Professional Documents
Culture Documents
Mark Hallworth,
7. Personnel
Guidance on the requirements for specific training, knowledge and skills.
Also gives guidance to the qualification of personnel.
Top Questions From Webinars
• Classification and Monitoring Differences
• Which occupancy state – “at-rest” or “in-operation” to be defined for the activity not directly related to manufacturing (e.g., inventory of raw
materials)?
• Is it correct to understand that the EM sampling personnel is considered not “personnel” in the following paragraph from GMP? (e.g., personnel to
perform surface/air sampling)
• Other Applications
• How does this apply to Cell and Gene Therapy?
• Any need for continuous NVP sampling in Grade C/D rooms, where manufacturing takes place but are not critical areas or connected to Grade B
rooms/hoods?
• How does the annex 1 apply to non-sterile production?
1. In Operation and At Rest Definition
• The questions associated with occupancy are more about an understanding of certification vs monitoring, than the operational state.
• There are two sources for what occupancy state requires. ISO14644-1 and Annex 1,
• ISO 14644-1
• 3.3 Occupancy states
• 3.3.1 as-built
▪ condition where the cleanroom or clean zone is complete with all services connected and functioning but with no equipment, furniture, materials or personnel present
• 3.3.2 at-rest
▪ condition where the cleanroom or clean zone is complete with equipment installed and operating in a manner agreed upon, but with no personnel present
• 3.3.3 operational
▪ agreed condition where the cleanroom or clean zone is functioning in the specified manner, with equipment operating and with the specified number of personnel
present
• EU ANNEX 1
• 4.29 Cleanroom classification should be carried out in the “at rest” and “in operation” states.
• i. The definition of “at rest” state is the condition whereby the installation of all the utilities is complete including any functioning HVAC, with the main manufacturing
equipment installed as specified but not operating and without personnel present in the room.
• ii. The definition of “in operation” state is the condition where the installation of the cleanroom is complete, the HVAC system fully operational, equipment installed and
functioning in the manufacturer’s defined operating mode with the maximum number of personnel present performing or simulating routine operational work.
• It is important to understand that these “states” in BOTH documents are intended for classification purposes and reflect the two extremes of room
functionality – test the room with no personnel working, but equipment turned on – and test the room in the most severe case possibly, i.e., room
working, machine operating and product flowing (either real, or simulated). – they DO NOT represent the monitoring conditions of the room – only the
test parameters, controlled conditions to put two points on a graph.
Occupancy State
• The only requirement for operational/at rest differentiation is that the room achieves the at rest conditions within 15 minutes;
which basically means the personnel leave, and the room air exchange rate can reestablish the defined at rest state – for
monitoring the client can state what that mean, as it is Risk based not classification based.
1. Which occupancy state – “at-rest” or “in-operation” to be defined for the activity not directly related to manufacturing (e.g.,
inventory of raw materials)?
If inventory is being performed, then the operational state is inventory performance using the required number of personnel and
appropriate alarms should be set. This is an operational state and different to the natural at rest state of the room.
2. Is it correct to understand that the EM sampling personnel is considered not “personnel” in the following paragraph from GMP? (e.g.,
personnel to perform surface/air sampling)
For room certification in the ‘at rest’ state the particle counter would be turned on and sufficient delay allowed for the operator to
leave the area and any disturbance due to their presence allowed to dissipate, typically 30-60 seconds. The tester should be outside
the room during performance. This is certification and as such tested only annually. For microbial testing – this is either monitoring,
so not applicable – or it is initial or ongoing room qualification and as such the presence f the testing personnel is noted in the record.
3. Should the occupancy state – “at-rest” and “in-operation” apply to the “room” or “area”? Multiple rooms
The occupancy state is tied to the normal maximum number of personnel present to perform routine operations, again for
classification only. It is a point of a curve to establish limits of operational performance. If different rooms have different occupancy
levels, this should be noted on the report – and should reflect the “normal maximum number of personnel required”.
4. Is it appropriate to define the condition as “at-rest” where the personnel still enter the production room after cleaning to take back
equipment/devices?
If the room has established an at rest state - <15 minutes, and then operators return into the area for any reason, it is now in
operational state – it may have different criteria for warnings and alarms etc., but it is no longer unoccupied. I would suggest that this
period be included in the operations phase of manufacture and ‘at rest’ begins when they leave.
2. Maximum Tubing Length
• It is not always possible to locate the particle counter at the location of the ideal sample
point. In these cases, it is required to transport the facsimile of the environment to the
particle counter – using tubing
• Tubing causes a shift in the total number of particles and the distribution of particles within
a sample. Care should be taken to minimize these losses
• Misinterpretation of ISO14644-1 Appendix C, regarding macro particles; resulted in a 1m
maximum tubing requirement being initially quoted.
