Professional Documents
Culture Documents
Residential Ventilation
Requirements
In the 1995 National Building Code
LEGAL DOCUMENT
Complying with Residential Ventilation Requirements in the 1995 National Building Code is not a substitute for the
National Building Code. While care has been taken to ensure accuracy in this manual and its illustrations, Canada
Mortgage and Housing Corporation does not assume responsibility for errors or oversights resulting from the informa-
tion contained herein.
The administration of building code requirements is a provincial responsibility. Local ventilation requirements may
differ from those of the National Building Code. Therefore, compliance with the National Building Code does not neces-
sarily constitute compliance with provincial requirements. The legal documents which must be referred to in matters
related to technical interpretation and code enforcement are the appropriate Provincial Building Codes.
COPYRIGHT
Distribution of this guide in its copyright form is restricted. Reproduction for commercial or advertising purposes shall
not be made without permission from Canada Mortgage and Housing Corporation.
International Standard Book Number 1–895389–02-X
© 1996 Canada Mortgage and Housing Corporation
ii
ACKNOWLEDGEMENTS
The project team which developed this manual was comprised of:
Project management and manual preparation and technical content:
Bert Phillips..................................................UNIES Ltd., Consulting Engineers, Winnipeg
Gary Proskiw ............................................................. Proskiw Engineering Ltd., Winnipeg
Design and Layout ......................................................... Doowah Design Inc., Winnipeg
Illustrations and Graphics ...................................David Morrow Illustrations, Winnipeg
iii
Table of Contents
BUILDER SUMMARY ............................................................................... A1
Code Overview........................................................................................................................A2
Design Requirements............................................................................................................A2
HRVs and ERVs .......................................................................................................................A3
Ventilation System Options ..................................................................................................A3
Getting it Right the First Time ........................................................................................... A12
Builder Responsibilities ..................................................................................................... A13
Energy Codes and Residential Ventilation ........................................................................A13
INTRODUCTION ..................................................................................... B1
Purpose of the Manual ..........................................................................................................B2
The Need for Ventilation ........................................................................................................B2
Elements of an Effective Indoor Air Quality Program ........................................................B2
Cost of Ventilating ..................................................................................................................B3
v
PREFACE
All dwellings require fresh air to deal with moisture, odours and indoor pollutants.
The 2005 National Building Code (NBC) requires that new dwellings have mechanical
ventilation systems capable of providing this fresh air.
Canada Mortgage and Housing Corporation prepared this manual to help builders un-
derstand and meet the NBC ventilation requirements. Performance, reliability or safety
testing has not been done on all systems which meet the NBC. As such, their inclusion
in this manual does not constitute an endorsement. However, based on the opinions of
industry experts, they should result in better ventilation in housing.
The people who contributed directly to the preparation of this manual are identified
in the Acknowledgements at the beginning of this manual. Their contributions of time
and energy were considerable. But, with your help, this manual can be improved.
If you have suggestions for clarification and/or improvements which would make
future versions of the manual more useful to you, please send them to:
Policy and Research Division
Canada Mortgage and Housing Corporation
700 Montreal Road
Ottawa, Ontario
K1A 0P7
Phone (613) 748-2658 Fax (613) 748-2402
LIMITATIONS
An improperly installed ventilation system may jeopardize occupant health and safety
or cause damage to the structure. Proper installation of residential ventilation systems
requires an understanding of:
w fuel-fired appliance codes,
This manual is intended for use by persons with this prerequisite knowledge.
vii
BUILDER SUMMARY
A
Builder Summary
The purpose of this manual is to help builders and residential HVAC installers understand the re-
quirements of Section 9.32 Ventilation in the NBC, and to offer ventilation system options that
comply with these requirements. The Builder Summary provides an overview of ventilation system
requirements and describes some ventilation systems that comply with the prescriptive require-
ments in the NBC. Later sections of this manual provide more detailed discussions and descriptions
of NBC requirements.
The ventilation system options presented in this manual cover most, but not all house designs and
occupant needs. Where these systems are not suitable, detailed ventilation system designs that
comply with either the prescriptive requirements in Section 9.32 or the more detailed “objective
based” design requirements in CAN/CSA-F326 ”Residential Mechanical Ventilation Systems” are
required. It is the builder’s responsibility to ensure that ventilation systems comply with the NBC.
The Builder Summary and the balance of this manual do not replace the specific requirements of the
NBC. In the event of a conflict of interpretation between this document and the NBC, the interpreta-
tion of jurisdiction having authority will prevail.
A1
BUILDER SUMMARY
Code Overview
The 2005 National Building Code requires most new dwelling units to have a mechani-
cal ventilation system installed. Suites in buildings that fall under Part 6 of the NBC
must be designed using ASHRAE Standard 62 “Ventilation for Acceptable Indoor Air
Quality” unless they have self-contained ventilation systems, in which case the builder
has the option of complying with the requirements of NBC Section 9.32 Ventilation.
Ventilation systems for all NBC Part 9 dwellings must be installed in compliance with
NBC Section 9.32 Ventilation or with CAN\CSA-F326 “Residential Mechanical Ventilation
Systems”.
A knowledgeable ventilation system installer can select and install one of the Part 9
ventilation system options described in this manual, or may custom design and install
a ventilation system, provided that it complies with the requirements of Section 9.32
or with the requirements of CAN\CSA-F326.
A2
BUILDER SUMMARY
A3
BUILDER SUMMARY
Exhaust-Only Ventilation,
Distribution by a Forced Air Heating System
See NBC Ventilation System Options A and E
APPLICATION CONTROLS
Dwelling using these system configurations require: A centrally located manual switch labelled “Ventila-
w forced air heating
tion Fan” operates principal exhaust fan at the Normal
Operating Exhaust Capacity. The furnace circulation fan
w no solid-fuel-burning appliances
operates continuously or on a timer control whenever
w any fireplaces to be of the direct-vented type principal exhaust fan is operated.
w all fuel-fired space- and/or water-heating appliances A switch in each room served by a supplemental ex-
to be of direct-vented or power-vented types haust fan operates the fan.
w make-up air for exhaust devices or an active soil If kitchen exhaust is provided by the principal exhaust
gas mitigation system if soil gas is deemed to be a fan, the control in the kitchen must be labelled “Kitchen
problem Exhaust”.
Automatic fan controls (e.g., dehumidistats) can also be
SYSTEM CHARACTERISTICS used.
Simplest and lowest installed cost for most applications
Does not easily include energy recovery. VARIATIONS
Generally not operated very much by occupants ADD AN OUTDOOR-AIR SUPPLY DUCT COUPLED TO A
FORCED AIR HEATING SYSTEM
May cause cool drafts that affect occupant comfort dur- NBC Options A and E upgrade system performance
ing cold weather by adding an outdoor air intake duct connected to the
furnace return duct. This will provide more uniform
VENTILATION AIR SUPPLY AND DISTRIBUTION distribution of outdoor air and reduced likelihood of
The principal ventilation (exhaust) fan exhausts from cold drafts causing occupant discomfort.
the kitchen and/or bathrooms and/or other location(s).
Replacement outdoor air is drawn in through the build- NBC VENTILATION SYSTEM OPTION A
ing envelope. The furnace circulation fan operates to mix NBC Option A uses a single speed PV fan and requires
and distribute outdoor air. use of some supplemental exhaust fans
NBC VENTILATION SYSTEM OPTION E
SUPPLEMENTAL EXHAUST NBC Option E uses a PV fan with a high speed/low
Supplemental exhaust is required from kitchens un- speed control which can meet both principal exhaust
less the principal ventilation system exhaust fan only flow requirements and supplemental exhaust require-
exhausts air from the kitchen OR a two speed principal ments
ventilation system exhaust fan is used.
