PROJECT : PHOENIX H-10 AT HYDERABAD

ARCHITECTS : CHAPMAN TAYLOR, NEW DELHI


CLIENT : PHOENIX SPACES PVT. LTD, HYDERABAD
: AMENITY

RATE
SL.NO DESCRIPTION UNIT TOTAL QTY INSTALLATIO REMARKS
. TOTAL
N

TOTAL FOR PART - A ( Carried forward to summary )

B HYDRANT SYSTEM

., installing, testing and commissioning of M.S.'C' class pipes confirming to


IS:1239 Pt - I Heavy grade with painting, suitable type of supports ( Shall be
fabricated by M.S. Channel / Angle / Flat for above 50 mm dia), anchor
fasteners, bolts nuts, clamps, "U" bolte, malleable specials such as
Reducers,Fittings,Tees, elbows(25mm to 50mm forged socket weld type-
3000psi, 65mm and above ERW butt welded fitting), flanges.The pipes shall be
1.0 painted with 2coats of etching primer & 2 coats of approved paint (Red),
anchor fasteners, bolts, nuts, clamps, rails "U" & threaded bolt, Including
cutting, Welding, fixing in / on walls, ceiling by using suitable supports etc, as
per drawings. The quoted rate shall also include for chasing / chipping walls,
making bore holes in walls / floor and making them good with filler material and
finished in cement morter etc. complete. Paints must have VOC value less
than 250 g/l.

a 150mm nominal dia Rmt 70


b 100mm nominal dia Rmt 220
c 80mm nominal dia Rmt 12
d 25mm nominal dia Rmt 24

., installing, testing and commissioning of M.S. pipes confirming to IS 1239 Pt -


I Heavy grade with suitable type of supports, malleable specials such as
Reducers,Tees, elbows, flanges. Including cutting, Welding as per drawings.
2.0
The rate quoted should e included with anticorrosive treatment with 4 mm thick
polymer corrosion resistant tape as per IS 10221, overlap shall be 15mm
minimum.
a 150mm nominal dia Rmt 6

., Installing, testing and commissioning CI butterfly valves as per BS 5155 (PN-


16) slim seal standared lever operated type upto 150mm.Above 150mm it shall
3.0
be gear operated, with required flanges, nuts, bolts etc. complete. (for low level
riser). The valves shall be fitted with Lock and Key facility for monitoring.

a 150mm nominal dia Nos. 1


b 100mm nominal dia Nos. 4
c 80mm nominal dia Nos. 5

., erecting and commissioning of Landing Hydrants comprising of the following


4.0
in the Fire duct;
Single headed hydrant valve type - A as per IS 5290, made of stainless steel
I with 63 mm dia instantaneous outlet of 80mm dia fanged inlet ,Blank caps , Nos. 10
chain and hand wheels etc complete.
15 M long, 63mm dia RRL hose with instataneuos couplings and Hoses shall
ii Nos. 10
be stored inside the hose cabinet.
iii 1 no. stainless steel short branch pipe with nozzle. Nos. 10
Hose reel drum of swinging type with 19mm dia Rubber braided hose of 40M.
iv length with Gate valve (upstream) and Shut off nozzle,25mm Ball valve Nos. 10
complete set.

Fire duct Shutter fabricated out of M.S.sheet of 16 swg., and frame, door shall
be 900mm x 1200mm x 150mm min. & fixed with 4 mm thick Glass, suitable
v Rubber beedibg and Locking arrangement. Quoted rate shall be includes all Nos. 10
fasteners etc, and complete shutter shall be powder coated of approved colour
both inside and out side, with locking key & emergency breaking glass

., installing, testing and commissioning of yard hydrant comprising of the


5.0
following,
Single headed hydrant valve as per IS 5290, made of stainless steel with 63
a mm dia instantaneous out & 80 mm dia fanged inlet, Blank cap , chain and Nos. 5
hand wheel etc complete.
15 M long, 63mm dia RRL hose with instataneuos couplings and Hoses shall
b Nos. 5
be stored in side the hose cabinet.
c 1 no. stainless steel short branch pipe with nozzle. Nos. 5

M.S. Hose cabinet stand mouted type fabricated out of M.S. sheet of 16 swg.
with glass fronted (4mm thick glass with rubber beeding) door and size of the
d cabinet shall be 600mm x 750 mm x 250 mm Quoted rate shall be includes Nos. 5
suitable stand for mounting, all fasteners etc, and cabinet shall be powder
coated of approved colour both inside and out side.

