Professional Documents
Culture Documents
NP Comcps GB 2.0
NP Comcps GB 2.0
We have taken all the necessary measures to ensure that your instrument provides total satisfaction.
EXTENT OF RESPONSIBILITY
* OLDHAM declines its responsibility towards any person for material damage, physical injury or death resulting
wholly or partly from inappropriate use, installation or storage of its equipment resulting from failure to observe
instructions and warnings and/or standards and regulations in force.
* OLDHAM neither supports nor authorises any company, physical or moral person to assume responsibility on
behalf of OLDHAM , even if it is involved in the sale of OLDHAM products.
* OLDHAM cannot be held responsible for direct or indirect damage or be required to pay direct or indirect
compensation resulting from the sale or use of any of its products IF THESE PRODUCTS HAVE NOT BEEN
DEFINED AND CHOSEN BY OLDHAM FOR THEIR SPECIFIC USE.
* None of this information may be reproduced, copied, divulged or translated, by physical, electronic or an y other
means, nor used as the basis for the manufacture or sale of OLDHAM equipment or for any other reasons
without prior consent from OLDHAM
WARNINGS
* This document is not contractually binding. In the interests of its customers, OLDHAM reserves to modify the
technical specifications of its equipment without notice, in order to improve its performance.
* READ THIS MANUAL CAREFULLY BEFORE FIRST USE OF THE EQUIPMENT: this manual must be read by
any person who is or will be responsible for using, maintaining or repairing this equipment.
* This equipment will only provide the announced performance levels if it is used, maintained and repaired
according to OLDHAM directives, by OLDHAM personnel or by personnel approved by OLDHAM
GUARANTEE
2 years guarantee in normal conditions of use on parts and technical labour, return in our workshops, excluding
consumables (sensors, filters, etc.)
3
Table of Contents
4
Chapter 6 General Configuration ............................................................................. 18
Presentation of Data ......................................................................................................................... 18
Use ................................................................................................................................................... 19
Step 1: Left zone .............................................................................................................................. 19
Step 2: Line Name zone ................................................................................................................... 20
Step 3: Internal Audible Alarm zone ................................................................................................. 20
Step 3: RS-485 Communication zone ............................................................................................... 21
Saving the Configuration .................................................................................................................. 21
5
Saving the Configuration .................................................................................................................. 47
6
I. GENERAL INFORM ATION
Read this entire Instruction Manual carefully before using the software application.
The Instruction Manual is designed to serve as a guide and reference tool for any individual working
with the COM_CPS software.
Oldham publishes this manual for the sole purpose of providing its customers with a simple and
precise source of information. Oldham shall is not responsible or liable for any misinterpretation that
may result from the reading of this manual. Although every effort is made to ensure accuracy, this
manual may contain unintentional technical inaccuracies. Should questions arise, please contact
Oldham for additional information.
Every effort has been made to ensure the accuracy of information presented in this manual. Product
updates and/or modifications may occur without prior notification which would not be incorporated
into the present document.
This Instruction Manual and its contents are the inalienable property of Oldham .
Neither Oldham nor any other affiliated organization shall be held responsible under any
circumstances for any damage whatsoever including damages for loss of production, interruption of
production, loss of information, COM_CPS software failure, personal injury, loss of time, money, or
materials, or for any indirect or consecutive consequence of loss occurring during the use of the
product or the inability to use the product, even if Oldham had been informed of such damages.
3. Translation
7
II. INTRODUCTION
The COM_CPS software runs on a PC platform. It is designed to be used exclusively with a CPS (C ar
Park System) central detection controller from Oldham . CPS central controller operations are addressed
in a separate manual.
2. Principles of Operation
Once installed on a PC, the COM_CPS software can be used for the procedures described below:
■ Step 1: general configuration settings for the CPS central detection controller (display language,
central controller name, password, line names, etc.). These functions are described in detail in
the “General Configuration” chapter on page 18.
■ Step 2: configurations for various types of detectors (type and range of measurement, alarm
thresholds, etc.) which can be connected to the CPS central measuring station to be configured.
These functions are described in detail in the “Configuration of Various Detectors” chapter on
page 22.
■ Step 3: creation of installation architecture, or module attribution (detector, relay module, logic
input module, logic output module) at various locations along the installation. These functions are
described in detail in the “Installation Architecture” chapter on page 28.
■ Step 4: definition of the "events – relay activation” relationship. This function is described in
detail in the “Relay Action Matrix” chapter on page 34.
■ Step 5: definition of the "events – analog outputs” relationship. This function is described in detail
in the “Outputs Action Matrix” chapter on page 41.
■ Step 6: definition of the "logic inputs (LI) – logic output activation” relationship. This function is
described in detail in the “Logic Inputs Action Matrix” chapter on page 46.
■ Step 7: identification of events acting on the CPS central measuring controller’s shared relays,
internal activated audible alarm delays, forced ventilation shut-down schedules and forced
ventilation settings. These functions are described in detail in the “Relay Information” chapter on
page 48.
■ Step 8: transfer of configuration data from the PC to the CPS central measuring controller or
transfer of central controller settings to the PC for verification and/or modification. These
functions are described in detail in the “Transfer of Configuration Settings” chapter on page 51.
Clear, detailed instructions for all of the functions described above are categorized according to
order of use and can be accessed through the tabs in the software interface.
8
3. Quick Start
Each of the steps described in the "Principles of Operation" passage on page 8 must be completed
systematically in order to properly configure the application. There is no quick start option.
The CPS central measuring controller is designed to monitor environmental conditions (carbon
monoxide, etc.) in parking facilities and tunnels. Its primary technical characteristics include:
■ Wall-mounted or rack-mounted central controller
■ 8 lines
■ Max. of 32 modules per line (256 total modules max.)
■ Many modules available, each with a specific function such as:
- detector module (CO, NO, NO 2, O2, explosive gasses, etc.);
- 16 logic inputs module;
- 4 analog outputs module;
- 8 relay module;
- 4 relay module.
■ Communication via RS-485 JBUS to a supervision system and via RS-232 or USB to a PC for
configuration.
■ Optional printer.
COM_CPS must be installed on a PC running Windows 2000 or Windows XP. The minimum
requirements to install COM_CPS are:
■ Windows 98 SE, Windows NT, Windows 2000, Windows XP or Windows Vista with 256 MB RAM.
■ A CD-ROM drive
■ At least 10 MB of free hard drive space
■ An optional USB connection or free RS 232 port (optional) to link the CPS central detection
controller to the PC.
