PELLET BURNER
Pell ECO series

TECHNICAL PASSPORT
INSTALLATION and OPERATION MANUAL
FOR AUTHORIZED INSTALLER / SERVICE SHOP

Version i0.2.1
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

2
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

TABLE OF CONTENTS
1. EXPLANATION OF SYMBOLS AND SAFETY INSTRUCTIONS ............................ 4
1.1. Explanation of symbols .................................................................................. 4
1.2. Requirements to burner installation room .................................................... 4
1.2.1. Instructions to burner installer ...................................................................... 5
1.2.2. Instructions to installation user ..................................................................... 5
1.2.3. Minimum clearances for installation and combustibility of construction .........
materials ....................................................................................................... 6
2. PRODUCT DESCRIPTION ................................................................................ 7
3. FUEL .............................................................................................................. 8
4. TRANSPORTATION OF THE BURNER ............................................................. 10
5. DELIVERY OF THE BURNER ........................................................................... 10
6. STORAGE OF THE BURNER ........................................................................... 11
7. MOUNTING OF THE BURNER ....................................................................... 11
7.1. Pellet burner connection to the fuel hopper and pellet auger ..................... 11
7.2. Connecting the burner to the mains power supply ...................................... 12
7.3. Trouble-shooting .......................................................................................... 14
8. BURNER OPERATING ................................................................................... 15
8.1. Ignition ......................................................................................................... 15
8.2. Burning ......................................................................................................... 15
8.3. Automatic cleaning system ........................................................................... 15
8.4. Installer prescriptions regarding burner servicing and maintenance ............ 15
8.5. Important recommendations for long-lasting and correct operation
of the boiler .................................................................................................. 16

9. CONTROL UNIT ............................................................................................. 16


9.1. Controller view. Explanation of buttons and indicators ................................ 16
9.2. User's menu ................................................................................................. 19
9.3. Installer's menu ............................................................................................ 21
10. SETTING OUTPUT MODES OF OPERATION OF THE PELLET BURNER ............ 26
10.1. Calibration of auger fuel feed rate ................................................................ 26
10.2. Burner output adjustment ............................................................................ 27
11. WARRANTY TERMS ...................................................................................... 28
12. TECHNICAL FEATURES OF PELLET BURNER PELL ECO ................................... 30
12.1. Elements of pellet burner ............................................................................. 30
12.2. Spare parts ................................................................................................... 31
12.3. Technical parameters .................................................................................... 32
13. RECYCLING ................................................................................................... 33
14. BINDING OF THE CONNECTORS .................................................................... 34
3
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

1. EXPLANATION OF SYMBOLS AND regulations must be observed:


SAFETY INSTRUCTIONS • local construction regulations on
installation, air supply and exhaust
1.1. Explanation of symbols gas extraction as well as chimney
CAUTION! - Important connection.
recommendation or warning • regulations and norms concerning the
concerning safety conditions during fitting of the heating installation with
installation and operation of the pellet safety devices.
burner
DANGER! - fault or improper use i Use only original BURNiT parts
may cause injury or be hazardous WARNING! Installation and
to life of humans or animals. setting the pellet burner should


FIRE HAZARD! - fault or improper be done by an authorized
installation and operation may specialist / service shop and must
follow the safety instructions
cause fire. and rules of operation.
INFORMATION - Important
information on the proper DANGER of intoxication,
suffocation.
operation of the product.
Inadequate inflow of fresh air
1.2. Requirements to pellet burner to the boiler room may result in
installation room dangerous leak of exhaust gases
during burner operation.
This manual contains important - Make sure the air inlets and
information for the safe and correct
installation, start-up and trouble-free
operation and maintenance of the pellet
 exhaust gas outlets are not
clogged or closed.
- If faults are not remedied
burner. immediately, the burner must
The pellet burner can be used for heating not be operated
rooms only in the manner described in - The user must be provided with
this manual. written instructions on the fault
and the hazard it entails.
The application and any other was the
It is mandatory to assure a

area of operation is not recommended by
the manufacturer and is not responsible backup power generator of
corresponding rated power!
for the occurrence of defects or failures.
(see 12.3)
Note the pellet burner type data
indicated on the factory rating label and DANGER of fire when burning
flammable materials or liquids.
the technical data provided in chapter 12 - Flammable materials/liquids
in order to ensure proper operation of must not be left in close
the product.

1.2.1. Instructions to boiler installer


! proximity of the burner and
heating boiler.
- Instruct system user of the
During installation and operation, the allowed minimum clearances
country-specific requirements and from surrounding objects.
4
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

• Do not install the burner in sleeping It is mandatory to assure a


premises.


backup power generator of
• Do not connect the burner to any other corresponding rated power!
air-intake systems .
(see 12.3)
• The burner must be connected to the
boiler as a heating device
Safety rules for user operation:
• Improper installation may cause fire or
- Operate the pellet burner on
injury. Contact your local construction
supervisory body in case you need recommended fuel only, and to that
prior approval for installation of this end you must regularly inspect the
product. boiler room.
• Mandatory is the installation of smoke - Do not use flammable liquids for
detectors in the room where the ignition or increase of burner output.
burner is installed. - Collect ash in lid-covered fireproof
• Pellet burner is NOT designed for containers.
installation in motorhomes, caravans - Clean the burner surface using non-
etc. flammable agents only.
- Do not place flammable objects onto
1.2.2. Instructions to installation user
the burner housing and heating boiler
DANGER of intoxication or cabinet or in their proximity. (see
explosion diagram 1 for the minimum clearances)
Toxic gases may be discharged - Do not store flammable materials in the
when burning waste, plastics,
boiler room.
liquids.

$ - Use only the fuels indicated in - Boilers, chimneys and other


this manual. connections of mounted burner must
- In case of danger of explosion, meet standards for fire and emergency
ignition or discharge of exhaust safety of the country.
gases in the room, stop the - It is mandatory to strictly observe
pellet burner from operation. instructions for connecting the burner
CAUTION! Danger of injury to power network as well as to all
/ damage of system due to peripherals.
incompetent operation. - Structural changes to burner by user
- The pellet burner must be can cause damage to equipment or
serviced only by persons familiar injury.
with the operation manual. - Do not allow contact transmission of
- As a user, you are only allowed

electrical wire or touch any part of the
to start the pellet burner up, boiler, where the surface temperature
adjust the temperature of the
burner, shut the burner down can exceed 70 °C.
and clean it. - Dismount the burner when the boiler
- Unattended children must not are heating alternative (mainly) of fuel
be allowed access to premises - wood, wood briquettes, coal or other
with running pellet burner fuel.
inside.
5
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

- This manual should be kept throughout 1.2.3. Minimum clearances for


the lifetime of the burner. installation and combustibility of
CAUTION! Hot surface! construction materials
Risk of burns if you touch the The applicable minimum clearances in
running system. Burner housing, your country may differ from the ones
specified below. Please, consult your
;
body and flange are hot surfaces
during burner operation. installer.
It is strictly prohibited to open The minimum distance from the burner,
boiler doors with the burner heating boiler or exhaust gas pipe to
running.
objects or walls must be at least 200 mm.

