You are on page 1of 60

Instruction manual COM_CPS

Part Number :NCCPSGB


Révision : 2.0

The Fixed Gas Detection Experts


Copyright  2015 by Oldham
All rights reserved. Reproduction in any form, in whole or in part, without the express written
consent of Oldham is strictly prohibited.
The information contained within this manual is true and correct to the best of our
knowledge.
Due to ongoing research and development, the specifications of this product may be
changed at any time without notice.
Microsoft and Windows are registered trademarks of Microsoft Corporation in the United
States and other countries.
Oldham
Rue Orfila
Z.I. Est – CS 20417
62027 ARRAS Cedex FRANCE
Phone: +33 (0)3 21 60 80 80
Fax: +33 (0)3 21.60.80.00
GAS DETECTION
We are delighted that you have chosen an OLDHAM instrument and would like to thank you for your
choice.

We have taken all the necessary measures to ensure that your instrument provides total satisfaction.

Now it is important to read this document carefully.

EXTENT OF RESPONSIBILITY
* OLDHAM declines its responsibility towards any person for material damage, physical injury or death resulting
wholly or partly from inappropriate use, installation or storage of its equipment resulting from failure to observe
instructions and warnings and/or standards and regulations in force.

* OLDHAM neither supports nor authorises any company, physical or moral person to assume responsibility on
behalf of OLDHAM , even if it is involved in the sale of OLDHAM products.

* OLDHAM cannot be held responsible for direct or indirect damage or be required to pay direct or indirect
compensation resulting from the sale or use of any of its products IF THESE PRODUCTS HAVE NOT BEEN
DEFINED AND CHOSEN BY OLDHAM FOR THEIR SPECIFIC USE.

CLAUSES CONCERNING PROPERTY


* Drawings, plans, specifications and information included in this document contain confidential information that is
the property of OLDHAM

* None of this information may be reproduced, copied, divulged or translated, by physical, electronic or an y other
means, nor used as the basis for the manufacture or sale of OLDHAM equipment or for any other reasons
without prior consent from OLDHAM

WARNINGS
* This document is not contractually binding. In the interests of its customers, OLDHAM reserves to modify the
technical specifications of its equipment without notice, in order to improve its performance.

* READ THIS MANUAL CAREFULLY BEFORE FIRST USE OF THE EQUIPMENT: this manual must be read by
any person who is or will be responsible for using, maintaining or repairing this equipment.

* This equipment will only provide the announced performance levels if it is used, maintained and repaired
according to OLDHAM directives, by OLDHAM personnel or by personnel approved by OLDHAM

GUARANTEE
2 years guarantee in normal conditions of use on parts and technical labour, return in our workshops, excluding
consumables (sensors, filters, etc.)

3
Table of Contents

Chapter 1 General Information................................................................................... 7


The Instruction Manual .......................................................................................................................7
The Software ......................................................................................................................................7
Translation .........................................................................................................................................7

Chapter 2 Introduction ............................................................................................... 8


Purpose of the Application ..................................................................................................................8
Principles of Operation .......................................................................................................................8
Quick Start .........................................................................................................................................9
Basic Overview of the CPS Central Measuring Controller Characteristics ..........................................9

Chapter 3 Installation ................................................................................................. 9


System and Hardware Requirements .................................................................................................9
Installing the COM_CPS software ......................................................................................................9
Connect a serial output from the PC to the CPS. ............................................................................. 10
Connect a USB output from the PC to the CPS. ............................................................................... 10
Step 1: Installing the USB communication driver .............................................................................. 10
Step 1: Establish a connection between the PC and the CPS central controller. .............................. 10
Remove the COM_CPS Software ..................................................................................................... 11

Chapter 4 Overview of the Software ........................................................................ 11


Running the Software ....................................................................................................................... 11
Selection of the Display Language ................................................................................................... 11
The Main Screen .............................................................................................................................. 12
Menus .............................................................................................................................................. 13
File ................................................................................................................................................... 13
Communication ................................................................................................................................ 13
Transfer ............................................................................................................................................ 14
? ....................................................................................................................................................... 14
The fast access zone........................................................................................................................ 14
The Print Button ............................................................................................................................... 15
Right click ......................................................................................................................................... 15
Printing ............................................................................................................................................. 15
Matrix display ................................................................................................................................... 16
General Overview ............................................................................................................................. 16
Cell contents ................................................................................................................................ 16
Exiting the Software ......................................................................................................................... 17

Chapter 5 Using the Software .................................................................................. 17


Step 1: Configuring the CPS central detection controller .................................................................. 17
Step 2: Configuration transfer to a CPS central detection controller ................................................. 17
Step 3: Reviewing and/or modifying data transferred from the CPS ................................................. 18

4
Chapter 6 General Configuration ............................................................................. 18
Presentation of Data ......................................................................................................................... 18
Use ................................................................................................................................................... 19
Step 1: Left zone .............................................................................................................................. 19
Step 2: Line Name zone ................................................................................................................... 20
Step 3: Internal Audible Alarm zone ................................................................................................. 20
Step 3: RS-485 Communication zone ............................................................................................... 21
Saving the Configuration .................................................................................................................. 21

Chapter 7 Configuring the Detectors ....................................................................... 22


Presentation of Data ......................................................................................................................... 22
Top of the Window ........................................................................................................................... 22
Bottom of the Window ...................................................................................................................... 23
Use ................................................................................................................................................... 23
Modify the Settings for a Detector .................................................................................................... 23
Remove a Detector From the List ..................................................................................................... 28
Saving the Configuration .................................................................................................................. 28

Chapter 8 Installation Architecture .......................................................................... 28


Presentation of Data ......................................................................................................................... 28
Use ................................................................................................................................................... 29
Numbering the Lines ........................................................................................................................ 29
Adding a sensor to a CPS line. ......................................................................................................... 29
Adding a module (input, output, relay) to a CPS line ........................................................................ 30
Removing equipment from a CPS line. ............................................................................................. 33
Saving the Configuration .................................................................................................................. 33

Chapter 9 Relay Actions........................................................................................... 34


Presentation of Data ......................................................................................................................... 34
Define relay actions .......................................................................................................................... 34
View the configuration of a relay ...................................................................................................... 37
Change the configuration of a relay .................................................................................................. 38
Remove the configuration of a relay ................................................................................................. 39
List of Low Speed – High Speed Assignment ................................................................................... 40
Saving the Configuration .................................................................................................................. 40

Chapter 10 4-20 mA Output Actions .......................................................................... 41


Presentation of Data ......................................................................................................................... 41
Define the analog outputs actions .................................................................................................... 41
View the configuration of an output. ................................................................................................. 43
Change the configuration of an output. ............................................................................................. 44
Remove the configuration of an output. ............................................................................................ 45
Saving the Configuration .................................................................................................................. 45

Chapter 11 Logic Input Actions (LI) ........................................................................... 46


Presentation of Data ......................................................................................................................... 46
Use ................................................................................................................................................... 46

5
Saving the Configuration .................................................................................................................. 47

Chapter 12 Relay Data ................................................................................................ 48


Presentation of Data ......................................................................................................................... 48
Use ................................................................................................................................................... 48
Configure the internal CPS central controller relays ......................................................................... 48
Configure delays for the buzzer relays ............................................................................................. 49
Configure the times when forced ventilation is blocked .................................................................... 49
Configure the operation intervals for forced ventilation ..................................................................... 50
Saving the Configuration .................................................................................................................. 51

Chapter 13 Transfer Configuration Settings ............................................................. 51


Transfer from PC CPS .................................................................................................................. 51
Step 1: establish a physical connection ............................................................................................ 51
Step 2: configure the connection ...................................................................................................... 51
Step 3: data transfer ......................................................................................................................... 52
Transfer from CPS PC .................................................................................................................. 52
Step 1: establish a connection .......................................................................................................... 52
Step 2: configure the connection ...................................................................................................... 52
Step 3: data transfer ......................................................................................................................... 52

Chapter 14 Configuration Pages ................................................................................ 53


General configuration tab ................................................................................................................. 53
Configuring the Detectors tab ........................................................................................................... 53
Detector Tab:.................................................................................................................................... 53
Alarm 1 Tab ...................................................................................................................................... 53
Alarm 2 Tab ...................................................................................................................................... 54
Alarm 3 Tab ...................................................................................................................................... 54
Alarm 4 Tab ...................................................................................................................................... 54
Out of Range and Fault tab .............................................................................................................. 54

Chapter 15 Index ........................................................................................................ 55

6
I. GENERAL INFORM ATION

1. The Instruction Manual

Read this entire Instruction Manual carefully before using the software application.
The Instruction Manual is designed to serve as a guide and reference tool for any individual working
with the COM_CPS software.
Oldham publishes this manual for the sole purpose of providing its customers with a simple and
precise source of information. Oldham shall is not responsible or liable for any misinterpretation that
may result from the reading of this manual. Although every effort is made to ensure accuracy, this
manual may contain unintentional technical inaccuracies. Should questions arise, please contact
Oldham for additional information.
Every effort has been made to ensure the accuracy of information presented in this manual. Product
updates and/or modifications may occur without prior notification which would not be incorporated
into the present document.
This Instruction Manual and its contents are the inalienable property of Oldham .

2. The Softw are

Neither Oldham nor any other affiliated organization shall be held responsible under any
circumstances for any damage whatsoever including damages for loss of production, interruption of
production, loss of information, COM_CPS software failure, personal injury, loss of time, money, or
materials, or for any indirect or consecutive consequence of loss occurring during the use of the
product or the inability to use the product, even if Oldham had been informed of such damages.

