You are on page 1of 16

Whitepaper

IEC 61511 Based Design for Gas Detection Systems


Monitoring Hydrocarbon Storage Tank Systems
Srinivasan N. Ganesan, M.S., P.E. MENA Region Manager, Kenexis DMCC, Dubai, UAE
Edward M. Marszal, PE, ISA 84 Expert

ABSTRACT
The design of hydrocarbon gas detection systems using risk analysis methods is drawing a lot of attention because
industry experts have come to a consensus that design codes used in traditional gas detection system design work are
not sufficient for open-door process areas having serious hazards, such as fire, flammable gas and toxic gas. The ISA
Technical Report TR 84.00.07 provides guidelines for the design of fire and gas systems in unenclosed process areas in
accordance with the principles given in IEC 61511 standards. This paper presents an overview of the design of gas
detection systems using risk assessment methods that are described in the ISA technical report. These methods
are statistical in nature and are used to assign and verify targets for the performance metrics (detector coverage and
safety availability) of gas detection systems. This paper also provides an overview of the performance based safety life
cycle of gas detection systems from conceptual design stage to operations and maintenance.

1. INTRODUCTION
Risk assessment techniques are being increasingly used in the design of engineered safeguards, such as Fire and Gas
Detection and Suppression Systems (FGS), Safety Instrumented Systems (SIS) and Alarm Systems. The principles of
risk assessment used in the design of SIS can also be used in the design of Gas Detection Systems. A Gas Detection
System is a type of instrumented safeguard intended to reduce risks posed by process plants, such as safety risk,
environmental risk, and asset risk (commercial/business) to tolerable levels. However, gas detection systems are
only capable of mitigating the consequence of a loss of containment, whereas safety instrumented systems are
capable of preventing the consequence from occurring altogether.

All automated safety systems such as FGS, SIS, and High Integrity Pressure Protection Systems (HIPPS) need a “basis
of safety” for the selection and design of its functional elements (sensor, logic solver and final control elements). In
the design of Gas Detection Systems, it is important to select detectors of the appropriate technology and care must
be taken to position the right number of detectors at the correct location for the system to respond on demand. In
addition, the basis of safety specifies the mechanical integrity requirements for the equipment with respect to the type
and frequency of preventive maintenance tasks required. In short, the basis of safety is at the core of decisions that are
made with reference to selection and maintenance of instruments.

The two options for choosing basis of safety are – prescriptive and performance-based. Prescriptive basis of
safety (such as NFPA 72 and EN 54 for fire alarming equipment) specifies the type of equipment, its location for
installation and also addresses the requirements to maintain them. Not only do the prescriptive standards for FGS
design provide a very comprehensive set of rules for designing equipment, but they are also so well established
for the design of fire alarm systems that they are often employed, at least, for the signaling portion of gas detection
Whitepaper

systems. These standards have evolved to be very effective for the fire alarms in occupied buildings, such as office
buildings, hospitals, and schools, but often fall short for gas detection and even for fire detection in open process
areas.

Prescriptive standards provide detailed requirements for basis many gas and fire system applications. However,
they do not provide detailed requirements for gas detection in open-door areas, such as chemical process units
and hydrocarbon storage tank farms. Some of the gas detection system elements (sensor, logic solver, final control
element) typically found in chemical process facilities are not adequately covered by these prescriptive standards. In
addition, they do not provide an optimal solution to deal with the hazards associated with process facilities, such as oil
refineries and petrochemical plants. Specifically, they are not geared towards hazards such as, combustible hydrocarbon
gases and toxic gases. As a matter of fact, toxic gases are completely unaddressed by these prescriptive standards, and
combustible gases only slightly.

It is worthwhile to point out that the institutions that developed these prescriptive standards are cognizant of their
shortcomings and therefore allow the use of performance-based basis of safety in areas where the users of the
standards believe that the prescriptive guidance is ineffective. Performance-based standards use risk assessment
techniques for decisions involving selection, design, and maintenance of gas detection systems. The intent of the
performance-based approach is not to replace the prescriptive method, but to supplement it where prescriptive
methods are ineffective.