ADD AN OUTDOOR-AIR SUPPLY FAN
Supplemental exhaust is required for any bathrooms not Another variation is to install an auxiliary supply fan in
connected to the principal ventilation system exhaust the outdoor air supply duct described above to further
fan. improve control over the supply and distribution of
ventilation air.
A4
BUILDER SUMMARY
APPLICATION CONTROLS
These systems are suitable for all dwelling units with A centrally located manual switch labelled “Ventilation
forced air heating. Fan” operates the HRV/ERV at the Normal Operating
Exhaust Capacity. The furnace circulation fan operates
SYSTEM CHARACTERISTICS continuously or on a timer control whenever HRV/ERV is
HRV/ERV pre-heats outdoor air, reducing heating costs operated.
and improving occupant comfort
A switch in each room served by a supplemental ex-
HRV/ERV includes supply and exhaust fans and some haust fan operates the fan.
controls
If kitchen exhaust is provided by the HRV/ERV, the con-
HRV/ERV filters and core require routine maintenance trol in the kitchen must be labelled “Kitchen Exhaust”.
HRV/ERVs designed to operate with balanced airflows Automatic fan controls (e.g., dehumidistats) can also be
do not require additional makeup air when operating on used.
high speed to meet kitchen and bathroom exhaust.
May cost more to install than systems without heat VARIATIONS
recovery but the cost to heat ventilation air will be NBC VENTILATION SYSTEM OPTION B
reduced. NBC Option B uses a single speed HRV/ERV and re-
quires use of some supplemental exhaust fans
VENTILATION AIR SUPPLY AND DISTRIBUTION NBC VENTILATION SYSTEM OPTION F
HRV/ERV draws exhaust from the kitchen and/or NBC Option F uses an HRV/ERV with a high speed/low
bathrooms and/or other central location and supplies speed control which can meet both principal exhaust
outdoor air to the forced air heating system return air flow requirements and supplemental exhaust require-
plenum. The forced air system circulation fan operates ments
whenever the HRV/ERV to mixed and distribute outdoor
throughout the house.
SUPPLEMENTAL EXHAUST
Supplemental exhaust is required from kitchens unless
the HRVV/ERV only exhausts air from the kitchen OR a
two HRV/ERV is used.
Supplemental exhaust is required for any bathrooms not
connected to the HRV/ERV.
A5
BUILDER SUMMARY
An HRV/ERV with a high speed/low speed control can Automatic fan controls (e.g., dehumidistats) can also be
meet both principal exhaust flow requirements and used.
supplemental exhaust requirements for the dwelling
without requiring makeup air.
VARIATION
NBC VENTILATION SYSTEM OPTION C
VENTILATION AIR SUPPLY AND DISTRIBUTION – DEDICATED SUPPLY AND EXHAUST SYSTEMS WITHOUT
HEAT RECOVERY
An HRV/ERV draws exhaust air from the kitchen,
NBC Option C is similar to NBC Option D, except NBC
bathrooms and/or other central location and supplies
Option C uses a heater (electric or hydronic) to condi-
outdoor air through a small diameter duct system to
tion supply air during cold weather rather the heat
each bedroom, to any storey without a bedroom and, if
exchange core of an HRV/ERV and the fans are not
there is no storey without a bedroom, to the principal
part of a factory assembled package, as is the case
living area.
with HRVs.
A6
BUILDER SUMMARY
Exhaust-Only with a
Purpose Built Air Circulation System
Not illustrated in the NBC
The fan in this air circulation system must have a rated supplemental exhaust requirements
capacity of at least five times the actual Normal Operat- w an outdoor air intake connected to the intake side of
ing Exhaust Capacity of the Principal Ventilation Fan. the air circulation system to ensure more uniform
distribution of outdoor air and reduced likelihood of
cold drafts
w a supply fan in the outdoor air supply duct described
above to further improve control over the distribution
of ventilation air
A7
BUILDER SUMMARY
Ventilation system
serves only one NO Design to Part 6 of NBC
dwelling unit?
YES
Five or fewer
bedrooms? NO Design using CSA F326
YES
YES
GO TO
TREE #2
A8
BUILDER SUMMARY
1. Fuel-fired
space and/or water heating
appliances other than direct-vent,
mechanically vented or solid fuel-fired
types are installed? NO TO BOTH
2. Soil gas deemed to be a problem and an
active soil gas mitigation
system not installed?
YES TO EITHER
1. Fuel-fired
Make-up air required for all exhausts space- and/or water-heating
except Principal Ventilation System at appliances installed?
Normal Operating Exhaust Capacity
2. Attached storage garage?
Forced air
system with circulation fan
capacity at least 5 times actual Normal
Operating Exhaust Capacity
is installed?
YES
1. All fuel-fired
space and/or water
heating appliances are direct-vent
Use either HRV/ERV option NO or solid fuel mechanically vented types.
2. Soil gas is not deemed
to be a problem.
YES
A9
BUILDER SUMMARY
w Give copies to all the affected trades for their review to ensure:
w Closely inspect work before it is closed in. Verify that work has been done correctly
and control wiring and ductwork are in place.
w Inspect and test completed systems to verify operation and ensure components
meet NBC requirements.
w Follow up with trades to prevent the same problems on future jobs.
Builder Responsibilities
Builders are responsible for ensuring ventilation system performance and confor-
mance to codes and standards. Thus builders need a good general understanding of
residential ventilation systems and equipment even though they rely on knowledge-
able designers and trades people to provide detailed design knowledge.
Training for residential ventilation system design and installation is available through
some colleges, agencies and manufacturers. The Heating, Refrigerating and Air Condi-
tioning Institute of Canada (HRAI) (www.hrai.ca telephone 800-267-2231) has national
trades training and certification programs in place for residential heating, cooling and
ventilation system designers and installers.
Equally important is the builder’s obligation to inform the homeowner how to operate
and maintain the ventilation system. The builder should provide the homeowner with
ventilation equipment literature, schematics and information on its operation (e.g.,
the appropriate sections from this manual) and the name of the ventilation system
installer.
A10
INTRODUCTION
B
Introduction
The introduction discusses the need for ventilation, the elements of an indoor air quality strategy
and the cost of operating or not operating a residential mechanical ventilation system.
B1
INTRODUCTION
❏ local exhaust w local exhaust (e.g., bathroom fans and range hoods).
❏ general ventilation
All of these factors need to be considered for effective indoor air quality management.
Extraordinary measures may be required in dwellings with chemically sensitive oc-
cupants.
Cost of Ventilating
Energy is required to supply, condition (i.e., heat, cool, humidify and filter) and
distribute outdoor air, regardless of whether the air enters by fan or air leakage. A well
designed and controlled mechanical ventilation system will minimize the amount
of outdoor air needed to provide good indoor air quality, and thus minimize the cost
conditioning ventilation air.
On the other hand, there are costs associated with not properly ventilating houses.
Poor indoor air quality can affect occupant comfort and health. Failure to properly con-
trol moisture levels during cold weather can lead to condensation on and in windows,
walls and attics and related damage to the building .
