Republic of the Philippines

Department of Health
WESTERN VISAYAS SANITARIUM
AND GENERAL HOSPITAL
Santa Barbara, Iloilo

BILL OF QUANTITIES
Name of Project : VARIOUS INFRASTRUCTURE PROJECTS
 LOT 1: Center for Infectious deceases

Project Location : Western Visayas Sanitarium and General Hospital, Sta. Barbara, Iloilo

AUXILIARY WORKS
Fire Alarm Detection System (FDAS) at 1 lot
2nd Floor
Smoke Detector: conventional and
photoelectric type, 24Vdc, 3-wire function for
remote indicator. (24 pcs.)
Manual call station: conventional and push
type (3 pcs.)
FARI Fire Alarm Remote Indicator: 24Vdc (17
pcs.)
Fire alarm horn/serin: 24Vdc (3 pcs.)

Fire alarm strobe light: 24Vdc ( 3 pcs.)


Junction Box: Metal, gauge no.14/1.6mm
thick, 4" Octagonal x 2-1/8" depth with cover,
UL listed.
Utility Box: Metal, gauge no.14/1.6mm thick,
4" x 2" x 2-1/8" in size, UL Listed.
Raceway conduit: PVC Conduit, 1/2" diameter
x 10' long, thickwall (15mm)
Raceway Fitting Elbow: PVC, 1/2" diameter in
size, thickwall
Raceway Fitting Endbell: PVC, 1/2" diameter
in size, thickwall
1.25mm² TF wire
Strut conduit hanger: zinc coated steel, 1/2"
diameter, with bolts
Full threaded rod: 3/8" diameter x 10 feet long,
electro-galvanized finish.
Strut conduit hanger: zinc coated steel, 1/2"
diameter, with bolts
Strut clamp: zinc coated steel, 1/2" diameter,
with bolts
Miscellaneous and others: consumables and
others (like: screw, bolts & nuts, GI wires,
solvent cement, flat & angle bars, terminal
lugs, rubber & PVC electrical tapes, etc…)
Public Address and Background Music 1.00 lot
System (PABGM) at 2nd Floor
Amplifier syetm: 200W output, 220Vac input,
6 minimum channel (1 unit.)
Microphone mixer: 4 - inputs and 2 - outputs (1
pc.)
Speaker: ceiling and recessed mounting,
5/10W with built-in matching transformer. (6
pcs.)
Junction Box: Metal, gauge no.14/1.6mm
thick, 4" Octagonal x 2-1/8" depth with cover,
UL listed.
Utility Box: Metal, gauge no.14/1.6mm thick,
4" x 2" x 2-1/8" in size, UL Listed.