Diagram 1
Recommended clearances between the boiler with mounted burner and walls.
6
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Table 1. Combustibility of construction Longitudinally, under the housing, there


materials are air jacket, fuel ignition heater, fan and
Stone, bricks, ceramic control unit. On the upper part of the
Class tiles, baked clay, solutions, burner there is a feeder chute to which
А – non-
combustible plaster free of organic the pellet auger is attached. The housing
additives. of the burner has been designed to
Gypsum board panels, meet all regulatory safety requirements
Class basalt fiber needled felt, (no sharp or protruding elements) with
B – hard fiberglass board, AKUMIN, operating temperature not exceeding
combustible Izomin, Rajolit, Lignos,
50°C.
Velox, Heraklit.
The combustion chamber consists of two
Class С1/С2 Wood beech, oak
Medium Wood softwood, layered parts:
combustible wood Ember resistant outer tube and inner
Asphalt, cardboard, combustion chamber with holes for air
Class cellulose, tar, fiberboard, intake along its entire length, opening
C3 – easy for fuel ignition heater and opening for
combustible cork, polyurethane,
polyethylene. photosensor.
Between the two parts there is a gap
For general safety considerations, we which provides for free circulation of the
recommend that the boiler be placed air necessary both for cooling and oxygen
on a foundation with height of 100 mm supply into the combustion chamber.
made of class A material, see table 1. The feeder chute allows 360° rotation
for its best convenient positioning
2. PRODUCT DESCRIPTION when connecting the pellet auger to the
hopper.
The BURNiT Pell ECO pellet burner for
hot water boilers is designed to burn
only and exclusively wood pellets and it
is intended to heat up heating boilers.
The built-in control unit and automatic
cleaning function ensure the automated
operation of the burner and optimal
burning of the fuel.
2.1. Design.
The burner is made of high-quality
stainless steel able to withstand
temperatures of up to 1150°С. The
burner must be installed on a heating Diagram 2.
boiler. Pellet burner Pell ECO design
The burner consists of two parts:
combustion chamber and air jacket.
7
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

• Built-in controller. control panel of the burner (10 А).


The main control unit, located in the • Power interruption. In case of power
burner, manages the entire heating interruption, all parameter settings are
process. stored in the memory of the controller.
Controller functions: Upon the subsequent restart of the
1) fully automated ignition and pellet burner, the controller resumes the
feed; execution of the program from the
2) self-cleaning function, activation point when the power interruption
depending on the configured occurred.
intervals;
3) controls the operation of the 3. FUEL
circulation pump of the central
heating; All pellets are biomass manufactured
4) controls the operation of the pump of from common low-growing plants and
the domestic hot water; trees. The most common household type
5) option for control by room pellets are made of sawdust and milled
thermostat; wood chippings which are waste material
6) timer; from wood used in the production of
• Photo-sensor - monitors the power of logs, furniture and other products. Wood
the burner flame is the richest raw material which does
• Dry contactless resistance heater not have any impact on the production
assuring ignition of fuel costs of food products or ethyl alcohol
• Innovative cleaning system of the (ethanol). The raw material is processed
combustion chamber under high-pressure and temperature
• Air feed fan, step-regulated (0% to 100 and is pressed to produce small-size
%). cylindrical pellets. The production
2.2. Burner safety devices process may utilize soft wood material
• Elbow-shape feeder chute. The (such as softwood, pine), hardwood (oak)
geometrical shape of burner feeder as well as recycled waste wood. Wood
chute prevents backfire entry from pellets are produced in hammer mills or
burner into pellet hopper. wood pellet plants.
• Thermostatic protection (80°С). The Advantages of wood pellets:
thermostatic protection is fitted on the Convenient storage. Pellet bags can be
feeder chute. When the surface of the stored on a small area in a dry garage,
feeder chute reaches 80°С, the control basement, service room or shed.
stops the feeding of pellets into the Easy loading. In most cases the boiler
burner and signals for fault. hopper needs loading only once a week –
• Fuse. In case of electrical fault in the this depends on the hopper capacity.
system of the burner (short circuit, high Better control of fuel quantity. The small
current, etc.), the overload is borne by size of the pellets allows for precise fuel
the electrical fuse fitted on the main feeding. On the other hand, the supply
8
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

of air for reaching optimal combustion pellets (consistently under 10% as


efficiency is easier to adjust since the opposed to 20% to 60% moisture content
fuel quantity in the combustion chamber of the logs). Low moisture content,
remains constant and predictable. controlled fuel portions and precise air
Fuel efficiency. High combustion setting means high combustion efficiency
efficiency is also determined by and very low carbon oxides in the flue
consistently low moister content of gases.

Table 2. European Certification of Wood Pellets for Heating Purposes

Parameters Units ENplus-A1 ENplus-A2 EN-B


6 (± 1) 6 (± 1) 6 (± 1)
Diameter mm 8 (± 1) 8 (± 1) 8 (± 1)
Lenght mm 15 ≤ L ≤ 40 1) 15 ≤ L ≤ 40 1) 15 ≤ L ≤ 40 1)
Bulk dentsity kg / m2 ≥ 600 ≥ 600 ≥ 600
Calorific/heating value MJ / kg ≥ 16,5-19 ≥ 16,3-19 ≥ 16,0-19
Humidity /moisture Ма .-% ≤ 10 ≤ 10 ≤ 10
Dust Ма .-% ≤ 1 3) ≤ 1 3) ≤ 1 3)
Mechanical durability Ма .-% ≥ 97,5 4) ≥ 97,5 4) ≥ 96,5 4)
Ash Ма .-% 2) ≤ 0,7 ≤ 1,5 ≤ 3,5
Melting point of ash °C ≥ 1200 ≥ 1100 -
Chlorine content Ма .-% 2) ≤ 0,02 ≤ 0,02 ≤ 0,03
Sulfur content Ма .-% 2) ≤ 0,03 ≤ 0,03 ≤ 0,04
Nitrogen content Ма .-% 2) ≤ 0,3 ≤ 0,3 ≤ 1,0
Copper content mg / kg 2) ≤ 10 ≤ 10 ≤ 10
Chromium content mg / kg 2) ≤ 10 ≤ 10 ≤ 10
Arsenic content mg / kg 2) ≤ 1,0 ≤ 1,0 ≤ 1,0
Cadmium content mg / kg 2) ≤ 0,5 ≤ 0,5 ≤ 0,5
Mercury content mg / kg 2) ≤ 0,1 ≤ 0,1 ≤ 0,1
Plumbum content mg / kg 2) ≤ 10 ≤ 10 ≤ 10
Nickel content mg / kg 2) ≤ 10 ≤ 10 ≤ 10
Zinc content mg / kg 2) ≤ 100 ≤ 100 ≤ 100
1) Not more than 1% of the pellets may be longer than 40 mm, max. Length 45 mm;
2) Dry weight;
3) Particles <3.15 Mm, particulate matter, before handing over the goods;
4) Measurements with lignotester limit value ≥ 97,7% by weight.
When purchasing pellets, ask for conformity declaration and certificate issued
by an accredited laboratory and make sure the fuel meets the requirements
i indicated in the manual. If you purchase large amount of pellets (bulk supply
for the entire heating season for example), ask your supplier to provde
accurate and true information about the storage conditions.

