Test Report
ModelNo: 3PH100K
Preparedby: J C KATARIA
Page 1 of
TEST REPORT
EN 61558-2
Safetyofpowertransformers,powersupplies,reactorsandsimilarproducts—Part1:
General requirements andtests
EN 61558-2
Part 2: Particular requirementsand tests for variable transformers and power supply
units incorporating variable transformers
Report
Report No. ....................................... :
Test specification:
Standard..........................................: IEC 61558-2-12:2011 Used in conjunction with
EN 61558-1:2005+A1:2009
Testprocedure................................: LVD
Non-standard test method…….…..: N/A
Test item
Description ……………………..……: 100 KEPREJ STABILIZER
Trademark …………………….….…: N/A
Model and/or type reference…….…: AMS/ 03-2K21/ 2889
Rating(s) ………………………..……: Input: 160-250Vac, 50/60Hz;
Output: 210-230Vac, 50/60Hz, 72.7A Max;
Capacity: 100KVA
Manufacturer……………………..….:KEPREJ POWERTRONICS
Address………………………………..:E.138, GIDS ELECTRONICS ESTATE, SECTOR 25, GANDHINAGAR
Page 2 of
Particulars: test item vs. test requirements
Short-circuit protection…………………...………..: --
General remarks:
The test results presented in this report relate only to the object tested.
Thisreportshallnotbereproduced,exceptinfull,withoutthewrittenapprovaloftheIssuingtestinglaboratory. "(see
Enclosure #)" refers to additional information appended to thereport.
"(see appended table)" refers to a table appended to the report.
Model no. Input: 160-250Vac, 50/60Hz; Output: 210-230Vac, 50/60Hz, 36.3A Max;
Capacity: 10KVA
Model no. Input: 160-250Vac, 50/60Hz; Output: 210-230Vac, 50/60Hz, 54.5A Max;
Capacity: 15KVA
Page 3 of
Copy of marking plate:
Page 4 of
EN 61558-2
4. GENERAL REQUIREMENTS P
Thetransformershallcausenodamagetopersons P
orsurroundings.
6. RATINGS P
6.101 The rated output voltage shall not exceed P
(EN61558-2-14)
– 50Va.c.or120Vripple-freed.c.forvariable N/A
safety isolating transformers.(EN61558-2-14)
The rated output voltage shall exceed: N/A
(EN61558-2-14)
– 200kVAforpoly-phasevariable N/A
auto-transformers;(EN61558-2-14)
– 1kVAforsingle-phasevariableseparating N/A
transformers;(EN61558-2-14)
– 5kVAforpoly-phasevariableseparating N/A
transformers;(EN61558-2-14)
Page 5 of
EN 61558-2
– 25kVAforsingle-phasevariableisolating N/A
transformers;(EN61558-2-14)
– 40kVAforpoly-phasevariableisolating N/A
transformers;(EN61558-2-14)
– 10kVAforsingle-phasevariablesafetyisolating N/A
transformers;(EN61558-2-14)
– 16kVAforpoly-phasevariablesafetyisolating N/A
transformers.(EN61558-2-14)
Transformers without limitation of the rated output N/A
shallbesubjecttoagreementbetweenthepurchaser
and the manufacturer.(EN61558-2-14)
6.103 Theratedsupplyandinternaloperationalfrequencies Not exceed 500 Hz P
shall not exceed 500 Hz.(EN61558-2-14)
6.104 Theratedsupplyvoltageshallnotexceed1000V a.c. 160-250Vac P
(EN61558-2-14)
7. CLASSFICATION P
7.1 Transformersareclassifiedaccordingtoprotection P
against electric shock: Class I, II,III
7.2 According to protection against abnormal use : P
-inherently short-circuit proof N/A
-non-inherently short-circuit proof N/A
-non-short-circuit proof P
-fail safe N/A
7.3 Accordingtoprotectionagainstharmfulingressof IP20 P
water in according with IEC529:
7.4 According to their mobility: Fixed transformer P
7.5 According to their time of operation Continuous P
7.6 According to their intended use: Associated P
7.7 Optionally, tw N/A
7.8 According to the environmental conditions where P
they are intended to be used:
normal environment P
special environments N/A
Page 6 of
EN 61558-2
b)ratedoutputvoltagerangeinvoltsorkilovolts; 210-230Vac P
(EN61558-2-14)
For transformers incorporating a rectifier, the rated N/A
output voltage range after the rectifier shall be
marked with the arithmetic mean value. If, however,
the output voltage is given as an r.m.s. value, this
shall be stated. (EN61558-2-14)
c) rated output (VA, kVA or W)................................ : 20KVA P