Page 1 of 9 BOQ: Lot 1


Republic of the Philippines
Department of Health
WESTERN VISAYAS SANITARIUM
AND GENERAL HOSPITAL
Santa Barbara, Iloilo
Raceway conduit: PVC Conduit, 1/2" diameter
x 10' long, thickwall (15mm)
Raceway Fitting Elbow: PVC, 1/2" diameter in
size, thickwall
Raceway Fitting Endbell: PVC, 1/2" diameter
in size, thickwall
XLE Audio cable
1.25mm² TF wire
Strut conduit hanger: zinc coated steel, 1/2"
diameter, with bolts
Full threaded rod: 3/8" diameter x 10 feet long,
electro-galvanized finish.
Strut conduit hanger: zinc coated steel, 1/2"
diameter, with bolts
Strut clamp: zinc coated steel, 1/2" diameter,
with bolts
Miscellaneous and others: consumables and
others (like: screw, bolts & nuts, GI wires,
solvent cement, flat & angle bars, terminal
lugs, rubber & PVC electrical tapes, etc…)
Telephone, Lan & CCTV System at 2nd 1.00 lot
Floor
Telephone outlet: RJ11 Female module, Flush
mounting (15 pcs.)
Telephone unit: conventional type (15 pcs.)
Lan outlet: Flush mounting (1 pc.)
CCTV camera: IP and PoE type, 2MP, IR and
doom type, ceiling or wall mounting (8 pcs.)
Junction Box: Metal, gauge no.14/1.6mm
thick, 4" Octagonal x 2-1/8" depth with cover,
UL listed.
Utility Box: Metal, gauge no.14/1.6mm thick,
4" x 2" x 2-1/8" in size, UL Listed.
Raceway conduit: PVC Conduit, 1/2" diameter
x 10' long, thickwall (15mm)
Raceway Fitting Elbow: PVC, 1/2" diameter in
size, thickwall
Raceway Fitting Endbell: PVC, 1/2" diameter
in size, thickwall
CAT5E UTP Cable
Strut conduit hanger: zinc coated steel, 1/2"
diameter, with bolts
Full threaded rod: 3/8" diameter x 10 feet long,
electro-galvanized finish.
Strut conduit hanger: zinc coated steel, 1/2"
diameter, with bolts
Strut clamp: zinc coated steel, 1/2" diameter,
with bolts
TEL and LAN Patch panel cabinet assembly:
12U volume capacity with PABX extension
unit that be connected to existing main PABX
unit at EE room ground floor. Includes two
patchpanels with keytone RJ45 connector jacks
intended for the TEL and spare for LAN
function includes 1U power supply outlets and
TEL connectors. (1 set)
CCTV Patch panel cabinet assembly: 12U
volume capacity with NVR network video
recorder, 1 terabytes hard drive, 19 inches
monitor and mouse. Includes two minimum
sets of patchpanels with keytone RJ45
connector jacks and 1U power supply outlets.
Provide HDMI cable use for monitor and
mouse from the new NVR to second floor
nurse call station. NVR details; 16channel

Page 2 of 9 BOQ: Lot 1


Republic of the Philippines
Department of Health
WESTERN VISAYAS SANITARIUM
AND GENERAL HOSPITAL
Santa Barbara, Iloilo
capacity with built-in pOE and LAN
network/internet jack provision for remote
monitoring control. (1 set)
Miscellaneous and others: consumables and
others (like: screw, bolts & nuts, GI wires,
solvent cement, flat & angle bars, terminal
lugs, rubber & PVC electrical tapes, etc…) (1
lot)
Nurse Call Station System 1.00 lot
Communication at 2nd Floor
Nurse call master station (NCMS.2): 20 call
capacity, can call all group, call log features
and software. Includes power supply and
provide UPS/battery for emergency function.
(1 unit)
Nurse call Substation (NCSS.NS): surface
mount (1 unit)
Nurse call Substation (NCSS.2): with
extension push button (19 units)
Nurse call corridor light (CL) (14 pcs.)

Nurse call reset button (CRB) (14 pcs.)


Nurse call bathroom call button with pull cord
(BCB) (13 pcs.)
Strut conduit hanger: zinc coated steel, 1/2"
diameter, with bolts
Full threaded rod: 3/8" diameter x 10 feet
long, electro-galvanized finish.
Miscellaneous, consumables and others (like:
screw, bolts & nuts, bits, hangers & support,
pull boxes, electrical tape, etc…)
Total for Auxiliary Works