Industry practitioners recognized the need for more guidance for performance-based design for gas detection systems
and came to a consensus that this guidance has to come from a standards organization like the International Society
of Automation (ISA). ISA Standards Panel 84 created a special working group called “working group 7” specifically to
address performance-based design of fire and gas systems. The ISA Technical Report TR 84.00.07 that came out of the
working group 7 provides guidelines for fire and gas systems in accordance with the principles provided in IEC 61511
standards. The Technical Report TR84.00.07 has generated considerable interest among oil & gas operating companies
and EPC companies and it jumpstarted the application of risk assessment techniques to design fire and gas detection
and suppression systems.

The basis of the IEC 61511 standard is to specify targets for performance metrics for each safety instrumented function
that is protecting the plant from process-related risks. The target is selected based on the risk associated with the
hazard that the safety instrumented function is intended to prevent. Gas detection systems pose challenges when trying
to use risk analysis techniques that are compliant with ISA84/IEC 61511 standards for safety instrumented systems.
The hazards associated with gas detection systems (especially as applied in the chemical process industries) are general
in nature and it is difficult to characterize them in the context of layer of protection analysis (LOPA). Initiating events
caused by leaks due to corrosion, erosion, and other physicochemical forces are not included in LOPA. Although the
concept of probability of failure on demand is applicable to gas detection system functions, component equipment
failures are not the only consideration and usually not even the most important. The inability of a gas detection
system function to detect a gas leak because of lack of coverage can also lead to failure on demand. Recent data from
the UK North Sea area indicate that more than 30% of major gas releases were not detected by automated systems.
The ISA 84 working group 7 determined that a gas detection system can be designed similar to a SIS if detector
coverage is considered as an additional performance metric. In addition to assigning targets for safety availability
Whitepaper

(equivalent to SIL), targets for detector coverage need to be assigned for gas detection systems so that the verification
and validation of detector coverage is required in the gas detection system design.

2. FIRE AND GAS DESIGN LIFE CYCLE


The safety life cycle defined in the ISA Technical Report TR84.00.07 for fire and gas systems is very similar to the one
defined for safety instrumented systems in the IEC61511 standard. Risk scenarios must be identified before fire
and gas systems can be selected for a particular application. The hazards and consequences associated with each
scenario must be analyzed taking into account the impact on human lives and assets. It is also important to consider the
frequency of occurrence of the consequence while making decisions on the fire and gas system. If it is anticipated that
the consequence will occur quite frequently, then a more rugged risk mitigation system needs to be considered.

A risk assessment is performed before making a decision on the need for a fire and gas system. If the unmitigated
risk is tolerable, there would be no design for a fire and gas system. If the unmitigated risk is not tolerable,
recommendations would be made to design a fire and gas system to reduce the overall risk to tolerable levels.

If a decision is made to install a fire and gas system, the initial design is typically done using heuristics (rules of thumb).
The ISA Technical Report TR 84.00.07 proposes that the procurement and installation of fire and gas systems should
not immediately follow the initial design. Instead, the technical report suggests that the coverage provided by the
detector layout in the initial design be calculated and verified to check if it meets its target. In addition to the coverage,
the safety availability (equivalent to SIL) for each function should be calculated and verified in a way identical to
verifying the SIL of a safety instrumented system in accordance with the IEC 61511 standard. The typical work flow in
the safety life cycle of performance-based fire and gas system design is shown in Figure 1.

