Professional Documents
Culture Documents
Requirements: The equivalent to 4/0 copper per the IEEE Fusing Chart is 19#940%.A typical maximum fault
current for a distribution substation is ~18 kA at 30 cycles
Requirements: The equivalent to 4/0 copper per the IEEE Fusing Chart is 19#940%.A typical maximum fault
current for a distribution substation is ~18 kA at 30 cycles