9
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

We recommend to use pellet with size of - Dimensions of the packaging of the


6 - 8mm. Density 600 - 750kg/m3 heating auger: 260х120х1700 mm
value 4.7 - 5.5 kWh/kg. Ash content – less
than 1% and moisture content up to 8%, 5. DELIVERY OF THE PELLET BURNER
EN ISO 17225-2:2014 • Inspect the integrity of the packaging
The optimal density of the pellets which upon delivery.
guarantees their quality is 605-700 kg per • Check whether all components
cubic meter. have been delivered to you. Burner
Pellet moisture content must not exceed consignment package includes
10%. Make sure you store your fuel in a (diagram 3):
dry and well-ventilated place.
The optimal pellet ash content is ≤ 1%.
This also provides for less frequent
cleaning intervals for the burner.
The table 2 contains the parameters
which we recommend that you take into
consideration when choosing fuel for
your „Pell ECO” burner.

4. TRANSPORTATION OF THE PELLET


BURNER
When loading, transporting and
unloading of the device appropriate
safety equipment must be used in
accordance with Directive 2006/42/SE.
Product must be in original packaging
following the instructions on the label -
to be protected from adverse weather
conditions (snow, rain and dust) from
the shocks, and other activities likely to
cause damage. In case of malfunction of
the fan or the motor drive (noise, friction)
or failure of high-tech elements such as
broken LCD screen, contact your nearest
authorized service center for repairs and
Diagram 3. Pell ECO burner consignment
maintenance.
elements
- Dimensions of the packaging of the
1) Pellet Burner Pell ECO with built-up
burner: Control unit
Pell 35 ECO Pell 55 ECO
2) Feeding chute mounted to the burner
Width, mm 275 305
3) Auger
Length, mm 612 800
4) Technical passport. Installation and
Height, mm 533 520
operation manual
10
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

5) Service booklet and Warranty card Mounting, installation and setup


If any of the above items are missing, of burner should be carried out by
authorized technician. Installer


contact your supplier.
shall advise the user of the
installation minimum clearances
6. STORAGE OF PELLET BURNER to combustible materials and
liquids.
Pell ECO burners shall be stored in dry
Table 3
and well ventillated spaces, free from any
Pell 35 ECO Pell 55 ECO
gases, liquids, acids and oil vapours that
А 350 350
may damage the burner. Storing burner
B 450 450
and auger in spaces with fertilizers,
C 450 550
chlorinated lime, acids, chemicals, ect.
is not allowed. Recommended storage
temperature shall be from +5°С tо +40°С. 7.1. Pellet burner connection to the fuel
Recommended relative humidity -below hopper and pellet auger
70%. When stored, the devices shall not Take the feeder chute flexible hose (from
have direct contact with the ground, the auger set). Using a bracket, clamp
placed on pallets, maximum two tiers and one end of the hose onto the motor-end
in their original packaging. The storage outlet of the pellet auger.
period is not more than 2 years from date - Remember – pellet auger must be
of manufacture. It is recommended that installed at 45° angle to the ground
every burner is tested before installation. horizontal surface.
Quality and safety of the burner must - Fill the hopper with fuel (see table 2 for
be confirmed by a test mentioned in the parameters of the fuel types used)
warranty card. - Plug the power cord of the pellet auger
into the indicated Schuko-type burner
7. MOUNTING OF THE BURNER socket on the left side of the burner
Recommended boiler chamber sizes for housing.
mounting of Pell ECO pellet burner:

Diagram 5. Mounting the pellet burner Pell


ECO to WBS boiler
Diagram 4. Mounting of Pell ECO pellet 1. WBS boiler; 4. Auger;
burner to boiler combustion chamber 2. Pellet burner Pell ECO; 5. Fuel hopper.
3. Auger flexible pipe;
11
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

7.2. Connecting the pellet burner to the Improper cable connections may
mains power supply damage the regulator!
Such connection must be


performed by a technician / It is mandatory to assure a


service shop authorized for such backup power generator of
operations. corresponding rated power! (see
Caution! ELECTRIC SHOCK 12.3)
HAZARD! The device may be damaged if


- Before opening the unit: switch struck by a lightning. Make sure
off the voltage and secure the it is unplugged during the storms.
unit against accidental restart.
- Observe installation instructions.

Diagram 6. Wiring diagram of connection of internal devices / sensors to the burner

KSD
30180DEG0

STB
NC contact

OD
brown
NPBC V3M -2

brown Sensor Buffer bottom


Heater
Sensor DHW
Temperature sensor in
the water jacket of the boiler
Sensor Buffer top

brown
blue
FAN

Photosensor

Inputs Outputs
Group 1 FM Fan main
RT Room thermostat FSG Fan smoke gases
PS Photo sensor SF Screw fuel
RB Temperature sensor at the top of the buffer SB Screw burner
B Boiler temperaure sensor PH Pump heating
Group 2 PWH Pump water heater
WH Water heater IGN Igniter
PT Tempearture sensor at the bottom of the buffer FC Fan cleaning
OD Sensor reverse burning
12
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Diagram 7. Wiring diagram of connection of external devices / sensors to the burner

Fuel
Feeder

brown
blue
NPBC V3M-2

CH Pump
220 V
blue

L N
brown
blue

Pump
DHW
220 V
brown

L
blue

NL
bottom

Sensor
Buffer
brown
OD

blue

DHW
Sensor
NL
brown

blue

NL
Sensor
Boiler
brown

blue
NL

Sensor
Buffer
brown
top
blue Therm.
NL

Room
brown

L N
Power
Supply
220 V

The burner must be connected to a Create tight connection with the


220V/50Hz mains using power plug (3 electrical mains which complies with the
meters long, bound to the burner). local regulations.
13
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