3. Translation

This manual is a translation of the original, which was written in French.


In case of any discrepancies between the French version and any translated version, the French
version shall take precedence and shall prevail in all matters pertaining to any relationship between
the parties.
Any and all translations of the present manual into a foreign language are provided for convenience
and reference purposes only.

7
II. INTRODUCTION
The COM_CPS software runs on a PC platform. It is designed to be used exclusively with a CPS (C ar
Park System) central detection controller from Oldham . CPS central controller operations are addressed
in a separate manual.

1. Purpose of the Application

The COM_CPS software allows you to:


■ configure one or more central detection controllers through a PC, to save these settings and to
transfer them to the CPS central detection controller(s);
■ transfer the settings from a CPS central detection controller for review or modification with the
COM_CPS software.

Figure 1: the COM_CPS software is designed to


configure CPS central measuring controllers via a PC. D1

2. Principles of Operation

Once installed on a PC, the COM_CPS software can be used for the procedures described below:
■ Step 1: general configuration settings for the CPS central detection controller (display language,
central controller name, password, line names, etc.). These functions are described in detail in
the “General Configuration” chapter on page 18.
■ Step 2: configurations for various types of detectors (type and range of measurement, alarm
thresholds, etc.) which can be connected to the CPS central measuring station to be configured.
These functions are described in detail in the “Configuration of Various Detectors” chapter on
page 22.
■ Step 3: creation of installation architecture, or module attribution (detector, relay module, logic
input module, logic output module) at various locations along the installation. These functions are
described in detail in the “Installation Architecture” chapter on page 28.
■ Step 4: definition of the "events – relay activation” relationship. This function is described in
detail in the “Relay Action Matrix” chapter on page 34.
■ Step 5: definition of the "events – analog outputs” relationship. This function is described in detail
in the “Outputs Action Matrix” chapter on page 41.
■ Step 6: definition of the "logic inputs (LI) – logic output activation” relationship. This function is
described in detail in the “Logic Inputs Action Matrix” chapter on page 46.
■ Step 7: identification of events acting on the CPS central measuring controller’s shared relays,
internal activated audible alarm delays, forced ventilation shut-down schedules and forced
ventilation settings. These functions are described in detail in the “Relay Information” chapter on
page 48.
■ Step 8: transfer of configuration data from the PC to the CPS central measuring controller or
transfer of central controller settings to the PC for verification and/or modification. These
functions are described in detail in the “Transfer of Configuration Settings” chapter on page 51.
Clear, detailed instructions for all of the functions described above are categorized according to
order of use and can be accessed through the tabs in the software interface.

8
3. Quick Start

Each of the steps described in the "Principles of Operation" passage on page 8 must be completed
systematically in order to properly configure the application. There is no quick start option.

4. Basic Overview of the CPS Central Detection Controller


Characteristics

The CPS central measuring controller is designed to monitor environmental conditions (carbon
monoxide, etc.) in parking facilities and tunnels. Its primary technical characteristics include:
■ Wall-mounted or rack-mounted central controller
■ 8 lines
■ Max. of 32 modules per line (256 total modules max.)
■ Many modules available, each with a specific function such as:
- detector module (CO, NO, NO 2, O2, explosive gasses, etc.);
- 16 logic inputs module;
- 4 analog outputs module;
- 8 relay module;
- 4 relay module.
■ Communication via RS-485 JBUS to a supervision system and via RS-232 or USB to a PC for
configuration.
■ Optional printer.

III. INSTALL ATION


This chapter describes the procedures for installing and uninstalling the software and for establishing a
direct connection (RS-232 serial connector or USB) between the CPS central detection controller and the
PC running the COM_CPS software.

1. System and Hardware Requirements

COM_CPS must be installed on a PC running Windows 2000 or Windows XP. The minimum
requirements to install COM_CPS are:
■ Windows 98 SE, Windows NT, Windows 2000, Windows XP or Windows Vista with 256 MB RAM.
■ A CD-ROM drive
■ At least 10 MB of free hard drive space
■ An optional USB connection or free RS 232 port (optional) to link the CPS central detection
controller to the PC.

2. Installing the COM_CPS softw are

The installation procedures for this software are standard. After inserting the disc into the CD ROM
drive, instructions will appear on screen to guide you through the installation.
If the auto-installer does not execute properly, run the program by double clicking on the
Setup.exe icon in the CD ROM drive.

A folder named OLDHAM > COM_CPS will be created in the Start > Programs menu.

9
3. Connect a serial output from the PC to the CPS.

This establishes a connection between the PC running the COM_CPS software and the CPS central
detection controller via an (RS-232) serial cable run between the PC and the CPS central controller.
Follow the steps below to make the connection:
1. Plug the connector into a free serial (COM) port on the PC.
2. Plug the connector into the CPS RS-232 serial port (see the central detection controller manual
for the location of the connector).

4. Connect a USB output from the PC to the CPS.

The corresponding USB driver must be installed before the PC is connected to the central
measuring station.
Step 1: Installing the USB communication driver

Follow the instructions in the paragraph below if you are connecting your PC to the CPS
central measuring controller with a USB connection.
A communication driver must be installed on the PC running the COM_CPS software in order to
enable communication between the PC’s USB port and the central measuring controller.
The CD ROM contains various drivers corresponding to different versions of Windows. Select the
driver appropriate for the version of Windows on your PC, decompress the file and double-click on
the executable file to install the driver. A PDF help file is included for each driver.

File name Operating system


CDM 2.00.00 Vista XP Windows 2000, XP, Vista and Server 2003
Server2003 2000.zip
CDM 2.00.00 x64.zip Windows 64-bit
CDM 2.00.00.zip Windows 32-bit
CDM 3.01.04 98 ME.zip Windows 98 and ME. Choose VCP FTDIBUS.INF

Table 1: RS-232 and USB Communication Drivers delivered.

Step 1: Establish a connection between the PC and the CPS central controller.

This establishes a connection between the PC running the COM_CPS software and the CPS central
measuring controller via a USB cable run between the PC and the CPS central controller.
Follow the steps below to make the connection:
1. Ensure that the communication driver has been installed on the PC as indicated in the paragraph
“Installing the communication driver.”
2. Plug the connector into a free USB port on the PC.
3. Plug the connector into the CPS (see the central detection controller manual for the location of
the connector).

10
5. Remove the COM_CPS Softw are

Follow the steps below to remove the COM_CPS software:


1. Select Start > Settings > Control Panel > Add or Remove Programs.
2. Search for COM_CPS in the list of programs.
3. Right-click on COM_CPS, then click on the “Uninstall/Change” button.
4. When prompted, click "Yes to all."
5. Once the program has been uninstalled, select the folder Program Files (usually on the C: drive).
Save the contents of the OLDHAM \ COM_CPS folder if necessary. Then, delete the COM_CPS
folder.
6. The COM_CPS software has been completely removed.

IV. OVERVIEW OF THE SOFTWARE


This chapter describes the actions pertaining to software startup and shutdown, how to select the
language displayed in menus, and the various formats for additional information (tabs, information zones,
etc.).
1. Running the Software

In the Windows task bar, select Start > Programs > OLDHAM COM_CPS and click on the
COM_CPS icon.

2. Selection of the Displa y Language

Display language options are presented in the startup window as shown below. All menus thereafter
will be displayed in the language selected.

Figure 2: Language selection upon software startup.

11
M0

3. The Main Screen

After launching the software, the various zones will appear in the window, which you can use to
easily program the CPS central measuring controller or to view configuration data coming in from
the CPS central measuring controller.
A B CD E F G

Figure 3: View of the startup window

Item Function: Page


A Software menus 12

B Quick access zone, identical to clicking on a tab. (zone F). 14

C Save as button, identical to File > Save as. 12

D Print button. Creates a PDF compilation of data relative to the present configuration file. 15

E Display matrix for detectors, logic inputs, relays and analog outputs. 15

F Configuration tabs. 15

G Information zone, changes in relation to the selected tab (F). 17


Table 2: Explanation of reference markers

12
4. Menus

File
This menu is used to create, save, or open a configuration file.

Figure 4: the File menu.

M1

Item Description
New Opens a new blank configuration window.
Open Opens a previously saved configuration file.
Save Saves configuration currently displayed under the name displayed in the title bar. The title of the
saved document is formatted as "CPS_DATE_TIME.txt."
Save As Saves the configuration file currently displayed on screen under a new name. The default file name
is "CPS_DATE_TIME.txt."
Configuration check Automatically verifies the conformity of the configuration before sending it to the CPS central
controller.
Print as PDF Publish the current configuration settings as a PDF file on the PC’s printer (a PDF pilot program is
installed with the software). This file provides a fair amount of detail about the selected option (see
the paragraph titled “The Print Button” on page 15).
Exit Shuts down the software after automatically saving work in progress
Table 3: the File menu submenus.

Communication
This menu defines the configuration settings for communication between the PC an d the CPS
central detection controller.

These settings determine how the PC and the CPS central detection controller communicate
and transfer the configuration data defined with the COM_CPS software.
The settings that control the serial connection communication between the CPS central
detection controller and the supervision system are described in the paragraph titled
“Configuration of the serial connection to the supervision system” on page 21.

Figure 5: the Communication menu.

13
Item Description Voir page

Port Selection of the PC port used for communication between the PC and the COM_CPS 51
software.
Rate Selection of the transmission rate between the PC and the COM_CPS software for the 51
selected port. The rate should be set to 19200 baud.

Table 4: the Communication menu submenus.

Transfer
This menu is used to select the direction of data transfer between the PC running the COM_CPS
software and the CPS central detection controller with the connection type used (RS-232 or USB).