The installation procedures for this software are standard. After inserting the disc into the CD ROM
drive, instructions will appear on screen to guide you through the installation.
If the auto-installer does not execute properly, run the program by double clicking on the
Setup.exe icon in the CD ROM drive.
A folder named OLDHAM > COM_CPS will be created in the Start > Programs menu.
9
3. Connect a serial output from the PC to the CPS.
This establishes a connection between the PC running the COM_CPS software and the CPS central
detection controller via an (RS-232) serial cable run between the PC and the CPS central controller.
Follow the steps below to make the connection:
1. Plug the connector into a free serial (COM) port on the PC.
2. Plug the connector into the CPS RS-232 serial port (see the central detection controller manual
for the location of the connector).
The corresponding USB driver must be installed before the PC is connected to the central
measuring station.
Step 1: Installing the USB communication driver
Follow the instructions in the paragraph below if you are connecting your PC to the CPS
central measuring controller with a USB connection.
A communication driver must be installed on the PC running the COM_CPS software in order to
enable communication between the PC’s USB port and the central measuring controller.
The CD ROM contains various drivers corresponding to different versions of Windows. Select the
driver appropriate for the version of Windows on your PC, decompress the file and double-click on
the executable file to install the driver. A PDF help file is included for each driver.
Step 1: Establish a connection between the PC and the CPS central controller.
This establishes a connection between the PC running the COM_CPS software and the CPS central
measuring controller via a USB cable run between the PC and the CPS central controller.
Follow the steps below to make the connection:
1. Ensure that the communication driver has been installed on the PC as indicated in the paragraph
“Installing the communication driver.”
2. Plug the connector into a free USB port on the PC.
3. Plug the connector into the CPS (see the central detection controller manual for the location of
the connector).
10
5. Remove the COM_CPS Softw are
In the Windows task bar, select Start > Programs > OLDHAM COM_CPS and click on the
COM_CPS icon.
Display language options are presented in the startup window as shown below. All menus thereafter
will be displayed in the language selected.
11
M0
After launching the software, the various zones will appear in the window, which you can use to
easily program the CPS central measuring controller or to view configuration data coming in from
the CPS central measuring controller.
A B CD E F G
D Print button. Creates a PDF compilation of data relative to the present configuration file. 15
E Display matrix for detectors, logic inputs, relays and analog outputs. 15
F Configuration tabs. 15
12
4. Menus
File
This menu is used to create, save, or open a configuration file.
M1
Item Description
New Opens a new blank configuration window.
Open Opens a previously saved configuration file.
Save Saves configuration currently displayed under the name displayed in the title bar. The title of the
saved document is formatted as "CPS_DATE_TIME.txt."
Save As Saves the configuration file currently displayed on screen under a new name. The default file name
is "CPS_DATE_TIME.txt."
Configuration check Automatically verifies the conformity of the configuration before sending it to the CPS central
controller.
Print as PDF Publish the current configuration settings as a PDF file on the PC’s printer (a PDF pilot program is
installed with the software). This file provides a fair amount of detail about the selected option (see
the paragraph titled “The Print Button” on page 15).
Exit Shuts down the software after automatically saving work in progress
Table 3: the File menu submenus.
Communication
This menu defines the configuration settings for communication between the PC an d the CPS
central detection controller.
These settings determine how the PC and the CPS central detection controller communicate
and transfer the configuration data defined with the COM_CPS software.
The settings that control the serial connection communication between the CPS central
detection controller and the supervision system are described in the paragraph titled
“Configuration of the serial connection to the supervision system” on page 21.
13
Item Description Voir page
Port Selection of the PC port used for communication between the PC and the COM_CPS 51
software.
Rate Selection of the transmission rate between the PC and the COM_CPS software for the 51
selected port. The rate should be set to 19200 baud.
Transfer
This menu is used to select the direction of data transfer between the PC running the COM_CPS
software and the CPS central detection controller with the connection type used (RS-232 or USB).
?
This menu displays the software version number.
With a single click on a line in this zone (Figure 8), you can:
■ Automatically select the corresponding tab (item C) and display pertinent configuration data.
■ View the display matrix (item b) for the corresponding tab (item D) (Detector, Logic Input, etc.).
14
A B C D E
Item Function:
A Fast access zone.
B Visualization matrix
C Tab selected by clicking in (A).
D Tabs to select the type of information to be displayed in the matrix (B).
E Tab to visualize all modules. Corresponds to the addition of visualizations possible with all of the other 4 tabs of (B).
Table 7: Description of the connections with the fast access zone.
Right-click
Right-clicking on this icon will display two options
Item Description
Detailed PDF Report All of the defined configuration settings are included; the report will be at least 20 pages in
length.
Summary PDF Report Only the main configuration settings are included in the report which will be at least 14
pages in length.
Printing
Clicking on this button will open the selected report type in a PDF-format print window (see
preceding paragraph Right-click).
15
7. Matrix displa y
General Overview
This zone may be completely blank when the software is first run, but after configuring the software,
the matrix (Figure 8: Sample window. , item B), will display either all (All, ref. E) or a selection
(Detector, Logic Input, Relay, Analog Output - ref. D) of the available modules.
■ The CPS lines (ref. A) are vertically numbered from 1 to 8.
■ The modules (ref. B) for each line are horizontally numbered from 1 to 32
■ Each module (shown with a colored square and a number) is displayed in the corresponding cell (ref.
C).
A B C D E
Item Function:
A Column of CPS line numbers (1 to 8)
B Numbers (1 to 32) of the modules on each line (1 to 8) of the CPS.
C Matrix display. Each cell displays (see previous page for the codes):
- The number corresponding to the type of detector or module connected.
- A colored background corresponding to the type of module connected (color is displayed in the tabs, ref. D).
D Tabs to select the type of information to be displayed in the matrix.
E Tab to visualize all modules. Corresponds to the addition of visualizations possible with all of the other 4 tabs.
Table 8: Matrix display detail. 001
Clicking the All tab (ref. E) displays all of the connected modules.
Clicking on a different tab (Detectors, Logic Input, Relay, Analog Output) will display only the
corresponding module type.
Cell contents
Each cell (Figure 10) is automatically assigned a number according to the module type assigned
during configuration (see detail in VIII, on page 28).
The following key will help you to understand the matrix:
Item Meaning
Reference Detector type (1 to 10) defined with the tab Configuration of detector types (see page 22).
Color Grey: Detector module (see page 22 for details about sensors).
Blue: 4 or 8 relay module (see page 34 for details about relay modules).