2.1. Identify Gas Detection System Requirements


The first step in the FGS safety life cycle is identifying the need for a gas detection system. The need for a gas detection
system usually stems from risk assessment studies, such as PHA, HAZOP, and “What-if”-checklist. Typically, the study
team would come to a qualitative consensus that the unmitigated risk is not tolerable and would recommend the
implementation of a gas detection system for mitigating the risk to tolerable levels. Even sem-quantitative risk analysis
techniques like layer of protection analysis (LOPA) often recommend the implementation of fire and gas systems.
And finally, a lot of jurisdictions around the world mandate the creation of safety cases that include quantitative risk
assessment (QRA) studies in plant design as a pre-requisite to issue an operational permit for the facility.
Whitepaper

Figure 1. Typical work flow in the safety life cycle of performance-based FGS

If a QRA study has been the basis for an operational license from an authority, the process facility needs to have
a gas detection system in place whose performance is in accordance with the assumptions made in the QRA study –
otherwise, the basis for the safety case and operational permits are invalid. In addition, industry best practices and
corporate HSE policies often require gas detection systems to be implemented in a process facility to mitigate risk. Last
but not the least, insurance companies often require a fully functional fire and gas system as a pre-requisite to insure the
facility.

2.2. Gas Detection System Philosophy Development

Once the need for a gas detection system has been established, the next step in the safety life cycle is the development
of a gas detection system philosophy document (which often incorporates requirements for fire detection as well as gas
detection). Efforts should be directed towards the creation of a comprehensive fire and gas philosophy that would be
the basis for making decisions involving the design of fire and gas systems. The fire and gas system philosophy would
define the tools, techniques, policies, and procedures surrounding fire and gas system design. The document, compliant
with the IEC 61511 standard and ISA Technical Report 84.00.07, is developed once, most likely at the corporate level, so
the philosophy can be applied to all fire and gas systems within the organization. In other words, it provides a common
framework for making decisions involving fire and gas systems throughout the organization.
Whitepaper

The intent of the fire and gas philosophy document is to standardize the methods that will be used in identifying the
hazards the fire and gas systems intend to protect against. Hazards will be identified based on criteria such as properties
of material being processed (flammability, reactivity, toxicity), and process conditions (pressure, temperature). The
philosophy document will have the list of requirements for the safety analysis that is going to be performed. In addition
to setting up the methods and procedures for designing fire and gas systems, there will be criteria for various design-
related tasks, such as zone definition, and zone grading. There will also be criteria for assigning

targets for performance metrics (detector coverage and safety availability) and criteria for choosing the appropriate
technology for detectors and voting architecture for detection equipment.

2.3. Gas Detection System Zone Definition and Categorization

The next step in the life cycle is zone definition, which requires a thorough understanding of the process being analyzed.
Technical documentation such as process flow diagrams, piping & instrumentation diagrams, cause & effect diagrams,
and plot plans would aid in the understanding of the facility being studied. The process starts out by identifying zones
within the entire plant area. Zones are small areas that are geographically limited so that specific mitigation actions
could be taken depending upon the hazard present within the particular zone.

It is worthwhile to point out why zone definition is critical to the safety life cycle. Different areas in a process plant
have different gas release hazards. Some process units such as amine treatment units and sulfur recovery units pose a
H2S toxic gas hazard. Some areas may be prone to pool fires while others may be prone to gas releases or gas jet fires.
Therefore, it becomes important to define and segregate the zones from each other.

Finally, the definition of zones will assist plant operations personnel trained in hazard communication to respond
effectively to an emergency situation. In a fire or gas release scenario, operations personnel will be forced to shut down
process units and bring them to a safe state as a proactive measure to mitigate the consequence. Emergency response
action plans in a process facility are developed with a good understanding of the nature and location of the hazards.