Figure 6: the Transfer menu.

Item Description See page


From CPS to PC Data transfer from the COM_CPS software to the PC 52
From PC to CPS Data transfer from the PC to the CPS software. 51
Table 5: the Transfer menu submenus.

?
This menu displays the software version number.

Figure 7: the ? menu. M4

Item Description See page


About Displays the software version number. -

Table 6: the menu submenus.

5. The fast access zone

With a single click on a line in this zone (Figure 8), you can:
■ Automatically select the corresponding tab (item C) and display pertinent configuration data.
■ View the display matrix (item b) for the corresponding tab (item D) (Detector, Logic Input, etc.).

14
A B C D E

Figure 8: Sample window.

Item Function:
A Fast access zone.
B Visualization matrix
C Tab selected by clicking in (A).
D Tabs to select the type of information to be displayed in the matrix (B).
E Tab to visualize all modules. Corresponds to the addition of visualizations possible with all of the other 4 tabs of (B).
Table 7: Description of the connections with the fast access zone.

6. The Print Button

Right-click
Right-clicking on this icon will display two options

Figure 9: options from the print icon.

Item Description
Detailed PDF Report All of the defined configuration settings are included; the report will be at least 20 pages in
length.
Summary PDF Report Only the main configuration settings are included in the report which will be at least 14
pages in length.

Printing
Clicking on this button will open the selected report type in a PDF-format print window (see
preceding paragraph Right-click).

15
7. Matrix displa y

General Overview
This zone may be completely blank when the software is first run, but after configuring the software,
the matrix (Figure 8: Sample window. , item B), will display either all (All, ref. E) or a selection
(Detector, Logic Input, Relay, Analog Output - ref. D) of the available modules.
■ The CPS lines (ref. A) are vertically numbered from 1 to 8.
■ The modules (ref. B) for each line are horizontally numbered from 1 to 32
■ Each module (shown with a colored square and a number) is displayed in the corresponding cell (ref.
C).
A B C D E

Figure 10: Matrix display. 004

Item Function:
A Column of CPS line numbers (1 to 8)
B Numbers (1 to 32) of the modules on each line (1 to 8) of the CPS.
C Matrix display. Each cell displays (see previous page for the codes):
- The number corresponding to the type of detector or module connected.
- A colored background corresponding to the type of module connected (color is displayed in the tabs, ref. D).
D Tabs to select the type of information to be displayed in the matrix.
E Tab to visualize all modules. Corresponds to the addition of visualizations possible with all of the other 4 tabs.
Table 8: Matrix display detail. 001

Clicking the All tab (ref. E) displays all of the connected modules.
Clicking on a different tab (Detectors, Logic Input, Relay, Analog Output) will display only the
corresponding module type.

Cell contents
Each cell (Figure 10) is automatically assigned a number according to the module type assigned
during configuration (see detail in VIII, on page 28).
The following key will help you to understand the matrix:
Item Meaning
Reference Detector type (1 to 10) defined with the tab Configuration of detector types (see page 22).
Color Grey: Detector module (see page 22 for details about sensors).
Blue: 4 or 8 relay module (see page 34 for details about relay modules).
Green: 4 analog outputs module (see page 41 for details about analog output modules).
Yellow: 16 logic inputs module (see page 46 for more information about logic inputs modules

Table 9: Detail of display matrix cell data.

16
8. Exiting the Softw are

Select File > Exit. Displayed data will be automatically saved.

V. USING THE SOFTWARE


This chapter summarizes the use of the software during configuration before sending the data to the CPS
central measuring controller or when consulting data sent from the CPS central measuring controller to the
COM_CPS software.

1. Step 1: Configuring the CPS central detection controller

To configure the CPS, follow the tabs in the order they appear on screen and to adjust the
configuration settings as follows:
See page
■ General configuration: selection and/or display of general settings for the CPS central measuring controller 18
(name for the central controller and lines, password, preset printing times for status tables, activation conditions for
the internal audible alarms, transfer speed for the serial connection and the JBUS slave number for the central
controller).
■ Configuration of detectors: define the set of characteristics for all of the detectors (gas type, measurement 22
range, associated alarms, etc.) which can be used by the CPS central detection controller.
■ Installation architecture: assignment of detectors, input modules, output modules and relay modules to 28
addresses on the 8 lines of the CPS central detection controller.
■ Relay actions: Definition of the relay(s) activated when an alarm condition is triggered (alarm 1-4, fault, out 34
of range) by one of the detectors.
■ 4-20 mA output actions: definition of the analog outputs (4-20 mA) corresponding to various detectors 41
■ LI actions: Definition of the connection matrix between the logic inputs (LI) and the associated outputs 46
(analog or relay).
■ Relay data: definition of the operation of the CPS central detection controller’s three shared relays, audible 48
alarm controller relay, and the relays relating to forced ventilation.

2. Step 2: Configuration transfer to a CPS central detection


controller

■ First, establish a connection (RS-232 or USB) between the PC and the CPS central detection controller
as described on page 10.
■ Transfer the configuration settings created on the PC to the CPS central detection controller by
selecting Transfer > From PC to CPS in the menu bar. This is described in detail in XIII on page 51.

17
3. Step 3: Review ing and/or modifying data transferred from the
CPS

■ First, establish a connection between the PC and the CPS central detection controller as described on
page 10.
■ Transfer the data recorded by the CPS central detection controller by selecting Transfer > From CPS to
PC in the menu bar.
■ The data displayed can be reviewed or modified according to the instructions in Configuring the CPS
central detection controller on page 17.

The following chapters describe the information presented in the tabs used to configure the CPS
detection controller.

VI. GENERAL CONFIGURATION


This tab is used to define and/or display the general settings for the CPS central detection controller
(name for the central controller and lines, password, preset printing times for status tables, activation
conditions for the internal audible alarms, transfer speed for the serial connection, JBUS slave number).

1. Presentation of Data

The screen shot below shows the General Configuration screen.


A B

C D E F G
Figure 11: General Configuration tab. 003A

Item Function: See page


A Area to define the central controller name, access password, and display language for central detection 19
controller menus.
B Area to define line names and to activate / deactivate lines. 20
C Area to select printing options for the CPS central controller printer. 19
D Area to define pre-set automatic printing times for status tables. 19
E Area to define alarms and faults to activate the CPS central detection controller's audible alarm. 20
F Area (hidden or displayed) to configure the communication speed and the JBUS number for the central 21
detection controller when used in conjunction with a supervision system.
G Button used to display or to hide the zone (F) described above. 21
Table 10: Detail of the data presented in the General Configuration tab.

18
2. Use

Follow the instructions below to set the parameters of the General Configuration tab.

Step 1: Left zone


The left zone is shown below:

Figure 12: The left zone of the General Configuration tab. 003B

■ Central controller name: Enter the name (27 characters max.) which will appear on the central
detection controller display screen and in the margins of printed reports.
■ COMCPS version: uneditable zone which indicates the version number for the present
application.
■ CPS Version: uneditable zone which indicates the version number for the software application
loaded on the CPS central detection controller. This information will only be displayed upon
communication between the software application and the CPS central detection controller.
■ Password: define the password which will enable access to certain menus on the CPS central
detection controller; this password will be composed of a max. of 4 characters, 0-9, and A-F
(password is not case specific). All menus are displayed with the default password "1000."
■ CPS Language: Select the CPS central detection controller display language from the drop-
down list.
■ Printing configuration:
These options are used to specify printing times (max. 4) and which statuses to print on the CPS
central controller's integrated printer. The printing configuration can be set in two steps:
- Step 1: select the statuses to be printed.
- Step 2: select printing times.

Click on the icon to select the statuses to be printed. The printing configuration window shown
below will appear:

Figure 13: The left portion of the General Configuration tab. 006

19
Select the events that should be included in the printed report. Click OK to close the window.
For example, if only “AL1” is selected, only Alarm 1 events, faults and system failures will be
included in the printed report. You may not deselect “Fault” or “System Failure.”
Step 2 consists of defining the times for printing the data selected in Step 1.

Figure 14: Zone for setting printing times.

Schedule between 1 to 4 times to print status reports (selected in Step 1); the reports will be
automatically printed on the printer connected to the CPS central detection controller at the times
specified here. If the On box is not checked, printing will not take place at the scheduled time. This
option is used to temporarily deactivate status table printing without changing the original settings.
Entering “24” as a value will also cancel printing.

Step 2: Line Name zone


The line name zone is shown below:

Figure 15: The “Line name” zone of the General Configuration tab.

■ 1 to 8: Enter the line name (32 characters max.) which will appear on the CPS central detection
controller display screen.

■ A selected checkbox ( ) activates the corresponding line on the CPS central detection controller
(power to line).
A deselected checkbox ( ) shuts down the corresponding line (no power to line).

Step 3: Internal Audible Alarm zone


The internal audible alarm zone is shown below:

Figure 16: The internal audible alarm zone of the General Configuration tab.

The CPS central detection controller’s internal audible alarm will activate when an alarm or fault
condition occurs if the corresponding checkbox is selected:

20
■ Alarm 1, Alarm 2, Alarm 3, Alarm 4: audible internal alarm activated by the alarm number triggered
on any of the measuring lines of the CPS central controller.
■ Out of Range and Fault: audible internal alarm activated by the “Out of Measuring Range” alarm or by
a fault.
■ System Failure: audible internal alarm activated by the fault alarm from the CPS central detection
controller.
■ Module Failure: audible internal alarm activated by an alarm triggered during any fault (excessive
temperature, power supply, etc.) of a module external to the CPS central detection controller (detector,
relay module, output module, etc.).