Green: 4 analog outputs module (see page 41 for details about analog output modules).
Yellow: 16 logic inputs module (see page 46 for more information about logic inputs modules
16
8. Exiting the Softw are
To configure the CPS, follow the tabs in the order they appear on screen and to adjust the
configuration settings as follows:
See page
■ General configuration: selection and/or display of general settings for the CPS central measuring controller 18
(name for the central controller and lines, password, preset printing times for status tables, activation conditions for
the internal audible alarms, transfer speed for the serial connection and the JBUS slave number for the central
controller).
■ Configuration of detectors: define the set of characteristics for all of the detectors (gas type, measurement 22
range, associated alarms, etc.) which can be used by the CPS central detection controller.
■ Installation architecture: assignment of detectors, input modules, output modules and relay modules to 28
addresses on the 8 lines of the CPS central detection controller.
■ Relay actions: Definition of the relay(s) activated when an alarm condition is triggered (alarm 1-4, fault, out 34
of range) by one of the detectors.
■ 4-20 mA output actions: definition of the analog outputs (4-20 mA) corresponding to various detectors 41
■ LI actions: Definition of the connection matrix between the logic inputs (LI) and the associated outputs 46
(analog or relay).
■ Relay data: definition of the operation of the CPS central detection controller’s three shared relays, audible 48
alarm controller relay, and the relays relating to forced ventilation.
■ First, establish a connection (RS-232 or USB) between the PC and the CPS central detection controller
as described on page 10.
■ Transfer the configuration settings created on the PC to the CPS central detection controller by
selecting Transfer > From PC to CPS in the menu bar. This is described in detail in XIII on page 51.
17
3. Step 3: Review ing and/or modifying data transferred from the
CPS
■ First, establish a connection between the PC and the CPS central detection controller as described on
page 10.
■ Transfer the data recorded by the CPS central detection controller by selecting Transfer > From CPS to
PC in the menu bar.
■ The data displayed can be reviewed or modified according to the instructions in Configuring the CPS
central detection controller on page 17.
The following chapters describe the information presented in the tabs used to configure the CPS
detection controller.
1. Presentation of Data
C D E F G
Figure 11: General Configuration tab. 003A
18
2. Use
Follow the instructions below to set the parameters of the General Configuration tab.
Figure 12: The left zone of the General Configuration tab. 003B
■ Central controller name: Enter the name (27 characters max.) which will appear on the central
detection controller display screen and in the margins of printed reports.
■ COMCPS version: uneditable zone which indicates the version number for the present
application.
■ CPS Version: uneditable zone which indicates the version number for the software application
loaded on the CPS central detection controller. This information will only be displayed upon
communication between the software application and the CPS central detection controller.
■ Password: define the password which will enable access to certain menus on the CPS central
detection controller; this password will be composed of a max. of 4 characters, 0-9, and A-F
(password is not case specific). All menus are displayed with the default password "1000."
■ CPS Language: Select the CPS central detection controller display language from the drop-
down list.
■ Printing configuration:
These options are used to specify printing times (max. 4) and which statuses to print on the CPS
central controller's integrated printer. The printing configuration can be set in two steps:
- Step 1: select the statuses to be printed.
- Step 2: select printing times.
Click on the icon to select the statuses to be printed. The printing configuration window shown
below will appear:
Figure 13: The left portion of the General Configuration tab. 006
19
Select the events that should be included in the printed report. Click OK to close the window.
For example, if only “AL1” is selected, only Alarm 1 events, faults and system failures will be
included in the printed report. You may not deselect “Fault” or “System Failure.”
Step 2 consists of defining the times for printing the data selected in Step 1.
Schedule between 1 to 4 times to print status reports (selected in Step 1); the reports will be
automatically printed on the printer connected to the CPS central detection controller at the times
specified here. If the On box is not checked, printing will not take place at the scheduled time. This
option is used to temporarily deactivate status table printing without changing the original settings.
Entering “24” as a value will also cancel printing.
Figure 15: The “Line name” zone of the General Configuration tab.
■ 1 to 8: Enter the line name (32 characters max.) which will appear on the CPS central detection
controller display screen.
■ A selected checkbox ( ) activates the corresponding line on the CPS central detection controller
(power to line).
A deselected checkbox ( ) shuts down the corresponding line (no power to line).
Figure 16: The internal audible alarm zone of the General Configuration tab.
The CPS central detection controller’s internal audible alarm will activate when an alarm or fault
condition occurs if the corresponding checkbox is selected:
20
■ Alarm 1, Alarm 2, Alarm 3, Alarm 4: audible internal alarm activated by the alarm number triggered
on any of the measuring lines of the CPS central controller.
■ Out of Range and Fault: audible internal alarm activated by the “Out of Measuring Range” alarm or by
a fault.
■ System Failure: audible internal alarm activated by the fault alarm from the CPS central detection
controller.
■ Module Failure: audible internal alarm activated by an alarm triggered during any fault (excessive
temperature, power supply, etc.) of a module external to the CPS central detection controller (detector,
relay module, output module, etc.).
■ Baud rate: set the communication speed for the RS-485 serial connection between the CPS central
detection controller and the supervision system.
This is the speed of the CPS- supervision screen connection. This should not be confused with
the speed selected in Communication > Speed corresponding to the CPS-PC connection.
■ JBUS Slave Number: set the CPS central detection controller slave number if the controller is
connected to a JBus network. The maximum value for the slave number is 255
■ Parity: parity is taken into consideration with the check box.
■ Odd: parity is odd when the box is checked and even when the box is not checked.
■ 2 stop: when the box is checked, 2 stop bits are included in the message.
Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.
By default, the file name will be given in the format: CPS_Date_Time.txt.
For example: CPS_080307_1532.txt (CPS_DDMMYY_HHMM.txt).
21
VII. CONFIGURING THE DETECTORS
Once the "General Configuration" is complete, (see VI, on page 18), this tab can be used to set and/or
display all of the characteristics for each detector (gas type, measurement range, alarms, etc.) which
can be used during the configuration of the CPS central detection controller.
1. Presentation of Data
The screen shot below shows the Configuring the Detectors screen.
A
B C D E E E E F
Figure 18: The Configuring the Detectors tab. 007
A B C D
Figure 19: Top of the Window
None of the data presented in this zone may be changed. The data displayed here is pulled from the
configuration settings for the detector selected in the list of available detectors ( Figure 18, ref. C).
22
Item Function:
A Range: value and unit of measure (A) for the detector selected from the list of available detectors.
