English (GB) Installation and operating instructions
English (GB)
2
4. Standard control panel
bar
English (GB)
The pumps are fitted with this control panel as standard. 6
1
3
3 0
Fig. 2 Setpoint set to 3 bar, constant pressure control
4 4.1.2 Pump in constant-curve control mode
3
Setting to minimum curve: 5. Advanced control panel
English (GB)
• Press continuously to change over to the minimum curve The pumps can be fitted with the advanced control panel as an
of the pump (bottom light field flashes). When the bottom light option.
field is on, press for 3 seconds until the light field starts
flashing.
• To change back, press continuously until the desired
setpoint is indicated. 1
Example: Pump set to minimum curve.
Figure 5 shows that the bottom light field is flashing, indicating
minimum curve.
2
H
6 3
Q
Fig. 5 Minimum curve duty Fig. 6 Advanced control panel
4
5.1 Home display
Pos. Symbol Description
English (GB)
Makes the pump ready for operation/starts and 1 2 3 4
stops the pump.
Start:
If you press the button when the pump is Home Status Settings Assist
stopped, the pump will only start if no other
Setpoint Control mode
functions with higher priority have been
5 enabled. See section 9. Priority of settings. Const. pressure
Stop:
5.00 bar
If you press the button when the pump is
running, the pump will always be stopped. Operaring mode Actual controlled value
When you stop the pump via this button, the
Normal
icon will appear in the bottom of the 4.90 bar
display.
9 8 7 6 5
Fig. 7 Example of "Home" display
5
5.3 Menu overview for advanced control panel
English (GB)
5.3.1 Home
CRE, CRIE,
Multipump
Home CRNE, SPKE, CME
system
MTRE
● ● ●
5.3.2 Status
CRE, CRIE,
Multipump
Status CRNE, SPKE, CME
system
MTRE
Operating status ● ● ●
Operating mode, from ● ● ●
Control mode ● ● ●
Pump performance ● ● ●
Actual controlled value ● ● ●
Resulting setpoint ● ● ●
Speed ● ● ●
Acc. flow and specific energy ● ● ●
Power and energy consumption ● ● ●
Measured values ● ● ●
Analog input 1 ● ● ●
Analog input 2 ● ● ●
Analog input 3 ● ● 1) ● 1)
Pt100/1000 input 1 ● ● 1) ● 1)
Pt100/1000 input 2 ● ● 1) ● 1)
1)
Analog output ● ● ● 1)
Warning and alarm ● ● ●
Actual warning or alarm ● ● ●
Warning log ● ● ●
Alarm log ● ● ●
Operating log ● ● ●
Operating hours ● ● ●
Fitted modules ● ● ●
Date and time ● ● ●
Product identification ● ● ●
Motor bearing monitoring ● ● ●
Multi-pump system ●
System operating status ●
System performance ●
System input power and energy ●
Pump 1, multi-pump system ●
Pump 2, multi-pump system ●
Pump 3, multi-pump system ●
Pump 4, multi-pump system ●
1)
Only available if an advanced functional module (FM300) is fitted.
6
5.3.3 Settings
English (GB)
CRE, CRIE,
Multipump
Settings CRNE, SPKE, CME Section Page
system
MTRE
Setpoint ● ● ● 7.1 Setpoint 12
Operating mode ● ● ● 7.2 Operating mode 12
Set manual speed ● ● ● 7.3 Set manual speed 12
Control mode ● ● ● 7.4 Control mode 12
Analog inputs ● ● ●
Analog input 1, setup ● ● ●
7.5 Analog inputs 16
Analog input 2, setup ● ● ●
Analog input 3, setup ● ● 1) ● 1)
Pt100/1000 inputs ● ● 1) ● 1)
1)
Pt100/1000 input 1, setup ● ● ● 1) 7.6 Pt100/1000 inputs 17
1)
Pt100/1000 input 2, setup ● ● ● 1)
Digital inputs ● ● ●
Digital input 1, setup ● ● ● 7.7 Digital inputs 17
1) 1)
Digital input 2, setup ● ● ●
Digital inputs/outputs ● ● ●
Digital input/output 3, setup ● ● ● 7.8 Digital inputs/outputs 18
Digital input/output 4, setup ● ● 1) ● 1)
Relay outputs ● ● ●
7.9 Signal relays 1 and 2 (Relay
Relay output 1 ● ● ● 18
outputs)
Relay output 2 ● ● ●
Analog output ● ● 1) ● 1)
1)
Output signal ● ● ● 1) 7.10 Analog output 19
Function of analog output ● ● 1) ● 1)
Controller settings ● ● ● 7.11 Controller (Controller settings) 20
Operating range ● ● ● 7.12 Operating range 21
Setpoint influence ● ● ● 7.13 External setpoint function 21
Ext. setpoint infl. ● ● ● 7.13 External setpoint function 21
Predefined setpoints ● ● 1) ● 1) 7.14 Predefined setpoints 23
Monitoring functions ● ● ●
Motor bearing monitoring ● ● ● 7.22 Motor bearing monitoring 27
Bearings replaced (Motor bearing
Motor bearing maintenance ● ● ● 28
maintenance)
Limit-exceeded function ● ● ● 7.15 Limit-exceeded function 24
LiqTec function ● ● ● 7.16 LiqTec (LiqTec function) 24
Special functions ● ● ●
7.17 Stop function (Low-flow stop
Low-flow stop function ● ● ● 25
function)
Pipe filling function ● ● ● 7.18 Pipe filling function 26
7.19 Pulse flowmeter (Pulse flowmeter
Pulse flowmeter setup ● ● ● 27
setup)
Ramps ● ● ● 7.20 Ramps 27
Standstill heating ● ● ● 7.21 Standstill heating 27
Communication ● ● ●
Pump number ● ● ● 7.24 Number (Pump number) 28
7.25 Radio communication
Enable/disable radio comm. ● ● ● 28
(Enable/disable radio comm.)
1) Only available if an advanced functional module (FM300) is fitted.
Continued on page 8.
7
Continued from page 7.
English (GB)
CRE, CRIE,
Multipump
Settings CRNE, SPKE, CME Section Page
system
MTRE
General settings ● ● ●
Language ● ● ● 7.26 Language 28
Set date and time ● ● ● 7.27 Date and time (Set date and time) 28
Units ● ● ● 7.28 Unit configuration (Units) 28
7.29 Buttons on product
Enable/disable settings ● ● ● 29
(Enable/disable settings)
Delete history ● ● ● 7.30 Delete history 29
Define Home display ● ● ● 7.31 Define Home display 29
Display settings ● ● ● 7.32 Display settings 29
7.33 Store settings (Store actual
Store actual settings ● ● ● 29
settings)
7.34 Recall settings (Recall stored
Recall stored settings ● ● ● 29
settings)
Run start-up guide ● ● ● 7.37 Run start-up guide 30
1)
Only available if an advanced functional module (FM300) is fitted.
5.3.4 Assist
CRE, CRIE,
Multipump
Assist CRNE, SPKE, CME Section Page
system
MTRE
Assisted pump setup ● ● ● 7.41 Assisted pump setup 30
Setup, analog input ● ● ● 7.42 Setup, analog input 31
Setting of date and time ● ● ● 7.43 Setting of date and time 31
7.44 Multi-pump setup (Setup of
Setup of multi-pump system ● ● ● 31
multi-pump system)
Description of control mode ● ● ● 7.45 Description of control mode 33
Assisted fault advice ● ● ● 7.46 Assisted fault advice 33
8
6. Grundfos GO 6.1 Communication
English (GB)
The pump is designed for wireless radio or infrared When Grundfos GO initiates communication with the pump, the
communication with Grundfos GO. indicator light in the middle of Grundfos Eye will flash green. See
Grundfos GO enables setting of functions and gives access to section 10. Grundfos Eye.
status overviews, technical product information and actual Furthermore, on pumps fitted with an advanced control panel a
operating parameters. text will appear in the display saying that a wireless device is
Grundfos GO offers the following mobile interfaces (MI). See fig. trying to establish connection. Press on the pump in order to
8. establish connection with Grundfos GO or press to reject
connection.
Establish communication using one of these communication
1 types:
• radio communication
+ • infrared communication.
