Sp0125 Rev.00

July 11, 2000

Field procedure to reset ETS 100 factory parameters

Press brakes with ETS100 control

ETS100 parameters general factory rockwell compumotor backgauge


thermal compensation board enter

The following tables confirm factory parameter settings for ETS100, Rockwell or Compumotor
Backgauge, and thermal compensation board (if equipped).

1) For Press brakes with ETS100 control:


Parameter screen access: General Factory Parameters
1. Enter keystrokes: 8, CLEAR, 1, 5, 7
2. Record the General Factory parameters in the following table:
Kf = TL = S1 =
b U= S2 =
f V= S3 =
Note: 'V' parameter not field resettable.
3. Press EXIT to return to main screen.

2a) Option: With Compumotor or Rockwell (Electrocraft) Backgauge Motor:


Parameter screen access: Compumotor or Rockwell Backgauge X Axis Tuning Parameters
1. From the main screen, enter keystrokes: 8, CLEAR, 1, 5, 0
2. Confirm the parameters from one of the following tables:

Compumotor Backgauge Rockwell Backgauge X


X Axis Tuning Axis Tuning Parameters
Parameters
0 MxA= 0 MxA=
1 MxV= 1 MxV=
2 DrG= 2 DrG=
3 InG= 3 ViG=
4 InL= 4 PiG=
5 PrG= 5 PrG=
6 HmV= 6 HmV=
7 SpR= 7 SCL=
3. Press EXIT to return to the main menu.
Rapid City, SD, USA Surrey, BC, Canada Willmar, MN, USA
Telephone: 605-718-2550 Telephone: 1-888-862-2072 Telephone: 320-235-9412
Fax: 605-718-2551 Fax: 1-888-862-2781 Fax: 320-235-7176

Page 1 of 1
2b) Option: With Thermal Compensation Board v5.2+
Parameter screen access: ETS100 Thermal Compensation parameter screen

1. From the main screen enter key strokes: 8, CLEAR, 1, 5, 9


2. Confirm the Thermal Compensation board parameters from the following table:

Pz = Th = Ps =
Tz = Tg = S2 =

3. Press EXIT to return to the main menu.

*NOTE:

1. Pz is "z" = 001 (at start)


2. Th = ? 218 when cold.
3. Ps – Pressure transducer reading. This parameter should be 252 or 253. When Ps > 255 the
pressure transducer is not working and the machine will not work correctly.
4. Tz should be the same as Th at ambient temperature
5. Tg should be 0 at ambient temperature

3) Re-enter the ETS100 Factory Parameters.


1. Perform a global reset of the main PLC board by entering: 8, CLEAR, 1, 5, 2. Press EXIT to
return to the main menu.
2. Press: 8, CLEAR, 1, 5, 7 and enter the General Factory parameters recorded in the above
table. Press EXIT to save the data.
3. i) To enter the Compumotor or Rockwell Backgauge X Axis Tuning Parameters: Press:
8, CLEAR, 1, 5, 0 and enter the X Axis Tuning Parameters recorded in the above table.
Press EXIT to save the data.
ii) To enter the Thermal Compensation Parameters: Press: 8, CLEAR, 1, 5, 9 and enter the
Thermal Compensation Parameters recorded in the above table. Press EXIT to save the
data.

Upon completion of the factory parameter change, verify correct press brake functionality with
field service report sign off by the customer representative.