Materials and Equipment Details

uPVC (POLYVINYL CHLORIDE) PIPE

1. General

1.1 The pipe shall conform with the requirements of the Philippines National
Standard Specification for Unplasticized Polyvinyl Chloride (uPVC) Pipes for
Potable Water Supply (PNS 65:1993) or equivalent except as otherwise
specified herein. This standard specifies the requirements for unplasticized
polyvinyl chloride (uPVC) pipes with nominal outside diameter of 63 mm to
500 mm intended for the conveyance of potable water under pressure and of
temperatures up to 45oC for use below ground.

2. Definitions

2.1 For the purpose of this specification, the following definitions shall apply:

(a) nominal pressure (PN) – The nominal maximum internal pressure that
the pipe can sustain in continuous use. This is expressed in
megapascals (MPa) at 28 oC.

(b) design maximum induced stress – The estimated maximum tensile


stress on the wall of the pipe along the transverse axis due to internal
pressure to which the pipe can be subjected continuously without
failure. This is used in calculating the wall thickness of the pipe. For the
purpose of this specification the maximum induced stress in 8.5 MPa at
28 oC.

(c) pipe series – It is used in classifying the pipe, which is the ratio of the
design maximum induced stress to the nominal pressure of the pipe.
The pipe series number may be rounded off to the nearest whole
number.

(d) nominal dimensions – Nominal dimensions and values indicated herein


are minimum limits as defined in this specification.

(e) unplasticized polyvinyl chloride (uPVC) pipe – A pipe produced


basically from an extrusion grade uPVC material of high molecular
weight which does not contain any plasticizer.
(f) rework material – uPVC plastics from a processor’s own production that
has been reground, palletized or solvated after having been previously
processed.

3. Classification

3.1 Pipes shall be classified in accordance with the pipe series and/or the
nominal pressure as follows:

(a) Series 10 (PN 0.86 MPa)


(b) Series 8 (PN 1.03 MPa)
(c) Series 7 (PN 1.25 MPa)
(d) Series 5 (PN 1.60 MPa)

In designing the maximum nominal pressure of the uPVC pipe under ambient
temperatures other than 28 oC, Table 1 – Maximum Induced Stress for Other
Temperatures may be utilized in arriving at the maximum induced stress to
be used. The said table may also be used in derating the nominal pressures
of the pipe specified in this specification.

Table 1
Maximum Induced Stress for Other Temperatures

Coefficient to be Applied to
Water Temperature, t, oC the Maximum Induced Stress

0 < t < 25 1
25 < t < 35 0.8
35 < t < 45 0.63

4. Requirements

4.1 Materials

(a) The materials from which the pipes are made shall consist substantially
of polyvinyl chloride that conforms with PNC 291 or equivalent, to
which may be added only those additives necessary to facilitate the
manufacture of quality pipes of good surface and sound physical,
mechanical and chemical properties.
(b) None of the additives shall be used separately or together in quantities
sufficient to constitute a toxic, organoleptic or microbial growth hazard
or to impair the fabrication or welding properties of the product, or to
impair the chemical, mechanical and physical properties (particularly
long-term hydrostatic and impact strength) as defined in this
specification.

(c) The use of the manufacturer’s own clean rework material produced
during the manufacture and production testing of products conforming
with this standard is permissible. No other rework material shall be
used.

4.2 Dimensions

(a) Standard Configurations – Shown in Figure 1 are the standard


configurations of uPVC pipes with elastomeric sealing ring socket
ends (sizes 63 mm to 500 mm).

(b) Dimension and Tolerances – The outside diameters, socket depths,


socket diameters, minimum wall thickness, effective lengths of the
different pipe series/nominal pressures and the tolerances are
indicated in table 2.
(c) Length – Unless otherwise specified by the Procuring Entity, the
length of the pipes shall be taken mean the effective length, Le, as
shown in Figure 1. The minimum effective lengths are indicated in
Table 2. A tolerance of +20 mm is allowable.

4.3 Physical Characteristics

(a) Appearance – The pipe shall be homogeneous throughout and free


from cracks, holes, encrustation, and other foreign inclusions.
Excessive die lines and/or stress marks (particularly in the socket and
bell groove) as well as discernible material marbling are not allowed.
The ends of the pipe shall be cleanly cut and square to the axis of the
pipe.