d) rated output current (A) ....................................... : 72.7A Max P
e) rated frequency (Hz)............................................ : 50/60Hz P
f) rated power factor (if not 1) .................................. : 0.8 P
g)symbolorabbreviationACforalternatingcurrent or AC P
DC for direct currentoutput;
h) Relevant graphical symbols shown in 8.11 P
indicating the kind of transformers; (EN61558-2-14)
i) manufacturer's name or trademark GUANGDONG EAST P
POWER CO., LTD
j) model or type reference ZTY-20KVA P
k) vector group according to IEC 60076-1 (for N/A
three-phase transformer if required);
l)symbolforclassIIconstruction,forclassII N/A
transformersonly;
m) symbol for class III construction, for class III N/A
transformers only;
n) index IP (if not IP00) or ordinary transformer IP20 P
o) rated max. ambient temperature ta (if not 25℃) : 40℃ P
p) rated minimum ambient temperature tamin ,if N/A
lower than + 10 °C and if a temperature sensitive
device is used.
q)short-timeoperationorintermittentoperation: N/A
rated operating and restingtime
r) for tw-marked transformers N/A
s) transformers to be used with forced air cooling N/A
where the fan is not a part of the transformer shall
be marked with “AF” followed by the air speed
t) purchaser with the following information N/A
for stationary transformers with a rated output Fixed transformer N/A
exceeding 1 000 VA, the short-circuit voltage
expressed as a percentage of the rated supply
voltage;
the electrical function of the transformer N/A
8.2 Marking for transformers IP00 or for associated P
transformers: type and trademark, instruction sheets
Page 7 of
EN 61558-2
Page 8 of
EN 61558-2
Page 9 of
EN 61558-2
– lampshavingcapslargerthanB9andE10
– type Dfuse-holders.
Theinsulatingpropertiesoflacquer,enamel,paper, P
cotton, oxidefilm
openings in class II transformers, and openings in N/A
class I transformers other than those in conductive
parts connected to a protective earth terminal
It shall not be possible to touch bare hazardous live P
parts or hazardous live parts protected only by
lacquer, enamel, paper, cotton, oxide film or sealing
compound
9.1.3 Nonhazardouslivepartsoftheoutputcircuitisolated P
from the input circuit by double or reinforced
insulation may be accessible under the following
conditions:
for no-load output voltages not exceeding 35 V peak N/A
a.c. or 60 V ripple-free d.c., both poles may be
accessible.
for no-load output voltages exceeding 35 V peak P
a.c.or60Vripple-freed.c.andnotexceeding250V
a.c.,onlyoneofthepolesmaybeaccessible.
9.2 For transformers with a primary supply plug, the N/A
pins of the plug shall not be hazardous live
measured 1s after withdrawal of the plug.
For transformers without a primary supply plug, P
the terminals provided for connecting the
transformer to the supply source shall not be
hazardous live measured 5 s after disconnection of
the supplysource.
ifthenominalcapacitanceacrossthepinsdoesnot N/A
exceed 0,1 µF, no test isconducted.
The primary supply switch of the transformer, ifany, N/A
is in the off-position, unless it is more unfavourable
in theon-position.
The test shall be carried out 10 times or with a P
device used to switch off at the most unfavourable
electrical angle of the supply voltage.
Page 10 of
EN 61558-2
Thevoltageismeasuredbetweentheinputterminals or P
between the supply leads or between the pins of
thesupplyplugusedfortheconnectiontothesupply
source after 1 s or 5s.
If the voltage exceeds 60 V ripple free d.c., the N/A
dischargeismeasuredinthesameconditionsand
shall not exceed 45µC.
Page 11 of
EN 61558-2
– 1000Va.c.or1415Vripple-freed.cforauto- and P
separating transformers;(EN61558-2-14)
– 50Va.c.or120Vripple-freed.cforsafety N/A
isolatingtransformers(EN61558-2-14)
For independent transformers, this output voltage N/A
limitation applies even when output windings, not
intendedforinterconnection,areconnectedinseries.