6.1.1 Radio communication
2
Radio communication can take place at distances up to 30
3 metres. The first time Grundfos GO communicates with the pump,
+ you must enable communication by pressing or on the
pump control panel. Later when communication takes place, the
Pos. Description
Grundfos MI 202:
Add-on module enabling radio or infrared
1 communication. You can use MI 202 in conjunction with
an Apple iPhone or iPod with 30-pin connector and iOS
5.0 or later, e.g. fourth generation iPhone or iPod.
Grundfos MI 204:
Add-on module enabling radio or infrared
communication. You can use MI 204 in conjunction with
2 an Apple iPhone or iPod with Lightning connector, e.g.
fifth generation iPhone or iPod.
MI 204 is also available together with an Apple iPod
touch and a cover.
Grundfos MI 301:
Separate module enabling radio or infrared
3 communication. You can use the module in conjunction
with an Android or iOS-based smart device with
Bluetooth connection.
9
6.2 Menu overview for Grundfos GO
English (GB)
CRE, CRIE,
Multipump
Dashboard CRNE, SPKE, CME
system
MTRE
● ● ●
CRE, CRIE,
Multipump
Status CRNE, SPKE, CME
system
MTRE
System mode ● 2)
Resulting setpoint ● ●
Resulting system setpoint ● 2)
Actual controlled value ● ● ● 2)
Motor speed ● ●
Power consumption ● ●
Power cons., sys. ● 2)
Energy consumption ● ●
Energy cons., sys. ● 2)
Acc. flow, specific energy ● ● ● 2)
Operating hours ● ●
Operating hours, system ● 2)
Pt100/1000 input 1 ● ● 1)
Pt100/1000 input 2 ● ● 1)
Analog output ● ● 1)
Analog input 1 ● ●
Analog input 2 ● ●
Analog input 3 ● ● 1)
Digital input 1 ● ●
Digital input 2 ● ● 1)
Digital in/output 3 ● ●
Digital in/output 4 ● ● 1)
Fitted modules ● ●
Pump 1 ● 2)
Pump 2 ● 2)
Pump 3 ● 2)
Pump 4 ● 2)
1)
Only available if an advanced functional module (FM300) is fitted.
2)
Only available if Grundfos GO is connected to a multipump system.
CRE, CRIE,
Multipump
Settings CRNE, SPKE, CME Section Page
system
MTRE
Setpoint ● ● ● 7.1 Setpoint 12
Operating mode ● ● ● 7.2 Operating mode 12
Control mode ● ● ● 7.4 Control mode 12
Pipe-filling function ● ● ● 7.18 Pipe filling function 26
7.29 Buttons on product (Enable/disable
Buttons on product ● ● 29
settings)
LiqTec ● ● 1) 7.16 LiqTec (LiqTec function) 24
Stop function ● ● ● 7.17 Stop function (Low-flow stop function) 25
Controller ● ● ● 7.11 Controller (Controller settings) 20
Operating range ● ● ● 7.12 Operating range 21
Ramps ● ● 7.20 Ramps 27
Number ● ● 7.24 Number (Pump number) 28
7.25 Radio communication (Enable/disable
Radio communication ● ● 28
radio comm.)
1) Only available if an advanced functional module (FM300) is fitted.
Continues on page 11.
10
Continued from page 10.
English (GB)
CRE, CRIE,
Multipump
Settings CRNE, SPKE, CME Section Page
system
MTRE
Analog input 1 ● ●
Analog input 2 ● ● 7.5 Analog inputs 16
Analog input 3 ● ● 1)
Pt100/1000 input 1 ● ● 1)
7.6 Pt100/1000 inputs 17
Pt100/1000 input 2 ● ● 1)
Digital input 1 ● ●
7.7 Digital inputs 17
Digital input 2 ● ● 1)
Digital in/output 3 ● ●
7.8 Digital inputs/outputs 18
Digital in/output 4 ● ● 1)
Pulse flowmeter ● ● 7.19 Pulse flowmeter (Pulse flowmeter setup) 27
Predefined setpoint ● ● ● 7.14 Predefined setpoints 23
Analog output ● ● 1) 7.10 Analog output 19
External setpoint funct. ● ● 7.13 External setpoint function 21
Signal relay 1 ● ●
7.9 Signal relays 1 and 2 (Relay outputs) 18
Signal relay 2 ● ●
Limit 1 exceeded ● ● ●
7.15 Limit-exceeded function 24
Limit 2 exceeded ● ● ●
Alternating operation, time ● 2) 7.44 Multi-pump setup (Setup of multi-pump
1) + 2)
31
Time for pump changeover ● system)
Standstill heating ● ● 7.21 Standstill heating 27
Motor bearing monitoring ● ● 7.22 Motor bearing monitoring 27
Service ● ● 7.23 Service 28
Date and time ● ● 1) 7.27 Date and time (Set date and time) 28
Store settings ● ● 7.33 Store settings (Store actual settings) 29
Recall settings ● ● 7.34 Recall settings (Recall stored settings) 29
Undo ● ● ● 7.34.1 Undo 29
Pump name ● ● ● 7.35 Pump name 29
Connection code ● ● ● 7.36 Connection code 30
Unit configuration ● ● 7.28 Unit configuration (Units) 28
1)
Only available if an advanced functional module (FM300) is fitted.
2)
Only available if the Grundfos GO is connected to a multipump system.
CRE, CRIE,
Multipump
Alarms and warnings CRNE, SPKE, CME Section Page
system
MTRE
Alarm log ● ● ● 7.38 Alarm log 30
Warning log ● ● ● 7.39 Warning log 30
"Reset alarm" button ● ● ●
CRE, CRIE,
Multipump
Assist CRNE, SPKE, CME Section Page
system
MTRE
Assisted pump setup ● ● 7.41 Assisted pump setup 30
Assisted fault advice ● ● ● 7.46 Assisted fault advice 33
7.44 Multi-pump setup (Setup of multi-pump
Multi-pump setup ● ● ● 31
system)
11
7. Description of functions 7.4 Control mode
English (GB)
Examples
Normal
Manual • One external pressure sensor.
Min.
TM06 4024 1515
p p
Q
Stop
Fig. 11 Constant pressure
Fig. 9 Operating modes
Controller settings
Factory setting
For recommended controller settings, see section 7.11 Controller
See section 16. Factory settings. (Controller settings).
7.3 Set manual speed Factory setting
This menu is only available in the advanced control panel. With See section 16. Factory settings.
Grundfos GO, you set the speed via the "Setpoint" menu.
You can set the pump speed in % of the maximum speed. When
you have set the operating mode to "Manual", the pump will run
at the set speed.
Factory setting
See section 16. Factory settings.
12
7.4.2 Constant temperature 7.4.3 Constant differential pressure
English (GB)
Pump variant Constant temperature Constant differential
Pump variant
pressure
CME ●
CRE, CRIE, CRNE, SPKE, MTRE ● CME ●
CRE, CRIE, CRNE, SPKE, MTRE ●
This control mode ensures a constant temperature. Constant
temperature is a comfort control mode that can be used in The pump maintains a constant differential pressure,
domestic hot-water systems to control the flow to maintain a fixed independently of the flow in the system. See fig. 14.
temperature in the system. See fig. 12.
H
H
t
p
p
Fig. 13 Constant temperature
p
p
p p p
Controller settings
For recommended controller settings, see section 7.11 Controller
(Controller settings).
Factory setting
See section 16. Factory settings.
13
7.4.4 Constant differential temperature 7.4.5 Constant flow rate
English (GB)
Q
Fig. 18 Constant flow rate
Fig. 16 Constant differential temperature This control mode requires a flow sensor as shown below:
This control mode requires either two temperature sensors or one Example
differential-temperature sensor as shown in the examples below.
The temperature sensors can either be analog sensors
connected to two of the analog inputs or two Pt100/Pt1000
sensors connected to the Pt100/1000 inputs, if these are
Q
available on the specific pump.
The setup of the sensor can be made in the "Assist" menu under
"Assisted pump setup". See section 7.41 Assisted pump setup. Fig. 19 Constant flow rate
Controller settings
For recommended controller settings, see section 7.11 Controller
(Controller settings).
Factory setting
See section 16. Factory settings.