The definition and categorization of zones in a typical process facility are shown in Figure 2. The categorization of zones
is necessary to select the appropriate mitigation techniques and actions for each particular zone. The different zone
categories such as H, N, G, E, T, and V define different attributes of a process area. The first type of zone is type H
which would include hydrocarbon process areas having fire and combustible/toxic gas hazards. The second type
of zone is type N which would also include process areas, but with non-hydrocarbon fire hazards. The area with non-
hydrocarbon fire hazard is not grouped into type H zone because the detection and suppression equipment for non-
hydrocarbon-related fires is different from those of hydrocarbon-related fires.
Whitepaper

Figure 2. Definition and categorization of zones

The third type of zone is type G which would include occupancy areas, such as control rooms, maintenance workshops,
and administrative offices that are normally occupied by people and no chemical processing occurs inside them.
The fourth type of zone is type E which would include non-hydrocarbon special equipment protection areas like
instrument control rack rooms that house unrated electrical equipment and pose an explosion hazard if flammable
gases were to enter the zone.

The fifth type of zone is type T which includes gas turbine enclosures and engine enclosures for which the fire and gas
equipment requirements are very specific and stringent. The sixth and final zone type is type V which includes air intake
ducts of occupied buildings in close proximity to a hydrocarbon process area. Type V zone is similar to type E zone from a
standpoint of detecting flammable and toxic gases entering occupied buildings through an air intake system.

The third type of zone is type G which would include occupancy areas, such as control rooms, maintenance workshops,
and administrative offices that are normally occupied by people and no chemical processing occurs inside them.
The fourth type of zone is type E which would include non-hydrocarbon special equipment protection areas like
instrument control rack rooms that house unrated electrical equipment and pose an explosion hazard if flammable
gases were to enter the zone.

The fifth type of zone is type T which includes gas turbine enclosures and engine enclosures for which the fire and gas
equipment requirements are very specific and stringent. The sixth and final zone type is type V which includes air intake
ducts of occupied buildings in close proximity to a hydrocarbon process area. Type V zone is similar to type E zone from a
standpoint of detecting flammable and toxic gases entering occupied buildings through an air intake system.
Whitepaper

Figure 3. Typical zone list for a process area

The result of the zone definition task is a zone list that is shown in Figure 3. Each zone will be identified by a specific tag
number defining the zone along with a brief description of the zone’s location and its contents. The zone list will also
show the category (as mentioned above) along with the attributes why that category was chosen for that particular
zone. The zone list is entered into a database called the FGS design basis toolkit for managing the zones.

2.4. Setting and Verifying Performance Targets

Once all the zones are identified, targets for detector coverage and FGS safety availability (for FGS functions) in
each zone need to be assigned consistent with the corporate philosophy on fire and gas system design. The detector
coverage for the initial design will be calculated using quantitative models and will be verified to check if it meets
its target. Similarly, the FGS safety availability (equivalent to SIL) for the functionality in each zone will be
calculated and verified using conventional SIL verification techniques laid out in the IEC61511 standard.

If it is determined that the performance metrics fail to meet their target, the initial fire and gas system design will be
revised by making changes to the number and position of detectors. The

verification calculations are rerun on the revised design and this recursive process continues until the performance
metrics meet their target.

Assigning Detector Coverage

For the fire and gas detector coverage, the ISA Technical Report TR 84.00.07 identifies two types of coverage
assessment methods – scenario coverage and geographic coverage.

Scenario coverage is defined as the fraction of the release scenarios that would occur as a result of the loss of
Whitepaper

containment in a defined and monitored process area that can be detected by release detection equipment considering
the frequency and magnitude of the release scenarios and the defined voting arrangement.

Geographic coverage is defined as the fraction of the geometric area (at a given elevation of analysis) of a defined
monitored process area which, if a release were to occur in a given geographic location, would be detected by the
release detection equipment considering the defined voting arrangement.

Consistent with the above definitions from the ISA Technical Report, there are two common methods for assigning
targets for detector coverage – fully quantitative and semi quantitative. In the fully quantitative method, the targets for
detector coverage are calculated using rigorous mathematical models that estimate the likelihood of an event
and the magnitude of the consequence if that event were to occur. A consequence such as a gas release would be
modeled using dispersion modeling techniques to determine the size and location of the gas cloud. In addition,
fire and explosion models will be used to determine the impact on human lives and property if the gas cloud were
to ignite and explode.