The ventilation strategy and type of equipment selected to provide ventilation will
affect both the cost to install and the cost to operate the ventilation system. Incorpo-
rating heat recovery may increase ventilation system first costs but can substantially
reduce the operating cost and occupant discomfort, so the occupants are much more
likely to use the ventilation system as intended. Distributing ventilation air using a
furnace fan will generally require considerably more fan energy than only using the
ventilation system fan and dedicated ductwork for distribution. Selecting energy ef-
ficient exhaust, supply and distribution fans will reduce energy costs.
B2
INTRODUCTION
The tables and examples below provide comparative cost data for conditioning and distributing ventilation air in vari-
ous climates, using various strategies. The data are based on a continuous ventilation rate of 30 L/s. This is within the
Normal Operating Exhaust Capacity of houses with three to five bedrooms. Total cost to continuously ventilate can be
determined by adding the cost to condition air from Table A to the cost to distribute ventilation air from Table B. Heat
recovery of 70% is assumed, which is in mid range for HRV effectiveness.
TABLE B - APPROXIMATE FAN ENERGY COST TO SUPPLY AND DISTRIBUTE VENTILATION AIR $/YEAR
$/kWh $ 0.06 $ 0.08 $ 0.10 $ 0.12 $ 0.15 $ 0.20
Distribution Cost of Electricity Used to Distribute Ventilation Air
Strategy $/Year
Cont PSC $ 232.56 $ 310.08 $ 387.60 $465.12 $ 581.40 $ 775.20
Cycled PSC $ 97.56 $ 130.08 $ 162.60 $ 195.12 $ 243.90 $ 325.20
Cont ECM $ 97.56 $ 130.08 $ 162.60 $ 195.12 $ 243.90 $ 325.20
Cycled ECM $ 63.81 $ 85.08 $106.35 $ 127.62 $ 159.53 $ 212.70
Fully ducted $ 52.56 $ 70.08 $ 87.60 $ 105.12 $ 131.40 $ 175.20
HRV
Cont – Continuous furnace fan operation. Principal ventilation fan operates continuously
Cycled – Furnace fan cycles 1/3 time on, 2/3 off. Principal ventilation fan operates continuously
PSC – Permanent Split Capacitor furnace fan motor
ECM – Electronically commutated (i.e., energy efficient) furnace fan motor
B3
INTRODUCTION
In either of the above examples, all the electricity used by the furnace fan is converted
to heat which offsets space heating. At the energy prices used in this case, the energy
cost offset for space heating would be about one half the amount spent to operate the
furnace fan.
B4
INTRODUCTION
C
Code Requirements
This section of the manual presents an overview of the residential ventilation requirements of the
2005 NBC.
C1
What Does the Code Cover?
Part 9 of the NBC, Housing and Small Buildings Section 32 Ventilation, states:
w all Part 9 residential occupancies require provisions for either natural or mechanical
ventilation for the non-heating-season
w all Part 9 dwelling units with electrical power are required to have mechanical
ventilation for the heating-season
w self contained ventilation systems serving only one dwelling unit can be designed
in accordance with either the requirements in Section 9.32 of the NBC or “good
practice” such as that described in CAN/CSA-F326 “Residential Mechanical
Ventilation Systems”
w ventilation systems for residential suites in Part 6 buildings (i.e., gross floor areas
greater than 600 m2) with self-contained ventilation systems may be designed
following either ASHRAE Standard 62 “Ventilation for Acceptable Indoor Air Quality”
or Section 9.32 of the NBC.
Section 9.32 addresses ventilation requirements, exhaust requirements, protection
against depressurization, duct sizing, outdoor air distribution, fan ratings, heat and
energy recovery ventilators, outdoor intake and exhaust hoods and system installation.
Limitations
Mechanical ventilation systems which serve two or more dwelling units or suites must
be designed in compliance with Part 6 of the NBC (i.e., ASHRAE Standard 62 “Ventilation
for Acceptable Indoor Air Quality”).
Ventilation systems for Part 9 dwelling units with more than five bedrooms must
comply with “good practice” such as that described in CAN/CSA F326.
The requirements in Section 9.32 are not intended to address the ventilation needs of
spaces or activities with strong airborne contaminant sources.
Meeting the requirements of Section 9.32 does not guarantee acceptable air quality,
especially for individuals with acute chemical sensitivities or if occupants smoke.
C2
CODE REQUIREMENTS
Natural Ventilation
Dwellings not supplied with electricity must be provided with natural ventilation. Natu-
ral ventilation is provided by opening windows or other vent areas to a space.
Habitable rooms and spaces not provided with natural ventilation as specified in Table
9.32.2.3. “Air Change Rate” to control summer overheating must have mechanical
ventilation. Ventilation rates for spaces that do not have natural ventilation and are
mechanically cooled (i.e., air-conditioned) are specified in Table 9.32.2.3. “Air Change
Rate”. Spaces that do not have natural ventilation or mechanical cooling must have a
mechanical ventilation system with the capacity to supply at least one air change per
hour of outdoor air to the space or to exhaust at least one air change per hour from the
space.
The NBC has specific requirements for the unobstructed, openable ventilation areas
that must be provided for code conformance.
C3
CODE REQUIREMENTS
TABLE 9.23.3.3
“NORMAL OPERATING EXHAUST CAPACITY OF PRINCIPAL VENTILATION FAN”
Number of Bedrooms Capacity of Principal
Normal Operating Exhaust
in Dwelling Unit Ventilation Fan
1 16 24
2 18 28
3 22 32
4 26 38
5 30 45
More than 5 System must comply with CAN/CSA-F326-M
Ventilation air to replace the air exhausted by the principal ventilation fan can be
supplied to a dwelling unit as infiltration air through the building envelope or through
a supply air duct. The supply air duct may be connected to the intake side of a forced
air heating system or to an auxiliary supply fan. In all cases there is a requirement for
the principal ventilation system to include measures to distribute the ventilation air
throughout the dwelling unit.
Distribution of ventilation air in dwellings with ventilation systems coupled to the
forced air heating system is achieved by requiring that the furnace fan operate
anytime the principal ventilation system is activated. There may be a requirement to
temper outdoor air introduced into a forced air heating system. This is discussed later
in this section of the manual.
In dwellings where an auxiliary supply fan system provides outdoor air for ventilation,
the supply fan must operate whenever the principal ventilation system is operated
and must turn off whenever the principal ventilation system is turned off.
C4
CODE REQUIREMENTS
In houses with exhaust only ventilation, outdoor/ventilation air enters the house by
infiltration. A forced air distribution system must be operated to mix this outdoor air
throughout the house. The forced air distribution system must either be interlocked
so its circulation fan operates whenever the principal ventilation fan is activated or,
alternatively the forced air distribution system can be equipped with a control that
automatically activates the circulation fan at user-selected time intervals. Minimum
airflow rates for circulation fans in exhaust only ventilation systems is five times the
minimum Normal Operating Exhaust Capacity of Principal Ventilation Fan as specified
in Table 9.32.3.3.
w the principal ventilation system exhaust fan can be manually switched to “high”
from a switch located in the kitchen and the exhaust flow rate on “high” is at least
2.5 times the minimum Normal Operating Exhaust Capacity.
Exhaust fans serving bathrooms and kitchens must be controlled by manual switches
located in the rooms served. This includes applications in which the principal ventila-
tion system exhaust fans provide bathroom exhaust requirements.
C5
CODE REQUIREMENTS
w the only types of fuel-fired space- or water-heating appliances installed are direct
vented, mechanically vented or solid-fuel-burning appliances.
