Line voltage 380 ... 480 V +10 % -20 % Switching level: 0→1 11 V
Output Number 1
Rated voltage 400V IEC 480V NEC 1) Number as relay changeover contact 1
150 % base load current IL for 3 s, followed by 110 % base load current IL for 57 s PTC/ KTY interface
in a 300 s cycle time
1 motor temperature sensor input, sensors that can be connected PTC, KTY and
High Overload (HO) Thermo-Click, accuracy ±5 °C
200 % base load current IH for 3 s, followed by 150 % base load current IH for 57 Closed-loop control techniques
s in a 300 s cycle time
V/f linear / square-law / parameterizable Yes
General tech. specifications V/f with flux current control (FCC) Yes
Power factor λ 0.90 ... 0.95
V/f ECO linear / square-law Yes
Offset factor cos φ 0.99
Sensorless vector control Yes
Efficiency η 0.99
Vector control, with sensor No
Sound pressure level (1m) 68 dB
Encoderless torque control No
Power loss 1,540.0 W
Torque control, with encoder No
Filter class (integrated) Class A
Communication
Communication PROFINET, EtherNet/IP
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1 of 2 Generated Wed Dec 6 15:51:02 CET 2023
Data sheet for SINAMICS G120C
Cooling air requirement 0.153 m³/s (5.403 ft³/s) Comparison with the reference
35.0 %
converter (90% / 100%)
Installation altitude 1,000 m (3,280.84 ft)
Ambient temperature
I 1,000.0 W (1.1 %) 1,200.0 W (1.3 %) 1,540.0 W (1.6 %)
Operation -20 ... 40 °C (-4 ... 104 °F) 100%
Relative humidity
Max. operation 95 % RH, condensation not permitted 561.0 W (0.6 %) 636.0 W (0.7 %) 746.0 W (0.8 %)
50%
Connections
Signal cable 416.0 W (0.4 %) 449.0 W (0.5 %)
25%
0.15 ... 1.50 mm²
Conductor cross-section
(AWG 24 ... AWG 16)
Line side
50% 90% f
Version screw-type terminal
The percentage values show the losses in relation to the rated apparent power of
35.00 ... 120.00 mm² the converter.
Conductor cross-section
(AWG 2 ... AWG -3)
The diagram shows the losses for the points (as per standard IEC61800-9-2) of
Motor end the relative torque generating current (I) over the relative motor stator frequency
(f). The values are valid for the basic version of the converter without
Version Screw-type terminals options/components.
35.00 ... 120.00 mm² *calculated values
Conductor cross-section
(AWG 2 ... AWG -3)
Mechanical data
Degree of protection IP20 / UL open type
Dimensions
Standards
Compliance with standards UL, cUL, CE, C-Tick (RCM)
Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 2 of 2 Generated Wed Dec 6 15:51:02 CET 2023