7.3. Trouble - shooting

Table 4.
Fault Cause Solution
1. Low temperature in 1.1. Immediately consult your
the boiler on which 1.1. Inadequate sizing and/ installer about the problem.
the burner is installed. or combination of heating Mount the supplied filling and
Unable to reach
normal temperature appliances drainage cock on the drainage
outlet Y.
mode of 65° - 85° С
2.1. Poor adjustment of the 2.1. Contact your installer. It
2. Ejection of unburned fuel-to-air ratio from the is necessary to set the burner
pellets into the burner controller properly using gas analyzer
combustion chamber 2.2. Utilization of low-quality 2.2. Use only fuel which meets
of the boiler pellets (shorter than the the requirements specified in
specified length) the manual.
3.1. Utilization of low-quality 3.1. Use only fuel which meets
pellets (with higher ash the requirements specified in
3. Formation of clinkers content) the manual.
and noncombustible 3.2. Low performance of the 3.2. Increase turn-on
inclusions inside automatic cleaning function. frequency of the automatic
burner body. cleaning function.
3.3. Improper setting of fuel- 3.3. Adjust using gas analyzer
air mixture
4.1. Poor chimney draught or 4.1. Immediately consult your
high internal resistance of the installer about the problem.
boiler combustion chamber
4. Smoke in the pellet 4.2. Blockage
combustion
of
chamber
burner
due to 4.2. It is necessary to clean the
hopper build-up of noncombustible burner combustion chamber
materials using brush
4.3. Improper setting of fuel- 4.3. Adjust using gas analyzer
air mixture
5.1. Blockage of burner 5.1. It is necessary to clean the
combustion chamber due to burner combustion chamber
build-up of noncombustible using brush
5. Unstable flame materials
(photosensor detects 5.2. It is necessary to clean
> 180 units at 5.2. Dust on the photosensor the photosensor. Refer to
maximum output) the manual for the cleaning
procedure.
5.3. Improper setting of fuel- 5.3. Adjust using gas analyzer
air mixture
6. Boiler temperature 6.1. Grid power fluctuations It is mandatory to assure a
too high. Controller backup power generator of
failure 6.2. Power failure corresponding rated power!
(see 12.3)

14
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

8. BURNER OPERATING 8.4. Installer prescriptions regarding


burner servicing and maintenance
8.1. Ignition. Before the heating season it is mandatory
After the start up of the burner from to check up and clean the burner and its
the control panel, the main pellet auger components.
conveys certain amount of fuel from the It is mandatory to clean up the
pellet hopper to the burner. This specific combustion chamber of burner and
amount of pellets is set by the installer movable grate. In case of combustion
and depends on the fuel characteristics. chamber of burner and movable grate
Fuel falls directly into the combustion orifices clogged by non-combustive
chamber. Into combustion chamber the material, those should be released using
fuel is ignited by hot air. a bodkin. Clean thoroughly the inner
combustion chamber using the scraper
8.2. Burning. brush to remove all deposits on the
The burning process takes place in the metal surface. Use a vacuum cleaner to
combustion chamber. Flame intensity remove all sand and ashes from inside
is monitored by a photosensor which the combustion chamber. Check integrity
monitors the burning and feeds data of gasket between outer combustion
into the control unit which enables the chamber and closing hatch, replace if
starting or stopping of the combustion compromised.
process, if necessary. The output of the It is mandatory to clean dust off main
burner is determined by the intervals fan and controller board
preset on the control panel taking into 8.5. Important recommendations for
account the heating value, size and long-lasting and correct operation of the
density of the pellets. boiler
- For assembly and installation of the
8.3. Automatic cleaning system. burner follow the requirements in this
The “Pell ECO” pellet burner is equipped manual.
with innovative automatic cleaning - Use only recommended in this manual
system for the combustion chamber. fuel.
Thanks to a powerful fan built in the - Disassemble the burner from the boiler
burner body, air is being blown in at high body before clean it. Depending on fuel
speed and rate thus removing all residues and burner settings, clean the pellet
– ash, noncombustible inclusions, etc. burner once a month.
built up into the combustion chamber - User`s training for operation and
of the boiler. These automatic cleaning maintenance of burner is performed by
cycles continue depending on the an authorized installer or service shop.
parameters set by the command block. Failure to observe the
installation and operating

The cleaning cycles can be additionally
adjusted as well as their repeat rate requirements described in the
depending on the load of the burner. manual and the service booklet
voids the warranty.
15
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Type of
Procedure Duty of:
maintenance
Cleaning of movable grate (B). Unclogging the holes
Daily in the movable grate and combustion chamber (if User
clogged ones).
Dismantling of combustion chamber housing (A),
movable grate (B) and positioning plate (C). Cleaning
of combustion chamber (A), movable grate (B) and
Seasonally Installer
positioning plate (C) by scraper brush and vacuum
cleaner. Replacement of all gaskets (see Diagram 10
in 12.2.)

Diagram 8. Dismantling of the combustion chamber housing.

9. CONTROL UNIT
Button F function button. Apply for:
9.1. Controller view. Explanation of - exit of the current menu
buttons and indicators. - taking back to main screen
LCD screen: - burner transfer from one condition to
The controller another
screen displays the Button „Enter” – apply for switching
information for the from one parameter to another in
operation of the certain screen or to correct the certain
facility. parameter.
Explanation of
buttons: Buttons „Navigation arrow Up” and
„Navigation arrow Down” – Used
16
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

to change the value of a parameter in Flame 1 symbol means Low output


the menu and to move to the next menu mode of burner. In this mode the
page After entering the correct value burner operates at minimum
press button “Enter", to move to next output.
parameter. This symbol means Suspend mode
Display symbols explanation: of burner.
Auto Clean symbol appears in right The notice "Hi" appearance on the
upper part of display. Active auto screen where the boiler
cleaning symbol means boiler automatic temperature is displayed means
cleaning mode. that the measured Boiler body
Crossed-out flame symbol appears temperature is above 120°C. Flashing
in upper right part of display. and beeping alarm is activated. When
Means that the boiler enters into the issue is corrected, notification can be
Extinguish mode. deleted. When disconnect the burner
CH Only /Radiator/ symbol from electrical supply for few seconds
appears in upper part of display. and then switch on it again, boiler goes
Means than Central Heating priority is back to normal operation.
set to heat up the central heating. Notify the authorized installer/
Parallel pumps /shower and service to be performed
radiator/ symbol appears in upper immediately inspection of the
part of display. Means that is set equal boiler and heating installation.
priority to both pumps( CH+DHW). They Boiler increased temperature.
work in parallel and are controlled by Those two symbols appearance on
temperature sensors. the screen where the boiler
Summer mode /shower and sun/ temperature is displayed means that
symbol means than is set Summer boiler temperature has increased up to
heating mode. Only DHW pump is active. 99°C.
Burner flame symbol appears in Notify the authorized installer/
upper right part of display. Means service to be performed
that burner is activated. Burner goes into immediately inspection of the
boiler and heating installation.
Ignition mode and upcoming boiler fire
up. Error symbol appears in right upper
Flame 3 symbol means Maximum part of display. Flashing and beeping
output mode of burner. In this error symbol mean error or fault in
mode the burner operates at maximum burner operation. Use “Enter“ button to
output. move to next screen with error
notification in lower left part of display.
Flame 2 symbol means Medium
When the issue is corrected, error
output mode of burner. In this
notification can be deleted. When
mode the burner operates at partial
disconnect the burner from electrical
output.
17
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

supply for few seconds and then switch Symbol “T”