(EN61558-2-14)
The no-load output voltage shall exceed: N/A
(EN61558-2-14)
14 HEATING P
14.1 Transformersandtheirsupportsshallnotattain P
excessive temperature in normaluse.
Page 12 of
EN 61558-2
Page 13 of
EN 61558-2
– duration: 30min;
– amplitude: 0,35mm;
– frequencyrange:10Hz,55Hz,10Hz;
– sweeprate:approximatelyoneoctaveperminute.
– theno-loadinputcurrentoritsohmicvalue P
– the insulationresistance P
– a dielectric strengthtest P
Page 14 of
EN 61558-2
1,1 times the rated supply voltage or supply voltage 1.1 times the rated supply P
between 0,9 times and 1,1 times the rated supply voltage
voltage for non-inherently short-circuit proof
transformers
– forinherentlyshort-circuitprooftransformers,by N/A
the tests of15.2;
–fornon-inherentlyshort-circuitprooftransformers, N/A
by the tests of15.3;
– fornon-short-circuitprooftransformers,bythe P
tests of15.4;
– forfail-safetransformers,bythetestsof15.5; N/A
Page 15 of
EN 61558-2
16 MECHANICAL STRENGTH P
16.1 After tests of 16.2 and 16.3 and 16.4: P
- no damage P
- hazardous live parts not accessible by test pin P
according to 9.2
- no damage for insulating barriers P
- handles, levers, etc. Have not moved on shafts N/A
16.2 Forstationaryandportabletransformers:3blows, P
impact energy 0,5Nm
16.3 For portable transformers: 100 falls, 25 mm N/A
16.4 Portable Transformers with integrated pins, the following tests are carried out: N/A
a)plug-intransformers:tumblingbarreltest:50falls,≤ N/A
Page 16 of
EN 61558-2
Page 17 of
EN 61558-2
– twodays(48h)fortransformerswithprotection P
index IP20, orlower;
– sevendays(168h)fortransformerswithother N/A
protectionindex
AfterthistreatmentandthetestsofClause18,the P
transformer shall show no damage within the
meaning of thisstandard.
Page 18 of
EN 61558-2
- turns of winding P
- input and output windings P
- adjacent input or output windings N/A
- windings and iron core P
During the test of insulation between winding it N/A
is allowed to isolate the current collector from
the windings.(EN61558-2-14)
18.5 Touchcurrentandprotectiveearthconductorcurrent P
The touch current and protective earth conductor P
current are measured with the transformer loaded
as described in Clause 14 and the measurements
are made at steady state condition.
18.5.1 Touch current P
The touch-current is measured with the switch p P
in both position and the following combination of
switches e andn:
– switchnintheoffpositionandswitcheintheon P
position;
– switchnintheonpositionandswitcheintheoff P
position
18.5.2 Protective earth conductor current P
The protective earth conductor current is 0.1Ω P
measured with the transformer connected as
described in Clause 14
Theprotectiveearthconductorcurrent(s)shallnot P
exceed thevalues
19 CONSTRUCTION P
19.1.1 Variable auto-transformers(EN61558-2-14) P
19.1.1.1 Plug connected auto-transformerswhere the rated N/A
inputvoltageishigherthantheratedoutputvoltage,
shall not have any potential to earth at the output
socket higher than the rated output voltage.
(EN61558-2-14)
19.1.1.1.1 Polarizedinputandoutputplugandsocket-outlet N/A
system(EN61558-2-14)
Inthiscase,aninstructionshallbegivenfornotusing N/A
such a transformer with a non-polarized plug and
socket-outlet system.(EN61558-2-14)
19.1.1.1.2 Polaritydetectingdevice(fornonpolarizedinputand N/A
output plug and socket-outletsystem)
(EN61558-2-14)
Page 19 of
EN 61558-2
–forassociatedtransformers-allowedbythe
relevantendproductstandard.(EN61558-2-14)
19.1.2.4 Protectionagainstdirectcontactwiththeliveparts N/A
(contact path and drive) shall be ensured.