14
7.4.6 Constant level 7.4.7 Constant other value
English (GB)
Pump variant Constant level Pump variant Constant other value
CME ● CME ●
CRE, CRIE, CRNE, SPKE, MTRE ● CRE, CRIE, CRNE, SPKE, MTRE ●
The pump maintains a constant level, independently of the flow Any other value is kept constant.
rate. See fig. 20. Use this control mode if you wish to control a value which is not
available in the "Control mode" menu. Connect a sensor
H measuring the controlled value to one of the analog inputs of the
pump. The controlled value will be shown in percentage of sensor
range.
Controller settings
For recommended controller settings, see section 7.11 Controller
(Controller settings).
Factory setting
See section 16. Factory settings.
Controller settings
For recommended controller settings, see section 7.11 Controller
(Controller settings).
Factory setting
See section 16. Factory settings.
15
7.5 Analog inputs
Sensor function/measured parameter Pos.
English (GB)
16
7.6 Pt100/1000 inputs 7.7 Digital inputs
English (GB)
Available inputs depending on the functional module fitted in the
pump: Pump variant Digital inputs
CME ●
FM 200* FM 300*
Function (terminal) CRE, CRIE, CRNE, SPKE, MTRE ●
(standard) (advanced)
Pt100/1000 input 1, setup Available inputs depending on the functional module fitted in the
- ● pump:
(17 and 18)
Pt100/1000 input 2, setup
- ● FM 200* FM 300*
(18 and 19) Function (terminal)
(standard) (advanced)
* See section 13. Identification of functional module. Digital input 1, setup (2 and 6) ● ●
In order to setup the Pt100/1000 input for a feedback sensor, we Digital input 2, setup (1 and 9) - ●
recommend that you do this via the "Assisted pump setup" menu.
See section 7.41 Assisted pump setup. * See section 13. Identification of functional module.
If you wish to setup a Pt100/1000 input for other purposes, you To set up a digital input, make the settings below.
can do this manually. Function
You can setup the analog inputs via the "Setup, analog input" Select one of these functions:
menu. See section 7.42 Setup, analog input.
• Not active
If you perform the manual setting via Grundfos GO, you need to
When set to "Not active", the input has no function.
enter the menu for the Pt100/1000 input under the "Settings"
• External stop
menu.
When the input is deactivated (open circuit), the pump will
Function stop.
The Pt100/1000 inputs can be set to these functions: • Min. (minimum speed)
• Not active When the input is activated, the pump will run at the set
• Feedback sensor minimum speed.
Sensor used for the selected control mode. • Max. (maximum speed)
• Ext. setpoint infl. When the input is activated, the pump will run at the set
See section 7.13 External setpoint function maximum speed.
• Other function. • External fault
When the input is activated, a timer will be started. If the input
Measured parameter is activated for more than 5 seconds, the pump will be stopped
Select one of the parameters listed below, i.e. the parameter to and a fault will be indicated. This function depends on input
be measured in the system by the PT100/1000 sensor connected from external equipment.
to the actual PT100/1000 input. See fig. 24.
• Alarm resetting
When the input is activated, a possible fault indication will be
1 2
reset.
TM06 4012 1515
TT TT
• Dry running
3 When you have selected this function, lack of inlet pressure or
TT water shortage can be detected.
When lack of inlet pressure or water shortage (dry running) is
Fig. 24 Overview of PT100/1000 sensor locations detected, the pump will be stopped. The pump cannot restart
as long as the input is activated.
This requires the use of an accessory, such as these:
Parameter Pos. – a pressure switch installed on the suction side of the pump
Liquid temp. 1 – a float switch installed on the suction side of the pump.
Temperature 1 2 • Accumulated flow
Temperature 2 3 When you have selected this function, the accumulated flow
can be registered. This requires the use of a flowmeter which
Ambient temp. Not shown can give a feedback signal as a pulse per defined volume of
Measuring range water.
See section 7.19 Pulse flowmeter (Pulse flowmeter setup).
-50 to 204 °C.
• Predefined setpoint digit 1 (applies only to digital input 2)
Factory setting When digital inputs are set to predefined setpoint, the pump
See section 16. Factory settings. will operate according to a setpoint based on the combination
of the activated digital inputs.
See section 7.14 Predefined setpoints.
The priority of the selected functions in relation to each other
appears from section 9. Priority of settings.
A stop command will always have the highest priority.
Factory setting
See section 16. Factory settings.
17
7.8 Digital inputs/outputs Possible functions, digital input/output 4
English (GB)
Available inputs/outputs depending on the functional module • Not active • Not active
fitted in the pump: • External stop • Ready
• Min. • Alarm
FM 200* FM 300* • Max. • Operation
Function (terminal)
(standard) (advanced) • External fault • Pump running
Digital input/output 3, setup (6 and 10) ● ● • Alarm resetting • Warning
• Dry running • Limit 1 exceeded
Digital input/output 4, setup (11 and 18) - ●
• Accumulated flow • Limit 2 exceeded
* See section 13. Identification of functional module. • Predefined setpoint digit 3
You can select if the interface must be used as input or output. Factory setting
The output is an open collector and you can connect it to e.g. an
See section 16. Factory settings.
external relay or controller such as a PLC etc.
7.9 Signal relays 1 and 2 (Relay outputs)
+ 24V
Signal relays 1 and 2
Pump variant
(Relay outputs)
DO 3/4 TM06 4463_2315 CME ●
External
controller CRE, CRIE, CRNE, SPKE, MTRE ●
18
7.10 Analog output • Motor load
English (GB)
Pump variant Analog output Motor load
Signal range [%]
CME ● [V, mA]
CRE, CRIE, CRNE, SPKE, MTRE ● 0 100 200
0-10 V 0V 5V 10 V
Whether the analog output is available or not, depends on the
functional module fitted in the pump: 0-20 mA 0 mA 10 mA 20 mA
4-20 mA 4 mA 12 mA 20 mA
FM 200* FM 300*
Function (terminal) Reading is a percentage of the range between 0 and 200 % of the
(standard) (advanced)
maximum permissible load at the actual speed.
Analog output - ●
• Motor current
* See section 13. Identification of functional module.
Motor current
The analog output enables the reading of certain operating data Signal range [%]
to external control systems. [V, mA]
To set up the analog output, make the settings below. 0 100 200
Output signal 0-10 V 0V 5V 10 V
• 0-10 V 0-20 mA 0 mA 10 mA 20 mA
• 0-20 mA 4-20 mA 4 mA 12 mA 20 mA
• 4-20 mA.
Reading is a percentage of the range between 0 % and 200 % of
Function of analog output the rated current (I N).
• Actual speed • Limit 1 exceeded and Limit 2 exceeded
19
7.11 Controller (Controller settings)
Constant differential
English (GB)
Kp Ti
Controller temperature
Pump variant
(Controller settings)
CME ●
CRE, CRIE, CRNE, SPKE, MTRE ● t
The pumps have a factory default setting of gain (Kp) and integral
L2
time (Ti). -0.5 10 + 5L2
However, if the factory setting is not the optimum setting, you can
change the gain and the integral time: t
• Set the gain (Kp) within the range from 0.1 to 20.
t
• Set the integral-action time (Ti) within the range from 0.1 to t
3600 s. L2
0.5 0.5
p
0.5 0.5
0.5 0.5
p p
p p
Constant level Kp Ti
L1
L
ǻS
L1 < 5 m: 0.5 -2.5 100
0.5 L1 > 5 m: 3
L1 L1 > 10 m: 5
ǻS L
2.5 100
L1 = Distance [m] between pump and sensor.
Kp
Constant
Heating Cooling Ti General rules of thumb
temperature
system 1) system 2) If the controller is too slow-reacting, increase Kp.
If the controller is hunting or unstable, dampen the system by
reducing Kp or increasing Ti.
Factory setting
0.5 -0.5 10 + 5L2
t See section 16. Factory settings.
L2
L2
20
7.12 Operating range Example with constant curve with linear influence
English (GB)
Actual setpoint = actual input signal x (setpoint - user set min.
Pump variant Operating range speed) + user set min. speed.
CME ● At a "user set min. speed." of 25 %, and a setpoint of 85 % and an
external setpoint of 60 %, the actual setpoint is 0.60 x (85 - 25) +
CRE, CRIE, CRNE, SPKE, MTRE ●
25 = 61 %. See fig. 28.
Set the operating range as follows:
Speed [%]
• Set the minimum speed within the range from fixed minimum
speed to user-set maximum speed.