Unlike a safety instrumented system, a gas detection system can only mitigate the consequence but cannot prevent the
initiating event from happening. Initiating events (such as a gas release) caused by factors such as welded joint failure,
pipe/equipment corrosion, and gasket failure cannot be adequately addressed during a risk analysis study like HAZOP.
It is therefore not possible to plan ahead for a consequence of this nature and the frequency of occurrence cannot be
calculated based on a familiar matrix of initiating events. Instead, historical failure data of equipment will be used to
estimate leak rate. The leak size is assumed to follow a standard statistical distribution and the likelihood of occurrence
will be calculated using the estimated leak rate and leak size.

Once the parameters are estimated, a risk integration task is carried out integrating the consequence and
likelihood to generate a list of possible scenarios. Each scenario will be associated with a certain risk level and it will
be modeled using event trees. The risk posed by each scenario will be modified taking into account various mitigating
factors, such as ignition probability, explosion probability, occupancy probability, and mitigation effectiveness. The
individual risk associated with hundreds of thousands of scenarios in each zone will be integrated using a risk
integration tool (event tree) like the one shown in Figure 4.

The semi quantitative approach is similar with respect to level of analysis effort to LOPA (layer of protection analysis)
used in SIS design where tables with orders of magnitude in risk parameters are used to establish performance
requirements. The semi quantitative techniques need to be calibrated

in order to ensure accuracy of the results. It is a team-based risk analysis of a fire and gas zone using calibrated risk
assessment tables.
Whitepaper

Figure 4. Risk integration using event tree for scenario coverage

The likelihood of an event (based on type of equipment in the zone), magnitude of the consequence (based
on process parameters such as temperature, pressure and material composition), and mitigating factors (such as
occupancy and ignition sources) are considered in determining the level of risk, utilizing a process similar to a risk graph.
Grades are assigned inside each zone using a risk graph or a risk matrix that is developed for this purpose. Figure 5
shows a typical example of the different grades that could be used inside a zone and the associated level of risk along
with targets for the performance metrics (detector coverage & safety availability).
Whitepaper

Figure 5. Zone grades and associated level of risk

The performance target assigned to each grade in a zone is intended to make the risk tolerable for that particular zone.
In the table shown in Figure 5, the risk associated with Grade A is the highest and the risk associated with Grade C
is the lowest. Therefore, it is prudent to assign 90%

geographic coverage and 95% safety availability for Grade A and 60% geographic coverage and 90%
safety availability for Grade C to reduce risk to tolerable levels.

It is important to note that a detailed and comprehensive calibration of the tables containing the performance targets
is essential to the dependability and reliability of the semi-quantitative approach. A fully quantitative risk analysis
is performed on typical process zones that have been assigned performance targets and zone grade and the
magnitude of risk reduction is determined. The data from this analysis is used to develop an empirical model that
is the backbone for this approach. The calibration technique is going to be based on geographic coverage as opposed
to scenario coverage because of the strong positive correlation between these two coverage methods. In addition,
geographic coverage is significantly easier and less expensive to determine than scenario coverage.

In addition to selecting different grades within a zone, it is also important to define boundaries for the different graded
areas within that particular zone. In other words, one can conveniently assume that the hazards do not exist outside the
graded areas in any particular zone. As mentioned earlier, the criteria for assigning grades within a zone must be
available in the FGS philosophy document. The assignment of the extents of a graded area is done in a very similar
fashion to electrical area classification, where potential leak sources are identified and areas within a certain distance
of those sources are set off as “graded”. While performing a geographic coverage assessment, the calculations are
limited only to the graded areas and not to the entire zone.