(b) Color – The color of the pipe shall be nearest to RAL 5012 and shall be
uniform throughout the entire surface of the pipe.

(c) Effect of Materials on Water Quality – When used under the


conditions for which they are designed, non-metallic materials in
contact with, or likely to come into contact with potable water shall
not constitute a toxic hazard, shall not support microbial growth and
shall not give rise to unpleasant taste or odor, cloudiness or
discoloration of the water.
Concentration of substances, chemical and biological agents leached
from materials in contact with potable water, and measurements of
the relevant organoleptic/physical parameters shall not exceed the
maximum values recommended by the World Health Organization in
its publication “Guidelines for Drinking Water Quality” Volume 1
“Recommendations” (WHO, Geneva, 1984).

If lead or mono/di-alkyl tin compounds are permitted to be used as


stabilizers, the quantities of lead or tin measured as metals shall be
determined in accordance with the method described in PNS 966/ISO
3114. The permitted level shall not exceed the limits specified in
Table 3.

Table 3
Maximum Levels of Toxic Substances

Extraction Total Concentration


Toxic Substances 1st 3rd of 3 Extracts

Lead, mg/L 1.00 0.05

Di-alkyl Tin, C4
And other higher
Monologues measured
as tin, mg/L 0.02

Cadmium, mg/L 0.01

Mercury, mg/L 0.001

(d) Physical Properties – The pipe shall conform with the physical
properties specified in Table 4.

Table 4
Physical Properties

Property Value Test Method

Vicar Softening Temperature,


o
C, minimum 76 PNS 952/ISO 2507
Longitudinal Reversion, % max. 5 PNS 951/ISO 2505

Water Absorption, g/M2, max. 40 PNS 953/ISO 2508

(e) Resistance to Acetone – The pipe shall not show signs of delamination
or disintegration when immersed in acetone. Flattering and/or
swelling of the pipe shall not deemed to constitute failure when tested
in accordance with PNS 978/ISO 3472.

(f) Resistance to Sulfuric Acid – The mass of the specimen shall not
increase by more than 0.316 g nor decrease by more than 0.013 g
when tested in accordance with PNS 979/ISO 3473. The effect of the
acid on the surface appearance of the specimen (roughening,
bleaching or blackening) shall be ignored.

4.4 Mechanical Properties

The pipe shall conform with the applied pressure for the hydrostatic
pressure tests indicated in Table 5 of PNS 65:1993 when tested in
accordance with PNS 509/ISO 1167.

Table 5
Applied Pressure for Pressure Test at 28oC

Unit MPa
Series 10 8 7 5
Burst Pressure 3.80 4.56 5.49
7.10
Short Term Pressure 3.60 4.30 5.20 6.70
Long Term Pressure 2.50 3.00 3.60 4.65

For specific calculation, the following formula for deriving the applied
pressure may be used.
2 x S x tmin.
P = ------------------
Dm – tmin.
Where:

p is the applied pressure, MPa


S is the design stress at 28oC, MPa
tmin is the minimum wall thickness, mm
Dm is the maximum mean outside diameter, mm

(a) Hydrostatic Pressure Test Requirement

(1) Burst Pressure – The pipe shall withstand the applied pressure
for at least 60 seconds without failure. The value for the
induced stress used in calculating pressure requirement is 37.5
MPa at 28oC.

(2) Short Term Pressure – The pipe shall withstand the applied
pressure for at least one hour without failure. The value for
the induced stress used in calculating pressure requirement is
35.7 MPa at 28oC.

(3) Long Term Pressure – The pipe shall withstand the applied
pressure for at least 1000 hours without failure. The value for
the induced stress used in calculating pressure requirement is
24.6 MP at 28oC.

(b) Resistance to External Blows – The true impact rate of the batch at
28oC shall not exceed 10% when tested in accordance with PNS
967/ISO 3127.

NOTE – The true impact rate is the total number of broken test pieces
divided by the total number of blows, expressed as percentage as if
the whole batch had been tested. In practice, test pieces are drawn at
random from the batch and only estimate of the true impact rates are
obtained.

