JXCP1-TF2Z197EN

2 Specifications (continued) 4 Installation 4 Installation (continued)


ORIGINAL INSTRUCTIONS 2.2 PROFINET specifications 4.1 Installation • Do not connect multiple wires to one connector terminal.
Item Specification Warning Power Supply Connector
Instruction Manual Protocol PROFINET (Version 2.32) • Do not install the product unless the safety instructions have been read Wire the power supply cable to the power supply plug connector, then
IP address setting 0.0.0.0 to 255.255.255.255 and understood. insert it into connector PWR on the controller.
Step Motor Controller - PROFINET range (set using DHCP server) • Design the installation so that the temperature surrounding the • Use special screwdriver (Phoenix Contact No. SZS0.4×2.0) to open /
(24 VDC Servo) Communication speed 100 Mbps controller is 40oC max. Leave enough space between the controllers close lever and insert the wire into the connector terminal.
Communication Full duplex/ Half duplex (automatic
so that the operating temperature of the controllers remains within the • Applicable wire size: 20 AWG (0.5 mm2).
Series JXCP1#-# method negotiation) specification range.
• Mount the controller vertically with 30 mm minimum space on the top
Standard Ethernet cable
Communication cable and bottom of the controller as shown below.
(STP, CAT5 or higher, 100BASE-TX) Power supply connector.
• Allow 60 mm minimum space between the front of the controller and a
Setup file GSDML file SMC Part No. JXC-CPW.
The intended use of the step motor controller is to control door (lid) so that the connectors can be connected and disconnected.
the movement of an electric actuator while connected to Occupied area Input 36 byte / Output 36 byte Phoenix Contact Part No:
10 mm minimum
the PROFINET communication protocol.. Connectable nodes Max. 65,535 nodes DFMC1,5/3-ST-LR
(for actuator body size 25 mm or more)
Vendor ID 83h (SMC Corporation)
1 Safety Instructions
Device ID 0Fh
These safety instructions are intended to prevent hazardous situations
Pin
and/or equipment damage. These instructions indicate the level of Terminal Function Description
Warning No.
potential hazard with the labels of “Caution,” “Warning” or “Danger.” 30 mm minimum
They are all important notes for safety and must be followed in addition Special products (-X) might have specifications different from those 1 C24V Power supply (+) Positive control power.
to International Standards (ISO/IEC) *1), and other safety regulations. shown in this section. Contact SMC for specific drawings. Positive power for the
IEC 60204-1: Safety of machinery - Electrical equipment of machines. 2 M24V Motor power (+) actuator motor supplied
(Part 1: General requirements) 3 Name and function of individual parts via the controller.
ISO 10218-1: Robots and robotic devices - Safety requirements for Positive power for
3 EMG Stop (+)
industrial robots - Part 1: Robots. emergency stop signal
Controller
• Refer to product catalogue, Operation Manual and Handling Negative common power for
Precautions for SMC Products for additional information. 4 0V Common power (-) M24V, C24V, EMG and LK
• Keep this manual in a safe place for future reference. RLS.
5 - NC Not connected
Caution indicates a hazard with a low level of risk which, if
Caution
not avoided, could result in minor or moderate injury. 6 LK RLS Unlocking (+)
Positive power for lock
release.
Warning indicates a hazard with a medium level of risk 30 mm minimum (direct mounting)
Warning
which, if not avoided, could result in death or serious injury.
50 mm minimum (DIN rail mounting)
Danger indicates a hazard with a high level of risk which, if
Danger
not avoided, will result in death or serious injury.

