Catalog #: 2080-IF4 Preferred Availability

Micro800 4 Point Analog Input Plug-In


Lifecycle status: ACTIVE

Technical Specifications
Electrical Number of analogue inputs 4

Resolution of the analogue inputs 12 Bit

Input, current Yes

Input, voltage Yes

Input, resistor No

Input, resistance thermometer No

Input, thermocouple No

Input signal, configurable No

Output, current No

Output, voltage No

Output signal configurable No

Analogue inputs configurable Yes

Analogue outputs configurable No

Type of electric connection Screw connection

Data range 0 to 65535

Channel to channel isolation Non-isolation

Update time 180 ms per enabled channel

Input group to bus isolation No isolation

Voltage: ±1.5% @ over full temperature range, -20...65°C


Module error (-4...149°F), Current: ±2.0% @ over full temperature range,
-20...65°C (-4...149°F)

https://www.rockwellautomation.com/es-pr/products/details.2080-IF4.html 1/3
30/10/23, 15:53 2080-IF4 | Allen-Bradley

Solid: 0.14 mm2 (26 AWG)...1.5 mm2 (16 AWG) @ Rated @ 90 °C


(194 °F) insulation maximum, Stranded: 0.14 mm2 (26
Wire size
AWG)...1.0 mm2 (18 AWG) @ Rated @ 90 °C (194 °F) insulation
maximum

Suitable for safety functions No

SIL according to IEC 61508 None

Recommended maximum shielded cable length 10 m

Voltage ranges 0V

Current range 0 mA

Field input calibration Not required

Voltage terminal: ±1% full scale @ 25°C, Current terminal:


Overall accuracy
±1% full scale @ 25°C

Environmental Surrounding air temperature, max 65 °C

North American temperature code T4

Power consumption <60 mA @ 3.3V

Emissions CISPR 11 (IEC 61000-6-4): Class A

ESD immunity IEC 61000-4-2: 6 kV contact discharges, 8 kV air discharges

EFT/B immunity IEC 61000-4-4: ±2 kV @ 5 kHz on shielded ports

IEC 60068-2-30 (Test Db, unpackaged damp heat), 5...95%


Relative humidity
noncondensing

IEC 61000-4-6, 10V rms with 1 kHz sine-wave 80% AM from 150
Conducted RF immunity
kHz...80 MHz

Surge transient immunity IEC 61000-4-5: ±2 kV line-earth(CM) on shielded ports

-20...65 °C (-4...149 °F): IEC 60068-2-1 (Test Ad, Operating


Operating temperature Cold), IEC 60068-2-2 (Test Bd, operating dry heat), IEC 60068-
2-14 (Test Nb, operating thermal shock)

IEC 61000-4-3: 10V/m with 1 kHz sine-wave 80% AM from


80...2000 MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 900
Radiated RF immunity
MHz, 10V/m with 200 Hz 50% pulse 100% AM @ 1890 MHz,
10V/m with 1 kHz sine-wave 80% AM from 2000...2700 MHz,

Operating altitude 2000 m

-40...85 °C (-40...185 °F), IEC 60068-2-1 (Test Ab, Unpackaged


Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged
Nonoperating temperature
Nonoperating Dry Heat), IEC 60068-2-14 (Test Na,
Unpackaged Nonoperating Thermal Shock)

https://www.rockwellautomation.com/es-pr/products/details.2080-IF4.html 2/3
30/10/23, 15:53 2080-IF4 | Allen-Bradley

Output Non-linearity ±0.1% @ in percent full scale


Specifications

General Repeatability ±0.1%


Specifications

Mechanical Vibration IEC 60068-2-6 (Test Fc, operating), 2 G @ 10...500 Hz

IEC 60068-2-27 (Test Ea, unpackaged shock): DIN rail mount:


Shock
25 g, nonoperating, Panel Mount: 35 g nonoperating

Mounting torque 0.2 Nm

0.22...0.25 Nm (1.95...2.21 lb-in) (using a 2.5 mm (0.10 in.) flat-


Terminal screw torque
blade screwdriver)

Input Input impedance >100 kΩ for voltage mode, 250 Ω for current mode
Specifications

Certification Explosion safety category for gas None

Explosion safety category for dust None

Certifications

Korean Register of Shippin

This product was certified with the above certifications as of 2023-10-18. Products sold before or after this date might carry