B Instantaneous alarms: Bargraph (B) of the values for each of the active instantaneous alarms for the detector selected
in the list of available detectors. A deactivated alarm (see paragraph Alarm 1 – Alarm 4 Tabs) on page 25) will not be
displayed in the bargraph.
The red zone corresponds to alarm condition values and the blue zone corresponds to values that do not trigger alarms.
The colors will change if alarms are set to a rising edge trigger in the Alarm tab (see page 25).
C Averaged alarms: Bargraph (C) of the values for each of the active averaged alarms for the detector selected in the list
of available detectors. A deactivated alarm (see paragraph Alarm 1 – Alarm 4 Tabs) on page 25) will not be displayed
in the bargraph.
D Out of Range and Fault: Out of Range and Fault value settings (D) (see paragraph Out of Range and Fault Tab on
page 26.
Table 12: Detail of the top part of the Configuring the Detectors window.
Figure 20: View of the bottom portion of the Configuring the Detectors tab.
2. Use
Configure a detector from the Configuring the Detectors tab by following the instructions below.
NOTE: if the application was closed after configuration (see previous chapter), simply import the
previously saved configuration file by going to the File menu and selecting Open and navigating to
the desired file.
D E
Figure 21: Selection of a detector. 010
23
■ In the List of Detector Types (Figure 21, ref. D), click the number (1 to 10) that will receive the
data for the detector being configured. Each number corresponds to a type of decector. This list
(Figure 21, ref. D) can contain up to 10 types of the detectors usable by the CPS central
controller.
■ Detectors: open the drop-down list (Figure 21, ref. A) and select (Figure 21, rep. E) the detector
to you wish to configure with the CPS. This detector will be included in the List of Detector Types
(Figure 21, ref. D) once the drop-down list has been closed. These detectors have pre-defined,
but editable alarm thresholds.
If a specific detector is not included in the list, select Other. (Figure 21, ref. A). Other detectors
have no predefined alarm thresholds ..
NOTE: this list can contain any number of detectors designed by Oldham . However, the central
measuring controller can only accept up to 10 types of detectors at a time, and only those listed in the
table List of Detector Types (Figure 21, ref. D).
■ Detector name: user-defined name (Figure 21, ref. B), for the detector selected in the table (C),
12 characters max. (no accents or special characters). Example: CO – INLET.
■ Range: the two fields (Figure 22: The range of a predefined detector cannot be changed. 011
for a detector belonging to the group of predefined detectors in the drop down list (Figure 22, ref. A
and C.)
A B C
Figure 22: The range of a predefined detector cannot be changed. 011
Only the options Other (Figure 23, ref. C), or Analog Input in the Detectors list allow modification of
the Range (ref. A) and unit (ref. B).
Select the value and the unit (ref A and ref. B) from the drop-down lists.
A B C D E
Figure 23: The range of an “Other” detector can be changed. 012
■ Abbreviated Name: fill out this field (Figure 23, ref. E) with any 5-character name. This name
will be displayed on the CPS central controller display.
■ Hysteresis: enter the hysteresis value (Figure 23, ref. D) in the correct unit of measure for the
given range. Hysteresis impacts the value at which the alarm is cleared. So, if a rising edge
trigger (used, for example with CO), a 1% max. hysteresis for a range of 100 ppm will constrain
the triggering of alarms 1, 2, 3 and 4 as shown below:
24
However, these values must be inversed for falling edge triggers (used for oxygen, for example).
Reminder: Falling edge and Rising edge are defined in the Alarm 1 - Alarm 4 tabs (see paragraph
below).
Note: pre-configured alarm thresholds to be displayed when a pre-programmed sensor is selected. You
may modify these values, however by following the instructions in this paragraph. The pre -configured
values are those recommended by the manufacturer.
These four tabs are identical: each tab is used to define the characteristics of each of the 4 gas
alarms. Alarms can be configured for delays, acknowledgement, triggering, and an instantaneous
and an averaged alarm threshold (including integration time). The instantaneous and averaged
alarm thresholds can be activated or deactivated.
A B C
Figure 25: "Alarm" tab. 013
■ Settings: (Figure 25, ref. A) define the delay, the acknowledgement type and the trigger type for
the alarm.
Setting Description
Delay Value, in seconds, of the delay between when the alarm threshold is passed and when the instantaneous
and averaged alarms are triggered.
Acknowledgement Manual: the alarm can only be dismissed after the “Acknowledge” button on the CPS central detection
controller has been pushed.
Automatic: the alarm will be automatically dismissed once the alarm condition has ended.
Triggering Rising edge: Instantaneous and averaged alarms are activated as a value increases. Use this option for
detectors measuring combustible gases, CO, H 2S, etc.
Falling edge: Instantaneous and averaged alarms are activated as a value decreases. Use this option for
oxygen sensors, for example.
25
■ Instantaneous: (Figure 25, ref. A) definition of the alarm threshold which would activate an
instantaneous alarm.
Setting Description
Threshold Corresponds to the value that would trigger an instantaneous alarm. Set the threshold by using one of the
two methods described below:
- directly, by using the cursor;
- by entering the numerical threshold value with a keyboard.
The unit of measure displayed to the right of this field is defined in the Detector tab.
Active If the box is unchecked: the instantaneous alarm is deactivated.
If the box is checked (see Figure 26, ref. B): the instantaneous alarm is activated. In this case, the alarm
bargraph will appear in the upper part of this tab (see Figure 26, ref. A. The value displayed indicates the
percentage of the alarm in relation to the total value of the range. The blue section corresponds to the
range which will not trigger an alarm; the red zone corresponds to the range which will activate the alarm.
Table 14: Instantaneous alarm settings for a detector.
A
B
Figure 26: When the “Active” box is checked (ref. B), the bargraph (ref. A) is displayed. For comparison, see Figure 25
where the box is not checked.
■ Averaged: (Figure 27, ref. B) definition of the alarm threshold that triggers an averaged alarm.
Setting Description
Threshold Corresponds to the value that would trigger an averaged alarm. Set the threshold by using one of the two
methods described below:
- directly, by using the cursor;
- by entering the numerical threshold value with a keyboard.
The unit of measure displayed to the right of this field is defined in the Detector tab.
Integration time Selection of the value (in minutes) of integration for the averaged alarm. Select this value by using one of
the two methods described below:
- directly, by using the cursor;
- by entering the numerical threshold value with a keyboard.
Active If the box is unchecked: the averaged alarm is not active.