It will generally be easier and less costly to avoid the need to install make-up air sys-
tems than to comply with the requirements for them.
C7
CODE REQUIREMENTS
w if connected to the house electric system, not have a disconnect switch between
the CO alarm and the breaker in the electrical panel
w be mechanically fastened on or near the ceiling, as recommended by the
manufacturer
C8
CODE REQUIREMENTS
Where air from the principal ventilation system is introduced into the house through
dedicated ductwork, the air must be tempered to at least 12oC unless it is supplied by
an HRV or ERV. This ventilation air must be delivered to rooms through outlets located
in the ceiling or on the wall at least 2 meters above the floor. These outlets must be
designed to promote diffusion (mixing with room air) across the ceiling.
C9
Untempered make-up air can be introduced into normally unoccupied areas of the
dwelling unit. Otherwise it must be tempered to at least 12oC before being introduced
to either occupied spaces or a supply duct system. Make-up air introduced to occupied
spaces must be delivered through outlets located in the ceiling or on the wall at least
2 meters above the floor. These outlets must be designed to promote diffusion across
the ceiling.
While HRVs and ERVs may be economical for pre-heating ventilation air, they are gen-
erally not practical or economical for exhaust air make-up systems. Residential HRVs
and ERVs are not suitable for dirty applications such as range hoods and clothes dry-
ers. HRVs and ERVs are discussed in more detail in the section titled “Heat and Energy
Recovery Ventilators”. Specifying and installing heating coils (hydronic or electric) and
related controls is a job for a qualified designer or contractor.
C10
SYSTEM COMPONENTS
D
System Components
This section provides information on some specific components of ventilation systems.
Information is included on:
w Fans
w Exterior Hoods
w Dampers
w Ductwork
D1
SYSTEM COMPONENTS
Fans
Ventilation systems designed to meet Section 9.32 Ventilation of the NBC must have
exhaust fans and may require fans to supply outdoor air and make up air. When select-
ing fans, several criteria must be considered. These are discussed in detail below.
FAN CERTIFICATION
Fans must conform to Canadian Standards Association (CSA) C22.2 No. 113-M, “Fans
and Ventilators”. This standard includes requirements for electrical safety, fire and
personal injury. CSA C22.2 No. 113-M does not include testing for airflow performance
or noise. Fans that have been certified to CSA 22.2 No. 113-M are identified with the
Association’s certification mark.
Condensation on cold surfaces and electrical components of fans can create an electri-
cal safety hazard. For this reason, fans handling untempered outdoor air must be
designed and approved by the manufacturer for such use.
Air handling performance of fans required under Section 9.32 must be rated in ac-
cordance with:
w CAN/CSA C260-M “Rating the Performance of Residential Ventilating Equipment” or
HVI916 “Airflow Test Standard” for fans
w CAN/CSA-C439 “Rating the Performance of Heat/Energy-Recovery Ventilators” for
ERVs
Section 9.32 also imposes noise restrictions on required fans that are located in or
near normally occupied spaces. This is to reduce the likelihood that fan noise will be a
reason that occupants do not properly ventilate their homes. Where compliance with
sound ratings is required, fan sound ratings must have been determined using CAN/
CSA C260-M or HVI 915 “Procedure for Loudness Rating of Residential Fan Products”.
Airflow performance and noise data for residential fans is published in the Home
Ventilating Institute “Certified Home Ventilating Products Directory”. This directory is
available on-line at www.hvi.org or from
Heating, Refrigeration and Air Conditioning Institute of Canada
2800 Skymark Avenue, Building 1, Suite 201
Mississauga, Ontario, Canada L4W 5A6
Tel 1-800-267-2231 or (905) 602-4700 Fax (905) 602-1197
In Section 9.32, the ESP at which a fan’s airflow must be rated is based on the applica-
tion of the fan and the nature of the duct system to which it is connected. Specific
requirements are:
w all required fans with ductwork connected to both the fan inlet and outlet side must
have their airflow rated at an ESP of at least 100 Pa (0.4 in W.C.). This type of ap-
plication will include most inline fans and HRV/ ERV installations.
w principal ventilation fans in exhaust-only systems with ductwork connected only
on one side of the fan must have their airflow rated at an ESP of at least 62 Pa (0.25
in W.C.). Typical examples of this application would be rangehoods and/or ceiling
mount bathroom fans when they are used as principal ventilation fans.
w all other required fans must have their airflow rated at an ESP of at least 25 Pa (0.1
in W.C.). This includes rangehoods and ceiling mount bathroom fans used to meet
supplemental exhaust requirements.
D3
SYSTEM COMPONENTS
FAN CONFIGURATION
PROPELLER FANS are inexpensive fans suitable for low pressure applications. Com-
mon applications are low cost bathroom fans, low cost range hoods and through the
wall fans. As a rule, ductwork should only be connected to the fan outlet side since air
flow decreases rapidly as the amount of ductwork or number of fittings increases.
SQUIRREL CAGE FANS are less sensitive to the amount of ductwork and number of
fittings than propeller fans. They are suitable where ductwork is connected both up-
stream and downstream of the fan. Squirrel cage fans are commonly installed in HRVs
and ERVs, better quality range hoods and central exhaust systems.
IN LINE CENTRIFUGAL FANS (centrifugal fans that fit in line with the ductwork) are
popular as central exhaust fans because of their convenient installation, good perfor-
mance and quiet operation.
FAN COSTS
INSTALLED COST or the cost to a builder of better quality fans is often lower than for
budget fans because better quality fans are often easier to install and are less likely to
result in a callback.
OPERATING COST is the occupant’s cost to run and maintain a fan. Better quality fans
are likely to consume less electricity and require less maintenance. Oversized fans
use more electricity and increase heating and cooling requirements. Size and efficien-
cy are important selection criteria for fans which will operate several thousand hours
per year.
D4
SYSTEM COMPONENTS
w screens, grilles and/or filters must be easily removable for cleaning, without the
need for special tools
w the area of the opening in a hood must be at least as large as the required area of
the duct served
w where screens or grilles with a mesh size of less than 6mm are installed in an open-
ing, the area of the opening at the screen or grille must be larger than the required
area of the duct served: 3 times the required area of the duct served for mesh sizes
of less than 4 mm (5/32 inch); 2 times the area of the duct served for mesh sizes
between 4 and 6 mm (5/32 to ¼ inch)
w Intake openings must have corrosion resistant rodent/bird screen or grille. Minimum
450 mm
w Locate the bottom of the inlet at least 450 mm (18 inches) above finished grade
or other nearer horizontal surface and above the maximum depth of expected
snow accumulation.
w Air intakes will pick up debris and lint. Openings must be accessible for cleaning
(not under low decks).
D5
SYSTEM COMPONENTS
GOOD PRACTICE
Fuel codes specify minimum clearances between penetrations in the envelope (e.g.,
windows and intake and exhaust hoods) and combustion appliance flue vents, gas
meters, oil fill pipes, etc. Marking the location of all penetrations and outside services
on the drawings will go a long way toward ensuring that clearance restrictions are not
violated. Do not locate exhaust outlets where condensation from the exhaust air can
cause a hazard (e.g., ice on a sidewalk).
When specifying intake or exhaust hoods, consider:
w Ease of sealing the hood to the building rain screen and air barrier to prevent water
and air leakage into the building envelope.
w method of connecting the duct to the hood and hood to the wall.
