO-110.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119c
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
21.3 Components
N4 CPU Files
Pro-Template v1.3.0.a
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.d
N4_ALA.lib V1.2.1.a Add. NMEA sentences
N4_kBus.lib V1.1.0.e corrections
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.83
TEMPLATE_BASE VT_2.0.6-n
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.40.3
DialogHandler 0.0.0.5
JournalManager 0.0.0.6
ToolBox 0.0.0.5
VMP Visu
NORIVIS_VMP-AES #1 V1.0.31.1
NORIVIS_VMP-AES #2 V1.0.31.2
N4 Config
Version 1.2.3 Update
N4 Config Files
Project Helper
ph.exe V1.1.0.0
22 Revision 1.1.4.d
22.1 Information
Scope of revision
Product software package 1.1.4.d
Release Date 2017-07-24
Test Date 2017-07-24
Build Date 2017-07-24
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Visu: Enhanced file check for trend and journal manager data base.
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
For updating an existing project, the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ at the project PC(s) has to be replaced with the new one!
Changes of the channel configuration requires a delete of the trend data base in path
“C:\Program Files (x86)\3S CODESYS\GatewayPLC\trend” at the project PC(s).
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image Winmate 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
N4 IOeco V1.1.0 FW-N4-IO-ECO-110.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119c
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
22.3 Components
N4 CPU Files
Pro-Template v1.3.0.a
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.d
N4_ALA.lib V1.2.0.c
N4_kBus.lib V1.1.0.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.82 corr. trend
TEMPLATE_BASE VT_2.0.6-n
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.40.3
DialogHandler 0.0.0.5
JournalManager 0.0.0.6 corr. journal manager
ToolBox 0.0.0.5
VMP Visu
NORIVIS_VMP-AES #1 V1.0.31.1
NORIVIS_VMP-AES #2 V1.0.31.2
N4 Config
Version 1.2.2
N4 Config Files
Config macro template V1.0.6
Project Helper
ph.exe V1.1.0.0
23 Revision 1.1.4.c
23.1 Information
Scope of revision
Product software package 1.1.4.c
Release Date 2017-07-03
Test Date 2017-07-03
Build Date 2017-07-04
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
For updating an existing project, the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ at the project PC(s) has to be replaced with the new one!
Changes of the channel configuration requires a delete of the trend data base in path
“C:\Program Files (x86)\3S CODESYS\GatewayPLC\trend” at the project PC(s).
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image Winmate 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
N4 IOeco V1.1.0 FW-N4-IO-ECO-110.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119c
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
23.3 Components
N4 CPU Files
Pro-Template v1.3.0.a
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.d
N4_ALA.lib V1.2.0.c
N4_kBus.lib V1.1.0.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.81 corr. trend
TEMPLATE_BASE VT_2.0.6-n
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.41.1
DialogHandler 0.0.0.5
JournalManager 0.0.0.5
ToolBox 0.0.0.5
VMP Visu
NORIVIS_VMP-AES #1 V1.0.31.1
NORIVIS_VMP-AES #2 V1.0.31.2
N4 Config
Version 1.2.2
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.2
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.0
VisuGroups V1.0.0
DSP V1.0.2
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0
Project Helper
ph.exe V1.1.0.0
24 Revision 1.1.4.b
24.1 Information
Scope of revision
Product software package 1.1.4.b
Release Date 2017-06-27
Test Date 2017-06-26
Build Date 2017-06-26
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
For updating an existing project, the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ at the project PC(s) has to be replaced with the new one!
Changes of the channel configuration requires a delete of the trend data base in path
“C:\Program Files (x86)\3S CODESYS\GatewayPLC\trend” at the project PC(s).
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
Winmate
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
N4 IOeco V1.1.0 FW-N4-IO-ECO-110.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119c
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
24.3 Components
N4 CPU Files
Pro-Template v1.3.0.a
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.d
N4_ALA.lib V1.2.0.c
N4_kBus.lib V1.1.0.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.80 Rev. trend
TEMPLATE_BASE VT_2.0.6-n
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.30.9
DialogHandler 0.0.0.3
VMP Visu
NORIVIS_VMP-AES #1 V1.0.31.1
NORIVIS_VMP-AES #2 V1.0.31.2
N4 Config
Version 1.2.2 Rev. for cfg. journal printer
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.2
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.0
VisuGroups V1.0.0
DSP V1.0.2
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
PrinternCfg V1.0.0 New
Project Helper
ph.exe V1.1.0.0
25 Revision 1.1.4.a
25.1 Information
Scope of revision
Product software package 1.1.4.a
Release Date 2017-06-22
Test Date 2017-06-21
Build Date 2017-06-21
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Visu: New journaling module for definition of channel compilations for printing and storage to
portable memory devices. Revision of condition colour activation at bar graph and gauge.