4.2 Mounting Wiring specifications


Warning • The controller can be direct mounted (model JXCP17#) using 2 x M4 Prepare the electrical wiring according to the following specifications (to
• Always ensure compliance with relevant safety laws and screws or mounted on a DIN rail (model JXCP18#). be prepared by the user).
standards. • When using DIN rail mounting, hook the controller on the DIN rail and
• All work must be carried out in a safe manner by a qualified person in press the lever down to lock it. Item Specifications
compliance with applicable national regulations.
Caution Single, stranded wire → AWG20 (0.5 mm2)
No. Name Description • The rated temperature of the insulation
If the mounting surface for the controller is not flat or is uneven, excessive Applicable wire size
2 Specifications 1 Display LED to indicate the controller status. coating should be 60oC or more.
stress may be applied to the enclosure, which can cause failure. Be sure
The O.D. should be ø2.5mm or less.
2.1 General specifications 2 PROFINET P1 / P2 Connect to the PROFINET network to mount on a flat surface.
Item Specifications Connector for the teaching box 4.3 Environment
Serial I/O connector
Compatible motor Step motor (servo 24 VDC) 3 (LEC-T1) or the controller Stripped wire length
(8 pin) SI Warning
communication cable (JXC-W2A-C).
Power supply voltage: 24 VDC +/-10%
Power supply Encoder connector • Do not use in an environment where corrosive gases, chemicals, salt
(motor drive control, stop, lock brake release) 4
(16 pin) ENC water or steam are present.
200 mA maximum (controller) Connections for actuator cable. • Do not use in an explosive atmosphere.
Motor power connector 4.5 Ground connection
Current consumption Refer to the actuator specifications for total 5 • Do not expose to direct sunlight. Use a suitable protective cover.
(6 pin) MOT • Place a ground cable with crimped terminal under one of the M4
power consumption. • Do not install in a location subject to vibration or impact in excess of
Connector for controller power mounting screws with a shakeproof washer and tighten the screw.
Compatible encoder Incremental A/B phase (800 pulse/rotation) the product’s specifications.
supply (24 VDC) using the power
Memory Eeprom Power supply • Do not mount in a location exposed to radiant heat that would result in Caution
supply plug.
Lock control Forced lock release terminal 6 connector temperatures in excess of the product’s specifications.
Control power (+), Stop signal (+), The M4 screw, cable with crimped terminal and shakeproof washer must
(6 pin) PWR
Motor power (+), Lock release (+), • Avoid mounting the controller near a vibration source, such as a large be prepared by the user.
Cable length Actuator cable: 20 m maximum
Common power (-) electromagnetic contactor or circuit breaker on the same panel. The controller must be connected to Ground to reduce noise. If higher
Cooling method Natural air-cooling • Do not use in an environment with strong magnetic fields present.
Applicable electric Label indicating the electric actuator noise resistance is required, ground the 0 V (signal ground). When
0°C to 40°C (version S1.*/S2.*/V1.*/V2.*)
Operating 7 actuator model number model number which can be 4.4 Wiring grounding the 0 V, avoid flowing noise from ground to 0 V.
0°C to 55°C (version S3.*/V3.* or later)
temperature
No freezing
label connected to the controller. • A dedicated Ground connection must be used. Grounding should be
Caution to a D-class ground (ground resistance of 100 Ω maximum).
Storage temperature -10oC to 60oC (no freezing) Label indicating the model number
8 Controller label • Do not perform wiring while the power is on. • The cross-sectional area of the ground cable shall be 2 mm2 minimum.
of the controller.
Operating humidity 90% RH or less (no condensation) • Confirm proper insulation of wiring. • The Grounding point should be as near as possible to the controller.
9 MAC address Label to indicate MAC address
50 MΩ (500 VDC) • Do not route wires and cables together with power or high voltage Keep the grounding cable as short as possible.
Insulation resistance Functional Ground
between external terminals and case cables.
(When the controller is mounted,
220 g (Direct mounting type) 10 FE connection • Keep wiring as short as possible to prevent interference from
Weight tighten screws and connect the
240 g (DIN rail mounting type) electromagnetic noise and surge voltage.
grounding cable).
• Do not use an inrush current limited type of power supply for the
controller.
Page 1 of 2
JXCP1-TF2Z197EN
5 Setting 7 How to Order
5.1 Initial Setting Refer to the catalogue on the SMC website (URL:
• Appropriate setting is required in order to establish the communication https://www.smcworld.com) for the How to Order information.
of the controller (JXCP1) on the PROFINET network.
• Please refer to the PLC setting software "SIMATIC Manager Version
5.5 (STEP7) for the representative PROFINET master device. 8 Outline Dimensions (mm)
• The required setting method such as the GSDML file installation varies Refer to the drawings / operation manual on the SMC website (URL:
depending on which setting software will be used, so if software other https://www.smcworld.com) for outline dimensions.
than STEP7 is used, please refer to the operation manual of the
applicable setting software.
In order to move the electric actuator to a specific position, it is necessary 9 Maintenance
to set up the patterns of operation with a PC using the controller setting 9.1 General Maintenance
software or by using a teaching box. This set up data will be recorded in
Caution
the memory of the controller.
• Not following proper maintenance procedures could cause the product
Refer to the Operation Manual on the SMC website (URL:
to malfunction and lead to equipment damage.
https://www.smcworld.com) for further setting details.
• Before performing maintenance, turn off the power supply. Check the
voltage with a tester 5 minutes after the power supply is turned OFF.
5.2 Configuration • If any electrical connections are disturbed during maintenance, ensure
• A GSDML file and icons file are required to configure the controller. they are reconnected correctly and safety checks are carried out as
The latest GSDML file can be downloaded from the SMC website required to ensure continued compliance with applicable national
(URL: https://www.smcworld.com). regulations.
• Do not make any modification to the product.
• Do not disassemble the product, unless required by installation or
6 LED Display maintenance instructions.
Refer to the table below for the LED status. Caution
LED Details • Maintenance should be performed according to the procedure
OFF Power is not supplied indicated in the Operation Manual.
Power supply • When equipment is serviced, first confirm that measures are in place
PWR Green LED is
status. Power is supplied to prevent dropping of work pieces and run-away of equipment, etc,
ON
then cut the power supply to the system. When machinery is restarted,
OFF Normal operation check that operation is normal with actuators in the correct position.
Controller alarm
ALM Red LED is
status. Alarm generated
ON Warning
OFF Normal operation • Perform maintenance checks periodically.
Controller • Confirm wiring and screws are not loose. Loose screws or wires may
SF Red LED is Alarm generated (Linked to
status.
ON ALM)
PROFINET communication
OFF cause unexpected malfunction.
is established.
PROFINET • Conduct an appropriate functional inspection and test after completing
Red LED is PROFINET communication
BF communication maintenance. In case of any abnormalities (if the actuator does not
flashing is not established.
status move, etc.), stop the operation of the system. Otherwise, an
Red LED is Both Port1 and Port2 are unexpected malfunction may occur and it will become impossible to
ON not connected. ensure safety. Operate an emergency stop instruction to confirm safety.
• Do not put anything conductive or flammable inside of the controller.
Refer to the table below for the LED and controller status • Ensure sufficient space around the controller for maintenance.

LED
Controller status 10 Limitations of Use
PWR ALM SF BF
Green 10.1 Limited warranty and Disclaimer/Compliance Requirements
LED is
When power is supplied LED is - - Refer to Handling Precautions for SMC Products.
OFF
ON
When PROFINET LED is LED is
- -
communication is normal OFF OFF 11 Product disposal
Controller Red Red This product shall not be disposed of as municipal waste. Check your
LED is
alarm LED is LED is -
OFF local regulations and guidelines to dispose of this product correctly, in
generated ON ON
order to reduce the impact on human health and the environment.
Controller Green Red
Motor
system error LED is LED is - -
controller
generated ON ON
Writing to Green
controller LED is - - - 12 Contacts
Eeprom flashing
Refer to www.smcworld.com or www.smc.eu for your local distributor /
importer.
Caution
Do not turn OFF the power supply for the controller or connect /
disconnect the cable while data is being written to EEPROM (PWR LED
(green) is flashing). URL: https://www.smcworld.com (Global) https://www.smc.eu (Europe)
This is to avoid the possibility of incorrect / corrupt data (step data, SMC Corporation, Akihabara UDX15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101
parameter). 0021
Specifications are subject to change without prior notice from the manufacturer.