Figure 6 shows the extent of grading and the geographic coverage for a typical process zone. The geographic coverage
shown on the right is a color-coded map where red indicates that no detectors can detect the hazard, yellow means
that only one detector can detect the hazard and green indicates that two or more detectors can detect the
hazard. The visual map may also be supplemented with tables indicating percentage of the geographic area with no
coverage, coverage by one detector and coverage by two or more detectors.
Whitepaper

Figure 6. Extent of grading and geographic coverage in a process zone

Verifying Detector Coverage

After assigning the targets for detector coverage, the next step is to verify the fire and gas system detector coverage.
The verification is based on factors such as zone definition, performance targets, and approved procedures for
performing coverage calculations. The result of this analysis will be a visual fire and gas map that is a color-coded
representation of the areas covered and the extent of coverage of each area.

The performance of the detector plays a major role in a gas detector mapping assessment and it is usually provided
by the equipment manufacturer. When performing a gas detector mapping assessment one needs to consider
many attributes of the zone in consideration, the first consideration would be the performance of the detector.
Subsequently, the size and shape of the gas release needs to be considered relative to the location of the detection
equipment. When employing geographic coverage, the analyst sets the size of a “design basis” cloud, usually by
determining the minimum gas cloud size that could result in a significant consequence (often, 4, 5 or 10 meters in
diameter, depending on the situation). This design basis cloud is the moved around the zone that is under analysis. For
each point in the zone, the ability of each individual detector to detect the design basis cloud if it were centered
at that point is determined, fully in three dimensions. For scenario coverage, each potential release (considering
multiple hole sizes, multiple release orientations and multiple wind directions) is plotted, and then each detector is
assessed to determine if it would detect that release. The methods for gas detection coverage analysis are visually
described in Figure 7.
Whitepaper

Figure 7. Gas Detection Mapping Technique Illustration

The geographic fire detector coverage for an example gasoline storage area with a few export pumps is shown in Figure
8. In this geographic coverage figure, green indicates coverage by two or more detectors, yellow indicates coverage by a
single detector, and red indicates no coverage. It is also important to note that the areas containing equipment and vessel
internals are eliminated from the coverage calculations.

Figures 9 and 10 show geographic risk profiles that result from the more rigorous quantitative risk analysis process and
associated scenario coverage assessment. The first result (Figure 9) shows the unmitigated risk, or the risk assuming that
there is no gas detection system in place.

Figure 8. Geographic Coverage of a Typical Gasoline Tank Area

The geographic risk profile in a zone is represented using the visible color spectrum, where a color indicates the frequency
of a gas release (or a fire release) existing at that specific location. At any particular location, colors on the right side of
the visible color spectrum indicate high likelihood of a gas release or fire and colors on the left side of the visible spectrum
indicate low likelihood of a gas release or fire.
Whitepaper

Figure 9. Geographic Risk Profile (Unmitigated by Gas Detection)

Figure 10 presents the mitigated geographic risk profile that includes risk reduction by the gas detection system. In this
case, the gas system comprises of two point detectors on the left side of the tank and an open path detector between
the tank and the associated transfer pumps. The graph contains colors predominantly on the left side of the visible color
spectrum indicating that the risk has been substantially reduced. This figure is drawn, once again, by considering all of
the leaks that are possible, but instead of plotting all of the gas clouds, only the gas clouds that are not detected by

the gas detection array are plotted. In addition, a calculation of the fraction of releases that are detected is calculated.
This detection fraction is the scenario coverage, which can subsequently be used in the risk integration event tree.