Configuration: New work sheet for journal (Laser) printer IP address settings.
Notes
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
For updating an existing project, the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ at the project PC(s) has to be replaced with the new one!
Changes of the channel configuration requires a delete of the trend data base in path
“C:\Program Files (x86)\3S CODESYS\GatewayPLC\trend” at the project PC(s).
Group alarm output channels must not be included in any horn or optical acknowledgements
(configuration work sheet “group assignm.”). The group alarm acknowledgement will be
automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has to be set
even higher than the bus timeout, worksheet “Modbus”, entry “BusTout” normally “timeout” =
“BusTout”+2s!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
Winmate
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
N4 IOeco V1.1.0 FW-N4-IO-ECO-110.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119c
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
25.3 Components
N4 CPU Files
Pro-Template v1.3.0.a
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.d
N4_ALA.lib V1.2.0.c
N4_kBus.lib V1.1.0.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.79 Rev. trend; new journaling
TEMPLATE_BASE VT_2.0.6-n Rev. of condition colour
activation at bar graph and
gauge
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.30.9
DialogHandler 0.0.0.3
VMP Visu
NORIVIS_VMP-AES #1 V1.0.31.1
NORIVIS_VMP-AES #2 V1.0.31.2
N4 Config
Version 1.2.2 Rev. for cfg. journal printer
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.2
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.0
VisuGroups V1.0.0
DSP V1.0.2
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.1.0.0
26 Revision 1.1.3.a
26.1 Information
Scope of revision
Product software 1.1.3.a
Release Date 2017-05-31
Test Date 2017-05-31
Build Date 2017-05-31
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
ALA: New implementation for COMxs integration.
PLC: Enhanced project template with new COMxs and MODBUS request checks.
Devices: Update of NORISYS 4 PLC – RTOS, RTS & TSP for project PC.
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files (x86)\3S
CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by CODESYS,
store the archive extract files in your project folder.
Group alarm output channels must not be included in any horn or optical
acknowledgements (configuration work sheet “group assignm.”). The group alarm
acknowledgement will be automatically enforced by the group channels!
The Modbus request “timeout” in the configuration worksheet “Modbus assignm.” has
to be set even higher than the bus timeout, worksheet “Modbus”, entry “BusTout”
normally “timeout” = “BusTout”+2s!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
Winmate
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V119c
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
26.3 Components
N4 CPU Files
Pro-Template v1.3.0.a New runtime system 119b;
new COMxs RTS lib.
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.d
N4_ALA.lib V1.2.0.c Correction for MODBUS
N4_kBus.lib V1.1.0.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.76
TEMPLATE_BASE VT_2.0.6-m
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.30.9
DialogHandler 0.0.0.3
VMP Visu
NORIVIS_VMP-AES #1 V1.0.31.1 Minor fixes
NORIVIS_VMP-AES #2 V1.0.31.2 Corr. IP adress
N4 Config
Project Helper
ph.exe V1.1.0.0
27 Revision 1.1.2.b
27.1 Information
Scope of revision
Product software 1.1.2.b
Release Date 2017-04-19
Test Date 2017-04-19
Build Date 2017-04-19
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
PLC: Corr. Proj. template check routine
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Make sure that the project target selection is same as the installed runtime at the target
PC, read AA57_10x_Installation_NORIVIS4_from_Project_EN.