(c) Flattening – The pipe shall not show evidence of splitting, cracking
and breaking when flattened to a minimum of 40% of its outside
diameter when tested in accordance with PNS 800/ASTM D2241.

4.5 Joints

Elastomeric sealing ring type joints shall be supplied for sizes 63 mm up to


500 mm. The elastomeric sealing ring shall conform with PNS 1008/ISO
4633. The quantity of sealing ring shall be the number of pipe supplied plus
ten percent for each size of pipe.

5. Sampling and Testing


5.1 At least one piece or set (depending on the quantities specified by the test
method) of samples(s) per production batch (one production run or one
production shift, whichever is shorter) shall be taken at random for testing in
accordance with the methods and procedures specified in this specification.

5.2 The frequency of sampling and testing of pipes is shown in Table 6.

Table 6
Sampling and Testing Schedule for Assessment of Compliance

Clause Requirements Minimum Frequency

4.2 (b) Diameter and Wall Thickness Hourly


4.2 (c) Length Every 8 hours
4.3 (a) Appearance Every pipe

Type of Test

4.1 Material Once every 6 months


or every change of
formulation
4.3 (c) Effect of Materials on Water Quality -do-
4.3 (d) Vicat Softening -do-
4.3 (e) Water Absorption -do-
4.3 (f) Resistance to Sulfuric Acid -do-
4.4 (a) (3) Long Term Pressure -do-
4.5 Joints -do-

Quality Control Test

4.3 (d) Longitudinal Reversion Every 8 hours


4.3 (e) Resistance to Acetone -do-

4.4 (a) (1) Burst Pressure -do-


4.4 (a) (2) Short Term Pressure Every 24 hours
4.4 (b) Resistance to External Blows Every 8 hours

6. Marking
6.1 The pipe shall be clearly marked with the following information spaced at
intervals not more than one meter:

1. Name of Product
2. Nominal outside diameter, mm
3. Series and/or Nominal pressure, MPa
4. Manufacturer’s name and/or its recognized trademark
5. The words “Made in ( country )”
6. The words “for Potable Water”

GATE VALVES
1. GATE VALVE W/ OPERATING NUT
a. Gate valves shall conform to ISO , ANSI AWWA Standards.
b. All Gate valves shall be fabricated in ductile iron. The minimum working
pressure of all gate valves shall be PN10. Gate valves shall be of the resilient
face type .The operating stem shall have ‘o’ -ring seals. The direction of
opening for all gate valves shall be anti-clockwise as viewed from the top.
Valve ends shall be flanged type. All external body and flange surfaces shall
be coated with epoxy paint, or similar approved by the Engineer. All interior
surfaces except the finished and seating surfaces, shall be coated with epoxy
paint, or similar approved by the Engineer.
BOLTS AND NUTS
1. Bolts shall be made of Galvanized Steel
2. Bolts, anchor bolts, nuts and washers shall be of low carbon steel, Grade B of ASTM
A307.
3. Threads and tapping for all bolts and nuts respectively shall conform to ISO 261
4. Bolt head and nut shapes shall be hexagonal and shall conform to ISO 272.
5. Washers shall be provided under nuts and under the heads of bolts.
6. Bolts, anchor bolts, nuts and similar threaded fasteners, after being properly
cleaned, shall be galvanized in accordance with the requirements of ASTM A153.
SADDLE CLAMP
1. Materials is high grade polypropylene.
2. Dimension conforms to ISO standards.
3. Material of bolt and nuts shall be stainless steel.
4. Clinching Ring is made of acetal co-polymer Conforming to 14236.
5. Rubber gasket/O-ring shall be made from nitrile rubber conforming to ISO 4633,
suitable for potable and chlorinated water.
6. Thrust Ring is made from Nylon.
7. Compression joint shall conform to ISO 3501 as per ISO 14236.
8. Fitting color shall be black.
9. No loose component.
10. Markings: Manufacturer’s Name/Trademark/Trademark, size PP maybe in the form
of sticker or paint.
PE TUBING
1. Material – the extrusion compound shall either be Grade P33, Class C or Grade P34,
Class C (PE3306 or PE3406) as defined by ASTM D1248
2. Dimensions – Standard Dimension Ratio (SRD) shall be as follows: Outside Size
Nominal Dia. (mm) (in) Pressure Thickness 20mm ½ PN for δs=8 Mpa - 32mm 1”
PN for δs= 8 Mpa 3.0
3. Standard – Conforming to ISO 161/1/ISO 3607 Series, SDR PR based on controlled
Outside Diameter
4. Markings – shall be clearly marked at intervals of not more than 0.6 M with nominal
size, type of (PE 3306, OR PE 3406). Standard Dimension Ration (SDR 11),
manufacturer’s trade name and production code, and the seal of approval from an
accredited testing laboratory.
5. Joint method – Compression Fittings, Mechanical Jointing