TYPE OF GRILLE
Common “heating” grilles are designed to direct air into room areas normally occupied
by people, that is the “occupied zone”. “Air-conditioning” grilles direct cool air along the
ceiling or wall, allowing it to mix with space air before entering the occupied zone. If
the air supplied will be cool at times, air-conditioning grilles are appropriate.
SIZE
Undersized grilles restrict air flows and may be noisy. The grille and terminal box
should have a free area at least equal to the cross sectional area of the connected
duct. Where free area data is not available from a grille manufacturer, it may be esti-
mated as 50% of the face area of the grille, 25% if the grille includes a filter.
D6
SYSTEM COMPONENTS
MOUNTING LOCATION
EXHAUST GRILLES IN KITCHENS (except for range hoods) must be located in the
ceiling or on a wall at least 2 meters above the floor. Exhaust grilles located within 3
meters horizontally of a range must be equipped with grease filters at the intake end.
PRINCIPAL EXHAUST AIR INTAKES located in kitchens, bathrooms and water closets
must be located in the ceiling or on a wall at least 2 meters above the floor. This re-
quirement will generally preclude using a rangehood as the principal ventilation fan.
SUPPLY AIR GRILLES should be selected and located to avoid drafts in the occupied
zones. For ventilation systems not coupled to forced air heating systems, supply air
outlets must be located in ceilings or on walls at least 2 meters above the floor and
installed to promote diffusion (i.e., mixing with space air) across the ceiling before the
air enters the occupied zone.
Dampers
Dampers control air flow by obstructing the air flow passage to reduce or stop air flow
in a duct. Air flow in one branch of a duct system can be increased by “dampering
down” air flow in another branch. While the air flow in some ducts can be increased
by sacrificing air flow to others, the net result will be a reduction in total air flow and
perhaps an increase in noise levels. Dampers cannot compensate for undersized fans
or for ducts which excessively restrict air flow.
BALANCING DAMPERS are required in all ventilation system branch ducts not fitted
with registers. Balance dampers must be accessible and have a lock and a position
indicator.
BACKDRAFT DAMPERS prevent air from flowing backwards in ducts. Exhaust systems,
except HRVs and ERVs, must have backdraft dampers to reduce air leakage when the
fan is off. Poorly designed backdraft dampers may stick or freeze open or shut. Back-
draft dampers need to function smoothly and seal tightly when closed. The fan must
overcome the weight and balance of the damper. A heavy or stiff damper will restrict
air flow.
MOTORIZED OR POWER DAMPERS provide automatic and positive duct opening and
closure. The damper drive motor may operate at line voltage or low voltage and must
be interlocked with the fan they serve. Motorized dampers which handle untempered
outdoor air must be approved by the manufacturer for that use.
D7
SYSTEM COMPONENTS
D8
SYSTEM COMPONENTS
SPECIAL REQUIREMENTS
Condensation on the cold surfaces and electrical components of fans can create an
electrical safety hazard. For this reason, electrical devices which handle untempered
outdoor air must be designed and approved by their manufacturer for such use. Make
up air ducts which carry untempered air through heated spaces must be insulated and
have an air/vapour barrier on the outside surface to minimize surface condensation.
AVOIDING COMPLAINTS
Introducing cool air into an occupied space, even in compliance with NBC require-
ments, has the potential to cause discomfort. Discomfort can be reduced by:
w eliminating the need for make up air systems by using direct-vented and/or me-
chanically-vented fuel-fired space- and water-heating appliances and/or where soil
gas is a problem, installing an active soil gas mitigation system
w using more than one pre heating or tempering measure and using good design and
installation practices (e.g., mixing outdoor air with house air and then introducing it
to a space through high wall air-conditioning type diffusers or mixing HRV/ERV sup-
ply air with house air in a forced air system)
D9
SYSTEM COMPONENTS
MODES OF OPERATION
MANUAL OPERATION requires the occupant to turn the ventilation system on and off. It
ensures the system is only turned on when the occupant turns it on.
AUTOMATIC OPERATION uses controls such as time clocks, dehumidistats and occu-
pancy sensors to operate the ventilation system.
CONTINUOUS OPERATION ensures that the house is always ventilated, but may result
in over ventilation at times. All ventilation systems must include manual controls, even
if the occupant installs automatic controls or plans to operate the ventilation system
continuously.
HIGH/LOW OPERATION uses a two speed fan which normally operates on low speed,
but on call for increased ventilation, switches to high speed. High speed operation may
be initiated by manual and/or automatic controls.
TYPES OF CONTROLS
ON/OFF SWITCHES give occupants control over when fans operate. They are inexpen-
sive and their operation is well understood. However, they do not ensure that fans will
be turned on and off as required.
TIMER SWITCHES (mechanical or electronic) have operating time ranges from a few
minutes to several hours. A timer switch turns the power off at a predetermined time
after the fan has been activated. Spring wound “crank timers” allow the user to select
the operating time with each use.
Electronic “touch timers” have a pre set period of operation, which can be adjusted.
Timer switches do not ensure that fans are operated when needed, but they ensure
that they will be turned off (or speed reduced in the case of High/Low operation).
DELAYED OFF SWITCHES are combination manual/timer switches. The fan is activated
manually. The user can then turn the fan off immediately or activate a timer which will
run the fan for a predetermined time period before turning it off. This has the advan-
tage of continuing ventilation after the occupant has left the room without allowing the
fan to run indefinitely.
D10
SYSTEM COMPONENTS
TIME CLOCKS which control the ventilation system based on time of day and day of
week may be appropriate where occupancy follows a regular schedule. The timer can
be scheduled to turn the ventilation system off after occupants normally leave and
turn it on again shortly before they return. Twenty four hour and seven day timers with
“holiday” over rides are readily available.
DEHUMIDISTATS operate the ventilation system (or activate high speed) when humid-
ity levels exceed the control setpoint. This may help control indoor humidity, but does
not ensure control of other pollutants.
It is common to adjust the dehumidistat to control window condensation, therefore the
appropriate humidity setpoint will vary with outdoor temperature. Occupants should
be instructed to lower the dehumidistat setting in the cold weather to reduce window
condensation and to turn the dehumidistat to the “off” position in the summer.
In dwellings with humidifiers, occupants should be advised to set the humidistat at
least 15% lower than the dehumidistat.
DEMAND CONTROLS operate the ventilation system only when needed. The ideal ven-
tilation system would monitor and control the level of all contaminants in the house
air. To date, only sensors for humidity, carbon dioxide and carbon monoxide have been
commercially developed and marketed for residential applications.
Fan cycling controls that cycle the principal ventilation system and/or furnace circula-
tion fan on and off on a user specified schedule are commercially available and are
permitted. These controls can automatically provide an average ventilation rate of less
than the full capacity of a single speed ventilation fan. They can be used to inter-
mittently operate a furnace circulation fan, meeting NBC requirement to distribute
ventilation air throughout the house while reducing the energy required to operate the
circulation fan.
OCCUPANCY SENSORS operate the ventilation system when they sense when some-
one is in a space. They are available for residential ventilation system control and are
allowed under the NBC.
MULTIPLE CONTROLS are permissible and often desirable. For example, a single
supplemental exhaust fan may serve more than one bathroom provided that a manual
switch is located in each bathroom. Automatic and manual control of a fan is also pos-
sible.
Multiple controls can be parallel wired so that any control can turn on the ventilation
system, regardless of the setting of others. If regular on/off switches are used, all con-
trols must be in the off position in order to turn a ventilation system component off.