Particle transport loss mechanisms
• Diffusion
• Sedimentation
• Turbulent inertial
deposition
• Inertial deposition
(bends)
• Inertial deposition
• Changes in tubing
diameter
• Other
Particle transport loss mechanisms
• Annex 1 section 5.9 recommends ideally no
more than 1m tubing
0
6:25:01
6:46:01
7:07:01
7:28:01
7:49:01
8:10:01
8:31:01
12:38:43
13:03:43
13:24:43
13:45:43
14:06:43
14:27:43
14:48:43
15:09:43
15:30:43
15:51:43
16:12:43
16:33:43
16:54:43
17:15:44
17:36:43
0
5
10
15
20
25
30
35
40
45
50
6:25:01
6:44:01
7:03:01
7:22:01
7:41:01
8:00:01
11:29:01
11:48:01
12:07:01
12:26:01
12:44:43
13:03:43
13:22:43
13:41:43
14:00:43
14:19:43
14:38:43
14:57:43
15:16:43
15:35:43
15:54:43
16:13:43
16:32:43
16:51:43
17:10:43
17:29:43
17:48:43
•
•
•
1 event = alert
0
1
2
3
4
5
6
7
8
9
10
6:25:01
6:41:01
6:57:01
12:01:01
748 5.0
12:17:01
12:32:43
12:48:43
13:04:43
13:20:43
13:36:43
13:52:43
14:08:43
14:24:43
14:40:43
14:56:44
15:12:44
15:28:43
15:44:43
16:00:43
16:16:43
16:32:43
16:48:43
17:04:43
17:20:43
17:36:43
Setting Appropriate Action Limits
• The performance of the monitoring system, the data gathered, norms established, and
trends should be reviewed periodically. Revision of alert and action alarm levels (relaxation
or tightening) should be considered based on performance evidence
• A trigger threshold value based on a series of consecutive higher readings. The higher
readings trigger a warning based upon the occurrence of a higher level of counts being
maintained over a period of time (for example, three consecutive 1-min readings all above
a specified level).
• A threshold value trigger based on a high frequency of elevated readings. Sometimes
referred to as “x out of y”, this strategy records readings that are above a specified
threshold; if a sufficient number of readings in a series are above the specified values, then
an alert or action alarm is triggered. For example, if 3 out of the last 10 readings are above
a threshold then an alert or action alarm will be triggered.
• Allow for any system – TUBING – losses in the setting of action levels.
Alert and Action Limits
• For new builds or processes (no historical data) how do you set alert levels?
• The EMPQ and data gathered during APS will give a good set of baseline data to establish some operational alert levels.
• Historically alerts can be set at 50-75% of the action limit, but even with a small amount of ‘live’ data more appropriate
alert and action levels can be defined.
• For grade A the ≥5.0µm data is more difficult to establish numerical values for as it is more a question of frequency of
occurrence than number alone.
• For more information, we have a technical paper regarding establishing alarm levels for GMP applications on our
website for download.
Alert and Action Limits cont.
• Annex 2008 stipulated 1 cubic meter sampling volume; Annex 2023 does not indicate a
number. What is an acceptable number?
• The 1m3 sample was for classification of a cleanroom based upon the number of ≥5.0µm particles
present in very small numbers (<20).
• The suitable sample volume for classification can now be calculated using the available formula in
ISO14644-1 (2015), along with the number of sample points required.
• However, for monitoring this is now risk based, the locations are based on a risk assessment and the
sample volume based on the number of particles present, the history of the sample point etc.
typically 3 x 1-minute sample will give sufficient data when portable monitoring is performed.
• In Grade A, and where continuous monitoring is required, the sample is a function of the
instrument flowrate and samples should be each minute, stored and trended accordingly
• Rolling cubic meter data is not desired as it smooths peaks and reduced the ability to respond in a
‘timely’ manner.
4. How to perform Continuous Microbial Monitoring?
New instrumentation can ensure a faster and safer process with real time or
near real time data
Two primary options
• Single Use devices
• Rapid and Alternative
Microbiological Methods
BioCapt Single Use
Traditional technology
Tested up to 4-hours in continuous use
Continuous vs Frequent Monitoring
Improved Traditional - Validation of 4-Hour use
• GROWTH PROMOTION TEST Table of Microorganisms ATCC used for GPT
Pseudomonas aeruginosa ATCC 9027
BCSU1 38
1 BCSU 2 39
2 BCSU2 40
BCSU3 36
BCSU1 38
3 BCSU2 35
BCSU3 40
RMM - Cell Fluorescence
Endogenous Fluorophore Absorption and Fluorescence Maxima
Absorption Fluorescence
Fluorophore (nm) (nm)
404 - 568,
Porphyrins Active component of blood cells 620 580 - 622
Active component of vegetative
Chlorophyll cells 425, 455, 670 660 - 685
• Cell fluorescence in the 400 – 700nm wavelength band would detect the presence of:
• NADH
• Riboflavin
• Key triggers in determining the activity of bacterial cells
Optical Fundamentals
Volts
2 µm
0.5 Noise
µm
Time
• The sample is pulled through the optical chamber and illuminated by the laser source.
• Elastic light scatter occurs when a particle enters a laser beam.
• The trigger from the elastic light scatter activates the fluorescence circuit to detect any
fluorescence from that particle at a wavelength shift.
• Filters ensure only the active component of fluorescence is detected and the scattered light
does not interfere with the signal
Performance Qualification
Particle Count
Microbial
Data
Sample Data
Real-Time
Microbial Data
• Any need for continuous NVP sampling in Grade C/D rooms, where manufacturing
takes place but are not critical areas or connected to Grade B rooms/hoods?
• There is no specific drive from regulation to put continuous sensors in these areas, although we do have applications where they
have been installed. These areas are normally monitored by operators moving from location to location using portable
instrumentation.
• This exercise has a cost, labour is difficult to find and train, when many of these rooms/locations can be covered by 1 or 2 fixed
sensors, allowing operators to perform more value-added functions.
Global Partnership
EU GMP Annex 1
QUESTIONS?
THANK YOU
Contact us at:
info@pmeasuring.com
Visit:
www.pmeasuring.com