Submersible Pump
1. Pump – Motor Unit
This unit shall include the following components:

a) Multi Stage Submersible Pump and all the accessories it needs to get a working
system with design discharge (Q) at a total pumping (dynamic) head (HT ) as
specified in the BOQ. Efficiency of this pump should not be less than 70% at the
design point.
b) Pump Element – The impellers shall be constructed of stainless steel, accurately
fitted, smoothly finished, and dynamically balanced at normal pump speeds with
stainless steel wear ring. The pump shaft shall be of type 304 stainless steel. The
valve casing, intermediate chamber and bottom chamber shall be of type 304
stainless steel. The pump shall include a stainless steel inlet strainer and a non-
return valve.

c) The pump shall have a nameplate showing the serial number of the equipment and
the name of the manufacturer. The nameplate shall show the capacity in liters per
second, TDH in meters and rated speed in revolutions per minute, such other
information as the manufacturer may consider necessary for complete identification
shall be shown on the plate. The nameplate shall be securely fastened to the
equipment in a location affording easy viewing
d) Submersible Pump shall be as manufactured by Grundfos or approved equivalent.
The motor must have a hermetically-sealed winding area to seal the winding from
moisture and with high temperature winding wire rated at 180°C. The motor shell
and splined shaft must be made of stainless steel. The motor shall be designed for
continuous duty operation and shall have a minimum service factor of 1.15. The
motor shall be water filled and shall incorporate a mechanical seal to restrict foreign
mater from entering the motor. The thrust bearings shall be of ample capacity to
carry the weight of all rotating parts plus the hydraulic thrust and shall be of ample
capacity to carry the weight of all rotating parts plus the hydraulic thrust and shall
be an integral part of the driver. It shall be equipped with expansion diaphragm to
compensate for filling water expansion/contraction due to temperature changes. It
shall be fitted with a nameplate on which all NEMA standard motor data shall be
stamped or engraved in English/Metric.
e) Submersible motor shall be as manufactured by Franklin Motor or approved
equivalent.

Column Pipe, Water Level Tube and Support Cable


a) The column pipe (riser piper) for the deepwell pump as specified in the BOQ shall
be uPVC suitable for 213 m depth furnished in 3.0 meters (10 ft.) maximum length,
and shall be connected with square threaded couplings with a special rubber (EPDM
or nitrile) between pipes to absorb vibration due to high pressure. This includes
stainless steel adaptors for the pump and for the discharge head as shown in the
drawings.

b) Column pipes shall be as manufactured by either by CRI, Apollo or approved


equivalent

c) The water level (sounding) tube intended for measuring static and pumping water
level as shown in the drawing shall be a HDPE 25 mm Ø SDR 11 and shall be tied
along with the riser pipes.

d) Support Cable – A stainless steel cable, 6.5mm Ø as specified in the BOQ shall be
provided and fastened with appropriate stainless steel clamp and tie wires to
support the pump and motor.