D11
SYSTEM COMPONENTS
ELECTRICAL INTERCONNECTIONS
The code requires that certain fans be controlled to operate in conjunction with other
devices. These include make-up air systems, furnace circulation fans, and auxiliary
supply fans. Methods of controlling fans include using:
w relays or double pole double throw switches,
Relays and double pole double throw switches can be used to simultaneously control
more than one electrical device. Relays can operate several sets of contacts at once
and may operate at line voltage or at low voltage. Double pole double throw switches
are light switch type devices which can simultaneously switch devices in two sepa-
rate electrical circuits.
Some exhaust devices have an integral switched electrical outlet or terminals which
are powered whenever the exhaust device is operated. This allows a make up air fan to
be easily electrically interconnected to the exhaust device.
While a knowledgeable electrician can make electrical connections inside most electri-
cal devices, this may invalidate warranties and will require special inspections and
approvals by an electrical inspector. It will be easiest if equipment with the needed
contacts or relays already factory installed are selected.
A current sensor on the power line to an electric device is a recommended method to
electrically interconnect it to devices that do not have switched electrical connections.
The current sensor senses when electricity flows in a power line. It can control a relay
which operates the second device when the first device is turned on.
An air flow sensing switch or pressure sensor located in the outlet of the first device
can also be used to control the second device. These are less desirable solutions
because flow sensing switches may restrict air flows or be immobilized by lint, dirt or
grease in the exhaust stream.
D12
SYSTEM COMPONENTS
SELECTING AN HRV/ERV
The performance of various HRV/ERVs can be compared based on the CAN/CSA C439
test results. Equipment certified by HVI have undergone standard tests to determine
air movement capacity, heat recovery efficiency and cold weather performance char-
acteristics.
When selecting an HRV/ERV consideration should be given to:
w installation convenience (e.g., top vs side ducts),
w whether the HRV/ERV will depressurize the house during defrost sufficiently to
require make-up air, ability of the equipment to meet the ventilation requirements,
heat recovery efficiency and ventilation performance during cold weather operation,
w ease of measuring and setting airflows (some units have built in balance dampers
and flow measuring stations), availability of qualified installers, service people and
parts, and installed cost..
D13
SYSTEM COMPONENTS
Ductwork
SIZING
Table 9.32.3.11.A. “Equivalent Duct Sizes” is a simplified duct sizing chart. It permits a user to determine allowable
duct sizes (i.e., diameters and lengths) using fan external static pressure and required airflow. Alternatively, detailed
duct system designs are permitted and will often result in smaller duct diameters. Detailed duct system designs are
required for applications that fall outside the limits of Table 9.32.3.11.A.
D14
SYSTEM COMPONENTS
w “maximum airflow in duct” refers to the maximum airflow rate that a given section of
duct (branch or trunk) must provide to satisfy the ventilation system design
w “fan’s ESP” or “fan’s external static pressure” refers to the external static pressure at
which the fan is rated to achieve the maximum airflow rate that the fan is required
or intended to provide
w where flexible duct is used, it may be sized by choosing the next higher diameter in
Table 9.32.3.11.A or by choosing the diameter for a duct twice as long as the actual
length
w where rectangular duct is used in place of round duct, it shall be selected according
to Table 9.32.3.11.B “Equivalent Duct Sizes”
DUCT MATERIALS
Ducts connected to a forced air heating system and range hoods must be made of
noncombustible materials. Ductwork not connected to a heating device may be made
of combustible materials. Ducts serving bathrooms or water closets must be con-
structed of a material impervious to water. Flexible ducts must meet the requirements
for Class 1 duct materials in CAN/ULC-S110-M, “Tests for Duct Materials”.
Exhaust intakes located within 3 meters of a range must be equipped with a grease fil-
ter at the intake end. Ductwork for range hoods and range top fans must have a filter at
the intake end and must be noncombustible and corrosion resistant and lead directly
to the outdoors without connection to other exhaust ducts or fans.
D15
SYSTEM COMPONENTS
WORKMANSHIP
Ductwork must be permanently supported or clipped to prevent sagging, excessive
movement and vibration. Use of vibration isolating connections between fans and
ducts is recommended. These are flexible fabric collars between fans and ductwork
that prevent fan vibration from being transmitted to the connected ductwork.
Assemble ductwork joints and fittings so as to inhibit air leakage. Joints between sec-
tions of round ductwork should be lapped at least 25 mm (1 inch) and mechanically
fastened.
Exhaust ducts passing through unheated spaces should be sloped to the outdoors to
prevent condensation dripback. HRV/ERV cold side exhaust ducts should be sloped
and supported to prevent water accumulation in low spots.
Good workmanship is demonstrated by straight duct runs with a minimum of bends
and elbows and tight fitting, mechanically fastened joints. Ductwork should be cleared
of debris to ensure airflow and air quality standards can be met. It is desirable to have
permanently install flow measuring stations for both the supply and return airflow
streams for HRV/ERVs. These are built into some HRV/ERVs. The HRAI Residential Me-
chanical Ventilation Guide should be followed as a guide to good practice.
A builder should ensure that the house designer is sensitive to mechanical system
requirements. A modest amount of planning and trades coordination will go a long way
in facilitating good workmanship, tidy installations and effective ventilation systems.
TERMINATIONS
Exhaust and ventilation ducts must not terminate in closed spaces such as crawl-
spaces, attics, soffits and garages. The air quality in these locations makes them an
unacceptable source for outdoor air, and the problems caused by condensation from
exhaust air during cold weather makes them unacceptable for exhaust outlets.
D16
SYSTEM OPTIONS
E
System Options
Detailed descriptions are provided for four basic ventilation system options which meet the National
Building Code requirements. Within each of these detailed descriptions are variations of the basic
options.
E1
SYSTEM OPTIONS
SYSTEM OPTIONS
Builders are responsible to ensure that ventilation systems installed in new dwellings meet the NBC. Builders may
choose to design ventilation systems or may select from the system options described in this section of the manual.
In any case, the builder should consult with the homeowner to ensure that the ventilation system selected will meet
the owners’ needs and expectations. He should also confirm that the systems will meet local code requirements.
The system options described in this manual will help builders meet the NBC requirements with a minimum of confu-
sion. One or more of these ventilation system options will be suitable for most dwellings, although some dwellings
may require custom designed ventilation systems.
The following pages contain specific information on each ventilation system option, including:
w Ventilation System Decision Trees to help users determine which ventilation system design approach to use (i.e.,
Part 6, Part 9 or CAN/CSA-F326) and which Part 9 ventilation system options may be used.
w A four page information pull out for each of the Part 9 ventilation system options described. The pull outs describe
the basic functions and controls for each ventilation system, provide data needed to size and select ventilation
system components and give a checklist of items for consideration when planning and installing the ventilation
system.
Users of this manual are encouraged to photocopy the pullouts or any other part of the manual that will help explain
ventilation system design, installation or operation to builders, subcontractors and customers.