• Set the maximum speed within the range from user-set 100 Max. speed
minimum speed to fixed maximum speed. Setpoint 85 (fixed)
The range between the user-set minimum and maximum speeds
Actual setpoint 61
is the operating range. See fig. 26.
TM00 6785 5095 Fig. 28 Example of setpoint influence with constant curve
24 % User-set min. speed
7.13.1 Setpoint influence functions
13 % Min. speed (fixed)
You can select these functions:
0%
• Not active
Fig. 26 Example of minimum and maximum settings When set to "Not active", the setpoint will not be influenced
from any external function.
Factory setting
• Linear function
See section 16. Factory settings. The setpoint is influenced linearly from 0 to 100 %. See fig. 29.
7.13 External setpoint function
Setpoint influence [%]
External setpoint
Pump variant
function
100
CME ●
CRE, CRIE, CRNE, SPKE, MTRE ●
[bar]
Sensor max.
Setpoint 2 100
Actual
1.2
Setpoint
Sensor min. 0 0
0 Actual 100 % External
TM06 4165 1615
21
• Linear with Stop and Inverse with Min. • Inverse with Stop and Inverse with Min.
English (GB)
100 100
0 0
0 20 100 % External 0 80 100 % External
0.5 3.5 V input 0.5 3.5 V input
0 5V 0 5V
0 10 V 0 10 V
0 20 mA 0 20 mA
4 20 mA 4 20 mA
-50 204 C -50 204 C
TM06 4167 1615
Min. or Min. or
Stop Stop
Fig. 30 Linear with Stop and Inverse with Min. Fig. 32 Inverse with Stop and Inverse with Min.
100
100
0
0 100 % External input 0
0.5 3.5 V 0 100 % External
TM06 4168 1615
0 10 V 0 5V
0 20 mA 0 10 V
4 20 mA 0 20 mA
-50 204 C 4 20 mA
Fig. 31 Inverse function -50 204 C
Fig. 33 Influence table (example with five points)
22
• Influence table with Stop at Min. Factory setting
The setpoint is influenced by a curve made out of two to eight
English (GB)
See section 16. Factory settings.
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point. 7.14 Predefined setpoints
If the input signal is below 10 %, the pump will change to
operating mode "Stop". Pump variant Predefined setpoints
If the input signal is increased above 15 %, the operating
mode will be changed back to "Normal". CME -
See fig. 34. CRE, CRIE, CRNE, SPKE, MTRE ●
Setpoint influence [%] You can set and activate seven predefined setpoints by
combining the input signals to digital inputs 2, 3 and 4 as shown
in the table below.
100 Set the digital inputs 2, 3 and 4 to "Predefined setpoints" if all
seven predefined setpoints are to be used. You can also set one
or two of the digital inputs to "Predefined setpoints" but this will
limit the number of predefined setpoints available.
Digital inputs
Setpoint
2 3 4
0
External 0 0 0 Normal setpoint or stop
0 20 100 %
0.5 3.5 V input 1 0 0 Predefined setpoint 1
0 5V
0 1 0 Predefined setpoint 2
0 10 V
0 20 mA 1 1 0 Predefined setpoint 3
4 20 mA
0 0 1 Predefined setpoint 4
-50 204 C
1 0 1 Predefined setpoint 5
TM06 4171 1615
0 1 1 Predefined setpoint 6
Normal
1 1 1 Predefined setpoint 7
Min. or 0 = Open contact
Stop 1 = Closed contact
Fig. 34 Influence table with Stop at Min. (example with five Example
points) Figure 36 shows how you can use the digital inputs to set up
seven predefined setpoints. Digital input 2 is open and digital
• Influence table with Stop at Max. inputs 3 and 4 are closed. If you compare with the table above,
The setpoint is influenced by a curve made out of two to eight you can see that "Predefined setpoint 6" is activated.
points. There will be a straight line between the points and a
horizontal line before the first point and after the last point.
Digital input 4 Setpoint 7
If the input signal is above 90 %, the pump will change to
Digital input 3 7 Setpoint 6
operating mode "Min.". 6
If the input signal is reduced below 85 %, the operating mode Digital input 2 5
Setpoint 5
4
will be changed back to "Normal". Setpoint 4
Actual setpoint
See fig. 35. 3
Setpoint 3
2
Setpoint 2
Setpoint influence [%] 1
Setpoint 1
100 Normal
Stop setpoint
If all digital inputs are open, the pump will either stop or run at the
normal setpoint. Set the desired action with Grundfos GO or with
0 the advanced control panel.
0 80 100 % External
Factory setting
0.5 3.5 V input
0 5V See section 16. Factory settings.
0 10 V
0 20 mA
4 20 mA
-50 204 C
TM06 4172 1615
Normal
Min. or
Stop
Fig. 35 Influence table with Stop at Max. (example with five
points)
23
7.15 Limit-exceeded function Example:
English (GB)
24
7.17 Stop function (Low-flow stop function)
H
English (GB)
Stop function
Pump variant
(Low-flow stop function)
CME ●
CRE, CRIE, CRNE, SPKE, MTRE ●
Stop pressure
You can set the low-flow stop function to these values:
• Not active ƸH
• Energy-optimal mode Start pressure
• High-comfort mode
25
Operating conditions for the low-flow stop function 7.18 Pipe filling function
English (GB)
You can only use the stop function if the system incorporates a
pressure sensor, a non-return valve and a diaphragm tank. Pump variant Pipe filling function
26
7.19 Pulse flowmeter (Pulse flowmeter setup) 7.21 Standstill heating
English (GB)
Pulse flowmeter Pump variant Standstill heating
Pump variant
(Pulse flowmeter setup)
CME ●
CME ● CRE, CRIE, CRNE, SPKE, MTRE ●
CRE, CRIE, CRNE, SPKE, MTRE ●
You can use the function to avoid condensation in humid
You can connect an external pulse flowmeter to one of the digital environments. When you set the function to "Active" and the
inputs in order to register the actual and accumulated flows. pump is in operating mode "Stop", a low AC voltage will be
Based on this, the specific energy can also be calculated. applied to the motor windings. The applied voltage is not high
To enable a pulse flowmeter, set one of the digital-input functions enough to make the motor rotate but will ensure that sufficient
to "Accumulated flow" and set the pumped volume per pulse. See heat is generated to avoid condensation in the motor including
section 7.7 Digital inputs. the electronic parts in the drive.
The ramps determine how quickly the pump can accelerate and
decelerate, respectively, during start/stop or setpoint changes.
You can set the following: grundfos.com/E-pump1-manual
• acceleration time, 0.1 to 300 s Factory setting
• deceleration time, 0.1 to 300 s. See section 16. Factory settings.
The times apply to the acceleration from 0 rpm to maximum
(fixed) speed and the deceleration from max. (fixed) to 0 rpm, 7.22 Motor bearing monitoring
respectively. You can set the motor bearing monitoring function to these
At short deceleration times, the deceleration of the pump may values:
depend on load and inertia as there is no possibility of actively • Active
braking the pump. • Not active.
If the power supply is switched off, the deceleration of the pump When the function is set to "Active", a counter in the controller will
will only depend on load and inertia. start counting the mileage of the bearings.
Speed The counter will continue counting even if the
Maximum function is changed to "Not active", but a
(fixed) warning will not be given when it is time for
Maximum Note replacement.
(User set) When the function is changed to "Active" again,
Minimum the accumulated mileage will again be used to
(User set) calculate the replacement time.
Time
0
TM03 9439 0908
Factory setting
See section 16. Factory settings.
27
7.23 Service 7.27 Date and time (Set date and time)
English (GB)
Factory setting
See section 16. Factory settings.
7.26 Language
28
7.29 Buttons on product (Enable/disable settings) 7.33 Store settings (Store actual settings)
English (GB)
Buttons on product Store settings
Pump variant Pump variant
(Enable/disable settings) (Store actual settings)
CME ● CME ●
CRE, CRIE, CRNE, SPKE, MTRE ● CRE, CRIE, CRNE, SPKE, MTRE ●
In this display, you can disable the possibility of making settings Grundfos GO
for protective reasons. In this menu, you can store the actual settings for later use in the
Grundfos GO same pump or in other pumps of the same type.
If you set the buttons to "Not active" the buttons on the standard Advanced control panel
control panel will be disabled. If you set the buttons to "Not In this menu, you can store the actual settings for later use in the
active" on pumps fitted with an advanced control panel, see same pump.
below.