Step 4: RS-485 Communication zone


The RS-485 communication zone is shown below:

Figure 17: The serial connection configuration zone. 058

Click the button to display this zone.(Figure 11, ref. G).

■ Baud rate: set the communication speed for the RS-485 serial connection between the CPS central
detection controller and the supervision system.

This is the speed of the CPS- supervision screen connection. This should not be confused with
the speed selected in Communication > Speed corresponding to the CPS-PC connection.

■ JBUS Slave Number: set the CPS central detection controller slave number if the controller is
connected to a JBus network. The maximum value for the slave number is 255
■ Parity: parity is taken into consideration with the check box.
■ Odd: parity is odd when the box is checked and even when the box is not checked.
■ 2 stop: when the box is checked, 2 stop bits are included in the message.

3. Saving the Configuration

Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.
By default, the file name will be given in the format: CPS_Date_Time.txt.
For example: CPS_080307_1532.txt (CPS_DDMMYY_HHMM.txt).

21
VII. CONFIGURING THE DETECTORS
Once the "General Configuration" is complete, (see VI, on page 18), this tab can be used to set and/or
display all of the characteristics for each detector (gas type, measurement range, alarms, etc.) which
can be used during the configuration of the CPS central detection controller.

1. Presentation of Data

The screen shot below shows the Configuring the Detectors screen.
A

B C D E E E E F
Figure 18: The Configuring the Detectors tab. 007

Item Function: See page


A Uneditable zone. Displays the values configured in zone B for the detector selected in zone C. 22
B Zone used to configure the detectors. 23
C List of detectors which can be used after configuration. 23
D Detector Tab: definition of the general settings for the detector. 23
E Alarm 1 - Alarm 4 Tabs: definition of various alarm thresholds associated with the selected detector. 25
F Out of Range and Fault Tab: definition of the levels that exceed the thresholds, sensor fault, and 26
activation of alarm verification.
Table 11: Detail of the Configuring the Detectors tab.

Top of the Window

The top of the window is shown below:

A B C D
Figure 19: Top of the Window

None of the data presented in this zone may be changed. The data displayed here is pulled from the
configuration settings for the detector selected in the list of available detectors ( Figure 18, ref. C).

22
Item Function:
A Range: value and unit of measure (A) for the detector selected from the list of available detectors.
B Instantaneous alarms: Bargraph (B) of the values for each of the active instantaneous alarms for the detector selected
in the list of available detectors. A deactivated alarm (see paragraph Alarm 1 – Alarm 4 Tabs) on page 25) will not be
displayed in the bargraph.
The red zone corresponds to alarm condition values and the blue zone corresponds to values that do not trigger alarms.
The colors will change if alarms are set to a rising edge trigger in the Alarm tab (see page 25).
C Averaged alarms: Bargraph (C) of the values for each of the active averaged alarms for the detector selected in the list
of available detectors. A deactivated alarm (see paragraph Alarm 1 – Alarm 4 Tabs) on page 25) will not be displayed
in the bargraph.
D Out of Range and Fault: Out of Range and Fault value settings (D) (see paragraph Out of Range and Fault Tab on
page 26.
Table 12: Detail of the top part of the Configuring the Detectors window.

Bottom of the Window


The bottom portion of the window is used to configure the various gas detectors. Refer to the Use
paragraph below for detailed instructions.

Figure 20: View of the bottom portion of the Configuring the Detectors tab.

2. Use

Configure a detector from the Configuring the Detectors tab by following the instructions below.

NOTE: if the application was closed after configuration (see previous chapter), simply import the
previously saved configuration file by going to the File menu and selecting Open and navigating to
the desired file.

Modify the Settings for a Detector

Step 1: Define the type of detector (“Detector” tab)


This tab is used to define the general data for a detector (type, name, measuring range and unit of
measure). All of the data defined in this window will be shown on the CPS central detection
controller display screen.
A B C

D E
Figure 21: Selection of a detector. 010

Follow the steps below to select a detector:

23
■ In the List of Detector Types (Figure 21, ref. D), click the number (1 to 10) that will receive the
data for the detector being configured. Each number corresponds to a type of decector. This list
(Figure 21, ref. D) can contain up to 10 types of the detectors usable by the CPS central
controller.
■ Detectors: open the drop-down list (Figure 21, ref. A) and select (Figure 21, rep. E) the detector
to you wish to configure with the CPS. This detector will be included in the List of Detector Types
(Figure 21, ref. D) once the drop-down list has been closed. These detectors have pre-defined,
but editable alarm thresholds.
If a specific detector is not included in the list, select Other. (Figure 21, ref. A). Other detectors
have no predefined alarm thresholds ..

NOTE: this list can contain any number of detectors designed by Oldham . However, the central
measuring controller can only accept up to 10 types of detectors at a time, and only those listed in the
table List of Detector Types (Figure 21, ref. D).

■ Detector name: user-defined name (Figure 21, ref. B), for the detector selected in the table (C),
12 characters max. (no accents or special characters). Example: CO – INLET.
■ Range: the two fields (Figure 22: The range of a predefined detector cannot be changed. 011
for a detector belonging to the group of predefined detectors in the drop down list (Figure 22, ref. A
and C.)

A B C
Figure 22: The range of a predefined detector cannot be changed. 011

Only the options Other (Figure 23, ref. C), or Analog Input in the Detectors list allow modification of
the Range (ref. A) and unit (ref. B).
Select the value and the unit (ref A and ref. B) from the drop-down lists.

A B C D E
Figure 23: The range of an “Other” detector can be changed. 012

■ Abbreviated Name: fill out this field (Figure 23, ref. E) with any 5-character name. This name
will be displayed on the CPS central controller display.
■ Hysteresis: enter the hysteresis value (Figure 23, ref. D) in the correct unit of measure for the
given range. Hysteresis impacts the value at which the alarm is cleared. So, if a rising edge
trigger (used, for example with CO), a 1% max. hysteresis for a range of 100 ppm will constrain
the triggering of alarms 1, 2, 3 and 4 as shown below:

Enabbled alamr when


103ppm reached Disabbled alarm when threshold :
threshold 100 ppm – 3%, 97 ppm

Figure 24: Example of hysteresis D_02

24
However, these values must be inversed for falling edge triggers (used for oxygen, for example).
Reminder: Falling edge and Rising edge are defined in the Alarm 1 - Alarm 4 tabs (see paragraph
below).

Step 2: Define alarm thresholds (“Alarm 1” – “Alarm 4” tabs)

Note: pre-configured alarm thresholds to be displayed when a pre-programmed sensor is selected. You
may modify these values, however by following the instructions in this paragraph. The pre -configured
values are those recommended by the manufacturer.

These four tabs are identical: each tab is used to define the characteristics of each of the 4 gas
alarms. Alarms can be configured for delays, acknowledgement, triggering, and an instantaneous
and an averaged alarm threshold (including integration time). The instantaneous and averaged
alarm thresholds can be activated or deactivated.

A B C
Figure 25: "Alarm" tab. 013

■ Settings: (Figure 25, ref. A) define the delay, the acknowledgement type and the trigger type for
the alarm.

Setting Description
Delay Value, in seconds, of the delay between when the alarm threshold is passed and when the instantaneous
and averaged alarms are triggered.
Acknowledgement Manual: the alarm can only be dismissed after the “Acknowledge” button on the CPS central detection
controller has been pushed.
Automatic: the alarm will be automatically dismissed once the alarm condition has ended.
Triggering Rising edge: Instantaneous and averaged alarms are activated as a value increases. Use this option for
detectors measuring combustible gases, CO, H 2S, etc.
Falling edge: Instantaneous and averaged alarms are activated as a value decreases. Use this option for
oxygen sensors, for example.

Table 13: General alarm settings for a detector.

25
■ Instantaneous: (Figure 25, ref. A) definition of the alarm threshold which would activate an
instantaneous alarm.
Setting Description
Threshold Corresponds to the value that would trigger an instantaneous alarm. Set the threshold by using one of the
two methods described below:
- directly, by using the cursor;
- by entering the numerical threshold value with a keyboard.
The unit of measure displayed to the right of this field is defined in the Detector tab.
Active If the box is unchecked: the instantaneous alarm is deactivated.
If the box is checked (see Figure 26, ref. B): the instantaneous alarm is activated. In this case, the alarm
bargraph will appear in the upper part of this tab (see Figure 26, ref. A. The value displayed indicates the
percentage of the alarm in relation to the total value of the range. The blue section corresponds to the
range which will not trigger an alarm; the red zone corresponds to the range which will activate the alarm.
Table 14: Instantaneous alarm settings for a detector.
A

B
Figure 26: When the “Active” box is checked (ref. B), the bargraph (ref. A) is displayed. For comparison, see Figure 25
where the box is not checked.

■ Averaged: (Figure 27, ref. B) definition of the alarm threshold that triggers an averaged alarm.
Setting Description
Threshold Corresponds to the value that would trigger an averaged alarm. Set the threshold by using one of the two
methods described below:
- directly, by using the cursor;
- by entering the numerical threshold value with a keyboard.
The unit of measure displayed to the right of this field is defined in the Detector tab.
Integration time Selection of the value (in minutes) of integration for the averaged alarm. Select this value by using one of
the two methods described below:
- directly, by using the cursor;
- by entering the numerical threshold value with a keyboard.
Active If the box is unchecked: the averaged alarm is not active.
If the box is checked (see Figure 27, ref. C): the averaged alarm is activated. In this case, the alarm bar
graph will appear in the upper part of this tab (see Figure 27, ref.A). The value displayed indicates the
percentage of the alarm in relation to the total value of the range. The blue section corresponds to the
range which will not trigger an alarm. The red zone corresponds to the range which will activate the alarm.
Table 15: Averaged alarm settings for a detector.