E2
SYSTEM OPTIONS
E3
SYSTEM OPTIONS
CONTROLS VARIATIONS
A centrally located manual switch labelled “Ventila- ADD AN OUTDOOR-AIR SUPPLY DUCT COUPLED TO A
tion Fan” operates principal exhaust fan at the Normal FORCED AIR HEATING SYSTEM - NBC Options A and E
Operating Exhaust Capacity. The furnace circulation fan upgrade system performance by adding an outdoor air
is controlled to operate whenever principal exhaust fan intake duct connected to the furnace return duct. An
is operated, or alternately the forced air system can be appropriately sized outdoor air intake supply duct will
equipped with a control that automatically operates the provide more uniform distribution of outdoor air and
furnace fan at user-selected time intervals. reduced likelihood of cold drafts causing occupant dis-
A manual fan control switch is required in each room comfort. The temperature of the mixture of house and
served by a supplemental exhaust fan. Where the outdoor air entering the forced air heating system at the
kitchen supplemental exhaust requirement is met by winter design condition must be warmer than 15oC un-
the principal exhaust fan, the control in the kitchen must less the manufacturer of the forced air heating system
be labelled “Kitchen Exhaust”. specifically allows lower mixed air temperatures.
Principal exhaust fans and supplemental exhaust fans NBC VENTILATION SYSTEM OPTION A - NBC Option A uses
may also be activated by automatic controls (e.g., dehu- a single speed PV fan and requires use of some supple-
midistats), provided the manual controls will operate the mental exhaust fans
fans regardless of the setting of the automatic controls
NBC VENTILATION SYSTEM OPTION E - NBC Option E uses
and the fans do not operate when all controls are in the
a PV fan with a speed control that operates the PV fan
off position.
at the Normal Operating Exhaust Capacity on low speed
Make-up air systems must operate automatically when and at an exhaust rate of at least 2.5 times the mini-
the device they serve is operated. mum Normal Operating Exhaust Capacity on high speed,
allowing it to meet the principal exhaust flow require-
BASIC COMPONENTS SPECIFICATION ments and the supplemental exhaust requirements
The principal ventilation fan must be approved by the of the kitchen and all bathrooms, without requiring
manufacturer for continuous operation. additional or supplemental exhaust fans.
Required fans must meet specific capacity and sound ADD AN OUTDOOR-AIR SUPPLY FAN - Another variation is
ratings. to install an auxiliary supply fan in the outdoor air sup-
Fans and other components exposed to untempered ply duct described above to further improve control over
outdoor air must be approved for such use. the supply and distribution of ventilation air.
Carbon Monoxide alarms must conform to CAN/CGA
6.19-M “Residential Carbon Monoxide Alarming Devices”.
Choosing Brushless DC motors for fans and properly
selecting the furnace fan speed to distribute ventila-
tion air will significantly reduce the fan energy used for
ventilation.
E4
SYSTEM OPTIONS
1 |COMBUSTION APPLIANCE
REQUIREMENTS
w fuel-fired fireplaces must be of the direct-vented
5|SUPPLY AIR INTAKE AND
EXHAUST OUTLET REQUIREMENTS
w locate outdoor air intakes well away from con-
type tamination sources (e.g., automobile exhaust,
w other fuel-fired space-heating for water-heat-
building exhaust) and at least 900 mm from
ing appliances must be either direct-vented or combustion appliance vents, oil fill pipes, gas
mechanically-vented types meters, etc.
w outdoor air intakes must be accessible for ser-
w solid-fuel-fired combustion appliances
(e.g., wood stoves) are not permitted vice
w label outdoor air intake hoods for easy
2| CO ALARM
REQUIREMENTS
w install a carbon monoxide alarms in or near
identification
w exhaust ducts must not discharge into enclosed
spaces
bedrooms of dwelling units with
• fuel-fired space- and/or water-heating appliances
installed in the dwelling unit or in connected spaces
• attached garages
6|PRINCIPAL VENTILATION
FAN REQUIREMENTS
w centrally located manual switch labelled “Ventila-
E5
SYSTEM OPTIONS
8|AIR DISTRIBUTION
SYSTEM REQUIREMENTS
9.32.2.3 if space is air-conditioned
|
9 DUCT REQUIREMENTS
VENTILATION SYSTEM
w outdoor air supply ducts directly connected to
furnace return plenums must be connected
downstream of all return branch ducts and at
least 3 m (10 ft.) upstream of furnace unless
connected through an acceptable mixing device
w equip all exhaust air intakes located within 3
meters horizontally of a range with a readily
serviceable grease filter at the intake end
w size ventilation system ductwork using NBC
Tables 9.32.3.11.A. and B. or Section 9.33
w insulate ducts carrying untempered outdoor air
through heated spaces or exhaust air through
unheated spaces to at least RSI 0.5 (R 2.8)
E6
SYSTEM OPTIONS
Damper or
bird screen
at outside
wall
Minimum
100 mm
(4”) above
finished grade
E7
SYSTEM OPTIONS
E8
SYSTEM OPTIONS
E9
SYSTEM OPTIONS
|COMBUSTION APPLIANCE
1 REQUIREMENTS |SUPPLY AIR INTAKE AND
5 EXHAUST OUTLET REQUIREMENTS
w provide make-up air for each exhaust device oth- w locate outdoor air intakes well away from con-
er than Principal Ventilation Fan operating at its tamination sources (e.g., automobile exhaust,
Normal Operating Exhaust Capacity if non-solid- building exhaust) and at least 900 mm from
fuel burning appliances other than direct-vented combustion appliance vents, oil fill pipes, gas
and mechanically vented types are installed meters, etc.
w outdoor air intakes must be accessible for ser-
2| CO ALARM
REQUIREMENTS
w install a carbon monoxide alarm in each room
vice
w label outdoor air intake hoods for easy identifica-
E10
SYSTEM OPTIONS
| SUPPLEMENTAL EXHAUST
7 REQUIREMENTS
w locate supplemental exhaust fan intakes (except
9|VENTILATION
REQUIREMENTS
SYSTEM DUCT
8| AIR DISTRIBUTION
SYSTEM REQUIREMENTS
space is air-conditioned
11|MISCELLANEOUS
w forced air distribution system circulation fans
must REQUIREMENTS
• move at least 5 times the actual Normal Operating w Ventilation equipment in unheated spaces
Exhaust Capacity
installed to avoid condensation on fans and mo-
• operate automatically when the HRV/ERV operates
tors as per manufacturer’s instructions
w Minimum allowable mixed air temperature enter-
ing the furnace is the lesser of 15oC and the
minimum allowed by the furnace manufacturer
w Supplemental exhaust fans must be controlled
by manual switch in each room served
E11
SYSTEM OPTIONS
Damper or
bird screen
at outside
wall
Minimum
100 mm
(4”) above
finished grade
E12
SYSTEM OPTIONS
E13
SYSTEM OPTIONS
E14
SYSTEM OPTIONS
1 |COMBUSTION APPLIANCE
REQUIREMENTS
w provide make-up air for each exhaust device
5|SUPPLY AIR INTAKE AND
EXHAUST OUTLET REQUIREMENTS
w locate outdoor air intakes well away from con-
other than HRV/ERV operating at its Normal tamination sources (e.g., automobile exhaust,
Operating Exhaust Capacity if non-solid-fuel building exhaust) and at least 900 mm from
burning appliances other than direct-vented and combustion appliance vents, oil fill pipes, gas
mechanically vented types are installed meters, etc.