Devices
N4 CPU RTOS V1.60 SC2x3V0160Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
Winmate
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
N4 IOeco V1.1.0 FW-N4-IO-ECO-110.hex
N4 ComXS V1.1.8 FW_N4E_COMXS_V010108.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V118b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
27.3 Components
N4 CPU Files
Pro-Template v1.2.0.a
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.b
N4_ALA.lib V1.1.0.q Corr. Proj template check
N4_ComXS.lib 7.8.15 12:51:26
N4_ComXS_Intern.lib 6.8.15 11:59:43
N4_kBus.lib V1.1.0.d
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.76
TEMPLATE_BASE VT_2.0.6-m
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.30.9
DialogHandler 0.0.0.3
VMP Visu
NORIVIS_VMP-AES #1 V1.0.30.1
NORIVIS_VMP-AES #2 V1.0.30.2
N4 Config
Version 1.2.0
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Project Helper
ph.exe V1.1.0.0
28 Revision 1.1.2.a
28.1 Information
Scope of revision
Product software 1.1.2.a
Release Date 2017-03-31
Test Date 2017-03-30
Build Date 2017-03-28
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
AES: AES supports twin VMP installation to have two full functional master units.
Visualization: Revised for configurable menu and page arrangement and adapted trend
module.
PLC: New N4_controls library. Revised Proj. template with corr. User_PLC examples.
PH Tool: Supports new twin VMP as well as VMP image and PC configuration download
via FTP
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Make sure that the project target selection is same as the installed runtime at the target
PC, read AA57_10x_Installation_NORIVIS4_from_Project_EN.
Devices
N4 CPU RTOS V1.60 SC2x3V0160Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
Winmate
PC Image Sonove 1.01.12 Master_Sonove_V01.01.12_img
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V118b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5, Design PC & Runtime SP10 Patch 0
XSOFT CodeSys 3.5, Design PC & Runtime V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
28.3 Components
N4 CPU Files
Pro-Template v1.2.0.a Rev. regarding rev. libs
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.b revised for twin-VMP use
N4_ALA.lib V1.1.0.p MODBUS Req. now 150
N4_ComXS.lib 7.8.15 12:51:26
N4_ComXS_Intern.lib 6.8.15 11:59:43
N4_kBus.lib V1.1.0.d revised for twin-VMP use
N4B_Base2.lib V1.0.0.b
NAR_Controls V1.0.4.a new controls
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.76 new menu, adap. trend,
templates
TEMPLATE_BASE VT_2.0.6-m revised templates
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.30.9 screen size adap. trend
DialogHandler 0.0.0.3 new for manag. dialogs
VMP Visu
NORIVIS_VMP-AES #1 V1.0.30.1 revised for twin-VMP use
NORIVIS_VMP-AES #2 V1.0.30.2 new for twin-VMP use
N4 Config
Version 1.2.0 revised for cfg. menu/pages
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
VisuButtons V1.0.0 Menu arrangement
VisuGroups V1.0.0 Channel at page assignment
DSP V1.0.2
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.1.0.0 New twin VMP, enhanced
image & config. download
29 Revision 1.1.1.e
29.1 Information
Scope of revision
Product software 1.1.1.e
Release Date 2017-11-24
Test Date 2017-11-24
Build Date 2017-11-24
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Group alarm output channels must not be included in any horn or optical
acknowledgements (configuration work sheet “group assignm.”). The group
alarm acknowledgement will be automatically enforced by the group channels!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image Winmate 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
N4 IOeco V1.0.0.g FW-N4-IO-ECO-100g.hex
V1.0.0.i FW-N4-IO-ECO-100i.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS & TSP V119b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
29.3 Components
N4 CPU Files
Pro-Template V1.1.1.d Corrected use of int. var.
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.b
N4_ALA.lib V1.2.0.b
N4_kBus.lib V1.1.0.ca Corr. in group ass. detect.
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.64.b
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.29
VMP Visu
NORIVIS_VMP-AES V1.0.29
30 Revision 1.1.1.d
30.1 Information
Scope of revision
Product software 1.1.1.d
Release Date 2017-06-20
Test Date 2017-06-20
Build Date 2017-06-20
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Group alarm output channels must not be included in any horn or optical
acknowledgements (configuration work sheet “group assignm.”). The group
alarm acknowledgement will be automatically enforced by the group channels!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image Winmate 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
N4 IOeco V1.0.0.g FW-N4-IO-ECO-100g.hex
V1.0.0.i FW-N4-IO-ECO-100i.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS & TSP V119b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
30.3 Components
N4 CPU Files
Pro-Template V1.1.1.d Corrected use of int. var.