. and fixing approved make 25mm dia. Gun metal automatic air release valve
9.0 Nos. 4
with unions, fittings, piping etc. complete.

., installing, testing and commissioning of Gun metal chrome finished Ball


10.0
valves with fittings of screwed end type.
a 25mm dia. Nos. 4

. & fixing of Orifice plate. The quoted rate shall include the suitable thickness
Orifice plate complete., on the hydrant outlet for necessary pressure reduction
11.0 Nos. 8
(if required) to maintain a maximum allowable outlet pressure including all
accessories.

TOTAL FOR PART - B ( Carried forward to summary )

C FIRE EXTINGUISHERS

., installing and commissioning Portable Fire extinguishers of following type &


1.0
capacity.

ABC powder type fire extinguisher of 2Kgs. Capacity, with initial filling in brand
new cylinder with powder coated finish, fitted with Gun metal union,stored
a Nos. 6
pressure type, discharge hose, wall mounting bracket etc. complete, confirming
to IS:15683. (inside lifts, pantry)

Carbon-di-oxide type fire extinguisher of 4.5Kgs. Capacity, with initial filling in


brand new cylinder with powder coated finish, fitted with Gun metal union,
b Nos. 45
stored pressure type, discharge hose, wall mounting bracket etc. complete, (for
electrical & utility rooms)

ABC powder type fire extinguisher of 6Kgs. Capacity, with initial filling in brand
new cylinder with powder coated finish, fitted with Gun metal union, stored
c Nos. 50
pressure type, discharge hose, wall mounting bracket etc. complete, confirming
to IS:15683. (for food court, service areas)

Water mist type fire extinguisher of 4lts. Capacity, with initial filling in brand new
cylinder with powder coated finish, fitted with Gun metal union, stored pressure
d Nos. 10
type, discharge hose, wall mounting bracket etc. complete, (near every
staircase)

Foam type fire extinguisher of 9lts. Capacity, with initial filling in brand new
cylinder with powder coated finish, fitted with Gun metal union, stored pressure
e Nos. 0
type, discharge hose, wall mounting bracket etc. complete, (near D.G room,
trafo yard)

. of floor mounting stand for to keep Extinguishers. Stand shall be MS powder


f Nos. 8
coated.

TOTAL FOR PART - C ( Carried forward to summary )

D SIGNAGES

Providing and installing in position the following type of sign boards made out of
1.0 3mm thick "Opaque" PVC foam board with computer cut, PVC non-reflective
self adhesive vinyle painted foam board, complete with mirror fasteners.

Signage with printed "IN CASE OF FIRE, USE STAIRS UNLESS


INSTRUCTED OTHERWISE" of 1.5cm height letters in red with white back
a. Nos. 10
ground.The size of the board shall be 25cm x 30 cm and shall be fixed at the
height of 2 mts. from finished floor near Manual call points.

Floor indentification signage ( ie, GROUND FLOOR …etc.) at each stair


enclosure on every floor, indicating the floor number in words, lettering size
b. Nos. 10
shall be 7.5 cm with contrasting colour from back ground.Size shall be 30cm x
20cm.

Providing and fixing in position the signages " FIRE ORDER" it should contain
2.0 the following matter on 3mm thick "Opaque" PVC foam board of computerised
cut, PVC non-reflective self adhesive vinyle painted foam board of 3' x 4'.

A) ALERT THE SECURITY AT SECURITY ROOM BY ACTUATING MANUAL


a Nos. 1
CALL POINT LOCATED AT STRATEGIC LOCATIONS.

B) EVACUATE THE OCCUPANTS BY USING FIRE EXITS AND


EMERGENCY EXITS ONLY AND ASSEMBLE AT VARIOUS ASSEMBLY
POITS.