If the box is checked (see Figure 27, ref. C): the averaged alarm is activated. In this case, the alarm bar
graph will appear in the upper part of this tab (see Figure 27, ref.A). The value displayed indicates the
percentage of the alarm in relation to the total value of the range. The blue section corresponds to the
range which will not trigger an alarm. The red zone corresponds to the range which will activate the alarm.
Table 15: Averaged alarm settings for a detector.
26
A B
C
Figure 27: When the “Active” box is checked, (ref. B), the bar graph (ref. A) will appear. For comparison, see Figure 25
where the box is not checked. 015
NOTE: the procedures described in Step 2 should be repeated, if necessary, for each of the other alarms
(AL 2, AL3, and AL4).
C D E
Figure 28: “Out of Range and Fault” tab.
Setting Description
Out of Range Use the keyboard to enter the value of the concentration of gas (Figure 28, ref. E), above which the value is
considered to be out of range. The unit of measure is the same as that defined for the detector on the
Detector tab (see Figure 21, on page 23).
An Out of Range alarm can activate an alarm, a relay, or a light. See IX, 0 and 0.
Note: only for the hydrogenated gas, methane, CNG, LPG version.
Verification If this box is checked (Figure 28, ref. C), verification will be activated for explosive gases. If a verification
alarm is active, the alarm will remain active until it is manually acknowledged, even if the level of gas has
fallen below the preset threshold.
Fault Use the keyboard to enter the value of the concentration of gas (Figure 28, ref. D) below which the
measurement is considered to be sent by a faulting detector. The unit of measure is the same as that defined
for the detector on the Detector tab.
A fault alarm activates either an alarm, a relay, or a light (see IX, 0 and 0).
Table 16: Out of Range alarm settings for a detector.
IMPORTANT NOTE: the procedures described in this paragraph should be repeated for each type of
detector that may be used in conjunction with the CPS central detection controller; these detectors will be
assigned to the central detection controller via the Installation Architecture tab (see page 28).
27
Remove a Detector From the List
A pre-defined detector cannot be removed from the list (ref. A). Only Other detectors can be
removed.
To remove a detector from the List of Detector Types, go to the Detector tab (ref. B). Select Other
(ref. C) from the Detectors drop-down list and delete the names from the Detector Name fields (ref.
D) and Enter the abbreviated name (ref. E).
A B C D E
Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.
Reminder:
By default, the file name will be given in the format: CPS_Date_Time.txt.
For example: CPS_080307_1532.txt (CPS_DDMMYY_HHMM.txt).
1. Presentation of Data
A B C
Figure 30: Sample representation of the “Installation Architecture” tab after configuration. 025
28
Item Function:
A Uneditable zone. Displays the list of available detectors and modules which can be connected in the lines of the cent ral
detection controller.
B Zone for the line number (1-8), module address (1-32) and name for the module.
C Equipment assignment table pulled from (A) to (E) for the selected line (D).
A red line represents a module with deactivated inputs. A black line represents a module with activated inputs.
Table 17: Installation Architecture data.
2. Use
NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.
3. Then, drag the selected equipment (A) to the line in area (C) below.
Clickthe on the gas name
from this table … … to the line
A B C
Figure 31: Drag and drop to add equipment to a CPS line. 019
Note:In the "All" tab, you can drag the module directly from zone (A), to the Figure 31: Drag in the
display matrix (Figure 32: The ) without needing to complete steps 2 and 3 above.
29
4. In area (C), right-click on the added module and select the line Module Name Configuration.
5. Enter the name in the window that appears.
For example, Gas inlet. This name will be displayed in the table (B) on the adjacent line.
6. Click OK to close the window.
Once equipment has been added to the line, the display matrix (see page 15) must be updated;
click the Detector button on this matrix to view the new equipment.
If you click on « detector » the matrix displays the detector type and its location.
Figure 32: The display matrix is updated after equipment is added. 019
023
If the Activated Inputs box is not checked (ref. A in the figure above), the inputs will not appear in the
action tables (see IX, 0 and 0).
Note: a relay module’s "inputs" correspond to 2 logic inputs which are designed to connect to any type
of logic signal (push button, contact, etc.). Their operation is similar to the 16 input module.
30
3. By default, the window will display input or output numbers (ref. A).
Line Number – Module Number – Input/Output/Relay Number
Customize the name in relation to the installation (Parking Level 4, for example) by clicking inside this
zone and typing the new name.
A B C
020
4. Click on the icon (ref. C) to display and configure the additional timer functions.
5. The following window will appear.
A B
6. Define the start and end time for up to 4 intervals for the timer(s) selected.
For example, select 09H00 09H30 as the Start-Stop times for Timer 1, line 1, and 10H00 10H30 as the
Start-Stop times for line 2, to activate the logic inputs using these timers during those times.
7. Click on the icon (Figure 35, ref. C) to close the timer window and to return to the previous screen.
31
8. In the drop-down box, select the timer or the priority input to be assigned to the module.
- None: no timer is used.
- Prog1: Timer 1 is used (the input will be activated by the logic contact and by Timer 1).
- Prog2: Timer 2 is used (the input will be activated by the logic contact and by Timer 2).
- Prog3: Timer 3 is used (the input will be activated by the logic contact and by Timer 3).
- Priority input: when a priority logic input is activated, it takes precedence over all others (logic input
module, relay output module, and instructions from the CPS central controller).
A
022
32
Removing equipment from a CPS line.
A B C
Figure 38: Drag and drop to remove equipment from a CPS line. 024
Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.
33
IX. RELAY ACTIONS
This window is used to define the relays for the relay modules which will be activated when events occur
(Alarms 1-4, fault, out of range).
1. Presentation of Data
Figure 39: Data displayed in the Relay Action Matrix tab. 412
Item Function:
A List of events, for 255 detectors max., defined and activated in the Configuring the Detectors tab, which can control one
or more relay modules in (B).
B List of the outputs of 256 relays max. belonging to the modules defined and activated in the Installation Architecture tab,
which can be controlled by the events in (A).
NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.
NOTE: the relay module(s) are defined in the Installation Architecture tab (see paragraph Adding a module
(input, output, relay) to a CPS line on page 30. If the modules were not previously defined, nothing will
appear in the zone of this tab called Programming the Relays.
34
A B
2. Select the type of event (Alarm 1, Out of Range, Fault, etc.) from the drop-down list Event Type
(ref. A), which will be associated with a relay output.
Selecting All will display all of the events that can control relays.