on it again, boiler goes back to normal indicates, that
operation (error notification is deleted). room termostat
Notify the authorized installer/ has been activated.
service to be performed In “CH only” mode when there is a signal
immediately inspection of the from room termostat, the burner burns
boiler and heating installation. 5 min at max power, followed by transer
Factory setting - Alarms to power level 2. After 5 min the burner
transfers to power level 1, and after 5
Reverse fire Alarm (when
BB min transfers in Suspend mode. When
the thermostat contact OD
ALARM there is no signal from room termostat
input is open)
or there is non-fullfilled requirement for
SENSOR Boiler Temperature Sensor is
DHW, the burner will fire up.
E1 missing (input B).
In “CH + DHW” mode when DHW
SENSOR Boiler Temperature Sensor (Domestic hot water) requirement is
E2 Short circuit ( input B). fullfilled and there is a signal from room
IGNITION termostat, the burner burns 5 min at max
Failure ingnition.
FAIL power, followed by transfer to power
Water Heater Temperature level 2. After 5 min burner transfers to
DHW E1
Sensor is missing (input WH) power level 1 and after 5 min transfers
Water Heater Temperature to Suspend mode. Hen there is no
DHW E2 Sensor Short circuit (input signal from room termostat or there is
WH). non-fullfilled requirement for DHW, the
Temperature sensor of lower burner will fire up.
CH btm part of buffer tank is missing When room termostat is activated, CH
E1 (in the event that mode is pump stops in both modes (CH Only,
selected Buffer)
CH+DHW). In CH+DHW mode when
Short circuit of temperature
CH btm sensor of lower part of buffer there is a signal from room termostat, CH
E2 tank (in the event that mode pump turns off. The burner countinues
is selected Buffer). to burn until DHW (Domestic hot water)
Temperature sensor of requiremend is fullfilled.
CH top E1 upperr part of buffer tank In "Summer Mode" room thermostat is
is missing (in the event that not active.
mode is selected Buffer).
Short circuit of temperature Lights for operating:
CH top E2 sensor of upper part of buffer
tank (in the event that mode - Pump heating system.
is selected Buffer). - Pump Domestic hot water.
When restarting the controller alarm
is deactivated.

18
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

9.2. User`s menu the pump will stop. It will restart once
9.2.1. Initial (start-up screen) "Standby" the water temperature inside the DHW
For access to user settings menu press tank drops by 5°C. In this way the water
and hold functional key F for 3-4 seconds. temperature inside the DHW tank will be
Use UP and DOWN kept at a hysteresis of 5°C, i.e. the water
arrow keys in CH temperature will be between 70°C and
Setup menu to 75°C.
select desired Use UP and DOWN
temperature of arrow keys in Set
engagement of circulation pump. Time menu to set
This menu is the unit’s built-in
active only mode timer/clock.
Buffer. From this Use UP and DOWN
menu you can arrow keys in Set
preset buffer tank Date menu to set
circulation pump switch-on and switch- the date.
off temperatures provided such heating Use UP and DOWN
installation scheme (with buffer tank arrow keys in Contrast menu to adjust
included) is selected, whereas the two the LCD display backlight level.
sensors reading these temperatures are Confirm settings by shifting to next
mounted in the upper, respectively lower submenu through a single pressing of the
part of the buffer tank. Use button F to functional key F.
navigate to the next menu.
In DHW Setup Use UP and DOWN
menu – set arrow keys in
domestic hot water Contrast menu to
(DHW) pump adjust the LCD
switch on/off display backlight level.
temperature. Use UP and DOWN arrow Confirm settings by shifting to next
keys to select desired temperature in submenu through a single pressing of the
“Set Temp _ _°” and hysteresis in functional key F.
“Hysteresis _ _°”. Upon reaching the Choose a language
preset temperature of water in boiler the by pressing
DHW pump will engage. It will stop when navigation arrows
water inside the DHW storage tank and button
reaches the preset temperature. “Enter”.
Example: On Set Temp 75°C and
Hysteresis 05°C when water inside the The burner is in
boiler heats up to 70°C the pump will standby mode.
start. When water temperature inside
the DHW storage tank reaches 75°C The display shows:
19
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

- Temperature in the boiler (23°C), time, pump). In this mode, the boiler can
and by pressing the Enter button you be managed via a room thermostat
can browse the quick menu (bottom left) or be temperature-controlled by the
where the following read-only data is temperature inside the connected
displayed: buffer tank to it (depending on the
t = 85° - Maximum set temperature; connection scheme) (see item 10.3.4,
menu CH Mode).
tDHW = 42° - Parameter tDHW indicates - Summer Mode – Summer mode. Boiler
temperature of domestic
hot water (DHW); works for heating of domestic hot water
only.
tCH = 77°/70° - Parameter tCH indicates If you have selected
top and bottom buffer temperature the (CH + DHW)
(visualized only in Buffer mode); option, upon
confirmation of
0 - Light intensity in the burner command via the
(in the range of 0 ÷ 190);
"F" button you may navigate to the next
- Burner status (detected screen.
errors, if any);
From this menu
- Current date. you can set up and
adjust DHW pump
9.2.2. Burner star up "Switch mode" activity periods.
Burner start-up. Use the arrow keys to set time (HH:MM).
After pressing the Use “Enter” button to checkmark desired
“F” button and time period option.
using the „navi- If no option is check-marked,
gation arrows”, the the controller will maintain DHW
“Auto” menu is selected. Pressing the "F" temperature as a priority. Only when
button will open the next page of the its preset value is reached, the CH
menu. circulation pump will start.
Set the priority mode of the burner
through "navigation arrows." 9.2.3. Burner shut-down "Standby"
Set the priority Pressing the “F”
mode of the burner button will take you
through “navigation to the main menu
arrows.” and by using the
navigation arrows
- CH + DHW – Both pumps /CH-central you can select the “Standby” menu and
heating pump and DHW – domestic confirm the selection by pressing “F”.
hot water pump /are active. The burner goes into extinguishing mode.
- CH only – In this mode of operation the
only active pump is the CH circulation
pump for the heating installation (CH
20
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

9.3. Installer's menu (setting the Important: Please enter the


combustion parameters in the burner exact power. Setting of higher

*
controller) or lower power than is written
on production label of the boiler
CAUTION! We recommend that can cause boiler damage or
this menu be used only by an
authorized installer/service physical injury.
shop in order to ensure efficient Fuel C - Set the calorific value of used
and safe operation of the fuel. The calorific value is marked on fuel
equipment package.
To access the Feed - Determine the number of cycles
s e t t i n g s for screw calibration. When entering
adjustment a larger number of cycles will get more
m o d e , precise results.
simultaneously Press "F" button to switch to next
press the “Enter” and „F” buttons and submenu.
hold them pressed for 4 /four/ seconds. Filling of auger:
This will display the controller hardware From this menu by
and software version on the screen. Press selecting "up arrow"
again button “Enter” and this will open button activate
the initial page for the burner settings. operation of main auger of the boiler
For access to service settings menu you (the auger in fuel hopper). Auger began
need a service menu code. working constantly. If the auger is empty
The service menu will take about 20 min. to be filled- well.
comprises only Capacity of Auger:
and uniquely When enter this
parameters with menu, controller
direct impact on automatically start to
boiler combustion operate 10 cycles. During these operating
process, as well as cycles the auger Switch-On and Switch-
on heating Off simulating normal operating behavior
installation management (depending on for combustion process. Transported
the peripherals management capacity of by auger pellets during these cycles
the boiler digital controller unit). should be collected (use a plastic bag)
and weighed when the last cycle is
9.3.1. Menu for automatic dose pellets
completed. The number on right-side of
for maximum power
the screen shows how many cycles you
Calculation of feeding: set for execution. The number on left-
Power - Enter the side of the screen shows which cycle is
maximum power of the currently running.
model of boiler.