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.b
N4_ALA.lib V1.2.0.b
N4_kBus.lib V1.1.0.c
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.64.b
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.29
VMP Visu
NORIVIS_VMP-AES V1.0.29
N4 Config
Version 1.1.0
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
DSP V1.0.2
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.0.1.0
31 Revision 1.1.1.c
31.1 Information
Scope of revision
Product software 1.1.1.c
Release Date 2017-05-11
Test Date 2017-05-10
Build Date 2017-05-10
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
RTOS
Corrections for COMxs integration
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Group alarm output channels must not be included in any horn or optical
acknowledgements (configuration work sheet “group assignm.”). The group
alarm acknowledgement will be automatically enforced by the group channels!
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image Winmate 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
N4 IOeco V1.0.0.g FW-N4-IO-ECO-100g.hex
V1.0.0.i FW-N4-IO-ECO-100i.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS & TSP V119b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
31.3 Components
N4 CPU Files
Pro-Template V1.1.1
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.b
N4_ALA.lib V1.2.0.b Correction for MODBUS
N4_kBus.lib V1.1.0.c
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.64.b
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.29
VMP Visu
NORIVIS_VMP-AES V1.0.29
N4 Config
Version 1.1.0
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
DSP V1.0.2
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.0.1.0
32 Revision 1.1.1.b
32.1 Information
Scope of revision
Product software 1.1.1.b
Release Date 2017-04-24
Test Date 2017-04-24
Build Date 2017-04-24
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
ALA
New implementation for COMxs integration.
Devices
Softwareupdate of NORISYS 4 PLC – RTOS & RTS as well as TSP for project PC.
Softwareupdate for COMxs regarding COMxs intercommunication re-implementation in
ALA.
PC-Visu
Bux fixes in Trend module. Bug fix in clear alarm history functionality.
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Devices
N4 CPU RTOS V1.70 SC2x3V0170Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image Winmate 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
N4 IOeco V1.0.0.g FW-N4-IO-ECO-100g.hex
V1.0.0.i FW-N4-IO-ECO-100i.hex
N4 ComXS V1.1.9 FW_N4E_COMXS_V010109.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS & TSP V119a
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
32.3 Components
N4 CPU Files
Pro-Template V1.1.1 New runtime system 119a;
new COMxs RTS lib.
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.b
N4_ALA.lib V1.2.0.a New COMxs integr.
N4_kBus.lib V1.1.0.c
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.64.b Bug fixes in trend
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.29
VMP Visu
NORIVIS_VMP-AES V1.0.29
N4 Config
Version 1.1.0
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
DSP V1.0.2
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.0.1.0
33 Revision 1.1.1.a
33.1 Information
Scope of revision
Product software 1.1.1.a
Release Date 2016-12-30
Test Date 2016-12-29
Build Date 2016-12-29
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
AES
If any engine control room station is set to ON-DUTY, the bridge will indicate its alarms
silent in addition to the acoustically indication of bridge alarms. If an engine control room
station is set to OFF-DUTY, the bridge will take over acoustic and optical alarming.
Integration of special harbor mode to silent all duty repeaters exempt the bridge which
indicates its alarms only. In the user PLC use the following code line to activate the
mode: "AES_I_bHarbourMode := TRUE".
DPS menu entry Engineer Call” revised to “Engineer Call / Duty Indication”.
Configuration
Added version number at page “MENU”.
PLC
Sometimes local time zone is not accepted if set manually in AES master.
Configuration
Revised page “DSP” at comment for DutyToBri option.
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Devices
N4 CPU RTOS V1.60 SC2x3V0160Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
Winmate
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V118b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
33.3 Components
N4 CPU Files
Pro-Template V1.1.0.c
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.b new bridge alarming
N4_ALA.lib V1.1.0.n bugfix for local time zone;
DPS cfg. file vers.102
N4_ComXS.lib 7.8.15 12:51:26
N4_ComXS_Intern.lib 6.8.15 11:59:43
N4_kBus.lib V1.1.0.c new bridge alarming; DSP
menu entry “eng. Call /duty
ind.”
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.64
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.29
VMP Visu
NORIVIS_VMP-AES V1.0.29 bug fix jump to channel;
corr. call from indic.; rev.
N4 Config
Version 1.1.0 new
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
DSP V1.0.2 corr. in DutyToBridge
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.0.1.0
34 Revision 1.1.0.e
34.1 Information
Scope of revision
Product software 1.1.0.e
Release Date 2016-12-09
Test Date 2016-12-09
Build Date 2016-12-09
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Visualization
The visualization was changed according to fixes in trend library.