26
A B

C
Figure 27: When the “Active” box is checked, (ref. B), the bar graph (ref. A) will appear. For comparison, see Figure 25
where the box is not checked. 015

NOTE: the procedures described in Step 2 should be repeated, if necessary, for each of the other alarms
(AL 2, AL3, and AL4).

Step 3: “Out of Range and Fault” tab:


This tab, shown below, is used to define the "out of range," “verification,” and “fault” values .
A B

C D E
Figure 28: “Out of Range and Fault” tab.

Setting Description
Out of Range Use the keyboard to enter the value of the concentration of gas (Figure 28, ref. E), above which the value is
considered to be out of range. The unit of measure is the same as that defined for the detector on the
Detector tab (see Figure 21, on page 23).
An Out of Range alarm can activate an alarm, a relay, or a light. See IX, 0 and 0.
Note: only for the hydrogenated gas, methane, CNG, LPG version.

Verification If this box is checked (Figure 28, ref. C), verification will be activated for explosive gases. If a verification
alarm is active, the alarm will remain active until it is manually acknowledged, even if the level of gas has
fallen below the preset threshold.
Fault Use the keyboard to enter the value of the concentration of gas (Figure 28, ref. D) below which the
measurement is considered to be sent by a faulting detector. The unit of measure is the same as that defined
for the detector on the Detector tab.
A fault alarm activates either an alarm, a relay, or a light (see IX, 0 and 0).
Table 16: Out of Range alarm settings for a detector.

IMPORTANT NOTE: the procedures described in this paragraph should be repeated for each type of
detector that may be used in conjunction with the CPS central detection controller; these detectors will be
assigned to the central detection controller via the Installation Architecture tab (see page 28).

27
Remove a Detector From the List
A pre-defined detector cannot be removed from the list (ref. A). Only Other detectors can be
removed.
To remove a detector from the List of Detector Types, go to the Detector tab (ref. B). Select Other
(ref. C) from the Detectors drop-down list and delete the names from the Detector Name fields (ref.
D) and Enter the abbreviated name (ref. E).
A B C D E

Figure 29: Removing an Other detector. 017

3. Saving the Configuration

Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.
Reminder:
By default, the file name will be given in the format: CPS_Date_Time.txt.
For example: CPS_080307_1532.txt (CPS_DDMMYY_HHMM.txt).

VIII. INSTALL ATION ARCHITECTURE


This tab is used to assign one or more pre-defined detectors (see 0, on page 22) to each of the lines of the
CPS central detection controller.
It is also used to review the current configuration for the detectors on these lines.

1. Presentation of Data

The screen shot below shows the Installation Architecture screen.

A B C
Figure 30: Sample representation of the “Installation Architecture” tab after configuration. 025

28
Item Function:
A Uneditable zone. Displays the list of available detectors and modules which can be connected in the lines of the cent ral
detection controller.
B Zone for the line number (1-8), module address (1-32) and name for the module.
C Equipment assignment table pulled from (A) to (E) for the selected line (D).
A red line represents a module with deactivated inputs. A black line represents a module with activated inputs.
Table 17: Installation Architecture data.

2. Use

NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.

Numbering the Lines


The CPS central detection controller has 8 output lines, each being able to receive 32 modules
(detector, input or output, or relay).
To number a piece of equipment on a line, join the equipment number to the line number. So, if line
number 1 has a piece of equipment in location number 3, it will be referred to as 1 -3, as seen in
Figure 30. This “code” is easily identifiable on the upper part of the application’s display matrix (s ee
Figure 10: Matrix , on page 16).
Adding a sensor to a CPS line.
Follow the steps below to add a sensor to a CPS line:
1. Select the detector or the module (input, output, relay).
In the table (A), click on the line corresponding to the detector or the module (input, output, relay)
to be used. Once selected, the line will have a blue background.
Reminder: The detectors listed here were defined on the Configuring the Detectors tab (see
chapter 0, on page 22).

2. Select the line that will receive the equipment.


Scroll through the table of lines (C) to find the line you wish to select. Click to select the line.

3. Then, drag the selected equipment (A) to the line in area (C) below.
Clickthe on the gas name
from this table … … to the line

A B C
Figure 31: Drag and drop to add equipment to a CPS line. 019

Note:In the "All" tab, you can drag the module directly from zone (A), to the Figure 31: Drag in the
display matrix (Figure 32: The ) without needing to complete steps 2 and 3 above.

29
4. In area (C), right-click on the added module and select the line Module Name Configuration.
5. Enter the name in the window that appears.
For example, Gas inlet. This name will be displayed in the table (B) on the adjacent line.
6. Click OK to close the window.
Once equipment has been added to the line, the display matrix (see page 15) must be updated;
click the Detector button on this matrix to view the new equipment.
If you click on « detector » the matrix displays the detector type and its location.

Figure 32: The display matrix is updated after equipment is added. 019

Adding a module (input, output, relay) to a CPS line


Add a 16 input, 4 output, or relay module by following the same process used to add a detector (see
above). The following notes however apply specifically to this type of module.
Once the module (logic input, analog output, relay) is dropped onto the line in the right-hand table
(Figure 31: Drag , ref. C) the module will not have been activated and will require further
configuration. Follow the steps below to activate and configure the module:
1. Right-click on the name of the module in the right hand side of the window (Figure 31: Drag , ref.
C) and select Configuring Module Inputs.
2. Check the Activated Inputs box to activate the use of the module's logic inputs.
A

Figure 33: The displayed input module has deactivated inputs.

023

If the Activated Inputs box is not checked (ref. A in the figure above), the inputs will not appear in the
action tables (see IX, 0 and 0).

Note: a relay module’s "inputs" correspond to 2 logic inputs which are designed to connect to any type
of logic signal (push button, contact, etc.). Their operation is similar to the 16 input module.

30
3. By default, the window will display input or output numbers (ref. A).
Line Number – Module Number – Input/Output/Relay Number
Customize the name in relation to the installation (Parking Level 4, for example) by clicking inside this
zone and typing the new name.
A B C

Figure 34: Example of an input module.

020

4. Click on the icon (ref. C) to display and configure the additional timer functions.
5. The following window will appear.
A B

Figure 35: Example of an input module timer. 021

Three timers are available: Timer 1, Timer 2, and Timer 3.


Each timer defines between 1 and 4 time intervals. Each interval will activate the logic inputs using the
timer.

6. Define the start and end time for up to 4 intervals for the timer(s) selected.
For example, select 09H00 09H30 as the Start-Stop times for Timer 1, line 1, and 10H00 10H30 as the
Start-Stop times for line 2, to activate the logic inputs using these timers during those times.

7. Click on the icon (Figure 35, ref. C) to close the timer window and to return to the previous screen.

31
8. In the drop-down box, select the timer or the priority input to be assigned to the module.
- None: no timer is used.
- Prog1: Timer 1 is used (the input will be activated by the logic contact and by Timer 1).
- Prog2: Timer 2 is used (the input will be activated by the logic contact and by Timer 2).
- Prog3: Timer 3 is used (the input will be activated by the logic contact and by Timer 3).
- Priority input: when a priority logic input is activated, it takes precedence over all others (logic input
module, relay output module, and instructions from the CPS central controller).
A

Figure 36: Selection of an input module timer.

022

8. Click OK to confirm your selection and to close the window.

9. The module (ref. A) is displayed in the configuration matrix.


The All tab displays all of the detectors and modules with the color code displayed above the matrix.
The Logic Inputs tab only displays modules with logic inputs.
The Relays tab only displays relay modules.
The Analog Outputs tab only displays modules with analog outputs.
A

Figure 37: View of a module in the configuration matrix. 033

32
Removing equipment from a CPS line.

Follow the steps below to remove equipment from a CPS line:


1. In the table of lines (C), select the line you wish to remove.
Use the cursor to scroll through the list.

A B C
Figure 38: Drag and drop to remove equipment from a CPS line. 024

2. Right click and select "Remove the module.”


3. Click OK in the confirmation window.
The equipment has now been removed from the line. The display matrix (Figure 32 on page 30) is updated
when equipment is removed.

3. Saving the Configuration

Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.

33
IX. RELAY ACTIONS
This window is used to define the relays for the relay modules which will be activated when events occur
(Alarms 1-4, fault, out of range).

1. Presentation of Data

The Relay Action Matrix tab is shown below.


A B

Figure 39: Data displayed in the Relay Action Matrix tab. 412

Item Function:
A List of events, for 255 detectors max., defined and activated in the Configuring the Detectors tab, which can control one
or more relay modules in (B).
B List of the outputs of 256 relays max. belonging to the modules defined and activated in the Installation Architecture tab,
which can be controlled by the events in (A).

Table 18: Relay Action Matrix settings.

2. Define rela y actions

NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.

NOTE: the relay module(s) are defined in the Installation Architecture tab (see paragraph Adding a module
(input, output, relay) to a CPS line on page 30. If the modules were not previously defined, nothing will
appear in the zone of this tab called Programming the Relays.

Follow the steps below to define relay actions:

1. Click on the Relay Action tab.


On the left (ref. A) you will see a list of the usable events signaled by event -generating equipment.
On the right (ref. B), you will see the outputs to be configured for available relays (see the Installation
Architecture tab).

34
A B

Figure 40: Example of the Relay Action window. 026

2. Select the type of event (Alarm 1, Out of Range, Fault, etc.) from the drop-down list Event Type
(ref. A), which will be associated with a relay output.