ELECTRICAL WORKS
Lighting Fixtures at 2nd Floor
F1:SQUARE LED DOWNLIGHT, 15W, 90- 100.00
305V INPUT, COLOR DAY LIGHT sets
RECESSED MOUNTING TYPE
F2: Water proof lighting fixtures, IP65, 16.00
655mmX91mmX94mm approximate size with sets
clear plastic cover and LED tube T8 size rated
9W, 230Vac, 60Hz, daylight color, 900 lumens
minimum. Includes mounting metal base.
F3 :SQUARE DOWNLIGHT, 9W, 90-305V 6.00 sets
INPUT, COLOR DAY LIGHT RECESSED
MOUNTING TYPE
F4: Emergency Light with built-in battery, 24.00
rated 3 hours minimum, 2x3W Optic LED sets
bulb.
F5: SQUARE DOWNLIGHT, 7W, 90-305V 15.00
INPUT, COLOR DAY LIGHT RECESSED sets
MOUNTING TYPE
F6: PANEL LED DOWNLIGHT 6.00 sets
LUMINAIRE, 40W, 90-305V INPUT,
COLOR DAY LIGHT RECESSED
MOUNTING TYPE, 3 000 lumens minimum.
EXIT Light with built-in battery, rated 3 hours 3.00 sets
minimum.
EF: EXHAUST FAN, Ceiling mounted, 40W 3.00 sets
230Vac, 4" diameter duct with flexible duct
and exterior cap. Includes hanger and fittings.
Wiring Devices at 2nd Floor 1.00 lot
One Gang, 10A 250V single pole switch, with
Flush Mounted Cover and Plate, wide series,

Page 3 of 9 BOQ: Lot 1


Republic of the Philippines
Department of Health
WESTERN VISAYAS SANITARIUM
AND GENERAL HOSPITAL
Santa Barbara, Iloilo
polar white color.
Two Gang, 2-10A 250V single pole switch,
with Flush Mounted Cover and Plate, wide
series, polar white color.
Three Gang, 3-10A 250V single pole switch,
with Flush Mounted Cover and Plate, wide
series, polar white color.
One Gang, 1-10A 250V 3-way switch, with
Flush Mounted Cover and Plate, wide series,
polar white color.
Utility Box: Metal, gauge no.14/1.6mm thick,
4" x 2" x 2-1/8" in size, UL Listed.
Raceway conduit: PVC Conduit, 3" diameter
x 10' long, thickwall (75mm)
Raceway Fitting Elbow: PVC, 3" diameter in
size, thickwall
Raceway Fitting Endbell: PVC, 3" diameter in
size, thickwall
Raceway conduit: PVC Conduit, 2 1/2"
diameter x 10' long, thickwall (65mm)
Raceway Fitting Elbow: PVC, 2 1/2" diameter
in size, thickwall
Raceway Fitting Endbell: PVC, 2 1/2"
diameter in size, thickwall
Raceway conduit: PVC Conduit, 2" diameter x
10' long, thickwall (50mm)
Raceway Fitting Elbow: PVC, 2" diameter in
size, thickwall
Raceway Fitting Endbell: PVC, 2" diameter
in size, thickwall
Raceway conduit: PVC Conduit, 1" diameter x
10' long, thickwall (25mm)
Raceway Fitting Elbow: PVC, 1" diameter in
size, thickwall
Raceway Fitting Endbell: PVC, 1" diameter
in size, thickwall
Raceway conduit: PVC Conduit, 3/4" diameter
x 10' long, thickwall (20mm)
Raceway Fitting Elbow: PVC, 3/4" diameter
in size, thickwall
Strut conduit hanger: zinc coated steel, 1/2"
diameter, with bolts
Strut clamp: zinc coated steel, 3" diameter,
with bolts
Strut clamp: zinc coated steel, 2-1/2" diameter,
with bolts
Strut clamp: zinc coated steel, 2" diameter,
with bolts
Strut clamp: zinc coated steel, 1" diameter,
with bolts
Strut clamp: zinc coated steel, 3/4" diameter,
with bolts
Strut clamp: zinc coated steel, 1/2" diameter,
with bolts
Solvent Cement, 400mL per can

3/4" x 20yard PVC Electrical Tape

Miscellaneous and others: consumables and


others (like: screw, bolts & nuts, GI wires,
solvent cement, flat & angle bars, terminal
lugs, rubber electrical, wire gutters, pull boxes,
epoxy paints, drill bits, butane, etc…)
Wires & Cables at 2nd Floor 1.00 lot
150mm² THHN copper wire
100mm² THHN copper wire