Trend
Enhanced error handling for reading data from DB with new cancel option for operator.
PLC/Configuration
Added NMEA request code 6 for NMEA string “VBW”.
Configuration
DSP section will not be imported from older projects.
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Devices
N4 CPU RTOS V1.60 SC2x3V0160Release_Build000001.elf
PC Image ISIC 1.01.10 Master_ISIC_Q87_V01.01.10_img.TIB
PC Image 1.01.10 Master_WinmateI330EAC_ID3_V01.01.10_img.TIB
Winmate
N4 IOeco V1.0.0.g FW-N4-IO-ECO-100g.hex
V1.0.0.i FW-N4-IO-ECO-100i.hex
N4 ComXS V1.1.8 FW_N4E_COMXS_V010108.hex
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V118b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
34.3 Components
N4 CPU Files
Pro-Template V1.1.0.c
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.a
N4_ALA.lib V1.1.0.l new: NMEA req. for “VBW”
N4_ComXS.lib 7.8.15 12:51:26
N4_ComXS_Intern.lib 6.8.15 11:59:43
N4_kBus.lib V1.1.0.b
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.64 new Trend lib.
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.29 bug fixes for date select;
enhancement for error
handling on DB reading
VMP Visu
NORIVIS_VMP-AES V1.0.27
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.1 new: NMEA req. for “VBW”
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
DSP V1.0.1
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.0.1.0
35 Revision 1.1.0.d
35.1 Information
Scope of revision
Product software 1.1.0.d
Release Date -
Test Date -
Build Date 2016-12-08
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
AES/Duty
The DUTY state of each AES device is stored remanent. After return from failure
or power down the original state is restored.
For DUTY allocation it is no more necessary, that at least one full DUTY station is
On DUTY. In case no other full DUTY station is selected, after some minutes NO
DUTY alarm will rise up.
DUTY can be transferred from ECR to bridge, when leaving the ECR.
Configuration can predefine, if a station needs to acknowledge DUTY allocation.
Configuration can predefine, if a station shall be silent on new normal alarms,
when the ECR is engaged.
A interface structure is provided, from which the user code in the PLC can read
all information concerning the DUTY and CALL state of all AES devices, see below.
AES/VMP
Login is provided. After login several settings are possible:
o In case the operator forgot his password, he can read a help text with a code,
that should be transferred to NORIS service. With this code the service can
determine the correct password.
o The operator can change his password.
o The remanent alarm printer puffer can be cleared.
o It is possible to set UTC date and UTC time and also the time zone.
o It is possible to parameterize channels all over the system including fading in
and out channels.
After some minutes without operator action the login is reset.
After some minutes without operator action open dialogs are closed.
When clicking outside of an open dialog this dialog is closed and the desired action
is performed immediately
AES/VMP/Duty/Call
Scrollbar inserted.
Buttons inserted for page up and down.
The button for calling an engineer now also shows the acknowledgement of the
called engineer.
Stations with full and with restricted DUTY are shown differently. Full DUTY
stations ON DUTY have a thick green frame, restricted stations ON DUTY have a
thin green frame.
Configuration
Revised page “DSP” to support new duty functionality.
Option ECR: 0 = false, 1 = true; The activation of this bit indicates, that this
device is mounted inside the Engine Control Room.
Option SilentOnEcr: 0 = false, 1 = true; The activation of this bit indicates, that
this device is does not buzzer, i.e. is switched silent, if the Engine Control Room
is engaged e.g. is ON DUTY. This does not affect special Alarms like Dead Man,
NoDuty, Engineer Alarm.
Option DutyHandshake: 0 = false, 1= true; If Duty is allocated to this device
by the Duty Master, then the operator has to accept the Duty allocation.
Option DutyToBridge: 0 = false, 1 = true; Before Duty is removed from ECR,
the bridge has to accept DUTY.