Selecting All will display all of the events that can control relays.
A

Figure 41: Selection of an event type. 026

3. Establish a connection between the event and the relay.


Select the event in the Events zone and drag the event to the relay line you wish to program in the
Programming the Relays table located at the right hand side of the window.
When the Confirmation window appears, click OK.

Figure 42: Establishing a connection between the event and the relay. 028

Multiple events can be linked to one relay. To link more than one event to the relay, select All
from the Event Type drop-down list, select multiple events from the list by holding down the
Ctrl key, and drag all of the events to the relay line in the Programming the Relays table. When
the Confirmation window appears, click OK.

35
3. Configure the relay functions.
In the right hand side of the Programming the Relays window, right-click on the line representing the
relays to be activated by the event selected in step 2 and select Configure the relay functions.

Figure 43: Configuring the relays. 029

4. Configuring relay functions.


A configuration window will appear. Enter the following data:

Figure 44: Relay configuration. 030B

- Relay name: User-definable relay name (20 characters max.) which will appear in the Name list of the
table (see Figure 43)
- Normal: this relay will activate if an alarm occurs. The relay will return to its original position when the
alarm has ended.
- Buzzer: this relay is used to control a buzzer (audible alarm). The audible alarm can be dismissed by
pressing the Acknowledge button on the CPS central detection controller.
- Low speed: This relay is designed to control ventilators running at low speed (star-triangle
configuration for a ventilation system with two speeds: high and low).
- High speed: This relay is designed to control ventilators running at high speed (star-triangle
configuration for a ventilation system with two speeds: high and low).
- High Speed List: select the relay controlling ventilators running at high speed that can work with the
present low speed relay. This list is empty if no high-speed relay has been defined.
- High Speed Index: Lists the available high speed relays.

Figure 45: Example of low speed configuration . 410

- Deactivated: the relay will remain in normal mode even if an alarm event occurs.

36
5. Click OK to close the window.
Relays are modified in accordance with the configuration as long as no logical impossibilities are
detected. If a logical impossibility is detected, an alert message will appear.

Figure 46: Last step in configuring a relay. 032

6. Configure the other relays as necessary.


Follow steps 1-4 of this paragraph to configure all of the other relay-controlling events.

NOTE: the relay module will now appear in the display matrix as a blue square (see Figure 10: Matrix
display. on page 16).
004

3. View the configuration of a rela y

Follow the steps below to view the configuration of a relay:


1. Click on the Relay Action tab.
On the right hand side of the Programming the Relays window, right-click on the line representing a
pre-configured relay and select Configuration of relay events.

Figure 47: Select Configuring of relay events. 034

2. Events currently assigned to the relay are listed in a table.

Figure 48: Relay configuration display (list of assigned events). 035

37
The following information is presented:
■ Type: detector type (name defined in the Installation Architecture tab).
■ Name: detector name (name defined in the Installation Architecture tab).
■ Line: Line and module number (defined in the Installation Architecture tab).
■ Status: Removed will appear if you select a line and click the Remove button.
■ Alarm: Type of alarm activating the relay (name defined in the Installation Architecture tab).

3. Click Exit to close the window.

4. Change the configuration of a rela y

Follow the steps below to change the configuration of a relay:


1. Click on the Relay Action tab.
On the right hand side of the Programming the Relays window, right-click on the line representing a
pre-configured relay and select Configuration of relay events.
2. View the events currently assigned to the relay.
The table displays the list of events currently assigned to the relay.

Figure 49: viewing the events currently assigned to a relay. 036

3. Add one or more events.


Click the Add button (see image above) to display the list of events that are not currently assigned to
the relay.
Select the event(s) to be added by checking the box (on the left) of the appropriate line and clicking the
Add button.

Figure 50: Add one or more events to a relay. 037

The events will be added to the Relay Configuration window (shown below); compare to Figure 49. Click Exit to close the window.

Figure 51: Add one or more events to a relay. 038

38
5. Remove the configuration of a relay

Follow the steps below to remove one or more events assigned to a relay:
1. Click on the Relay Action tab.
On the right hand side of the Programming the Relays window, right-click on the line representing a
pre-configured relay and select Configuration of relay events.

Figure 52: Select Configuring of relay events. 034

2. View the events currently assigned to the relay.


The table displays the list of events currently assigned to the relay.

Figure 53: Relay configuration display (list of assigned events). 038

3. Remove one or more events.


Click on the event you wish to remove (to remove multiple events simultaneously, hold down the Ctrl
key and select all of the events to be removed). Click the Remove button, and then click Exit to close
the window. The events linked to this relay will be removed after the window is closed.

Figure 54: Removing one or more events. 039

39
6. List of Low Speed – High Speed Assignment

This menu is used to view the outputs dedicated to controlling the ventilation relays.

1. Click on the Relay Action tab.


On the right hand side of the Programming the Relays window, right-click on the line representing
a pre-configured relay and select List of Low Speed – High Speed Assignment

Figure 55: Viewing the Low speed - High speed outputs. 040

2. The window for low speed and high speed ventilator outputs will appear.

Figure 56: Example of a list of low speed - high speed ventilator outputs 041

This window lists the outputs dedicated to controlling the low and high speeds for ventilators.
Reminder: These outputs are defined in the Relay Actions tab (see the Configuring relays window
on page 36).

7. Saving the Configuration

Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.

40
X. 4-20 M A OUTPUT ACTIONS
This window is used to define the 4-20 mA analog outputs which will be activated by the detectors.

1. Presentation of Data

The Analog Output tab is shown below. :


A B

C D E
Figure 57: The Analog output action matrix tab. 057

Item Function:
A List of events, for 255 detectors max., defined and activated in the Configuring the Detectors tab, which can control one
or more analog outputs (B).
B List of the analog outputs for the modules defined and activated in the Installation Architecture tab that can be controlled
by (A).
C User-defined name for the module’s analog output (Figure 61, page 43).
D Line-Module Analog Output indicator
E User-defined status for the module’s analog output (Figure 61, page 43).
Table 19: Settings of the Analog Output Actions Matrix.

2. Define the analog outputs actions

NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.

NOTE: the Analog outputs modules used are defined in the Installation Architecture tab. If the modules
were not previously defined, nothing will appear in the zone of this tab called Programming the Analog
Outputs. See also the note regarding logic input, analog output and relay modules on page 41.

Follow the steps below to define the analog outputs actions:

1. Click on the 4-20 mA Outputs Action tab.

2. Establish a connection between the event and the output.


Select the detector from the List of Detectors and drag it to the line corresponding to the output to be
programmed in the Programming Analog Outputs table.

41
Figure 58: Establishing a connection between the event and the output. 042

3. When the Confirmation window appears, click OK.

Figure 59: Establishing a connection between the event and the output. 043

Multiple events can be linked to one output. To link more than one event, hold down the Ctrl key, select
the events and drag them to the line corresponding to the appropriate output line in the Programming
Analog Outputs table.

Warning: the largest analog value will be recopied onto the analog output. When the Confirmation
window appears, click OK.

4. Select the output's configuration function.


In the right hand side of the Programming the Analog Outputs window, right-click on the line
representing the output to be controlled by the event selected in step 2 and select Configure the output
functions.

Figure 60: Configuring the analog outputs. 044

4. Configure the analog output.


A configuration window will appear. Enter the following data:

42
Figure 61: Output configuration. 045

- Output name: User-defined name for the output (20 characters max.) which will appear in the Name
list of the table (see Figure 60
- Activated: the 4-20 mA output signal varies, according to the input.
- Deactivated: the 4-20 mA output signal will be frozen at 0mA, regardless of the input signal.
- Max: returns the MAX value of a sensor group "normalized by / range" (see page 46).
Click OK to close the window. The output is mow modified in accordance with the configuratio n.

Figure 62: Configuring the outputs. 046

4. Configure the other relays as necessary.


Follow steps 1-3 of this paragraph to configure each of the other all of the other output -controlling
events.

NOTE: the 4-20 mA analog outputs module will now appear in the display matrix as a green square (see
Figure 10 on page 16).

3. View the configuration of an output.

Follow the steps below to view the configuration of an output:


1. Click on the 4-20 mA Outputs Action tab.
On the right hand side of the Programming the Analog Outputs window (lists the available and
configured analog outputs), right-click on the line representing a pre-configured output and select
Configuration of output events.

Figure 63: Configuration of output events. 047

43
2. Events currently assigned to the output are listed in a table.

Figure 64: Output configuration display (list of assigned events). 048

3. Click Exit to close the window.

4. Change the configuration of an output.

Follow the steps below to change the configuration of an output:


1. Click on the Output Action tab.
On the right hand side of the Programming the Analog Outputs window (lists the available and
configured analog outputs), right-click on the line representing a pre-configured output and select
Configuration of output events.
2. View the current configuration.
The current configuration for this output is displayed in the table.

Figure 65: viewing the events currently assigned to an output.

048

3. Add one or more events.


Click the Add button (shown previously) to display the list of events that are not currently assigned to
the output.
Select the event(s) to be added by checking the box (on the left) of the appropriate line and clicking the
Add button.

Figure 66: Add one or more events to an output. 516

44
Upon returning to the Analog Output Configuration window (below) the events will have been added.
Click Exit to close the window.

Figure 67: Add one or more events to an output.

5. Remove the configuration of an output.

Follow the steps below to remove one or more events assigned to an output:
1. Click on the Output Action Matrix tab.
On the right hand side of the Programming the Analog Outputs window (lists the available and
configured analog outputs), right-click on the line representing a pre-configured output and select
Configuration of output events.
2. View the events currently assigned to the output.
The List of Assigned Events for the output is displayed in a table.