Diesel Generating Set


a) Diesel Engine
The engine shall be of the water cooled, heavy duty, 4-cycle, naturally aspirated,
industrial type equipped with 12 volt DC solenoid engaged electric motor starter
and shall develop the full continuous horsepower required by the alternator using
diesel fuel when operating at a speed not exceeding 1800 rpm. The engine shall
have aluminum pistons, removable type cylinder sleeves, heavy-duty replaceable
precision type bearings and equipped with vane type oil pump, by-pass oil filter, oil
level indicator, a residential type silencer exhaust system.

b) The engine shall be manufactured by Perkins, Cummins, Caterpillar, John Deere or


approved equal.
Starter – The engine shall be equipped with 12 volts DC solenoid engaged electric
motor starter.
Lubricating System – The Lubricating system shall have a vane type oil pump, a by-
pass oil filter, an oil pressure gauge and oil level indicator.
Exhaust System – The engine shall be equipped with a residential silencer, sized in
accordance with the engine manufacturer’s recommendation. Maximum
backpressure measured at the exhaust header shall not be more than 350mm (14
in.) of water column. The silencer shall be fabricated of carbon steel designed for
1000°F service and shall be shop painted with silicon base high heat resisting
aluminum paint. The silencer shall be installed with Flexible metal expansion
section of stainless steel and not less than 450mm (18 in.) in length as shown on the
Drawings and shall be designed together with all pipes, bends, bolts, nuts and
clamps for temperature of not less than 1000°F. the entire exhaust assembly
excluding expansion joint shall be insulated with 250mm layers of magnesium
insulation with lugging as shown on the drawings. The silencer shall be of the TRS
series, Model 7548-TR32 as manufactured by Kittel, Los Angeles, California or
approved equal.
Fuel System – The fuel system shall include and injection pump, engine fuel transfer
pump, flexible fuel connections, fuel filters and shut-off valves.
Fuel Oil Storage Tank – The fuel oil tank shall have a capacity of at least 8 hours of
continuous operation and shall come complete with all accessories. Inside surface of
the tank shall be pickled or sandblasted to be clean of all dust and foreign matter
and lightly coated with oil. All tank openings shall be sealed prior to shipping.
Fuel Level Gauge – The contractor shall furnish and install a level gauge on the fuel
oil tank for visual indication of the amount of fuel remaining on the tank. The gauge
shall be either clear glass or plastic materials resistant to normal diesel fuel
corrosion. The level gauge shall be provided with valves on both ends for isolation
during routine maintenance and replacements. The gauge shall be of appropriate
length with graduation calibrated in both in liters ad percentage of the total fuel
tank capacity.
Safety Switches – The engine shall equipped with safety switch witch will cut-off the
engine on low oil pressure and high water temperature.
Battery – There shall be installed a battery complete with cables for supplying 12
volts DC power to the engine. The battery shall have the necessary ampere-hour
rating for cranking the engine for 10 minutes.
Battery Charger – The battery charger shall be 12 volts DC output, 220 volts AC
input. It shall have an ampere output sufficient to recharge the battery in 4 hours
when the battery is 50% discharge. The charger shall incorporate adjustable float
and equalizing voltage potentiometer. A current limit signal shall be supplied in the
control circuit from the current sensing resistor. It shall be of the full wave rectifier
type and shall include all the required standard components.
c) Alternator
1. The alternator shall be rated for standby operation at 0.80 PF, 3-
phase, 60 cps, 1800 rpm, 460 volts, 50°C ambient temperature at
75M a.s.l. and shall be directly coupled to the engine. It shall be
single bearing, synchronous type standards. The insulation shall
meet the NEMA MG 1-22.40 and 16.40 for class H insulation and
shall be further protected with 100% epoxy impregnation and
overcoat of resilient insulating material to reduce possible fungus
and/or abrasion deterioration per MIL 1-24092. Temperature rise
of the rotor shall be limited to NEMA class F ratings.
2. The excitation system shall be of brushless construction controlled
by a solid-state voltage regulator capable of maintaining voltage
within +/-2% at any constant load from 0% to 100% of the rating.
The regulator must be isolated to prevent tracking when connected
to SCR loads, and provide individual adjustments for voltage range,
stability and volts-per-hertz operation. The solid state regulator
module shall be shock mounted and epoxy encapsulated for