C) IF POSSIBLE TRY TO EXTINGUISH THE FIRE BY USING NEAREST /


SUITABLE PORTABLE EXTINGUISHER OR WATER FROM NEAREST WET
RISER.

D) BE CALM AND DO NOT GIVE ANY ROOM FROM PANIC, WALK, DO NOT
RUN.

E) IF YOU ENCOUNTER SERIOUS DIFFICULTY IN EVACUATION, FLAT


AND TRY TO ATTRACT ATTENTION OF RESCUE TEAM.

ACTION BY SECURITY/RECEPTION UPON RECEIPT OF INFORMATION


b THROUGH FIRE ALARM ORFIRE DETECTORS OR BY USING PUBLIC Nos.
ADDRESS SYSTEM.

A) ALERT THE OCCUPANTS BY USING PUBLIC ADDRESS SYSTEM.

B) INFORM FIRE CONTROL THROUGH ANY ONE OF THE FOLLOWING


PHONE NUMBERS: 101 / 2251780 / 2251781 / 2251782.

C) REFER EVACUATION PLAN FROM EVACUATING STANDARD PEOPLE.

D) GUIDE THE FIRE FORCE, ON THEIR ARRIVAL TO THE SEAT OF FIRE.

E) IN CASE OF THE CASUALTIES, CALL AMBULANCE BY DIALLING


NUMBER……..

FIRE FIGHTING AGNECY -------------------------------

PHONE : -----------------------
FAX : ----------------------------

Providing and fixing in position the signages indicating each lift bank by an
"alphabetical " letter. The sign indicating the letter of identification shall be
3.0 posted and maintained at each lift landing & on the side of the stairway door Nos. 10
from which egress is made. The numerals & signs shall be at least 12.5mm
high & bold.

TOTAL FOR PART - D ( Carried forward to summary )

E CIVIL WORKS

Exacavation of trenches up to 1.5 mts. in depth, for laying pipes upto 150mm
dia. Including forming bottom surface to required level, refilling the trenches
with selected excavated earth around the pipe in layers of 150mm thick,
1.0
watering, consolidating. Quoted price inclusive of disposing off / Carting away
the surplus earth out side the site to a dump yard acceptable local bodies or as
directed by the site engineer with a lead of 300 mts. etc. complete.

a Excavation in all kinds of soil Cum. 5


b Cutting of Rock with chiselling Cum. 0

. and installation of RCC hume pipes of 300 mm ia & NP 2 Class with collars
for road / below floor crossing of Fire water pipes. The rate shall includes
2.0 Rmt. 70
excavation, PCC ( 1:4:8 100 mm thick)bed and ends shall be closed with Brick
masonry work as directed by site engineer.

.and construction of PCC (1:2:4) pedastals / supports for Under ground / above
3.0 ground pipes. Quoted rate shall inclusive of excavation ( if required ), chipping / Nos 60
chasing, shuttering, plastering ( if required) etc. complete.
RATE
SL.NO DESCRIPTION UNIT TOTAL QTY INSTALLATIO REMARKS
. TOTAL
N
Sealing of Fire shafts at all floor levels by using M.S. angle Iorn frame around
4.0 the shaft, M.S. chequered plate and PCC of 1:2:4 (100mm thick) on the plate Sq.mts 6
for whole shaft area as per drawings and engineer - in - charge.

TOTAL FOR PART - E ( Carried forward to summary )

F AUTOMATIC SPRINKLER SYSTEM

., installing, testing and commissioning of M.S. 'C' class pipes confirming to


IS:1239, part - I, heavy grade, malleable specials extruded type, such as
Reducers, elbows,Fittings (25mm to 50mm forged socket weld type, 65mm and
above ERW butt welded fitting), flanges.The pipes shall be painted with two
coats of Epoxy primer & 2 coats of approved Paint (Red), Galvanized supports
at standard spacing, anchor fasteners, bolts, nuts, clamps, rails "U" & threaded
bolt, Including cutting, Welding, fixing in / on walls, ceiling by using the
supports etc, as per drawings. The quoted rate shall also include for chasing /
chipping walls, Floors, making bore holes in walls / floor and making them good
with non shrink filler material (as approved by Architect )in bore holes / finished
in cement mortar etc. complete. (Above Ground ) Paints must have VOC value
less than 250 g/l.