w outdoor air intakes must be accessible for ser-
2| CO ALARM
REQUIREMENTS
w install a carbon monoxide alarm in each room
vice
w label outdoor air intake hoods for easy identifica-
6|HRV/ERV
• fuel-fired space- and/or water-heating appliances
installed in the dwelling unit or in connected spaces
• attached garages REQUIREMENTS
w centrally located manual switch labelled “Ventila-
E15
SYSTEM OPTIONS
| SUPPLEMENTAL EXHAUST
7 REQUIREMENTS |VENTILATION SYSTEM
9 DUCT REQUIREMENTS
w locate supplemental exhaust fan intakes (except w equip all exhaust air intakes located within 3
range hood) in wall at least 2 meters above the meters horizontally of a range with a readily
floor or in ceiling serviceable grease filter at the intake end
w 50 L/s (105 cfm) supplemental exhaust is w size ventilation system ductwork using NBC
required from kitchens unless: Tables 9.32.3.11.A. and B. or Section 9.33
• the only HRV/ERV exhausts intake is in the kitchen, w insulate ducts carrying untempered outdoor air
10|NATURAL
manual control in the kitchen that increases the rate
of exhaust to at least 2.5 times the minimum Normal
Operating Exhaust Capacity. VENTILATION
w provide opening windows for natural ventilation
w 25 L/s (50 cfm) supplemental exhaust is re-
quired from bathrooms not served by HRV/ERV to each habitable space
exhaust OR
w Supplemental exhaust fans must be controlled
w provide mechanical ventilation of at least 1.0
by manual switch in each room served
ACH, or at the air change rates in NBC Table
w Sound ratings for supplemental exhaust fans 9.32.2.3 if space is air-conditioned
with less than 1 meter between themselves and
visible interior of bathrooms must be less than
2.5 sones CSA-C260 or 3.5 sones HVI 915 11|MISCELLANEOUS
REQUIREMENTS
w Door under-cuts (the greater of 1 mm/l/s and 15
8| AIR DISTRIBUTION
SYSTEM REQUIREMENTS
w ERV/HRV supplies outdoor air directly to each
mm) or transfer grilles allow air movement from
supply to exhaust grilles
w Ventilation equipment in unheated spaces
bedroom, to any storey without a bedroom, and
installed to avoid condensation on fans and mo-
if there is no storey without a bedroom, sup-
tors as per manufacturer’s instructions
ply to or exhaust from the principal living area.
If exhaust is used, the HRV/ERV exhaust must
not serve more than two other intakes in other
rooms
w Outdoor air supply outlets are located in ceiling
or wall at least 2 meters above the floor and
direct air across the ceiling. Air supplies have
diffusers with adjustable balance stops or acces-
sible dampers with locks and position indicators.
E16
BUILDER SUMMARY
Damper or
bird screen
at outside
wall
12
Minimum
100 mm
(4”) above
finished grade
11
Above snow line and
minimum 450 mm (18”)
above finished grade
E17
BUILDER SUMMARY
Exhaust-Only
with a Purpose Built Air Circulation System
Not illustrated in the Appendix to NBC 9.32
E18
BUILDER SUMMARY
CONTROLS VARIATIONS
A centrally located manual switch labelled “Ventila- ADD AN OUTDOOR-AIR SUPPLY DUCT - Upgrade system
tion Fan” operates principal exhaust fan at the Normal performance by adding an outdoor air intake duct con-
Operating Exhaust Capacity. The air distribution system nected to the return side of the circulation fan. An appro-
fan is controlled to operate whenever principal exhaust priately sized outdoor air intake supply duct will provide
fan is operated, or alternately the air distribution system more uniform distribution of outdoor air and reduced
can be equipped with a control that automatically oper- likelihood of cold drafts causing occupant discomfort.
ates its fan at user-selected time intervals. The mixture of house and outdoor air must be tempered
A manual fan control switch is required in each room to 12oC or warmer before being introduced into living
served by a supplemental exhaust fan. Where the areas of the dwelling unit.
kitchen supplemental exhaust requirement is met by ADD A SUPPLY FAN TO AN OUTDOOR AIR SUPPLY DUCT
the principal exhaust fan, the control in the kitchen must - Installing an auxiliary supply fan in the outdoor air
be labelled “Kitchen Exhaust”. supply duct described above will further improve control
Principal exhaust fans and supplemental exhaust fans over the supply and distribution of ventilation air.
may also be activated by automatic controls (e.g., dehu-
SINGLE SPEED PRINCIPAL VENTILATION FAN - Using a
midistats), provided the manual controls will operate the
single speed PV and requires use of some supplemental
fans regardless of the setting of the automatic controls
exhaust fans
and the fans do not operate when all controls are in the
off position. TWO SPEED PRINCIPAL VENTILATION FAN - A PV fan with
Make-up air systems must operate automatically when a speed control that operates the PV fan at the Normal
the device they serve is operated. Operating Exhaust Capacity on low speed and at an
exhaust rate of at least 2.5 times the minimum Normal
BASIC COMPONENTS SPECIFICATION Operating Exhaust Capacity on high speed will allow one
The principal ventilation fan must be approved by the fan to meet the principal exhaust flow requirements and
manufacturer for continuous operation. the supplemental exhaust requirements of the kitchen
and all bathrooms, without requiring additional exhaust
Required fans must meet specific capacity and sound fans.
ratings.
Fans and other components exposed to untempered
outdoor air must be approved for such use.
Carbon Monoxide alarms must conform to CAN/CGA
6.19-M “Residential Carbon Monoxide Alarming Devices”.
Choosing Brushless DC motors for fans will significantly
reduce the fan energy used for ventilation.
E19
BUILDER SUMMARY
|COMBUSTION APPLIANCE
1 REQUIREMENTS |SUPPLY AIR INTAKE AND
5 EXHAUST OUTLET REQUIREMENTS
w fuel-fired fireplaces must be of the direct-vented w locate outdoor air intakes well away from con-
type tamination sources (e.g., automobile exhaust,
w other fuel-fired space-heating for water-heat-
building exhaust) and at least 900 mm from
ing appliances must be either direct-vented or combustion appliance vents, oil fill pipes, gas
mechanically-vented types meters, etc.
w outdoor air intakes must be accessible for ser-
w solid-fuel-fired combustion appliances (e.g.,
wood stoves) are not permitted vice
w label outdoor air intake hoods for easy identifica-
2| CO ALARM
REQUIREMENTS
w install a carbon monoxide alarms in or near
tion
w exhaust ducts must not discharge into enclosed
spaces
bedrooms of dwelling units with
• fuel-fired space- and/or water-heating appliances
installed in the dwelling unit or in connected spaces
• attached garages
|PRINCIPAL VENTILATION
6 FAN REQUIREMENTS
w centrally located manual switch labelled “Ventila-
| MAKE-UP AIR
4 REQUIREMENTS
w make-up air fan must be controlled to operate
when the device served operates
w make-up air heated to at least 12 C unless deliv-
ered to a normally unoccupied area
w make-up air fan and heater designated for han-
dling untempered outdoor air
w sound ratings for make-up air fans with less than
1 meter between themselves and visible interior
of bathrooms must be less than 2.5 sones CSA-
C260 or 3.5 sones HVI 915
E20
BUILDER SUMMARY
| SUPPLEMENTAL EXHAUST
7 REQUIREMENTS
w locate supplemental exhaust fan intakes (ex-
9|VENTILATION
REQUIREMENTS
SYSTEM DUCT
by manual switch in each room served ACH, or at the air change rates in NBC Table
9.32.2.3 if space is air-conditioned
w Sound ratings for supplemental exhaust fans
with less than 1 meter between themselves and
visible interior of bathrooms must be less than
2.5 sones CSA-C260 or 3.5 sones HVI 915
11|MISCELLANEOUS
REQUIREMENTS
w Ventilation equipment in unheated spaces
OR
E21
BUILDER SUMMARY
Damper or
bird screen
at outside
wall
Minimum
100 mm
(4”) above
finished grade
E22