21
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Pending completion of all cycles 9.3.2. Cleaning setup

* do not press the buttons display


as it will stop the process!
The burner
performs automatic
cleaning before
When the last of these set cycles has been
each ignition and
executed, auger will stop automatically
shut-down.
and controller will activate automatically You can use this menu to adjust the
the option Weight. When option Weight running time of the main fan (FAN) and
is active enter the weight of pellets. To do of the cleaning motor (Cleaner).
this you must have electronic scale.
Select the desired option using the
Entering the amount of navigation arrows. Use the „Enter”
weighted pellets: button to open the next parameter. Use
Use this menu to
enter the amount of the button to open the next page of
weighted pellets when all set cycles have the menu.
been executed. In this submenu you
can activate or
Use accurate scales with range deactivate the
of at least 10 grams. Of the total automatic cleaning

*
weight (pellets and plastic bag) of the burner in
subtract the weight of the bag to
get the right amount of pellets Ignition (Start) mode or extinguished
during measurement! (Stop) mode. The checkmark in the box
indicates that the automatic cleaning
Usе "Up arrow" and "Down arrow" system is active.
buttons to enter the amount of weighted 9.3.3. Ignition setup
pellets as round the amount to 10 grams. In this submenu
Press "F" button to switch to next you can set the
submenu. number of attempts
Applying the calculated (Retries) to ignite
feed: the burner and the
In this sub-
time of the initial feed portion of pellets
menu controller
automatically calculates the interval for (Feed). Select the desired option using
fuel feeding during combustion cycle. the navigation arrows. Use the „Enter”
button to open the next parameter. Use
Example: (see picture) for combustion
cycle of 20 sec. calculated fuel feeding the button to open the next page of
is 8.8 sec. Use "Up arrow" and "Down the menu.
arrow" button to Apply or Cancel 9.3.4. Cycle setup
calculated value. By confirmation with Use this submenu
button “Apply” You confirm this and to adjust the
this setting is saved for maximum power running time of the
setup. heater (Heater) and
Press „F” button to confirm and exit the the running time
menu.
22
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

and output of the main fan during the Upon reaching 85°С, the burner enters
ignition of the initial portion of pellets. into suspend mode (Suspend).
Principle of operation: Select the desired option using the
After feeding the initial portion of pellets, navigation arrows. Use the „Enter”
the heater operates for 3 minutes , and button to open the next parameter. Use
the main fan is turned on at 20% of its
capacity and operates for 5 minutes (the the button to open the next page of
heater continues to work). If upon the the menu.
expiration of that period the photosensor
detects the presence of stable flame, the
burner enters into operating mode. If no 9.3.6. Setup of burning Level
stable flame is present, the burner feeds This submenu
in pellets again and repeats the process. allows you to adjust
the parameters of
NOTE! Fan B/E 20/1 is a set up the main mode of
for the main fan at 20% and set o p e r a t i o n


up for the fan for fume gases 1% Maximum output of the burner. It is
(if there is installed). Fan for the
fume gases must be connected indicated by three flames .
to termonal FSG (see shceme 6). You can modify the pellet quantity
(Feed), time interval at which these
Select the desired option using the pellets are fed (Cycle) and fan output as a
navigation arrows. Use the „Enter” percentage value (FAN).
button to open the next parameter. Use
Example: with the period set at 20
the button to open the next page of seconds, the pellet auger runs for 7,1
the menu. seconds feeding pellets in the burner,
9.3.5. Burn Level and is off for 12,9 seconds.
The burner has Select the desired option using the
three main levels of navigation arrows. Use the "Enter"
burning (three button to open the next parameter. Use
main output modes
the button to open the next page of
of operation). Use
the menu.
this menu to set the temperature
In this submenu
differences at which the burner will shift
you can adjust the
from higher output mode to lower (step
parameters of the
modulation).
medium output
Example: We have set maximum
mode of operation
temperature of 85°С. Upon reaching
of the burner.
77°С, the burner will shift down to lower
mode of operation (two flames). Upon It is indicated by two flames .
reaching 82°С, the burner enters into still We recommend to set at 50% of the main
lower mode of operation (one flame). mode.
23
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

You can modify the pellet quantity (Feed)


and fan output as a percentage value the button to open the next page of
(FAN). the menu.
Select the desired option using the 9.3.8. Suspend Time
navigation arrows. Use the „Enter” In this menu you
button to open the next parameter. Use can adjust the time
period for which
the button to open the next page of the burner will
the menu. remain in
In this submenu you suspended mode and the time can be set
can adjust the in minutes with a maximum duration of
parameters of the 180 minutes. If within a set time (20
lowest output mode minutes) the temperature in the boiler
of operation of the does not decrease, the burner enters
burner. It is indicated by one flame . into Extinguish mode – crossed-out flame
We recommend to set at 10÷35% of the .
main mode.
You can modify the pellet quantity (Feed) 9.3.9. Cleaning set up in working mode
and fan output as a percentage value In menu Interm.
(FAN). Cleaing self-
Select the desired option using the cleaning for the
navigation arrows. Use the „Enter” burner can be set.
button to open the next parameter. Use The main burner's
fan turns on during certain cycle on
the button to open the next page of higher power level for certain period of
the menu. time. All parameters can be changed.
Complete description of the output
modes is provided in section 10 of this 9.4. Auto Clean Setup
manual.
You can set time
9.3.7. Suspend and number of
This submenu allows you to adjust the engagements of
parameters of the suspended mode of the burner self-
operation of the burner. You can modify cleaning system.
the pellet quantity (Feed) and fan output It is mandatory to have at least one self-
as a percentage value (FAN). cleaning session in 24 hours.
Maximum number of self-cleaning
Select the desired sessions in 24 hours – six.
option using the Select the desired option using the
navigation arrows. navigation arrows. Use the „Enter”
Use the „Enter” button to open the next parameter. Use
button to open the next parameter. Use
24
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Burner Feeder -
the button to open the next page of internal burner
the menu. auger /feeder/
(Active for Pell
9.5. Hardware Setup burners)
Use this submenu Cleaner Motor - (Active for Pell burners)
to activate (with Tstat NO - Thermostat, normally open (if
check mark) or no check thermostat is normally closed).
d e a c t i v a t e There must be a checkmark on the
a d d i t i o n a l internal pellet auger of the burner
peripherals. (Burner Feeder)
CH PUMP – central heating pump Select the desired option using the
DHW PUMP – domestic hot water pump navigation arrows. Use the „Enter”
Thermostat . button to open the next parameter. Use
Select the desired option using the
navigation arrows. Use the „Enter” the button to open the next page of
button to open the next parameter. Use the menu.
This submenu
the button to open the next page
allows you to adjust
of the menu.
the conditions
From this screen
under which the
menu you can
photosensor
choose the
detects the presence of stable or unstable
burner operation
flame and signals the burner to shift to
management
operating mode or be extinguished.
mode.
Example: (see picture) If the light intensity
When selecting the mode "Thermostat"
in the burner is above 115 units over a
burner is controlled by the signal of
period of more than 30 sec, the burner
the external room thermostat. If not
will detect that there is a stable burning
installed external thermostat, the burner
process going on and will shift from
is controlled by the temperature in the
ignition to burning. If the light intensity
water jacket of the boiler.
in the burner is under 90 units over a
In the mode "Buffer" burner is controlled
period of more than 40 sec, the burner
by the temperature of the buffer bound
will detect that there is no stable burning
to the boiler. Upon reaching the desired
process going on and will extinguish the
temperature at the bottom of the buffer
burner and attempt to reignite.
(Buffer bottom) burner extinguishes.
Select the desired option using the
When the temperature falls below the
navigation arrows. Use the „Enter”
desired upper buffer (Buffer top), the
button to open the next parameter. Use
burner ignites again.
the button to open the next page of
the menu.
Use this menu to conduct fan operation
25
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