7.34 Recall settings (Recall stored settings)
Advanced control panel
If you have disabled the settings, you can still use the buttons to Recall settings
navigate through the menus but you cannot make changes in the Pump variant
(Recall stored settings)
"Settings" menu.
When you have disabled the possibility to make settings, the CME ●
symbol will appear in the display. CRE, CRIE, CRNE, SPKE, MTRE ●
29
7.36 Connection code • Setting of pump
English (GB)
– Go to Home
Pump variant Connection code – Run with Constant curve/Run with Constant pressure.
CME ● (See section 7.4 Control mode.
– Go to "Assisted pump setup".
CRE, CRIE, CRNE, SPKE, MTRE ●
See section 7.41 Assisted pump setup.
This menu is only available in Grundfos GO. – Return to factory settings.
You can setup a connection code to avoid having to press the * Applies only for pumps fitted with advanced functional module
connection button each time and to restrict remote access to the (FM 300). For further information, see section
product. 13. Identification of functional module.
Setting the code in the product using Grundfos GO
7.38 Alarm log
1. Connect Grundfos GO to the product.
This menu contains a list of logged alarms from the product. The
2. In the product dashboard, select "Settings".
log shows the name of the alarm, when the alarm occurred and
3. Choose "Connection code". when it was reset.
4. Enter the wanted code and press [OK].
The code must be a character string (ASCII). 7.39 Warning log
You can always modify the code. The old code is not needed. This menu contains a list of logged warnings from the product.
Setting the code in Grundfos GO The log shows the name of the warning, when the warning
You can define a default connection code in Grundfos GO so that occurred and when it was reset.
it automatically attempts to connect to the selected product via
7.40 Assist
this code.
When you select a product with the same connection code in The menu consist of a number of different assist functions which
Grundfos GO, Grundfos GO automatically connects to the are small guides that will take you through the steps needed to
product and you do not have to press the connection button on set up the pump.
the module.
7.41 Assisted pump setup
Define the default code in Grundfos GO in this way:
1. In the main menu, under "General", select "Settings". Pump variant Assisted pump setup
2. Choose "Remote".
CME ●
3. Enter the connection code in the field "Preset connection
CRE, CRIE, CRNE, SPKE, MTRE ●
code". The field now says "Connection code set".
You can always modify the default connection code by pressing The menu guides you through the following:
[Delete] and entering a new one. Setting of pump
If Grundfos GO fails to connect and ask you to press the • Selection of control mode. See page 12.
connection button on the product, it means that the product has
• Configuration of feedback sensors.
no connection code or has a different connection code. In this
case, you can only establish connection via the connection • Adjusting the setpoint. See page 12.
button. • Controller settings. See page 20.
• Summary of settings.
After setting a connection code, you must switch
off the product until the light in Grundfos Eye Example of how to use the "Assisted pump setup" for setting
Note
turns off before you can use the new connection up the pump to constant pressure:
code. Grundfos GO
7.37 Run start-up guide 1. Open the "Assist" menu.
2. Select "Assisted pump setup".
Pump variant Run start-up guide 3. Select control mode "Constant pressure" (Const. pressure).
CME ● 4. Read the description for this control mode.
5. Select which analog input to use as sensor input.
CRE, CRIE, CRNE, SPKE, MTRE ●
6. Select sensor function according to where the sensor is
This menu is only available in the advanced control panel. installed in the system. See fig. 23 on page 16.
The startup guide automatically starts when you start the pump 7. Select electrical input signal according to the sensor
for the first time. specifications.
You can always run the startup guide later via this menu. 8. Select measuring unit according to the sensor specifications.
The startup guide will guide you through the general settings of 9. Set the minimum and maximum sensor range values
the pump. according to the sensor specifications.
• Language. See section 7.26 Language. 10. Set the desired setpoint.
• Select date format.* 11. Set the controller settings Kp and Ti. See the
See section 7.27 Date and time (Set date and time). recommendations in section 7.11 Controller (Controller
• Set date.* settings).
See section 7.27 Date and time (Set date and time). 12. Type the desired pump name.
• Select time format.* 13. Check the summary of settings and confirm them.
See section 7.27 Date and time (Set date and time).
• Set time.*
See section 7.27 Date and time (Set date and time).
30
Advanced control panel 7.44 Multi-pump setup (Setup of multi-pump system)
English (GB)
1. Open the "Assist" menu.
2. Select "Assisted pump setup". Multi-pump setup
Pump variant (Setup of multi-pump
3. Select control mode "Const. pressure".
system)
4. Select which analog input to be used as sensor input.
5. Select the measured parameter which is to be controlled. See CME ●
fig. 23 on page 16. CRE, CRIE, CRNE, SPKE, MTRE ●
6. Select measuring unit according to the sensor specifications.
The multipump function enables the control of two pumps
7. Set the minimum and maximum sensor range values connected in parallel without the use of external controllers. The
according to the sensor specifications. pumps in a multipump system communicate with each other via
8. Select electrical input signal according to the sensor the wireless GENIair connection or the wired GENI connection.
specifications. A multipump system is set up via a selected pump, i.e. the master
9. Set the desired setpoint. pump (first selected pump).
10. Set the controller settings Kp and Ti. See recommendations in If two pumps in the system are configured with a
section 7.11 Controller (Controller settings). discharge-pressure sensor, they can all function as master
11. Check the summary of settings and confirm them by pressing pumps and take over the master pump function if the other should
[OK]. fail. This provides additional redundancy in the multipump
system.
7.42 Setup, analog input The multipump functions are described in the following sections.
7.44.1 Alternating operation
Pump variant Setup, analog input
Alternating operation functions as a duty/standby operating mode
CME ● and is possible with two pumps of same size and type connected
CRE, CRIE, CRNE, SPKE, MTRE ● in parallel. The main purpose of the function is to ensure an even
amount of running hours and to ensure that the standby pump
This menu is only available in the advanced control panel. takes over if the running pump stops due to an alarm.
The menu guides you through the following: Each pump requires a non-return valve in series with the pump.
Setup, analog input You can choose between two alternating operation modes:
• Analog inputs 1 to 3. See page 16. • Alternating operation, time
• Pt100/1000 input 1 and 2. See page 17. Change from one pump to the other is based on time.
• Adjusting the setpoint. See page 12. • Alternating operation, energy
• Summary. Change from one pump to the other is based on energy
consumption.
7.43 Setting of date and time If the duty pump fails, the other pump will take over automatically.
7.44.2 Backup operation
Pump variant Setting of date and time
Backup operation is possible with two pumps of same size and
CME ● type connected in parallel. Each pump requires a non-return
CRE, CRIE, CRNE, SPKE, MTRE ● valve in series with the pump.
One pump is operating continuously. The backup pump is
This menu is only available in the advanced control panel.
operated for a short time each day to prevent seizing up. If the
Whether this menu is available or not, depends on the functional
duty pump stops due to a fault, the backup pump will start
module fitted in the pump: automatically.
FM 200* FM 300*
Function (terminal)
(standard) (advanced)
Setting of date and time - ●
31
7.44.3 Setting up a multipump system Grundfos GO and wired pump connection
English (GB)
You can setup a multipump system in the following ways: 1. Connect the two pumps with each other with a 3-core
• Grundfos GO and wireless pump connection screened cable between the GENIbus terminals A, Y, B.
• Grundfos GO and wired pump connection 2. Power on both pumps.
• Advanced control panel and wireless pump connection 3. Establish contact to one of the pumps with the Grundfos GO.
• Advanced control panel and wired pump connection 4. Set up the needed analog and digital inputs via Grundfos GO
according to the connected equipment and the required
See step-by-step descriptions below.
functionality. See section 7.41 Assisted pump setup.
Grundfos GO and wireless pump connection 5. Assign a pump name to the pump using Grundfos GO. See
1. Power on both pumps. section 7.35 Pump name.
2. Establish contact to one of the pumps with Grundfos GO. 6. Assign pump number 1 to the pump. See section
3. Set up the needed analog and digital inputs via Grundfos GO 7.24 Number (Pump number).
according to the connected equipment and the required 7. Disconnect Grundfos GO from the pump.
functionality. See section 7.41 Assisted pump setup. 8. Establish contact to the other pump.