a 150mm nominal dia Rmt 110


b 100mm nominal dia Rmt 155
c 80mm nominal dia Rmt 195
d 65mm nominal dia Rmt 320
e 50mm nominal dia Rmt 715
f 40mm nominal dia Rmt 170
g 32mm nominal dia Rmt 355
h 25mm nominal dia Rmt 1120

., installing, testing and commissioning of M.S. 'C' class pipes confirming to


IS:1239 malleable specials extruded type, such as Reducers, elbows,
Fittings(25mm to 50mm socket weld type, 65mm and above butt welded fitting)
flanges. necessary puddle flanges for tank connection, The pipes shall be anti
2.0 corrosive wrapping treated. Wrapping material shall consist of three layers of
high molecular high density polyethylene, three layers of polymerized bitumen
and one layer of polyesters (total seven layers).Wrapping is applied over two
coats of anti corrosive rubber modified bituminous primer. (under groung
piping )

a 150mm nominal dia Rmt 6

., installing, testing and commissioning of Gun metal chrome finished Ball


3.0 valves with fittings of screwed end type. (for sprinkler drain pipe at every floor
level)
a 50 mm dia Nos 8

., Installing, testing and commissioning CI butterfly valves as per BS 5155 (PN-


16) slim seal standared lever operated type upto 150mm. Above 150mm it shall
4.0 be gear operated, with required flanges, nuts, bolts etc. complete. with tamper
switch arrangement (for low level riser). The valves shall be fitted with Lock and
Key facility for monitoring.
a 150mm dia Nos 8
b 100mm dia Nos 0

., Installing, testing and commissioning CI butterfly valves as per BS 5155 (PN-


16) slim seal standared lever operated type upto 150mm. Above 150mm it shall
5.0 be gear operated, with required flanges, nuts, bolts etc. complete. with tamper
switch arrangement. The valves shall be fitted with Lock and Key facility for
monitoring. (tapping provision for bfc sprinklers)
a 150mm dia Nos 8

., installing, testing and commissioning conventional Standard response


Sprinkler quartzoid bulb type with 15mm screwed end connection of 68 deg. C.
6.0 temperature rating, K-factor of 80 and orifice shall not be less than 6mm.
Sprinklers shall be UL Listed / FM approved with Chrome finished. Color/finish
of the cover plate shall be as approved by the clients / architects.
a Pendent sprinkler for amenity areas Nos 860
b Pendent sprinkler for toilet areas Nos 110

., installing, testing and commissioning of hydraulically operated Sprinkler


control valve, with water motor gong bell and trims as required, pressure
7.0
gauges, drain valves, ball valves, check valves, strainers etc. complete. Alarm
valve shall be UL Listed/ FM approved (for low level riser)
a 150mm dia. Nos 1

., installing, testing and commissioning of flow switch on sprinkler distribution


8.0 header on each floor and shall be connected to fire alarm panel through cable. Nos. 8
Flow switch shall be "UL" Listed and FM approved.

Stainless steel corrugated flexible pipe(braided hose) for dropping sprinklers


below false ceiling, pipe shall be 16 bar pressure rating and 1500 mm long 25
9.0 Nos. 110
mm dia with union / reducer collar, clamps etc. as required. It shall be FM
approved.

., installing, testing and commissioning of Sight glass unit for sprinkler drain,
drain valves, ball valves, check valves, Union etc. complete.Set shall be UL
10.0 Nos. 8
Listed. ( 25mm dia. Sight glass , 25 mm dia. Test valve & 50 mm dia. Drain
valve with accessories)

. & fixing of approved type rosette plates ( Recessed type, in two piece) for
11.0
Sprinklers below false ceiling area.
The Rosette shall be fabricated by M.S. plate of 2mm thick and the finish shall
a Nos 110
be powder coated and color shall be as approved by architects / clients.

TOTAL FOR PART - F ( Carried forward to summary )