Figure 10. Geographic Risk Profile (Unmitigated by Gas Detection)

FGS Safety Availability


As discussed earlier, performance targets for safety availability need to be assigned and verified along with
the detector coverage. The ISA Technical Report TR 84.00.07 specifically defines the metric in terms of safety
availability in lieu of safety integrity level (SIL) because it was believed that assigning safety integrity level would be
inappropriate for fire and gas systems. The effectiveness of a fire and gas system to respond on demand is primarily a
function of the detector coverage rather than the ruggedness of hardware elements. The detector coverage has to be
extremely high (99%) in order for the difference between SIL 2 and SIL 3 probability of failure to be of any significance.
Whitepaper

During the conceptual design of the fire and gas system, FGS safety functions are defined and targets for safety
availability are assigned in accordance with the guidelines given in the FGS philosophy document. The fire and gas
detection equipment selected to achieve the performance target must meet both the general and specific requirements
specification as applied to the overall system.

The factors that influence the FGS functions ability to achieve the target are component selection, fault tolerance,
functional test interval, effect of common cause failures, and the diagnostic coverage of devices in the loop. All
these variables are used in the calculations to verify if the specified safety availability target has been achieved. The
safety availability verification calculations are identical to the SIL calculations done for safety instrumented systems
and are based on the equations contained in the ISA Technical Report TR84.00.02.

The verification calculations are done using a customized tool kit that is developed from the equations given in the ISA
Technical Report TR84.00.02. As an option, the verification calculations can also be performed manually using the same
equations with the aid of a software application.

2.5. Gas Detection System Safety Requirements Specification

The next step in the gas detection system life cycle is to generate the gas detection system safety requirements
specification (SRS) for the system. The safety requirements specification is a comprehensive document that includes
detector placement drawings, cause & effect diagrams and general requirements on the attributes of the gas detection
system.

After verifying the safety availability of all the functions, the final design needs to be documented in a safety
requirements specification (SRS). The SRS defines how the gas detection system will perform and it is essentially
the basis for the design and engineering of the FGS equipment. It contains not only the functional specification that
defines the design basis but it also contains integrity specifications that define the system in terms of its performance
metrics (detector coverage and safety availability). The FGS requirements specification provides the functional
specification of the FGS logic solver which could be either take the form of cause and effect diagram or a binary logic
diagram. The IEC 61511/ISA 84 standards provide guidelines and a checklist for the items that must be part of the FGS
requirements specification.

2.6. Detailed Design & Procedure Development

The next step in the gas detection system design life cycle involves the detailed design and engineering of the
system. This step involves a variety of tasks such as loop sheet development, internal wiring diagram preparation, cable
schedule drawing development, and PLC (logic solver) programming. Along with the detailed design and engineering,
procedures are also developed for the fire and gas system for various phases of the life cycle, such as start-up,
operations, maintenance, and de-commissioning. It is quite likely that design shortcomings may be discovered during
procedure development and this may trigger the need to revisit the initial steps of the safety life cycle and make changes
to include provisions for bypasses and resets without having to take the system offline. If a hardware component in the
fire and gas system fails, the failed component must be detected and repaired within the mean-time to repair (MTTR)
that was assumed during the design phase and system maintenance procedures must clearly address repairs of this
Whitepaper

nature that have an impact on the facility’s tolerable risk level. Finally, the functional testing of the fire and gas system
needs to be carried out on a periodic basis and procedures need to be developed for the same.

2.7. Procurement, Construction & Installation

The next step in the fire and gas system life cycle involves the procurement, construction and installation of the
equipment that has been engineered. Physical hardware such as, instrumentation cabinets, cables, fire detectors, and
gas detectors will be purchased and installed on site. It is recommended that caution be exercised during the installation
of field equipment for gas detection systems because the location and orientation of the detection equipment has a
profound impact on the system’s ability to achieve tolerable risk. The location and orientation of the detectors must be
consistent with the values given in the safety requirements specification. Furthermore, the

placement of equipment with respect to the detectors must be consistent with the assumptions made during the
design phase. Upon successful completion of the hardware installation, the software is installed into the system and
the logic solver is custom programmed for the facility.