4. Assign a pump name to the pump using Grundfos GO. See 9. Via the Grundfos GO setup the needed analog and digital
section 7.35 Pump name. inputs according to the connected equipment and the required
5. Disconnect Grundfos GO from the pump. functionality. See section 7.41 Assisted pump setup.
6. Establish contact to the other pump. 10. Assign a pump name to the pump using the Grundfos GO.
7. Set up the needed analog and digital inputs via Grundfos GO See section 7.35 Pump name.
according to the connected equipment and the required 11. Assign pump number 2 to the pump. See section
functionality. See section 7.41 Assisted pump setup. 7.24 Number (Pump number).
8. Assign a pump name to the pump using Grundfos GO. See 12. Select the "Assist" menu and choose "Multi-pump setup".
section 7.35 Pump name. 13. Select the desired multipump function. See section
9. Select the "Assist" menu and choose "Multi-pump setup". 7.44.1 Alternating operation and 7.44.2 Backup operation
10. Select the desired multipump function. See section above.
7.44.1 Alternating operation and 7.44.2 Backup operation 14. Press [>] to continue.
above. 15. Set the time for pump changeover i.e. the time at which the
11. Press [>] to continue. alternation between the two pumps is to take place
12. Set the time for pump changeover i.e. the time at which the
This step applies only if you have selected
alternation between the two pumps is to take place
Note "Alternating operation, time" and if the pumps
This step applies only if you have selected are fitted with FM 300
Note "Alternating operation, time" and if the pumps 16. Press [>] to continue.
are fitted with FM 300
17. Select "BUS cable" as the communication method to be used
13. Press [>] to continue. between the two pumps.
14. Select "Radio" as the communication method to be used 18. Press [>] to continue.
between the two pumps. 19. Press "Select pump 2".
15. Press [>] to continue. 20. Select the additional pump from the list.
16. Press "Select pump 2".
The [OK] or button can be used to identify the
17. Select the additional pump from the list. Note
additional pump.
The [OK] or button can be used to identify the 21. Press [>] to continue.
Note
additional pump
22. Confirm the multipump setup by pressing [Send].
18. Press [>] to continue. 23. Press [Finish] in the appearing "Setup complete" dialog box.
19. Confirm the multipump setup by pressing [Send]. 24. Wait for the green indicator light in the middle of Grundfos Eye
20. Press [Finish] in the appearing "Setup complete" dialog box. to light up.
21. Wait for the green indicator light in the middle of Grundfos Eye The multipump system has now been setup.
to light up.
The multipump system has now been setup.
32
Advanced control panel and wireless pump connection Disabling a multipump system via Grundfos GO
English (GB)
1. Power on both pumps. 1. Select the "Assist" menu.
2. On both pumps, set up the needed analog and digital inputs 2. Select "Multi-pump setup".
according to the connected equipment and the required 3. Select "Disable".
functionality. See section 7.41 Assisted pump setup.
4. Press [>] to continue.
3. Select the "Assist" menu on one of the pumps and choose
5. Confirm the multipump setup by pressing [Send].
"Setup of multi-pump system".
6. Press [Finish].
4. Press [>] to continue.
The multipump system has now been disabled.
5. Select "Wireless" as the communication method to be used
between the two pumps. Disabling a multipump system via advanced control panel
6. Press [>] to continue. 1. Select the "Assist" menu.
7. Select the desired multipump function. See section 2. Select "Setup of multi-pump system".
7.44.1 Alternating operation and 7.44.2 Backup operation 3. Press [>] to continue.
above. 4. Confirm "No multi-pump function" by pressing [OK].
8. Press [>] three times to continue. 5. Press [>] to continue.
9. Press [OK] to search for other pumps. 6. Press [OK] to confirm.
The green indicator light in the middle of Grundfos Eye will
The multipump system has now been disabled.
flash on the other pumps.
10. Press the connect button on the pump which is to be added to 7.45 Description of control mode
the multipump system. This menu is only available in the advanced control panel.
11. Press [>] to continue. This menu describes each of the possible control modes. See
12. Set the time for pump changeover i.e. the time at which the also section 7.4 Control mode.
alternation between the two pumps is to take place.
7.46 Assisted fault advice
This step applies only if you have selected
This menu gives guidance and corrective actions in case of pump
Note "Alternating operation, time" and if the pumps
failures.
are fitted with FM 300.
13. Press [>] to continue.
14. Confirm the multipump setup by pressing [OK].
The multipump function icons will appear in the bottom of the
control panels.
The multipump system has now been setup.
Advanced control panel and wired pump connection
1. Connect the two pumps with each other with a 3-core
screened cable between the GENIbus terminals A, Y, B.
2. Set up the needed analog and digital inputs according to the
connected equipment and the required functionality. See
section 7.41 Assisted pump setup.
3. Assign pump number 1 to the first pump. See section
7.24 Number (Pump number).
4. Assign pump number 2 to the other pump. See section
7.24 Number (Pump number).
5. Select the "Assist" menu on one of the pumps and choose
"Setup of multi-pump system".
6. Press [>] to continue.
7. Select "Wired GENIbus" as the communication method to be
used between the two pumps.
8. Press [>] twice to continue.
9. Select the desired multipump function. See section
7.44.1 Alternating operation and 7.44.2 Backup operation
above.
10. Press [>] to continue.
11. Press [OK] to search for other pumps.
12. Select the additional pump from the list.
13. Press [>] to continue.
14. Set the time for pump changeover i.e. the time at which the
alternation between the two pumps is to take place.
33
8. Bus signal
English (GB)
9. Priority of settings
You can always set the pump to stop by pressing on the
pump control panel. When the pump is not in "Stop" mode, you
can always set the pump to stop by continuously pressing .
Furthermore, you can set the pump to maximum speed by
continuously pressing . You can always set the pump to
operation at maximum speed or to stop with Grundfos GO.
If two or more functions are enabled at the same time, the pump
will operate according to the function with the highest priority.
Example: If, via the digital input, the pump has been set to
maximum speed, the pump control panel or Grundfos GO can
only set the pump to "Manual" or "Stop".
The priority of the settings appears from the table below:
Grundfos GO or control
Priority Start/stop button Digital input Bus communication
panel on pump
1 Stop
2 Stop*
3 Manual
4 Max. speed*
5 Stop
6 Stop
7 Max. speed
8 Min. speed
9 Start
10 Max. speed
11 Min. speed
12 Min. speed
13 Start
14 Start
* If the bus communication is interrupted, the pump will resume its previous operating mode, for example "Stop", selected with Grundfos
GO or on the pump control panel.
34
10. Grundfos Eye
English (GB)
The operating condition of the pump is indicated by Grundfos Eye
on the control panel. See fig. 43, pos. A.
Power off.
No lights on.
Pump not running.
Warning.
One yellow indicator light permanently on.
Pump stopped.
35
11. Signal relays
English (GB)
The pump has two outputs for potential-free signals via two
internal relays.
You can set the signal outputs to "Operation", "Pump running",
"Ready", "Alarm" and "Warning".
The functions of the two signal relays appear from the table
below:
Power off. -
Off C NO NC C NO NC C NO NC C NO NC C NO NC
Pump running
"Normal", "Min."
in "Normal"
or "Max."
mode.
Green, rotating C NO NC C NO NC C NO NC C NO NC C NO NC
Pump running
in "Manual" "Manual"
mode.
C NO NC C NO NC C NO NC C NO NC C NO NC
Green, rotating
Pump in
operating "Stop"
mode "Stop".
Green, steady C NO NC C NO NC C NO NC C NO NC C NO NC
Warning, but
"Normal", "Min."
the pump is
or "Max."
running.
Yellow, rotating C NO NC C NO NC C NO NC C NO NC C NO NC
Warning, but
the pump is
running in "Manual"
"Manual"
mode. Yellow, rotating C NO NC C NO NC C NO NC C NO NC C NO NC
Warning, but
the pump was
stopped via "Stop"
"Stop"
Yellow, steady C NO NC C NO NC
command. C NO NC C NO NC C NO NC
Pump stopped
due to an "Stop"
alarm.
Red, flashing C NO NC C NO NC C NO NC C NO NC C NO NC
Pump stopped
due to
"Normal"
"Low-flow stop
function" Green, steady C NO NC C NO NC C NO NC C NO NC C NO NC
36
12. Installation of communication interface 4. Remove the securing screw (fig. 47, pos. A).
English (GB)
module (CIM)
Always use an antistatic service kit when A
handling electronic components. This will
prevent static electricity from damaging
Caution
components.