test. respective components is being activated


This menu allows a checkmark will appear in front of its
you to select name. Use the „Enter” button to select
maximum boiler the individual components.
temperature. In Description of components:
other words, the 1) FF – Fuel Feeder – main auger
maximum temperature to heat the boiler 2) BF – Burner Feeder – internal burner
on which the burner has been installed.
auger / feeder (active for Pell burners
The maximum value for this setting is
only)
85°С. Select the desired option using the
navigation arrows. Use the „Enter” 3) CH – Central Heating pump
button to open the next parameter. Use 4) DHW – Domestic Hot Water pump
5) Ign – Ignition
the button to open the next page 6) CM – Ignition (active for Pell burners
of the menu. only)
You can control the
Important. This menu is for
fan in real time,


installers only. It is active and
without confirming visible only if the controller is
anything, using in "Standby".
only the navigation arrows.
Important. This menu is for 10. SETTING OUTPUT MODES OF
OPERATION OF THE PELLET BURNER

installers only and it is active
and visible only if the controller PELL ECO
is in „Standby” mode.
CAUTION! You must use gas
Test EFan Speed Use this menu to
00
test the fan exhaust
 analyzer when setting the
burner.
(if installed). You The Pell ECO pellet burner is equipped
can control the fan with three-step output adjustment
in real time, without confirming anything, and their setting depends on the boiler
using only the navigation arrows. Use the and heat requirements of the heating
button to open the next page of the installation.
menu. 10.1. Calibration of auger fuel feed rate.
This menu allows The auger fuel feed rate changes
you to check the depending on the density and size of the
operation of the fuel used. Therefore it is necessary to
various pellet calibrate the main auger every time you
b u r n e r change the type of the fuel used.
components. Using the navigation CAUTION! It is recommended to
arrows, you can turn on and off the
various components and each time the  use the same fuel throughout
the heating season.
26
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Once you have installed the pellet auger setting the operation of the main auger
according to the instructions in the for these 20 sec.:
manual, fill the hopper with fuel (pellets). tFEED= 35 000 / (4,8 x 180 x 5,7)
Connect the power supply of the pellet hence tFEED= 7,1 sec.,
auger directly to the power mains. The where 35,000 is the desired output of the
auger is now in operation. Wait about burner in Watts (W),
15-20 minutes for the pellet auger to 4.8 is the heating value of the fuel in
fill with pellets. The auger is filled with kWh/kg,
pellets when pellets begin to fall from the 180 is the number of burning cycles per
T-branch of the auger at the point where 1 hour,
the flexible pipe is attached. 5.7 is the amount of pellets in grams fed
Filling of the pellet auger is necessary by the auger per 1 second. This way the
when the fuel in the hopper has been output mode can be changed and instead
depleted or when fuel has been changed. the number 35,000 – 35kW, we input the
Once you have ensured that the pellet desired kilowatts.
auger has been filled, take an empty Take also note of the fuel heating value
plastic bag and fixed it securely on the which would change the value for the
pellet auger, at the place of the flexible feed and the burner output.
pipe. Reconnect the auger to the power Using the above procedure, you can set
socket and measure the amount of any of the three output modes of the
pellets collected in the bag over a period burner.
of 15 minutes using scales/weighing Mode : Maximum output
scale. (In our example, the amount mode – It is indicated by three flames.
of pellets collected in the bag over a Pellet auger running time (Feed) – 7,1
15-minute period is 5130 grams (900 sec. (35kW)
sec). We then divide 5130 by 900 and get Main combustion cycle (Cycle) – 20 sec.
7.1 grams of pellets per 1 second. Repeat (recommended)
the measurement in order to obtain Fan output (Fan) - adjust using gas
conclusive results . analyzer.
10.2. Burner output adjustment.
In the burner output settings menu you Mode : Medium output mode
can adjust the running time of the main – It is indicated by two flames.
auger (Feed); main running interval We recommend to set value at 50% of
(Cycle) and fan output (Fan). the main mode.
Example for Pell 35 ECO model: we select Pellet auger running time (Feed) – 3 sec.
mode Cycle = 20 sec. The heating value of (17,5kW; 7,1 х 50% = 3,5)
your fuel is 4.8kWh/kg. (manufacturers
indicate the heating value of the fuel Mode : Medium output mode
on the packing – take it from there). – It is indicated by two flames.
We then employ the following formula We recommend to set value at 50% of
to calculate the number of seconds for the main mode.
27
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Pellet auger running time (Feed) – 3 sec. Important: For each of the
(17,5kW; 7,1 х 50% = 3,5) output modes the optimal fan
Main combustion cycle (Cycle) – 20 sec. setting is tweaked by using
(recommended) gas analyzer to control the
oxygen amount registered by
Fan output (Fan) - adjust using gas the device (within the range
analyzer. 10% ÷ 12%, and for the lower
modes up to 15%). The specific
Mode : Low output mode – It is setting depends also on the
indicated by one flame.
We recommend to set value at 25%
(0,25) of the main mode.
 internal resistance of the boiler
combustion chamber on which
the burner has been installed as
Pellet auger running time (Feed) – 1,8 well as on the chimney draught.
Therefore it is not possible to
sec. (8,5 kW; 7,1 х 25% = 1,8) provide here the exact value for
Main combustion cycle (Cycle) – 20 sec. the fan output and it must be
(recommended) entered by a competent installer
Fan output (Fan) – adjust using gas or service technician using gas
analyzer. analyzer

Important: You use a burner 11. WARRANTY TERMS


whose carbon footprint values The warranty terms are described in the
are approximately (СО = 100
ppm), which is 2.5 times lower Service booklet included in the supply.
than the maximum allowed
 limits for harmful emissions in
the EU Member States. Thus
you can reduce the amount of
harmful emission and contribute
to environment protection.