Page 4 of 9 BOQ: Lot 1


Republic of the Philippines
Department of Health
WESTERN VISAYAS SANITARIUM
AND GENERAL HOSPITAL
Santa Barbara, Iloilo
60mm² THHN copper wire
50mm² THHN copper wire
38mm² THHN copper wire

30mm² THHN copper wire

22mm² THHN copper wire


14mm² THHN copper wire
8.0mm² THHN copper wire
5.5mm² THHN copper wire
3.5mm² THHN copper wire
2.0mm² TW copper wire
1.25mm² TF wire
Panelboards & Circuit Breaker at 2nd
Floor
ATS.E: 1.00 set
Rated 2 - 200AT/250AF, 3P+G,
25KAIC@240V MCCB with complete
assecories for automatic transfer function and
indicators. Input signal voltage shall be three-
phase with manual and automatic mode
selector switch. Enclosure shall be metal in
NEMA 1 ingression protection. Grounding
copper terminal is rated 150A.
ATS.FS: 1.00 set
Rated 2 - 500AT/600AF, 3P+G,
25KAIC@240V MCCB with complete
assecories for automatic transfer function and
indicators. Input signal voltage shall be three-
phase with manual and automatic mode
selector switch. Enclosure shall be metal in
NEMA 3R ingression protection. Grounding
copper terminal is rated 300A.
For MDP additonal breakers: 1.00 set
2 - 200AT/250AF, 3P, 25kAIC@240V MCCB
1 - 125AT/250AF, 3P, 25kAIC@240V MCCB
Note: additional breakers shall be same model
& manufacturer or size to fit to the existing
bus-bar bracing and enclosure.
DP.S: 1.00 set
NEMA 1 metal enclosure, 250A copper bus-
bar at 250V, 3P+G, with protection:
main; 200AT/250AF, 3P, 25@240V MCCB
branches:
14 - 30AT/60AF, 2P, 18kAIC@240V CB BOLT-ON
1 - 60AT/60AF, 2P, 18kAIC@240V CB BOLT-ON
3 - space for 60AF, 2P CB BOLT-ON
Note: Grounding copper terminal blocks rated 150A
with 24 slots minimum.
PB.S: 1.00 set
NEMA 1 metal enclosure, 100A copper bus-
bar at 250V, 3P+G, with protection:
main; 50AT/100AF, 3P, 25@240V MCCB
branches:
3 - 15AT/60AF, 2P, 18kAIC@240V CB BOLT-ON
3 - 60AT/60AF, 2P, 18kAIC@240V CB BOLT-ON
6 - space for 60AF, 2P CB BOLT-ON
Note: Grounding copper terminal blocks rated 150A
with 18 slots minimum.
PB.S-ES: 1.00 set
NEMA 1 metal enclosure, 100A copper bus-
bar at 250V, 3P+G, with protection:
main; 60AT/100AF, 3P, 25@240V MCCB