TYPE AES_DEVICES_SINGLE :
STRUCT
(*Hint: MiSo := Master In, Slave Out; MoSi := Master Out, Slave In *)
bOk :BOOL; (*AES Device is ok *)
bDutyState :BOOL; (*Duty state of an AES Device *)
bMoSi_DutyReq :BOOL; (*Do overtake Duty *)
bMoSi_DutyOffReq :BOOL; (*Do release Duty *)
bMoSi_DutyReqAck :BOOL; (*Operator needs to accept Duty takeover *)
bMiSo_DutyAck :BOOL; (*Operator has accepted Duty takeover *)
bMoSi_DutyOffAllowed :BOOL; (*Duty Off allowed *)
bMoSi_DutyToBridge :BOOL; (*Bridge shall overtake Duty from ECR *)
bMiSo_DutyToBridgeAck :BOOL; (*Bridge has accepted DutyToBridge *)
bCfg_IsBridge :BOOL; (*From Config *)
bCfg_IsEcr :BOOL; (*From Config *)
bCfg_BeSilentOnEcrDuty :BOOL; (*From Config: Do not buzzer for normal alarms,
when ECR is engaged *)
bCfg_DoDutyHandshake :BOOL; (*From Config: Acknowledge required, when Duty
allocated from master *)
bCfg_DoDutyToBridge :BOOL; (*From Config: Do transfer Duty to Bridge before
leaving ECR *)
bCfg_ForceDuty :BOOL; (*From Config: Device is forced to be (always) on duty
*)
bCfg_NoValidDuty :BOOL; (*From Config: Device is a restricted Duty Station *)
bCfg_NoDutyKey :BOOL; (*From Config: Duty selection by Duty key is not
allow.*)
bCall :BOOL; (*Master/DSP is called *)
bCallAck :BOOL; (*Master/DSP has acknowledged the call *)
wCallingID :WORD; (*Call comes from ... ID... *)
byKbusAdr :BYTE; (*Address of the Device on kBus *)
wBaseGroup :WORD;
sName :STRING(40);
END_STRUCT
END_TYPE
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Devices
N4 CPU RTOS V1.60 SC2x3V0160Release_Build000001.elf
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V118b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
35.3 Components
N4 CPU Files
Pro-Template V1.1.0.c
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.2.a new duty handling; ch.
param.
N4_ALA.lib V1.1.0.k support of time setting by
operator at AES master
N4_ComXS.lib 7.8.15 12:51:26
N4_ComXS_Intern.lib 6.8.15 11:59:43
N4_kBus.lib V1.1.0.b fcn.s for new duty handling
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.63
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.27
VMP Visu
NORIVIS_VMP-AES V1.0.27 rev. duty station loss indic.,
new channel details &
param. mode
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.0
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
DSP V1.0.1 New: ECR, SilentOnEcr,
DutyHandshake,
DutyToBridge
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.0.1.0
36 Revision 1.1.0.c
36.1 Information
Scope of revision
Product software 1.1.0.c
Release Date -
Test Date -
Build Date 2016-12-01
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Visualization
The visualization was changed according to fixes in trend library.
Trend
Bug fixed UTC/LTC, values at channel list, weekdays, time change at auto mode, invisible
cursor. Features for refresh on non-auto and reset to now.
AES
Revised printer function to support older print out model, e.g. for project 5719/00 pager
interface. Use code line AES_ADRU_PRINT_Version := 1; to activate older print out
model (see NAR-KD-01039-10-en until Version 1.11).
PH-Tool
Copy of folder “PcBase” to project. Revised Interface.
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“ has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Devices
N4 CPU RTOS V1.60 SC2x3V0160Release_Build000001.elf
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V118b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
36.3 Components
N4 CPU Files
Pro-Template V1.1.0.c
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.1.g option for print out model
N4_ALA.lib V1.1.0.i
N4_ComXS.lib 7.8.15 12:51:26
N4_ComXS_Intern.lib 6.8.15 11:59:43
N4_kBus.lib V1.1.0.a
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.63 rev. Trend
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.27 bug fixes: UTC/LTC, values
at ch. list, weekdays, time
change at auto mode, invis.
Cursor; features: refresh
on non-auto and reset to
now
VMP Visu
NORIVIS_VMP-AES V1.0.25
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.0
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
DSP V1.0.0
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.0.1.0 copy of PcBase folder; rev.
interface
37 Revision 1.1.0.b
37.1 Information
Scope of revision
Product software 1.1.0.b
Release Date -
Test Date -
Build Date 2016-11-15
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Visualization
The visualization was changed according to rev. trend library.
Trend
Revised sizes and texts of several elements. Changes to support 4:3 screens.
Notes
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“has to be replaced with the new one!
The PC visualization stored as an archive to bind all used libraries correctly. If asked by
CODESYS, store the archive extract files in your project folder.