Figure 68: Analog output configuration display (list of assigned events). 048

3. Remove one or more events.


Click on the event you wish to remove (to remove multiple events simultaneously, hold down the Ctrl
key and select all of the events to be removed).
Click the Remove button, and then click Exit to close the window. The events linked to this output will
be removed.

6. Saving the Configuration

Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.

45
XI. LOGIC INPUT ACTIONS (LI)
This window is used to define the connection matrix between a maximum of 64 logi c inputs (LI) and
possible 256 outputs (analog or relay).

1. Presentation of Data

The screen shot below shows the of the Logic Inputs Action Matrix screen.
■ Lines (C) and (D): logic inputs for the modules, analog relays or contact inputs.
■ Columns (A) and (B): list of available outputs (relay or analog).
■ Case (E): action to be completed.
A B C D E

Figure 69: The LI action matrix tab. 050

Item Function:
A Name for output modules (relay or analog) added in the Relay Action Matrix and Outputs Action Matrix tabs.
B Line number – Module number – Output number localization for output modules (relay or analog) defined on the
Installation Architecture tab.
C Names for relay or analog output module inputs added in the Installation Architecture tab (configuration of the Relay
Action Matrix, Output Action Matrix, or name of the input modules defined in the Installation Architecture tab.
D Line number – Module number – Output number localization for input modules or inputs for relay and analog output
modules defined on the Installation Architecture tab.
E Defined action (green: start up, red: shut-down) for the line-column intersection (a column can affect multiple lines).
Table 20: Settings of the Logic Inputs Actions Matrix.

2. Use

NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.

NOTE: the inputs module(s) used are defined in the Installation Architecture tab. If the modules were not
previously defined, nothing will appear in the zone of this tab called Programming the Logic Inputs. It is
important to note that the number of available columns and lines depends on the configuration of the
installation. If no inputs are activated, the table will be blank. See the paragraph regarding logic input,
analog output and relay modules on page 41.

Follow the steps below to define the actions to take place on an output (analog or relay) in the
presence of an event on an input (16 input module, or relay or analog module).
1. Click on the LI Actions tab.

46
2. Define the output (A) activated when an input event occurs (B) by right-clicking at the
intersection of the appropriate line and column (C).
A B C

Figure 70: definition of an action at the intersection of a line and a column. 049

Reminder: the data in header rows (B) will only appear if the inputs have been activated as indicated in
the Note on page 41.
To define an action on the corresponding output of a relay module or an analog output, right-click on
the point of intersection for that line and column.
- Start up: select ON. The background of the cell will be green.
- Shut down: deactivate an action by selection OFF. The background of the cell will be red.
- Remove an action: Select Remove. The connection between the input and the output will be
removed. The background of the cell will be white.
The two types of actions (ON and OFF) cause the following actions for each cell: :

Logic Input Green background cell Red background cell White background cell

0 Relay functions normally Relay functions normally Relay functions normally

1 Relay forced to “activated” Relay forced to “deactivated” Relay functions normally

Table 21: output actions in relation to the configuration of the logic inputs action matrix.

An input (column) can act on one or more outputs (line). In this case, start over as indicated in
step 2.

3. Saving the Configuration

Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.

47
XII. RELAY DAT A
This window is used to define of the operation of the CPS central detection controller’s three shared
relays, audible alarm controller relay, and the relays relating to forced ventilation .

1. Presentation of Data

The screen shot below shows the Relay Data screen.


A B C

D
Figure 71: "Relay data" tab. 051

Item Function: See page


A Zone used to define events that activate each of the CPS central detection controller's 3 internal relays. 48
B Zone used to define the operation of the relays used for forced ventilation. 49
C Button used to display the configuration of the operation and shut down intervals for the forced ventilation 49
relays.
D Zone used to define the operation of the CPS central dection controller's internal audible alarm. 49
Table 22: settings of the Relay Data tab.

2. Use

NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.

Configure the internal CPS central controller relays


To define the event(s) that activate the three shared internal relays for the CPS central detection
controller (R1, R2, R3) check the box(es) that should activate the relay(s) when an event occurs that
triggers an alarm.

Figure 72: zone used to define relays. 052

The following events can be configured:

48
Name Function:
AL1, AL2, AL3, AL4 Alarm levels 1, 2, 3, or 4. See Configuring the Detectors tab, page 22.
Module error Alarm fault for a system module.
System failure Alarm triggered if there is a communication fault between modules, power supply short circuit or
module inversion. Always checked for R1.
Out of range and fault Alarm triggered if a gas level is out of range (exceeds the measurement range) or if there is a
fault (negative zero offset).
Positive security Always checked for R1. R2 and R3 can be set to positive security (relay active without alarm
condition) or normal security (relay active during alarm).
Table 23: settings for the internal CPS relays.

Configure delays for the buzzer relays


Reminder: for relays with a buzzer (warning) function

Figure 73: zone used to define buzzer delays. 053

To define the activation time and acknowledgement delays for buzzer relays:
Name Function:
Min. activation times Min. operation time for a buzzer relay.
Acknowledgement delay Delay after which the buzzer relay will shut off.
ON The buzzer relay and the functions described above will be activated.
Table 24: additional settings for the buzzer relay.

Configure the times when forced ventilation is blocked


These time settings define the hours when high speed ventilation is disabled so that it will not be
accidentally turned on due to noise pollution (during the night, for example).
- Blocked high-speed hours: Specify the time after which forced high speed ventilation cannot be
turned on, even if the CPS central detection controller signals such action.
- Enabled high speed hours: Specify the time after which forced high speed ventilation can be turned
on again if signaled by the CPS central detection controller.

Figure 74: Zone used to define time intervals to block high speed ventilation. 054

49
Configure the operation intervals for forced ventilation
To display these settings, click on the button (see Figure 71, on page 48).
A B

C D

Figure 75: view of the “Relay Data” tab after clicking the button. 055

Item Function:
A Diagram displaying concentration over time, alarms triggered and the intervals and delays used in controlling high and
low speed ventilation.
B Zone relating to normal operation of high and low speed ventilation.
C Close window.
D Button used to display simulated high and low speeds.
Table 25: forced ventilation settings.

Normal high speed-low speed operation


Follow the steps below to define the delay values for ventilators in normal operation. (Figure 75, ref. C):
Name Function:
T1. Min. duration PV operation Minimum duration, in seconds, for the ventilator to operate at low speed.
T2. GV operation delay Delay, in seconds, between starting up the ventilator in high-speed and the shut down of
the low-speed ventilator.
T3. Min. duration GV operation Duration, in seconds, for the ventilator to operate at high speed.
T4. PV-GV stop delay Duration, in seconds, after low or high speed ventilator operation has been stopped,
before the ventilator can be restarted at low speed.

Click the button to return to the previous screen.

Simulated high speed-low speed operation

Click on the button (Figure 75, ref. D) to display the zone used to define the simulated (test)
ventilator operation delays.

C D
Figure 76: Simulated high speed-low speed configuration zone. 056

50
These values are not used by the central detection controller in normal operation. They are only used to
quickly test the on/off time intervals for the ventilators.
Follow the steps below to define these values:
Name Function:
1. Min. duration PV operation Minimum duration, in seconds, for the ventilator to operate at simulated low speed.
2. GV operation delay Delay, in seconds, between starting up the ventilator in high-speed and the shut down of
the simulated low-speed ventilator.
3. Min. duration GV operation Duration, in seconds, for the ventilator to operate at simulated high speed.
4. PV-GV stop delay Duration, in seconds, after low or high speed ventilator operation has been stopped,
before the ventilator can be restarted at simulated low speed.

Click the button to return to the previous screen.

3. Saving the Configuration

Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.

XIII. TRANSFER CONFIGURATION SETTINGS


This chapter describes how to transfer data from the COM_CPS application to the CPS and from the CPS
to the COM_CPS application.

1. Transfer from PC CPS

Once the configuration is complete, the central controller needs to receive the new settings. Follow
the steps below to transfer the settings to the CPS:

Step 1: establish a physical connection

1. Use either the USB or RS-232 adapter to connect the PC to the CPS central detection controller.
NOTE: The CPS central controller is equipped with a USB connection. To use the USB connection, you
must first install the FTDI drivers on the PC.
Do not connect the USB cord until the driver has been installed.
Three installation guides are included with the COM_CPS software. Chose the appropriate guide for
your PC.
The COM_CPS software creates PDF files to save configuration data. Before creating PDFs, an
application to create and print PDF files must be installed.

2. Ensure that the CPS central detection controller is connected to a power source. (see CPS
instructions).

Step 2: configure the connection


1. In the menu bar, select [Communication > Port]. Select the COM port to use on the PC.
Note: communication speed is selected automatically.

51
Step 3: data transfer
1. In the menu bar, select [Transfer > from PC to CPS].
2. A message will appear on, instructing you to position the CPS central controller switch into the MEM
position before transferring the configuration settings.
3. Click OK once verification has ended.
4. During the transfer, a progress bar will indicate transfer progress.
5. Once the transfer is complete, the message Operation complete will appear on screen. Click OK. Data
has been uploaded from the PC to the CPS central detection controller.
6. Flip the switch back to its original position.

2. Transfer from CPS PC

Follow the steps below to download data recorded by the CPS central detection controller to the PC.

Step 1: establish a connection


1. Use either the USB or RS-232 adapter to connect the PC to the CPS central detection controller.
2. Ensure that the CPS central detection controller is connected to a power source. (see CPS
instructions).