A
Figure 42: Establishing a connection between the event and the relay. 028
Multiple events can be linked to one relay. To link more than one event to the relay, select All
from the Event Type drop-down list, select multiple events from the list by holding down the
Ctrl key, and drag all of the events to the relay line in the Programming the Relays table. When
the Confirmation window appears, click OK.
35
3. Configure the relay functions.
In the right hand side of the Programming the Relays window, right-click on the line representing the
relays to be activated by the event selected in step 2 and select Configure the relay functions.
- Relay name: User-definable relay name (20 characters max.) which will appear in the Name list of the
table (see Figure 43)
- Normal: this relay will activate if an alarm occurs. The relay will return to its original position when the
alarm has ended.
- Buzzer: this relay is used to control a buzzer (audible alarm). The audible alarm can be dismissed by
pressing the Acknowledge button on the CPS central detection controller.
- Low speed: This relay is designed to control ventilators running at low speed (star-triangle
configuration for a ventilation system with two speeds: high and low).
- High speed: This relay is designed to control ventilators running at high speed (star-triangle
configuration for a ventilation system with two speeds: high and low).
- High Speed List: select the relay controlling ventilators running at high speed that can work with the
present low speed relay. This list is empty if no high-speed relay has been defined.
- High Speed Index: Lists the available high speed relays.
- Deactivated: the relay will remain in normal mode even if an alarm event occurs.
36
5. Click OK to close the window.
Relays are modified in accordance with the configuration as long as no logical impossibilities are
detected. If a logical impossibility is detected, an alert message will appear.
NOTE: the relay module will now appear in the display matrix as a blue square (see Figure 10: Matrix
display. on page 16).
004
37
The following information is presented:
■ Type: detector type (name defined in the Installation Architecture tab).
■ Name: detector name (name defined in the Installation Architecture tab).
■ Line: Line and module number (defined in the Installation Architecture tab).
■ Status: Removed will appear if you select a line and click the Remove button.
■ Alarm: Type of alarm activating the relay (name defined in the Installation Architecture tab).
The events will be added to the Relay Configuration window (shown below); compare to Figure 49. Click Exit to close the window.
38
5. Remove the configuration of a relay
Follow the steps below to remove one or more events assigned to a relay:
1. Click on the Relay Action tab.
On the right hand side of the Programming the Relays window, right-click on the line representing a
pre-configured relay and select Configuration of relay events.
39
6. List of Low Speed – High Speed Assignment
This menu is used to view the outputs dedicated to controlling the ventilation relays.
Figure 55: Viewing the Low speed - High speed outputs. 040
2. The window for low speed and high speed ventilator outputs will appear.
Figure 56: Example of a list of low speed - high speed ventilator outputs 041
This window lists the outputs dedicated to controlling the low and high speeds for ventilators.
Reminder: These outputs are defined in the Relay Actions tab (see the Configuring relays window
on page 36).
Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.
40
X. 4-20 M A OUTPUT ACTIONS
This window is used to define the 4-20 mA analog outputs which will be activated by the detectors.
1. Presentation of Data
C D E
Figure 57: The Analog output action matrix tab. 057
Item Function:
A List of events, for 255 detectors max., defined and activated in the Configuring the Detectors tab, which can control one
or more analog outputs (B).
B List of the analog outputs for the modules defined and activated in the Installation Architecture tab that can be controlled
by (A).
C User-defined name for the module’s analog output (Figure 61, page 43).
D Line-Module Analog Output indicator
E User-defined status for the module’s analog output (Figure 61, page 43).
Table 19: Settings of the Analog Output Actions Matrix.
NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.
NOTE: the Analog outputs modules used are defined in the Installation Architecture tab. If the modules
were not previously defined, nothing will appear in the zone of this tab called Programming the Analog
Outputs. See also the note regarding logic input, analog output and relay modules on page 41.
41
Figure 58: Establishing a connection between the event and the output. 042
Figure 59: Establishing a connection between the event and the output. 043
Multiple events can be linked to one output. To link more than one event, hold down the Ctrl key, select
the events and drag them to the line corresponding to the appropriate output line in the Programming
Analog Outputs table.
Warning: the largest analog value will be recopied onto the analog output. When the Confirmation
window appears, click OK.
42
Figure 61: Output configuration. 045
- Output name: User-defined name for the output (20 characters max.) which will appear in the Name
list of the table (see Figure 60
- Activated: the 4-20 mA output signal varies, according to the input.
- Deactivated: the 4-20 mA output signal will be frozen at 0mA, regardless of the input signal.
- Max: returns the MAX value of a sensor group "normalized by / range" (see page 46).
Click OK to close the window. The output is mow modified in accordance with the configuratio n.
NOTE: the 4-20 mA analog outputs module will now appear in the display matrix as a green square (see
Figure 10 on page 16).
43
2. Events currently assigned to the output are listed in a table.
048
44
Upon returning to the Analog Output Configuration window (below) the events will have been added.
Click Exit to close the window.
Follow the steps below to remove one or more events assigned to an output:
1. Click on the Output Action Matrix tab.
On the right hand side of the Programming the Analog Outputs window (lists the available and
configured analog outputs), right-click on the line representing a pre-configured output and select
Configuration of output events.
2. View the events currently assigned to the output.
The List of Assigned Events for the output is displayed in a table.
Figure 68: Analog output configuration display (list of assigned events). 048
Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.
45
XI. LOGIC INPUT ACTIONS (LI)
This window is used to define the connection matrix between a maximum of 64 logi c inputs (LI) and
possible 256 outputs (analog or relay).
1. Presentation of Data
The screen shot below shows the of the Logic Inputs Action Matrix screen.
■ Lines (C) and (D): logic inputs for the modules, analog relays or contact inputs.
■ Columns (A) and (B): list of available outputs (relay or analog).
■ Case (E): action to be completed.
A B C D E
Item Function:
A Name for output modules (relay or analog) added in the Relay Action Matrix and Outputs Action Matrix tabs.
B Line number – Module number – Output number localization for output modules (relay or analog) defined on the
Installation Architecture tab.
C Names for relay or analog output module inputs added in the Installation Architecture tab (configuration of the Relay
Action Matrix, Output Action Matrix, or name of the input modules defined in the Installation Architecture tab.
D Line number – Module number – Output number localization for input modules or inputs for relay and analog output
modules defined on the Installation Architecture tab.
E Defined action (green: start up, red: shut-down) for the line-column intersection (a column can affect multiple lines).
Table 20: Settings of the Logic Inputs Actions Matrix.
2. Use
NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.