(EN61558-2-14)
19.1.3 Variable isolating and safety isolating N/A
transformers(EN61558-2-14)
19.1.3.1 The input and output circuits shall be electrically N/A
separatedfromeachother,andtheconstructionshall
besuchthatthereisnopossibilityofanyconnection
betweenthesecircuits,eitherdirectlyorindirectly,via
other conductive parts, except by deliberate action.
(EN61558-2-14)
19.1.3.2 The insulation between input and output winding(s) N/A
shallconsistofdoubleorreinforcedinsulation(rated for
the working voltage).(EN61558-2-14)
Page 20 of
EN 61558-2
Page 21 of
EN 61558-2
Page 22 of
EN 61558-2
Page 23 of
EN 61558-2
-Earth P
-Live part P
-Protective conductors forming part of other circuits P
19.20.2 Protection against PELV-circuits by insulation N/A
withstandingtestasdoubleorreinforcedinsulation
according to table8.
19.21 Protection against FELV-circuits by insulation N/A
correspondingtotheminimumtestvoltagerequired
for the primarycircuit.
19.22 No earthing in Class II transformers N/A
19.23 No earthing in Class III transformers N/A
20 COMPONENTS P
Components such as switches, plugs, fuses, lamp (see appended table ) P
holders, capacitors and flexible cables and
cordsshallcomplywiththerelevantIECstandardas far
as it reasonablyapplies
20.1 Appliance couplers for mains supply shall comply N/A
with the IEC 60320 series for IPX0 transformers
and IEC 60320-2-3 or IEC 60309 for other
transformers.
20.2 Automatic controls shall comply with IEC 60730 N/A
series and the appropriate parts 2 unless they are
tested with the transformer
20.3 Thermal linksshallcomplywithIEC60691asfaras P
reasonable.
20.4 Switches forming part of the transformer assembly N/A
shall comply with Annex F
20.5 There shall be no unsafe compatibility between the N/A
socket-outlets in the output circuit and a plug
intended for direct connection to a socket-outlet
whichcouldbeusedfortheinputcircuitinrelationto
installation rules, voltages, andfrequencies.
20.6 Thermalcut-outs,thermallinks,overloadrelays, N/A
fusesandotheroverloadprotectivedevicesshall
have adequate breakingcapacity.
20.6.1 FusesaccordingtoIEC60127andIEC60269are N/A
allowedtobecontinuouslyloadedbyacurrentnot
exceeding 1,1 times the ratedvalue
20.7 Thermalcut-outsshallmeettherequirementsof N/A
20.7.1.1and20.7.2,or20.7.1.2and20.7.2.
20.7.1 Requirements according to IEC 60730-1 N/A
20.7.1.1 Thermal cut-outs when tested as separate N/A
components shall comply with the appropriate
requirements and tests of IEC 60730-1
Page 24 of
EN 61558-2
– besubjectedtoanumberofcyclesofautomatic N/A
operation
The tests are carried out on three samples N/A
After the tests, there shall be no damage to the N/A
thermal cut-out and the transformer in the sense of
this standard
20.7.2 Thermalcut-outsshallhaveadequatebreaking N/A
capacity
20.7.2.1 A transformer with a non-self-resetting thermal N/A
cut-out is supplied at 1.1 times rated input voltage
and the output terminals are short-circuited until
the thermal cut-outoperates
20.7.2.2 A transformer with a self-resetting thermal cut-out N/A
is supplied at 1,1 times the rated input voltage with
the output terminals short-circuited
20.7.2.3 A PTC resistor of indirect heating type is N/A
considered to be a non-self-resetting thermal
cut-out by this standard.
20.8 Thermal-linksshallbetestedinoneofthefollowing P
twoways.