Step 2: configure the connection


1. In the menu bar, select Communication > Port. Select the COM port to use on the PC.
Note: communication speed is selected automatically.

Step 3: data transfer


1. In the menu bar, select Transfer > from CPS to PC.
2. The message, Do you want to read the CPS central controller configuration? will appear onscreen.
Click OK .
If the message Do not connect appears, verify that the CPS printer is in the OFF position and that the
switch is in the MEM position.
3. Select the folder where you want to download the file, and create a file name (a default name is
suggested).
4. During the transfer, a progress bar will indicate transfer progress.
5. Once the transfer is complete, the message Operation complete will appear on screen. Click OK. The
data has been downloaded from the CPS central controller to the PC.

52
XIV. CONFIGUR ATION P AGES
In order to simplify the process of programming the COM_CPS software, the following tables can be
photocopied and filled out for each of the modules to be programmed. This will allow you to quickly
reprogram the modules without risk of error if the need arises in the future.

1. General configuration tab

Central controller name


Password
CPS Language
Line names
- Line 1
- Line 2
- Line 3
- Line 4
- Line 5
- Line 6
- Line 7
- Line 8
Printing time 1
Printing time 2
Printing time 3
Printing time 4
Internal audible alarm  AL1  AL2  AL3  AL4
 Out of Range-Fault  Sys Failure  Err
Baud rate
JBUS Slave Number

2. Configuring the Detectors tab

Detector Tab:
Detector
Range
Detector name
Abbreviated name
Hysteresis

Alarm 1 Tab
Delay (sec)
Acknowledgement  Manual  Automatic
Triggering  Rising edge  Falling edge
Instantaneous threshold
Active  Checked  Not checked
Averaged threshold
Integration time (m)
Active  Checked  Not checked

53
Alarm 2 Tab
Delay (sec)
Acknowledgement  Manual  Automatic
Triggering  Rising edge  Falling edge
Instantaneous threshold
Active  Checked  Not checked
Averaged threshold
Integration time (m)
Active  Checked  Not checked

Alarm 3 Tab
Delay (sec)
Acknowledgement  Manual  Automatic
Triggering  Rising edge  Falling edge
Instantaneous threshold
Active  Checked  Not checked
Averaged threshold
Integration time (m)
Active  Checked  Not checked

Alarm 4 Tab
Delay (sec)
Acknowledgement  Manual  Automatic
Triggering  Rising edge  Falling edge
Instantaneous threshold
Active  Checked  Not checked
Averaged threshold
Integration time (m)
Active  Checked  Not checked

3. Out of Range and Fault tab

Out of range
Verification Active  Checked  Not checked
Fault

54
XV. INDEX

Green background, 56
?
Red background, 56
?, 11 White background, 56
About, 11 Change configuration
Analog output, 51
4 COM_CPS
Configuring the Detectors, 24
4-20 mA, 50
Exit, 14
Installation, 6
A Installation Architecture, 33
Acknowledgement Delay, 60 Installing the Software, 6
Action Logic Inputs Action Matrix, 54
Activate, 55 Main Screen, 9
Deactivate, 55 Outputs Action Matrix, 48
Remove, 55 Purpose of the Application, 3
Activate Relay Action Matrix, 39
Analog output, 50 Relay Data, 58
Activate an action, 55 Remove Software, 7
Activate inputs, 35 Run the Software, 8
Activated Inputs, 35 Setup.exe, 6
AL1-AL4, 59 System Requirements, 6
Alarm Using, 16
Relay, 43 COM_CPS
Analog (output), 48 General configuration, 18
Analog output COM_CPS Installation, 6
4-20 mA, 50 COM_CPS Software. See COM_CPS
Activated, 50 Communication, 10
Change configuration, 51 Configuration
Deactivated, 50 Analog output, 51
Max, 50 Pages, 66
Name, 50 Configuration Pages, 66
Remove configuration, 52 Configuration settings
View, 51 Transfer from CPC to PC, 65
Analog outputs Configuring the Detectors, 24
Activate an action, 55 Use, 26
Define the actions, 49 CPS, 3
Overview, 48 Buzzer Relay, 60
Analog Outputs, 48 Characteristics, 4
Audible internal alarm, 21, 28 Configure Internal Relays, 59
Autosave, 10 Download configuration, 65
Internal Relays, 59
B Lines, 13
Modules, 13
Baud rate, 21 Receive configuration settings, 64
Blue, 14 CPS Lines, 13
Buzzer Module, 13
Relay.
Relay (configure), 60 D
Buzzer relay
CPS Central Controller, 60 Deactivate
Analog output, 50
C Deactivate an action, 55
Deactivated
Cell

55
Relay, 42 L
Display Language
LI action matrix, 54
Select, 8
Logic Inputs, 54
Display Matrix
Logic Inputs Action Matrix, 54
Cell, 13
Logic outputs
Drivers
Deactivate an action, 55
Install, 6
Remove an action, 55
Low speed
E
Relay.
EL. See Logic Inputs
Even, 21 M
Exit, 10, 14
Matrix Cell, 13
Matrix Display
F
Overview, 13
Fast access zone, 11 Max
Fault, 59 Analog output, 50
File, 10 MEM, 64
Exit, 10 Menu
Save, 10 ?, 11
Forced ventilation Communication, 10
Accelerated operation, 62 File, 10
Hours for high speed disablement, 60 Transfer, 11
Hours for high speed Min. activation time, 60
re-enablement, 60 Module
Off, 60 On the line, 4
Operation interval, 61 On the Line, 13
From CPS to PC, 11 Module error, 59
FTDI, 64
FTDI Driver, 64 N
Name
G
Analog output, 50
General configuration, 18 New, 10
General Configuration Normal High speed-low speed, 61
Overview, 18 Normal
Use, 19 NT, 6
Generate PDF, 64
Green, 14, 56 O
Grey, 14
Odd, 21
Open, 10
H
Operating System, 6
High speed Operation
Relay. Principles, 3
Homepage, 9 Options
Printing, 19
I OS. See Operating System
Out of range, 59
Inputs
Outputs Action Matrix, 48
Activated, 35
Deactivated, 35
P
Installation, 6
Installation Architecture, 33 Parity, 21
Installing COM_CPS, 6 PDF, 9
Internal audible alarm, 58 Driver, 64
Generate, 64
J Port, 11
Positive security, 59
JBUS, 21
Principles of Operation, 3
Printing

56
Options, 19 S
Report, 12
Save, 10
Printing Options, 19
Save As, 10
Prog1, 36
Settings
Prog2, 36
Transfer from PC to CPS, 64
Prog3, 36
Setup.exe, 6
Purpose of the Application, 3
Simulated high speed-low speed, 62
Simulated high speed-low speed operation,
Q
62
Quick Start, 4 Slave, 21
Slave Number, 21
R Software
Install, 6
R1-R3, 59
Use, 16
Rate, 11
Stop, 21
Red, 56
System failure, 59
Relay
Add an Event, 43
T
Alarm type, 43
Associate an event, 43 Tab
Buzzer, 41 Configuring the Detectors, 24
Change the configuration, 43 General configuration, 18
Deactivated, 42 Installation Architecture, 33
Event, 43 Logic Inputs Action Matrix, 54
Event (add), 43 Outputs Action Matrix, 48
High speed, 41 Relay Action Matrix, 39, 42
Low speed, 41 Relay Data, 58
Normal, 41 Timer, 36
Relay function, 41 Transfer, 11
Remove the configuration, 44 From COM_CPS, 11
View configuration, 42 From PC, 11
Relay Action Matrix, 39 To COM_CPS, 11
Change the configuration, 43 To the PC, 11
Remove Configuration, 44 Transfer Configuration Settings, 64
View configuration, 42 Translation, 1
Relay Data, 58 Transmission Rate. See Rate
Overview, 58
RelayAction Matrix U
Define Actions, 39
USB
Relays
FTDI Driver, 64
CPS Internal, 59
Use
Internal CPS (configure), 59
Change the configuration of a relay, 43
Remove an action, 55
Configuring the Detectors, 26
Remove COM_CPS, 7
General Configuration, 19
Remove configuration
Logic Inputs, 55
Analog output, 52
Remove the configuration of a relay, 44
Report
View the configuration of a relay, 42
Detailed, 12
Print, 12
Select, 12
V
Summary, 12 View
RS-232 Analog output, 51
Direct Connection, 6 Vista, 6
RS-485
Baud rate, 21 W
Even, 21
JBUS, 21 White, 56
Odd, 21 Windows 2000
Stop, 21 Driver, 7
Running COM_CPS, 8 Operating System, 6

57
Windows 98
Driver, 7
Windows 98 ME
Driver, 7
Windows 98 SE
Operating System, 6
Windows NT
Operating System, 6
Windows Vista
Driver, 7
Windows XP
Driver, 7
Operating System, 6
Windows XP 64-bit
Driver, 7

X
XP, 6

58
The Fixed Gas Detection Experts

EUROPEAN PLANT AND OFFICES

Z.I. Est – rue Orfila CS 20417 – 62027 Arras Cedex FRANCE


Tél: +33 (0)3 21 60 80 80 – Fax: +33 (0)3 21 60 80 00
Website: http://www.oldhamgas.com

AMERICAS ASIA PACIFIC EUROPE


Tel: +1 713-559-9280 Tel: +86-21-3127-6373 Tel: +33-321-608-080
Fax: +1 281-292-2860 Fax: +86-21-3127-6365 Fax: +33-321-608-000
americas@oldhamgas.com sales@oldhamgas.com info@oldhamgas.com

60

You might also like