2.8. Pre-Startup Acceptance Testing (Validation)

The IEC 61511 standard requires that automated safety systems like gas detection systems be validated before
they can be turned over to operations and maintenance. Validation is the task of verifying the installation of gas
detection system equipment and software programming to check if the installation is conformance with both the safety
requirements specification and the detailed engineering documentation. Validation involves a complete physical
test of all safety critical functions starting from the field all the way to the plant control room. The deviations discovered
during this step will be documented in a record called “punch list” and the items in the punch list need to be satisfactorily
resolved before the system can be handed over to plant personnel.

2.9. Operations, Maintenance & Testing

Once the validation is completed, the system is turned over to operations and maintenance for day-to-day operations,
which include simple things such as responding to alarms, responding to failure alarms, and periodic functional testing
and preventive maintenance to ensure that performance levels that were specified during design are being achieved
round-the-clock throughout the life cycle of the facility. During the normal operation and maintenance phase of the
life cycle, periodic function testing and maintenance need to be carried out to ensure that the targets for the
performance metrics (detector coverage and safety availability) are still achieved.

2.10. Management of Change (MOC)

During the life cycle of the facility, any changes made to the facility or to that of the fire and gas system need to be
considered in the safety life cycle to make sure that the change(s) do not affect the performance of the system. It is not
unusual for a facility to go through a wide range of changes such as retrofitting equipment, adding new pumps, building
new structure, etc. These changes may increase the number of leak sources, change zone definition and may also change
the categorization of the zone discussed earlier. It is also possible that these changes may obstruct the ability of gas
Whitepaper

detection equipment and may compromise the achieved detector coverage. It is therefore very important to make sure
that the facility’s management of change procedures includes step-by-step instructions to review changes that have an
impact on the gas detection system. If it is determined that changes will impact the performance of the gas detection
system, the appropriate steps in the safety life cycle of the system needs to be revisited and design must be revised.

3. CONCLUSION

Risk assessment methods are being increasingly used in the design of instrumented safeguards, such as SIS, Alarm
Systems, HIPPS, etc. Gas detection systems are no exception to this trend. However, gas detection systems are
only capable of mitigating the consequence, whereas safety instrumented systems are capable of preventing the
consequence from occurring – which greatly complicates their analysis. The hazards associated with fire and gas
systems are general in nature and it is difficult to characterize them in the context of layers of protection analysis
(LOPA). Initiating events caused by pipe leaks due to corrosion, erosion, and other physicochemical forces are typically
not included in LOPA.

The ISA Technical Report TR 84.00.07 provides recommendations for the design of gas detection systems in open-door
chemical process areas having serious hazards. The technical report proposes that an FGS be designed similar to a
SIS if detector coverage is considered as an additional performance metric. This paper has provided an overview
of the risk-assessment methods used in the design of fire and gas systems and has described the methods available
to assign and verify targets for the performance metrics. This paper also provides a roadmap of the steps involved
the safety life cycle of a gas detection system explaining how each step is interconnected with the other and why it is
important to follow a holistic approach to the design of automated systems in a safety critical environment.

REFERENCES

1. ISA TR84.00.07 “The Application of ANSI/ISA 84.00.01 – 2004 Parts 1-3 (IEC 61511 Parts 1-3
Modified) for Safety Instrumented Functions (SIFs) in Fire & Gas Systems” Version A, October 2007.

LifeCycle Safety Solutions Life Safety Products Enterprise Mobility Systems


Empowering our clients to Unparalleled sales, service and support — LoneWorker and ManDown solutions
adopt the ISA 84.00.07 safety system fixed point, wireless, transportable, or engineered for the Oil & Gas Industry
design standard and the latest personal monitoring and a range of ancillary combined with a customizable suite
F&G mapping software tools to identify safety products; our experts are ready of wireless Voice/Text/Data services
risks that exist and develop a proactive to help solve your toughest flame powered by TELUS Mobility on the
FGS lifecycle philosophy. and gas detection challenge. latest hazardous area smart mobile devices.

You might also like