28
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Parameters of the controller for pellet burner Pell ECO


Pell 35 ECO Pell 55 ECO
Actuator Parameter value
Service code 00000012
Fan 300 sec
Cleaning Setup
Cleaner 1 sec
Use Cleaner Cleaner On start
On Stop
Retries 2
Ignition Setup
Feed 45 sec
Heater 3 min
Ignition Setup 5 min
Fan B/E
22/1
dt>8
Burn Level dt>4
dt>0
Feed 7,1 sec 11,2 sec
Setup Cycle 20 sec 20 sec
Fan 32/1 33/1
Feed 3,6 sec 5,6 sec
Setup Cycle 20 sec 20 sec
Fan 25 25
Feed 1,8 sec 2,8 sec
Setup Cycle 20 sec 20 sec
Fan 17 21
Feed 2 sec 2 sec
Suspend Cycle 120 sec 120 sec
Fan 5 5
Suspend Time - 0 min 0 min
Cycle 30 min/60 sec 15 min/60 sec
Interm. Cleaning
Fan B/E 50/1 85/1
Auto Clean Setup v 06:00 v 10:00 v 14:00
v 18:00 v 22:00 v 02:00
v CH Pump
Addons Activacion v DHW Pump
v Thermostat
v Thermostat
CH Mode
Buffer
Cleaning Motor
Hardware Setup
v Tstat NO
v NO
Vacuum Feeder
NC
Ign > 115/030 s 115/030 s
Ir Level Setup
Ext < 090/040 s 090/040 s
Set Temperature Max 85oC 85oC
Test Fan Speed 00 00
Test EFan Speed 00 00
FF /Fuel Feeder/
BF /Burner Feeder/
CH /Central Heating pump 220V/
Test Outputs
DHW /Domestic Hot Water pump 220V/
Ign /Ignition 220V/
CM /Ignition/

29
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

12. TECHNICAL FEATURES OF PELLET BURNER PELL ECO

12.1. Elements of pellet burner Pell ECO

9 10
Diagram 9. Elements of pellet burner Pell ECO
1. Pellet burner Pell ECO 6. Feeder chute
2. Control unit 7. Burner corps
3. Automatic pellet auger 8. Combustion chamber corps
4. Auger` motor 9. Combustion chamber
5. Auger flexible pipe connection 10. Movable grate

30
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

12.2. Spare parts for Pell ECO pellet burner

17
19 10
20
21
18
9
6
5
4
3
2
16
1 14
7
15 22
8
12
13 11

Diagram 10. Spare parts for pellet burner Pell ECO

Table 5

№ Part Number Pell 35 Pell 55 № Part Number Pell 35 Pell 55


ECO ECO ECO ECO
1 82081300000021 х 12 89080000000032 х х
1 82801300000045 х 13 89081200009740 х
2 89081300000027 х 13 89081200099319 х
2 82801300000046 х 14 89081200009992 х
3 89081300000028 х 14 89081200099317 х
3 89081300000079 х 15 89081200009796 х
4 89080000000030 х х 15 89081200099309 х
5 89081300000029 х х 16 89081200009993 х
6 89081300000045 х 16 89081200099315 х
6 89081300000080 х 17 32390031000011 х х
7 32640000000003 х 18 52000000000026 х х
7 32640032000017 х 19 52000000000027 х х
8 89080000000007 х х 20 52000000000028 х х
9 31080000000011 х х 21 52000000000025 х х
10 89081100000008 х х 22 32800000000013 х х
11 32590000000093 х х

31
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

12.3. Technical parameters

Table 6
Specifications Pell 35 ECO Pell 55 ECO
Nominal heat output kW 35 55
Min./ Max. heat output kW 5÷35 15÷55
Average power Firing-Up mode W ~ 400
consumption Operate mode W ~ 60÷70
Electric power supply V/Hz ~230 AC/50 Hz
Fuel wood pellets, Ø 6÷8mm /EN 14961-2:2011
Boiler mounting kitmm P P
Heat-output adjustment P P
Combustion Efficiency % 99 99
Emitted heat % 96 96
Weight of burner kg 17 20
Height 350 350
Minimal recommended size of Widthmm 450 450
boiler combustion chamber
Depth 450 550
H,mm
Height H 520 520
Overall dimensions Width L
L,mm 591 723
Depth DB,mm 240 274
Length
A, mm 358 408
Burner body
Height
C, mm 245 245
DiameterD, mm 170 170
Combustion chamber housing
Length
E, mm 233 320
DiameterG, mm Ø 60 Ø 60
Feeder chute
Length
I, mm 250 250
model ЕCO-L 25-40 ЕCO-L 25-40
G, mm
Diameter Ø 75 Ø 75
Pellet auger I, mm
Length 1500/2000/3000 1500/2000/3000
kg
Weight 5,5/7/8 5,5/7/8
Diameter Ø 60 Ø 60
Flexible connection tube N, mm
Length 700 700
Movable grate P P P
Built-in CPU control unit U P P
Central Heating pump/
Option for pumps control
Domestic Hot Water pump

32
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

13. RECYCLING AND WASTE DISPOSAL

Submit all packaging material for recycling Expired appliances must be collected
according to the local regulations and separately from other recyclable waste
requirements. containing substances hazardous to
At the end of life cycle of each product its health and environment. Both metal and
components are due to be disposed of in non-metal parts are sold out to licensed
conformity with regulatory prescriptions. organizations for recyclable metal or
According to Directive 2002/96/EC non-metal waste collection. In any case
regarding electrical and electronic they should not be treated as household
equipment waste, disposal thereof is waste.
required separately from the normal flow
of solid household waste.
Obsolete equipment shall be collected
separately from other recyclable waste
containing materials with adverse effect
on health and environment.
33
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

14. BINDING OF THE CONNECTORS

1 2

1. To terminate fine-stranded 2. Latch wired connector onto the base


conductors, actuate the clamp wia of the strain relief housing.
2.5mm screwdriver and insert stripped
conductor until it hits backstop.

3 4

3. Push down strain relief clamp via 4. Latch the top of the strain relief
2.5mm screwdriver alternately on both housing.
sides.

5. Lift up the white clip (1) by using screwdriver and pull out the connector (3).

34
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

35
12 Madara Blvd., 13 Chelopeshko Shose Str,
9700 Shumen, Bulgaria 1839 Sofia, Bulgaria
t: +359 54 874 555 t: +359 2 903 97 80
f: +359 54 874 556 f: +359 54 874 556
e-mail: ftrade@sunsystem.bg e-mail: sales@sunsystem.bg
www.sunsystem.bg