When unprotected, place the component on the
antistatic cloth.
5. Fit the CIM module by aligning it with the three plastic holders
(fig. 48, pos. A) and the connecting plug (fig. 48, pos. B).
Press home the module using your fingers.
A
D
C
Fig. 49 Connecting cable screens to earth
B
TM06 4084 1515
37
9. Route the wires for the CIM module, see the example in fig.
50.
English (GB)
FCC
Fig. 51 Position of FCC label
12. Fit the terminal box cover (fig. 45, pos. B) and cross-tighten
the four mounting screws (fig. 45, pos. A) to a torque of 6 Nm.
38
13. Identification of functional module 14. Identification of control panel
English (GB)
You can identify the fitted module in one of the following ways: You can identify the fitted module in one of the following ways:
Grundfos GO Grundfos GO
You can identify the functional module in the "Fitted modules" You can identify the control panel in the "Fitted modules" menu
menu under "Status". under "Status".
Pump display Pump display
For pumps fitted with the advanced control panel, you can identify For pumps fitted with the advanced control panel, you can identify
the functional module in the "Fitted modules" menu under the control panel in the "Fitted modules" menu under "Status".
"Status".
Motor name plate
Motor name plate You can identify the fitted control panel on the motor nameplate.
You can identify the fitted module on the motor nameplate. See See fig. 53.
fig. 52.
VARIANT
VARIANT ype :
Typ
Type P.C. : INPUT
Hp VARIANT
OUTPUT
PB :
:
Xxxxxxxxxxx
P.N. : Serial no : U in P
P2 : Hp
PB :
Hp VARIANT
PB : rpm FMFM :
E.P. Motor
ype :
Typ
Type P.C. : INPUT OUTPUT
DE : Env.Type
Env.Ty ype
p : TEFC ~ V n max: rpm:
NDE : SF : CL: f in : Hz Eff : HMI : Made in Hungary
:
HMI :
Xxxxxxxxxxx
P.N. : Serial no : U in P
P2 : Hp PB :
n max: rpm rpm FMFM : Wgt
Wggt : g Tamb :
kg F PF: I SF Ampp: A I 1/1 : A CIM :
E.P. Motor
DE : Env.Ty
Env.Type
ype
p : TEFC ~ V :
DK - 8850 Bjerringbro, Denmark
NDE :
Wgt
Wggt : gT
kg
SF :
amb :
CL:
F PF:
f in :
I SF Ampp: A I 1/1 :
Hz
A
Eff : HMI :
HMI:
HMI
CIM : :
Made in Hungary
DK - 8850 Bjerringbro, Denmark
CIM :
CIM :
Variant Description
Variant Description
HMI 200 Standard control panel
FM 200 Standard functional module HMI 300 Advanced control panel
FM 300 Advanced functional module
39
15. Changing the position of the control panel 4. Turn the plastic cover 180 °.
English (GB)
You can turn the control panel 180 °. Follow the instructions
Note Do not twist the cable more than 90 °.
below.
1. Loosen the four screws (TX25) holding the terminal box cover.
6. Fit the terminal box cover, and make sure that it is also turned
180 ° so that the buttons on the control panel are aligned with
the buttons on the plastic cover.
Tighten the four screws (TX25) with 5 Nm.
Fig. 55 Removing the terminal box cover
3. Press and hold in the two locking tabs (pos. A) while gently
lifting the plastic cover (pos. B).
TM05 5353 3612
40
16. Factory settings
English (GB)
● Function is enabled.
❍ Function is disabled.
- Function is not available.
17. Disposal
This product or parts of it must be disposed of in an
environmentally sound way:
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company
or service workshop.
The waste battery should be disposed of through the national
collective schemes. If in doubt, contact your local Grundfos
company.
Subject to alterations.
41
42
Argentina Finland Lithuania South Africa
Grundfos companies
Bombas GRUNDFOS de Argentina S.A. OY GRUNDFOS Pumput AB GRUNDFOS Pumps UAB GRUNDFOS (PTY) LTD
Ruta Panamericana km. 37.500 Centro Mestarintie 11 Smolensko g. 6 Corner Mountjoy and George Allen Roads
Industrial Garin FIN-01730 Vantaa LT-03201 Vilnius Wilbart Ext. 2
1619 Garín Pcia. de B.A. Phone: +358-(0)207 889 900 Tel: + 370 52 395 430 Bedfordview 2008
Phone: +54-3327 414 444 Telefax: +358-(0)207 889 550 Fax: + 370 52 395 431 Phone: (+27) 11 579 4800
Telefax: +54-3327 45 3190 Fax: (+27) 11 455 6066
France Malaysia E-mail: lsmart@grundfos.com
Australia Pompes GRUNDFOS Distribution S.A. GRUNDFOS Pumps Sdn. Bhd.
GRUNDFOS Pumps Pty. Ltd. Parc d’Activités de Chesnes 7 Jalan Peguam U1/25 Spain
P.O. Box 2040 57, rue de Malacombe Glenmarie Industrial Park Bombas GRUNDFOS España S.A.
Regency Park F-38290 St. Quentin Fallavier (Lyon) 40150 Shah Alam Camino de la Fuentecilla, s/n
South Australia 5942 Tél.: +33-4 74 82 15 15 Selangor E-28110 Algete (Madrid)
Phone: +61-8-8461-4611 Télécopie: +33-4 74 94 10 51 Phone: +60-3-5569 2922 Tel.: +34-91-848 8800
Telefax: +61-8-8340 0155 Telefax: +60-3-5569 2866 Telefax: +34-91-628 0465
Germany
Austria GRUNDFOS GMBH Mexico Sweden
GRUNDFOS Pumpen Vertrieb Ges.m.b.H. Schlüterstr. 33 Bombas GRUNDFOS de México S.A. de GRUNDFOS AB
Grundfosstraße 2 40699 Erkrath C.V. Box 333 (Lunnagårdsgatan 6)
A-5082 Grödig/Salzburg Tel.: +49-(0) 211 929 69-0 Boulevard TLC No. 15 431 24 Mölndal
Tel.: +43-6246-883-0 Telefax: +49-(0) 211 929 69-3799 Parque Industrial Stiva Aeropuerto Tel.: +46 31 332 23 000
Telefax: +43-6246-883-30 e-mail: infoservice@grundfos.de Apodaca, N.L. 66600 Telefax: +46 31 331 94 60
Service in Deutschland: Phone: +52-81-8144 4000
Belgium e-mail: kundendienst@grundfos.de Telefax: +52-81-8144 4010 Switzerland
N.V. GRUNDFOS Bellux S.A. GRUNDFOS Pumpen AG
Boomsesteenweg 81-83 HILGE GmbH & Co. KG Netherlands Bruggacherstrasse 10
B-2630 Aartselaar Hilgestrasse 37-47 GRUNDFOS Netherlands CH-8117 Fällanden/ZH
Tél.: +32-3-870 7300 55292 Bodenheim/Rhein Veluwezoom 35 Tel.: +41-44-806 8111
Télécopie: +32-3-870 7301 Germany 1326 AE Almere Telefax: +41-44-806 8115
Tel.: +49 6135 75-0 Postbus 22015
Belarus Telefax: +49 6135 1737 1302 CA ALMERE Taiwan
Представительство ГРУНДФОС в e-mail: hilge@hilge.de Tel.: +31-88-478 6336 GRUNDFOS Pumps (Taiwan) Ltd.
Минске Telefax: +31-88-478 6332 7 Floor, 219 Min-Chuan Road
220125, Минск Greece E-mail: info_gnl@grundfos.com Taichung, Taiwan, R.O.C.
ул. Шафарнянская, 11, оф. 56, БЦ GRUNDFOS Hellas A.E.B.E. Phone: +886-4-2305 0868
«Порт» 20th km. Athinon-Markopoulou Av. New Zealand Telefax: +886-4-2305 0878
Тел.: +7 (375 17) 286 39 72/73 P.O. Box 71 GRUNDFOS Pumps NZ Ltd.
Факс: +7 (375 17) 286 39 71 GR-19002 Peania 17 Beatrice Tinsley Crescent Thailand
E-mail: minsk@grundfos.com Phone: +0030-210-66 83 400 North Harbour Industrial Estate GRUNDFOS (Thailand) Ltd.