20.8.1 The thermal-links, when tested as separate P
components, shall comply with the requirements
and tests of IEC 60691
– the electricalconditions P
– the thermalconditions P
Page 25 of
EN 61558-2
21 INTERNAL WIRING P
21.1 Internalwiringandelectricalconnectionsprotectedor P
enclosed
Wireways smooth and free from sharp edges P
21.2 P
1,5mm) or bushings of insulating material
21.3 Bare conductors: distances adequately maintained N/A
21.4 When external wires are connected to terminal, P
internal wiring shall not work loose
21.5 Insulationofheat-resistantandnon-hygroscopic N/A
material for insulated conductors subject to
temperaturerise>limitingvaluesgivenin14.2
Page 26 of
EN 61558-2
22.6 Power supply cords may be cord sets fitted with N/A
appliance couplers in accordance with IEC 60320,
provided the transformers are single-phase
portable transformers with input current not
exceeding 16 A at the rated output
22.7 Nominalcross-sectionalarea(mm²);inputcurrent(A) N/A
atratedoutputnotlessthanshownintable9........:
22.8 Class I transformer with Power supply cord: N/A
green/yellowcoreconnectedtoearthingterminal
Plug for single-phase transformer with input current N/A
atratedoutput16AaccordingtoIEC60083,IEC60
906-1
Plugforotherportabletransformerscomplyingwith N/A
IEC60309
22.9 Type X, Y, or Z attachments allowed N/A
22.9.1 For type Z attachment: molding enclosure and N/A
Power supply cord cable do not affect insulation of
cord
22.9.2 Inlet openings or inlet bushing: without risk of N/A
damage to protective covering of Power supply cord
Insulation between conductor and enclosure: N/A
-forClassItransformer:insulationofconductorat N/A
least basicinsulation
-forClassIItransformer:insulationofconductorat N/A
least double or reinforcedinsulation
22.9.3 Inlet bushings: N/A
- no damage to Power supply cord N/A
- reliably fixed N/A
- not removable without aid of tool N/A
-notbenaturalrubber,exceptasanintegralpartof N/A
cordfortypeXwithaspecialcordandtypeYandZ for
class Itransformer.
22.9.4 For transformers with cords which are moved while operating: N/A
- cord protected against excessive flexing. N/A
-cord guard of insulating material N/A
-cord guard reliably fixed N/A
-flexingtestadshowninfigure7,loadedwith10Nif N/A
cordarea≥0.75mm2,5Nforothers,flexing20000
timesforZattachments,10000forothers.
Page 27 of
EN 61558-2
Page 28 of
EN 61558-2
Page 29 of
EN 61558-2
Page 30 of
EN 61558-2
Page 31 of
EN 61558-2
Page 32 of
EN 61558-2
Page 33 of
EN 61558-2
E. GLOW-WIRE TEST P
Glow-wire test is carried out in accordance with IEC P
659-2-1/0
Page 34 of
EN 61558-2
Page 35 of
EN 61558-2
-ifcurrent<2,1timesratedcurrent,thetestis N/A
repeated with the fuse shortcircuit.
-ifcurrent<2,75timesratedcurrent,thecircuitis N/A
considered to be adequatelyprotected.
- if current < 2,1 times rated current, the test is N/A
repeatedwiththefuseshortcircuitforthetime:30 min
for a quick acting fuse and 2 min for time lag
fuse.
H.26 CREEPAGE, CLEARANCES AND DISTANCES THROUGH INSULATION N/A
H.26.1 Thedistanceonconductivepatternonprintedcircuit N/A
board between different polarity may be reduced if
thetrackindexofthePTCisatleastmaterialgroup IIIa
to:-150 V/mm if protected againstdirt.
The distance may be less if the transformer N/A
complieswith clause H.15 if the distance is short
circuit.
H.26.2 Testiscarriedoutatatemperatureof50Kinexcess N/A
ofthemaximumtemperaturemeasuredinclause14
and15.
Page 36 of
11 TABLE: output voltage and output current under load; no-load output voltage P
Clause 11 12
rated output rated voltage sec. voltage delta Use Use V delta Use further
V V % no-load output no-load output information
%
Cl11 required
±10%
210-230Vac 160-250Vac 227 -1.3% 297 30.8%
Cl12 required
<100%
14 TABLE: heating P
t1 (℃) 25.0 --
t2 (℃) 25.1 --
Test voltage (V) 275VAC --
Winding temperature rise measurements: P
Parts dT (K) Limited
Metal enclosure 5.1 --
AC connector 10.4 --
Internal wire 18.9 105-40=65
PCB 22.7 130-40=115
Capacitor 30.6 105-40=65
Relay 25.7 --
Ambient 25.0 --
Temperature rise dT R1(Ω) R2(Ω) dT (K) Insulation
winding class
Transformer winding 1355 1604 58.7 --
Note: The temperature rise limit is based on max. ambient operating temperature 40℃.
Page 38 of