NOTE: the inputs module(s) used are defined in the Installation Architecture tab. If the modules were not
previously defined, nothing will appear in the zone of this tab called Programming the Logic Inputs. It is
important to note that the number of available columns and lines depends on the configuration of the
installation. If no inputs are activated, the table will be blank. See the paragraph regarding logic input,
analog output and relay modules on page 41.
Follow the steps below to define the actions to take place on an output (analog or relay) in the
presence of an event on an input (16 input module, or relay or analog module).
1. Click on the LI Actions tab.
46
2. Define the output (A) activated when an input event occurs (B) by right-clicking at the
intersection of the appropriate line and column (C).
A B C
Figure 70: definition of an action at the intersection of a line and a column. 049
Reminder: the data in header rows (B) will only appear if the inputs have been activated as indicated in
the Note on page 41.
To define an action on the corresponding output of a relay module or an analog output, right-click on
the point of intersection for that line and column.
- Start up: select ON. The background of the cell will be green.
- Shut down: deactivate an action by selection OFF. The background of the cell will be red.
- Remove an action: Select Remove. The connection between the input and the output will be
removed. The background of the cell will be white.
The two types of actions (ON and OFF) cause the following actions for each cell: :
Logic Input Green background cell Red background cell White background cell
Table 21: output actions in relation to the configuration of the logic inputs action matrix.
An input (column) can act on one or more outputs (line). In this case, start over as indicated in
step 2.
Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.
47
XII. RELAY DAT A
This window is used to define of the operation of the CPS central detection controller’s three shared
relays, audible alarm controller relay, and the relays relating to forced ventilation .
1. Presentation of Data
D
Figure 71: "Relay data" tab. 051
2. Use
NOTE: if the application was closed (see previous chapter), simply import the previously saved
configuration file by going to the File menu and selecting Open and navigating to the desired file.
48
Name Function:
AL1, AL2, AL3, AL4 Alarm levels 1, 2, 3, or 4. See Configuring the Detectors tab, page 22.
Module error Alarm fault for a system module.
System failure Alarm triggered if there is a communication fault between modules, power supply short circuit or
module inversion. Always checked for R1.
Out of range and fault Alarm triggered if a gas level is out of range (exceeds the measurement range) or if there is a
fault (negative zero offset).
Positive security Always checked for R1. R2 and R3 can be set to positive security (relay active without alarm
condition) or normal security (relay active during alarm).
Table 23: settings for the internal CPS relays.
To define the activation time and acknowledgement delays for buzzer relays:
Name Function:
Min. activation times Min. operation time for a buzzer relay.
Acknowledgement delay Delay after which the buzzer relay will shut off.
ON The buzzer relay and the functions described above will be activated.
Table 24: additional settings for the buzzer relay.
Figure 74: Zone used to define time intervals to block high speed ventilation. 054
49
Configure the operation intervals for forced ventilation
To display these settings, click on the button (see Figure 71, on page 48).
A B
C D
Figure 75: view of the “Relay Data” tab after clicking the button. 055
Item Function:
A Diagram displaying concentration over time, alarms triggered and the intervals and delays used in controlling high and
low speed ventilation.
B Zone relating to normal operation of high and low speed ventilation.
C Close window.
D Button used to display simulated high and low speeds.
Table 25: forced ventilation settings.
Click on the button (Figure 75, ref. D) to display the zone used to define the simulated (test)
ventilator operation delays.
C D
Figure 76: Simulated high speed-low speed configuration zone. 056
50
These values are not used by the central detection controller in normal operation. They are only used to
quickly test the on/off time intervals for the ventilators.
Follow the steps below to define these values:
Name Function:
1. Min. duration PV operation Minimum duration, in seconds, for the ventilator to operate at simulated low speed.
2. GV operation delay Delay, in seconds, between starting up the ventilator in high-speed and the shut down of
the simulated low-speed ventilator.
3. Min. duration GV operation Duration, in seconds, for the ventilator to operate at simulated high speed.
4. PV-GV stop delay Duration, in seconds, after low or high speed ventilator operation has been stopped,
before the ventilator can be restarted at simulated low speed.
Save the settings by going to File > Save as or File > Save. This will allow you to open the
configuration file from a new session.
Once the configuration is complete, the central controller needs to receive the new settings. Follow
the steps below to transfer the settings to the CPS:
1. Use either the USB or RS-232 adapter to connect the PC to the CPS central detection controller.
NOTE: The CPS central controller is equipped with a USB connection. To use the USB connection, you
must first install the FTDI drivers on the PC.
Do not connect the USB cord until the driver has been installed.
Three installation guides are included with the COM_CPS software. Chose the appropriate guide for
your PC.
The COM_CPS software creates PDF files to save configuration data. Before creating PDFs, an
application to create and print PDF files must be installed.
2. Ensure that the CPS central detection controller is connected to a power source. (see CPS
instructions).
51
Step 3: data transfer
1. In the menu bar, select [Transfer > from PC to CPS].
2. A message will appear on, instructing you to position the CPS central controller switch into the MEM
position before transferring the configuration settings.
3. Click OK once verification has ended.
4. During the transfer, a progress bar will indicate transfer progress.
5. Once the transfer is complete, the message Operation complete will appear on screen. Click OK. Data
has been uploaded from the PC to the CPS central detection controller.
6. Flip the switch back to its original position.
Follow the steps below to download data recorded by the CPS central detection controller to the PC.
52
XIV. CONFIGUR ATION P AGES
In order to simplify the process of programming the COM_CPS software, the following tables can be
photocopied and filled out for each of the modules to be programmed. This will allow you to quickly
reprogram the modules without risk of error if the need arises in the future.
Detector Tab:
Detector
Range
Detector name
Abbreviated name
Hysteresis
Alarm 1 Tab
Delay (sec)
Acknowledgement Manual Automatic
Triggering Rising edge Falling edge
Instantaneous threshold
Active Checked Not checked
Averaged threshold
Integration time (m)
Active Checked Not checked
53
Alarm 2 Tab
Delay (sec)
Acknowledgement Manual Automatic
Triggering Rising edge Falling edge
Instantaneous threshold
Active Checked Not checked
Averaged threshold
Integration time (m)
Active Checked Not checked
Alarm 3 Tab
Delay (sec)
Acknowledgement Manual Automatic
Triggering Rising edge Falling edge
Instantaneous threshold
Active Checked Not checked
Averaged threshold
Integration time (m)
Active Checked Not checked
Alarm 4 Tab
Delay (sec)
Acknowledgement Manual Automatic
Triggering Rising edge Falling edge
Instantaneous threshold
Active Checked Not checked
Averaged threshold
Integration time (m)
Active Checked Not checked
Out of range
Verification Active Checked Not checked
Fault
54
XV. INDEX
Green background, 56
?