Telefax: +0030-210-66 46 273 Albany, Auckland 92 Chaloem Phrakiat Rama 9 Road,
Bosna and Herzegovina Phone: +64-9-415 3240 Dokmai, Pravej, Bangkok 10250
GRUNDFOS Sarajevo Hong Kong Telefax: +64-9-415 3250 Phone: +66-2-725 8999
Zmaja od Bosne 7-7A, GRUNDFOS Pumps (Hong Kong) Ltd. Telefax: +66-2-725 8998
BH-71000 Sarajevo Unit 1, Ground floor Norway
Phone: +387 33 592 480 Siu Wai Industrial Centre GRUNDFOS Pumper A/S Turkey
Telefax: +387 33 590 465 29-33 Wing Hong Street & Strømsveien 344 GRUNDFOS POMPA San. ve Tic. Ltd. Sti.
www.ba.grundfos.com 68 King Lam Street, Cheung Sha Wan Postboks 235, Leirdal Gebze Organize Sanayi Bölgesi
e-mail: grundfos@bih.net.ba Kowloon N-1011 Oslo Ihsan dede Caddesi,
Phone: +852-27861706 / 27861741 Tlf.: +47-22 90 47 00 2. yol 200. Sokak No. 204
Brazil Telefax: +852-27858664 Telefax: +47-22 32 21 50 41490 Gebze/ Kocaeli
BOMBAS GRUNDFOS DO BRASIL Phone: +90 - 262-679 7979
Av. Humberto de Alencar Castelo Branco, Hungary Poland Telefax: +90 - 262-679 7905
630 GRUNDFOS Hungária Kft. GRUNDFOS Pompy Sp. z o.o. E-mail: satis@grundfos.com
CEP 09850 - 300 Park u. 8 ul. Klonowa 23
São Bernardo do Campo - SP H-2045 Törökbálint, Baranowo k. Poznania Ukraine
Phone: +55-11 4393 5533 Phone: +36-23 511 110 PL-62-081 Przeźmierowo Бізнес Центр Європа
Telefax: +55-11 4343 5015 Telefax: +36-23 511 111 Tel: (+48-61) 650 13 00 Столичне шосе, 103
Fax: (+48-61) 650 13 50 м. Київ, 03131, Україна
Bulgaria India Телефон: (+38 044) 237 04 00
Grundfos Bulgaria EOOD GRUNDFOS Pumps India Private Limited Portugal Факс.: (+38 044) 237 04 01
Slatina District 118 Old Mahabalipuram Road Bombas GRUNDFOS Portugal, S.A. E-mail: ukraine@grundfos.com
Iztochna Tangenta street no. 100 Thoraipakkam Rua Calvet de Magalhães, 241
BG - 1592 Sofia Chennai 600 096 Apartado 1079 United Arab Emirates
Tel. +359 2 49 22 200 Phone: +91-44 2496 6800 P-2770-153 Paço de Arcos GRUNDFOS Gulf Distribution
Fax. +359 2 49 22 201 Tel.: +351-21-440 76 00 P.O. Box 16768
email: bulgaria@grundfos.bg
Indonesia Telefax: +351-21-440 76 90 Jebel Ali Free Zone
PT. GRUNDFOS POMPA Dubai
Canada Graha Intirub Lt. 2 & 3 Romania Phone: +971 4 8815 166
GRUNDFOS Canada Inc. Jln. Cililitan Besar No.454. Makasar, GRUNDFOS Pompe România SRL Telefax: +971 4 8815 136
2941 Brighton Road Jakarta Timur Bd. Biruintei, nr 103
Oakville, Ontario ID-Jakarta 13650 Pantelimon county Ilfov United Kingdom
L6H 6C9 Phone: +62 21-469-51900 Phone: +40 21 200 4100 GRUNDFOS Pumps Ltd.
Phone: +1-905 829 9533 Telefax: +62 21-460 6910 / 460 6901 Telefax: +40 21 200 4101 Grovebury Road
Telefax: +1-905 829 9512 E-mail: romania@grundfos.ro Leighton Buzzard/Beds. LU7 4TL
Ireland Phone: +44-1525-850000
China GRUNDFOS (Ireland) Ltd. Russia Telefax: +44-1525-850011
GRUNDFOS Pumps (Shanghai) Co. Ltd. Unit A, Merrywell Business Park ООО Грундфос Россия
10F The Hub, No. 33 Suhong Road Ballymount Road Lower 109544, г. Москва, ул. Школьная, 39-41, U.S.A.
Minhang District Dublin 12 стр. 1 GRUNDFOS Pumps Corporation
Shanghai 201106 Phone: +353-1-4089 800 Тел. (+7) 495 564-88-00 (495) 737-30-00 17100 West 118th Terrace
PRC Telefax: +353-1-4089 830 Факс (+7) 495 564 88 11 Olathe, Kansas 66061
Phone: +86 21 612 252 22 E-mail grundfos.moscow@grundfos.com Phone: +1-913-227-3400
Telefax: +86 21 612 253 33
Italy Telefax: +1-913-227-3500
GRUNDFOS Pompe Italia S.r.l. Serbia
Croatia Via Gran Sasso 4 Grundfos Srbija d.o.o. Uzbekistan
GRUNDFOS CROATIA d.o.o. I-20060 Truccazzano (Milano) Omladinskih brigada 90b Grundfos Tashkent, Uzbekistan The Repre-
Buzinski prilaz 38, Buzin Tel.: +39-02-95838112 11070 Novi Beograd sentative Office of Grundfos Kazakhstan in
HR-10010 Zagreb Telefax: +39-02-95309290 / 95838461 Phone: +381 11 2258 740 Uzbekistan
Phone: +385 1 6595 400 Telefax: +381 11 2281 769 38a, Oybek street, Tashkent
Telefax: +385 1 6595 499
Japan www.rs.grundfos.com Телефон: (+998) 71 150 3290 / 71 150
www.hr.grundfos.com GRUNDFOS Pumps K.K. 3291
Gotanda Metalion Bldg., 5F, Singapore Факс: (+998) 71 150 3292
Czech Republic 5-21-15, Higashi-gotanda GRUNDFOS (Singapore) Pte. Ltd.
GRUNDFOS s.r.o. Shiagawa-ku, Tokyo 25 Jalan Tukang Addresses Revised 10.03.2015
Čajkovského 21 141-0022 Japan Singapore 619264
779 00 Olomouc Phone: +81 35 448 1391 Phone: +65-6681 9688
Phone: +420-585-716 111 Telefax: +81 35 448 9619 Telefax: +65-6681 9689
Telefax: +420-585-716 299
Korea Slovakia
Denmark GRUNDFOS Pumps Korea Ltd. GRUNDFOS s.r.o.
GRUNDFOS DK A/S 6th Floor, Aju Building 679-5 Prievozská 4D
Martin Bachs Vej 3 Yeoksam-dong, Kangnam-ku, 135-916 821 09 BRATISLAVA
DK-8850 Bjerringbro Seoul, Korea Phona: +421 2 5020 1426
Tlf.: +45-87 50 50 50 Phone: +82-2-5317 600 sk.grundfos.com
Telefax: +45-87 50 51 51 Telefax: +82-2-5633 725
E-mail: info_GDK@grundfos.com Slovenia
www.grundfos.com/DK
Latvia GRUNDFOS d.o.o.
SIA GRUNDFOS Pumps Latvia Šlandrova 8b, SI-1231 Ljubljana-Črnuče
Estonia Deglava biznesa centrs Phone: +386 31 718 808
GRUNDFOS Pumps Eesti OÜ Augusta Deglava ielā 60, LV-1035, Rīga, Telefax: +386 (0)1 5680 619
Peterburi tee 92G Tālr.: + 371 714 9640, 7 149 641 E-mail: slovenia@grundfos.si
11415 Tallinn Fakss: + 371 914 9646
Tel: + 372 606 1690
Fax: + 372 606 1691
ECM: 1164591
98960144 0915
www.grundfos.com
The name Grundfos, the Grundfos logo, and be think innovate are registered trademarks owned by Grundfos Holding A/S or Grundfos A/S, Denmark. All rights reserved worldwide. © Copyright Grundfos Holding A/S