protection against vibration and atmospheric deterioration.
3. Upon one-step application of any load up to 100% of the rated load
at .80 PF the voltage dip shall not exceed 20% and shall recover to
+/-2% of the rated voltage within one (1) second.
4. Alternator shall be capable of sustaining an overload capacity of
300% full load current at zero power factor for a period of ten
seconds without damage to it. Output voltage recovery after sudden
application or rejection of rated load shall be within 0.3 second.
5. A resettable line current sensing circuit breaker with inverse time
versus current response shall be furnished which protects the
generator form damage due to its own high current capability. This
breaker shall not trip within ten seconds specified above to allow
selective tripping of downstream fuse or circuit breaker under fault
condition. This breaker shall not trip within ten seconds specified
above allow to allow selective tripping of downstream fuse or circuit
breaker under a fault condition. This breaker shall not trip within
ten seconds specified above to allow selective tripping of
downstream fuse or circuit breaker under a fault condition. This
breaker shall not automatically reset preventing restoration of
voltage if maintenance is being performed. Field current-sensing
breaker will not be acceptable.
6. Alternator shall be open, drip-proof construction with and over-all
efficiency of at least 85% at full load.
7. Alternator windings and electrical components shall be tropicalized
8. Alternator shall be manufactured by Stamford, Marathon, Onan,
Kohler or approved equivalent.
d) General Control Panel
1. General – A set mounted alternator/engine control panel shall be
supplied with the generator set. The control panel shall be
vibration-isolated, dead front construction, 14 gauge steel NEMA 1
enclosure. Cabling and control wiring shall be either side or bottom.
2. Instrument – Panel shall contain, but not limited to the following
equipment.
a. Circuit breaker, thermal-magnetic, industrial type rating as
required.
b. 1 voltmeter with phase selector switch
c. 1 ammeter with phase selector switch and current
transformers
d. 1 frequency meter
e. 1 hours operation counter
f. Panel illumination lights and switches
g. Indicating relays and fault indicator lamps for low oil pressure,
high engine temperature and over speed.
h. Engine ammeter
i. Engine lube oil pressure gauge
j. Engine water temperature gauge
k. Tachometer
3. Operating Switches and Push buttons shall include
a. Manual start/stop pushbuttons/key switch
b. Emergency Stop Button
c. Control lamp test
d. Selector switch
e. Test switch
4. Operational Controls- During operation, the generating set shall be
monitored for the following disturbances:
a. Loss of lube-oil pressure
b. Excess engine temperature
c. Alternator overload
d. Alternator short circuit
e. Over speed
Should any of the faults listed under (a) to (e) arise, the individual
signal relay installed for the special task shall respond. To avoid
lasting damage if operation were to continue, the generating set
shall be automatically shut-off and a subsequently new starting
effort shall be blocked and corresponding fault indicator lamp shall
be on.
5. At protracted overloading of the alternator, the thermal over current
release with time delay shall cause the alternator main circuit breaker
to trip. The set shall continue in operation unloaded to obtain cooling
of the alternator.
6. In case of feeder short circuit during an emergency supply operation,
the alternator shall immediately be disconnected from the fault
location by means of the electromagnetic trip relay of the main circuit
breaker.
Hypo Chlorinating Equipment
General – The unit to be furnished shall be of the positive displacement type
with all parts constructed of materials non-corrosive to wet chlorine service.
a. Solenoid Dosing Pump
Flow Rate : 7 PLH @ 16 bar
Stroke Rate : 300 stroke/min
Frequency : Analogue
Connections : 4 mm in ; 6mm out
Power Supply : 40W, 100 - 240 V AC , 50 - 60 Hz
Weight : 4.40 kg
Liquid End Material :
Pump Head : PVDF
Balls : Ceramic
Diaphragm : PTFE
Accessories :
Foot Valve : PVC
Injection Valve : PVC
Gaskets / Seals : FPM or EPDM
Suction Tube : PVC , 4mm Ø x 4 m length
Delivery Tube : PE ,6 mm Ø x 2 m length
Bracket : Wall Mounted

a) Chlorine Test Kit

The test kit shall be colorimetric type and the residual chlorine shall be
determined by a simple visual comparison between permanent color
standards of known value and sample color. The test kit shall be
capable of analyzing for total chlorine using orthotolidine solution
method. The unit shall have a range of 0-5 m/l or ppm with increments
of 0.1 mg/l of ppm. Orthotolidine solution shall be provided with the
test kit.