List of Contents

LEGEND
Sheet No: Content Name
P-01 Index Page
We has been used the Following NFPA Standard to complete Sym Description Cft. Qnt.
Upright Sprinkler, K-11.2 UL
P-02 Product Details installation work Upright Sprinkler, K-5.6 UL
P-03 Factory Layout Plan NFPA 10: Standard For Portable Fire Extinguisher FHC_ CL - lll
Pendent Sprinkler, K-5.6
Hose, Class-III
UL
UL
P-04 Sprinkler System Master Layout Plan Landing Valve (65mm) LPCB

P-05 Schematic Diagram


NFPA 13: Standard For The Installation Of Sprinkler System Non Return Valve
Y-Strainer
UL
UL
P-06 Isometric Diagram NFPA 14: Standard For The Installation Of Standpipe System Butterfly Valve (Sup,) UL
UL
OS & Y Gate Valve(Sup)
P-07
P-08
Ground floor Plan Layout for fire Sprinkler System
1st Floor to Plan Layout for fire Sprinkler System
NFPA 17: Standard For Dry Chemical Extinguisher System Ball Valve BSI
Flow Switch UL

P-09 2nd Floor Plan Layout for fire Sprinkler System NFPA 20: Standard For Fire Pumps Pressure Gauge UL
Riser Point N/A
P-10 3rd Floor Plan Layout for fire Sprinkler System (True ceiling) NFPA 22: Standard For Water Tank Drain Riser Point N/A
UL
P-11 3rd Floor Plan Layout for fire Sprinkler System (Below False ceiling) Test & Drain Valve (50mm)

P-12 Sectional View of A-A, B-B


NFPA 72: National Fire Alarm Code Zone Control Assembly UL
Pillar Hydrant (2-Way) LPCB
P-13 & 14 System Installation Details NFPA 101: Life Safety Code Beaching Inlet (4-Way) LPCB
Fire Pump UL
P-15 Pipe Details of 40 Schedule ERW ASTM-53 NFPA 204M: Guide For Smoke and Heat Venting Flexible Joint BSI
P-16 to 18 Fire Pump Room Arrangement Layout Air Vent UL

P-19 & 20 Fire Pump Controller and Fuel System Details


NFPA 92A: Recommended Practice For Smoke Control System Pressure Relief Valve (6 Inch) UL
Water Flow Meter (6 Inch) FM
P-21 & 22 Sectional View of Fire Pump Room Arrangement NFPA 90A: Standard For The Installation Of A/C and FM
Alarm Check Valve (8 Inch) UL

Hydraulic Calculation Nodal Analysis


P-23 to 25
Ventilating System
APPLICABLE LOCAL CODES & STANDARDS
BUILDING DATA SHEET DNV Clothing Ltd. EXT.
100/101 Adamjee EPZ,
# PARAMETER DATA
Sidhdirgonj,Narayangonj,
SL. NO. PARAMETER DATA 1. BUILDING CODE BANGLADESH NATIONAL BUILDING CODE Bangladesh

ACCORD & ALLIANCE FIRE AND BUILDING SAFETY


2. OTHER STANDARDS
1 FACTORY NAME DNV CLOTHING LTD STANDARD FOR BANGLADESH RMG UNITS
ANANTA GROUP
2 NAME OF OWNER DNV CLOTHING LTD
Md. Ashikur Rahman
3 OCCUPANT FOURTH STORIED GARMENTS BUILDING M.Eng in ME

RAM CORPORATION Md. Ashikur Rahman


1/1D, Hatkhola Road, 10th Floor, Wari, PhD in ME (BUET)
4 NAME OF CONSULTANT
Dhaka-1203 Bangladesh
Email:info@ramcorporation.com
Hydraulic Calculation Sample: RAM Corporation
5 LOCATION OF PROTECTED
101, Adamjee EPZ, Siddirgong, Narayangong, Dhaka, Bangladesh From Density/Area Curve (NFPA13, FIGURE 11.2.3.1.1) Corporate Office: 1/1D,
PREMISES Hatkhola Road, 10th Floor, Wari,
0.20 GPM (Ordinary Hazard Group II) per square foot is Dhaka-11203, Bangladesh.
Email: info@ramcorporationbd.com
required to fall from the sprinklers onto the fire over the
FLOOR OR LEVEL ROOF TOP most remote 1591 square feet of area (Office Area, True
6 IDENTIFICATION Ceiling, at 3th Floor). Which required 1591*0.20 or 318.2
TOTAL HEIGHT: (60'-0" FEET AT SHED PEAK)
GPM water. Total number of sprinkler is 15 Nos. So each
sprinkler discharge rate required 21.213 GPM.
7 BUILDING TYPE FACTORY BUILDING.
Here Sprinkler has K-facet 5.6.
30,500 SQFT PER FLOOR So, each sprinkler minimum pressure required:
8 BUILDING AREA TOTAL AREA: 1,22,000 SQFT (APPROXIMATELY) p = (q/k)2 = ( 21.213/5.6)2 =14.35 psi
When q = flow in L/min
k = nozzle discharge coefficient or k-factor for head Index Page of Sprinkler
p = pressure in bar System
01