Red background, 56
?, 11 White background, 56
About, 11 Change configuration
Analog output, 51
4 COM_CPS
Configuring the Detectors, 24
4-20 mA, 50
Exit, 14
Installation, 6
A Installation Architecture, 33
Acknowledgement Delay, 60 Installing the Software, 6
Action Logic Inputs Action Matrix, 54
Activate, 55 Main Screen, 9
Deactivate, 55 Outputs Action Matrix, 48
Remove, 55 Purpose of the Application, 3
Activate Relay Action Matrix, 39
Analog output, 50 Relay Data, 58
Activate an action, 55 Remove Software, 7
Activate inputs, 35 Run the Software, 8
Activated Inputs, 35 Setup.exe, 6
AL1-AL4, 59 System Requirements, 6
Alarm Using, 16
Relay, 43 COM_CPS
Analog (output), 48 General configuration, 18
Analog output COM_CPS Installation, 6
4-20 mA, 50 COM_CPS Software. See COM_CPS
Activated, 50 Communication, 10
Change configuration, 51 Configuration
Deactivated, 50 Analog output, 51
Max, 50 Pages, 66
Name, 50 Configuration Pages, 66
Remove configuration, 52 Configuration settings
View, 51 Transfer from CPC to PC, 65
Analog outputs Configuring the Detectors, 24
Activate an action, 55 Use, 26
Define the actions, 49 CPS, 3
Overview, 48 Buzzer Relay, 60
Analog Outputs, 48 Characteristics, 4
Audible internal alarm, 21, 28 Configure Internal Relays, 59
Autosave, 10 Download configuration, 65
Internal Relays, 59
B Lines, 13
Modules, 13
Baud rate, 21 Receive configuration settings, 64
Blue, 14 CPS Lines, 13
Buzzer Module, 13
Relay.
Relay (configure), 60 D
Buzzer relay
CPS Central Controller, 60 Deactivate
Analog output, 50
C Deactivate an action, 55
Deactivated
Cell
55
Relay, 42 L
Display Language
LI action matrix, 54
Select, 8
Logic Inputs, 54
Display Matrix
Logic Inputs Action Matrix, 54
Cell, 13
Logic outputs
Drivers
Deactivate an action, 55
Install, 6
Remove an action, 55
Low speed
E
Relay.
EL. See Logic Inputs
Even, 21 M
Exit, 10, 14
Matrix Cell, 13
Matrix Display
F
Overview, 13
Fast access zone, 11 Max
Fault, 59 Analog output, 50
File, 10 MEM, 64
Exit, 10 Menu
Save, 10 ?, 11
Forced ventilation Communication, 10
Accelerated operation, 62 File, 10
Hours for high speed disablement, 60 Transfer, 11
Hours for high speed Min. activation time, 60
re-enablement, 60 Module
Off, 60 On the line, 4
Operation interval, 61 On the Line, 13
From CPS to PC, 11 Module error, 59
FTDI, 64
FTDI Driver, 64 N
Name
G
Analog output, 50
General configuration, 18 New, 10
General Configuration Normal High speed-low speed, 61
Overview, 18 Normal
Use, 19 NT, 6
Generate PDF, 64
Green, 14, 56 O
Grey, 14
Odd, 21
Open, 10
H
Operating System, 6
High speed Operation
Relay. Principles, 3
Homepage, 9 Options
Printing, 19
I OS. See Operating System
Out of range, 59
Inputs
Outputs Action Matrix, 48
Activated, 35
Deactivated, 35
P
Installation, 6
Installation Architecture, 33 Parity, 21
Installing COM_CPS, 6 PDF, 9
Internal audible alarm, 58 Driver, 64
Generate, 64
J Port, 11
Positive security, 59
JBUS, 21
Principles of Operation, 3
Printing
56
Options, 19 S
Report, 12
Save, 10
Printing Options, 19
Save As, 10
Prog1, 36
Settings
Prog2, 36
Transfer from PC to CPS, 64
Prog3, 36
Setup.exe, 6
Purpose of the Application, 3
Simulated high speed-low speed, 62
Simulated high speed-low speed operation,
Q
62
Quick Start, 4 Slave, 21
Slave Number, 21
R Software
Install, 6
R1-R3, 59
Use, 16
Rate, 11
Stop, 21
Red, 56
System failure, 59
Relay
Add an Event, 43
T
Alarm type, 43
Associate an event, 43 Tab
Buzzer, 41 Configuring the Detectors, 24
Change the configuration, 43 General configuration, 18
Deactivated, 42 Installation Architecture, 33
Event, 43 Logic Inputs Action Matrix, 54
Event (add), 43 Outputs Action Matrix, 48
High speed, 41 Relay Action Matrix, 39, 42
Low speed, 41 Relay Data, 58
Normal, 41 Timer, 36
Relay function, 41 Transfer, 11
Remove the configuration, 44 From COM_CPS, 11
View configuration, 42 From PC, 11
Relay Action Matrix, 39 To COM_CPS, 11
Change the configuration, 43 To the PC, 11
Remove Configuration, 44 Transfer Configuration Settings, 64
View configuration, 42 Translation, 1
Relay Data, 58 Transmission Rate. See Rate
Overview, 58
RelayAction Matrix U
Define Actions, 39
USB
Relays
FTDI Driver, 64
CPS Internal, 59
Use
Internal CPS (configure), 59
Change the configuration of a relay, 43
Remove an action, 55
Configuring the Detectors, 26
Remove COM_CPS, 7
General Configuration, 19
Remove configuration
Logic Inputs, 55
Analog output, 52
Remove the configuration of a relay, 44
Report
View the configuration of a relay, 42
Detailed, 12
Print, 12
Select, 12
V
Summary, 12 View
RS-232 Analog output, 51
Direct Connection, 6 Vista, 6
RS-485
Baud rate, 21 W
Even, 21
JBUS, 21 White, 56
Odd, 21 Windows 2000
Stop, 21 Driver, 7
Running COM_CPS, 8 Operating System, 6
57
Windows 98
Driver, 7
Windows 98 ME
Driver, 7
Windows 98 SE
Operating System, 6
Windows NT
Operating System, 6
Windows Vista
Driver, 7
Windows XP
Driver, 7
Operating System, 6
Windows XP 64-bit
Driver, 7
X
XP, 6
58
The Fixed Gas Detection Experts
60