Devices
N4 CPU RTOS V1.60 SC2x3V0160Release_Build000001.elf
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V118b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.8
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
37.3 Components
N4 CPU Files
Pro-Template V1.1.0.c
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.1.e
N4_ALA.lib V1.1.0.i
N4_ComXS.lib 7.8.15 12:51:26
N4_ComXS_Intern.lib 6.8.15 11:59:43
N4_kBus.lib V1.1.0.a
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.62 rev. Trend
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.24
VMP Visu
NORIVIS_VMP-AES V1.0.25
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.0
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
DSP V1.0.0
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.0.0.6
38 Revision 1.1.0.a
38.1 Information
Scope of revision
Product software 1.1.0.a
Release Date -
Test Date -
Build Date 2016-11-01
Requested by NAR R&D Division
Hardware change required No
Global Enhancements
Visualization
The visualization got changes in the task control to provide more stability. The
accessibility of the channel preferences is limited below user supervisor.
The PC visualization is now based on CodeSys 3.5 SP9Patch1, but runs on runtime 3.5.8!
For updating existing project the file "CODESYSControl.cfg" in the path „C:\Program Files
(x86)\3S CODESYS\GatewayPLC“has to be replaced with the new one!
Trend
Base structure changed. Trend module useable for all PC versions.
PC Images
Enhanced to support FTP access and equipped with runtime 3.5.8.
Location: \\vfile\Software\n4_pcbackup\_Master\
VMP display
Fadeout channels after reset updated.
Notes
Devices
N4 CPU RTOS V1.60 SC2x3V0160Release_Build000001.elf
Tools
CodeSys V2.3 V2.3.9.50
N4 CPU RTS V118b
ChipTool V7.2.0.2 / ControlLib: V2.34
CodeSys V3.5 SP9Patch1
XSOFT CodeSys V3.5.7
Microsoft Excel 2003 / 2007 / 2010 / 2013
FlashMagic V6.96
FlashLoaderDemonstrator V2.6.0
Terminal Program (230400 Baud avail.) e.g. Realterm V2.0.0.57
Acronis
38.3 Components
N4 CPU Files
Pro-Template V1.1.0.c
Com_N4Com.lib V1.1.0.a
EcM_EcoModul.lib V1.1.0.a
Eth_Ethernet.lib V1.1.0.d
FS1_FileSystem.lib V1.0.0.a
MB1_ModBusV1.lib V1.0.0.b
N4_AES.lib V1.1.1.e
N4_ALA.lib V1.1.0.i
N4_ComXS.lib 7.8.15 12:51:26
N4_ComXS_Intern.lib 6.8.15 11:59:43
N4_kBus.lib V1.1.0.a
N4B_Base2.lib V1.0.0.b
NAR_Standard.lib V1.0.0.c
AMS PC Visu
NORIVIS_BASE V1.1.61 rev. ch. pref. access rights;
Trend; rev. task control
TEMPLATE_BASE VT_2.0.6-b
NAR_ALA_CNT V1.0.0.4
NAR_ALA_Tmp V1.0.0.5
NAR_ETH_Ethernet23 V1.0.0.4
NAR_FS1_FileSystem23 V1.0.0.1
NAR_Standard23 V1.0.0.3
NAR_ALA_TREND V2.0.22
VMP Visu
NORIVIS_VMP-AES V1.0.25
N4 Config Files
Config macro template V1.0.6
ALA channels V1.0.0
IOeco V1.0.0
IOeco channels V1.0.0
IOeco assignm. V1.0.0
PLC assignm. V1.0.0
ch routing V1.0.0
Modbus V1.0.0
Modbus assign. V1.0.2
NMEA V1.0.0
NMEA assign. V1.0.0
groups V1.0.0
group assign. V1.0.2
NwMaster V1.0.0
PLC V1.0.3
visu V1.0.0
serial V1.0.0
ComXS V1.0.1
MeasValTbl V1.0.0
DevTbl V1.0.0
LimTbl V1.0.0
LimTbl assignm. V1.0.0
CfgGrp V1.0.0
VisCh V1.0.1
DSP V1.0.0
DSP FctGrp V1.0.0
SSP V1.0.0
SSP channel V1.0.0
SSP assign. V1.0.0
project V1.0.0
NwMasterID V1.0.0
Project Helper
ph.exe V1.0.0.6