Page 5 of 9 BOQ: Lot 1


Republic of the Philippines
Department of Health
WESTERN VISAYAS SANITARIUM
AND GENERAL HOSPITAL
Santa Barbara, Iloilo
branches:
6 - 20AT/60AF, 2P, 18kAIC@240V CB BOLT-ON
3 - space for 60AF, 2P CB BOLT-ON
Note: Grounding copper terminal blocks rated 150A
with 12 slots minimum.
PB.S-W1 : 14.00 set
NEMA 1 polycarbonated plastic/metal
enclosure distribution panel, flush mounted,
63AT at 250V, 2P+G copper bus-bar pin type,
with protections:
main,
32AT/63AF, 2P, 10kAIC@240V mcb DIN-
RAIL
branches:
1 - 16AT/63AF, 2P, 10kAIC@240V mcb DIN-RAIL
1 - 20AT/63AF, 2P, 10kAIC@240V mcb DIN-RAIL
1 - 25AT/63AF, 2P, 10kAIC@240V mcb DIN-RAIL
1 - space for 63AF, 2P, mcb DIN-RAIL
Note: Grounding copper terminal block rated 30A
with 6 slots minimum. Typical to PB.S-W1 to PB.S-
W14
PB.S-NS : 1.00 set
NEMA 1 polycarbonated plastic/metal
enclosure distribution panel, flush mounted,
63AT at 250V, 2P+G copper bus-bar pin type,
with protections:
main,
32AT/63AF, 2P, 10kAIC@240V mcb DIN-RAIL
branches:
1 - 16AT/63AF, 2P, 10kAIC@240V mcb DIN-RAIL
2 - 20AT/63AF, 2P, 10kAIC@240V mcb DIN-RAIL
1 - 25AT/63AF, 2P, 10kAIC@240V mcb DIN-RAIL
1 - 32AT/63AF, 2P, 10kAIC@240V mcb DIN-RAIL
1 - space for 63AF, 2P, mcb DIN-RAIL
Note: Grounding copper terminal block rated 30A
with 12 slots minimum.
CP.S-NP (NEGATIVE PRESSURE 1.00
CONTROLLER PANEL): Control Panel for assembly
Negative Pressure at Second Floor, NEMA 1
metal enclosure, powder coated paint. main
protection; 100AT/100AF, 3P, 25kAIC@240V
MCCB branches; 2 - 40AT/100AF, 3P,
25kAIC@240V MCCB 6 - 20AT/100AF, 2P,
25kAIC@240V MCCB controllers; 1 unit -
Programmable Logic Controller (PLC) with
analogue input & output extension/built-in
features. 2 sets - magnetic contactor rated 5Hp
3Ø with overload thermal relay & auxiliary
contacts.1 set - magnetic control relays for
input signal of pressure sensors device. 1 set -
control power supply, rated 24Vdc with built-
in battery and charger. Notes: (1.) Provide
terminal block that sufficient with extra/spare
for external (input/output) wires and cables.
These includes for power and signals function
of the assembly. (2.) Provide manual, testing
and automatic mode program and selections.
(3.) Provide indicators and alarm with
reset/acknowledge and emergency button. (4.)
Use crimp type terminal lugs all through-out
the terminations applicable for power and
controls. With shrinkable tubes and cable tags
that be based on the control, load and
schematic wiring diagram. (7.) Items that not
mentioned in the details but needed for the
functionality during operation are considered
and included. Refer to mechanical in regards
with the Negative pressure sensors.
50AT, 3P, 25kAIC@240V, Breaker (PB.S) 1.00 pc
60AT, 3P, 25kAIC240V, Breaker (PB.S-ES) 1.00 pc

Page 6 of 9 BOQ: Lot 1


Republic of the Philippines
Department of Health
WESTERN VISAYAS SANITARIUM
AND GENERAL HOSPITAL
Santa Barbara, Iloilo
250AT, 3P, 25kAIC@240V, Breaker (DP.S) 1.00 pc
ECB: 30AT, 2P, 25kAIC@250V MCCB 16.00 set
Total for Electrical Works

MECHANICAL WORKS
Medical Gas 1.00 lot
Ground Floor
Isolation Valve
Isolation Valve (heavy duty) 25mm (Ball
Valve with extensions, pressure tested, cleaned
for medical gas service, blow out proof stem)
Isolation Valve (heavy duty) 22mm (Ball
Valve with extensions, pressure tested, cleaned
for medical gas service, blow out proof stem)
Isolation Valve (heavy duty) 22mm lockable
(Ball Valve with extensions, pressure tested,
cleaned for medical gas service, blow out proof
stem)
Isolation Valve (heavy duty) 12mm (Ball
Valve with extensions, pressure tested, cleaned
for medical gas service, blow out proof stem)
Medical Oxygen Outlets
Medical Oxygen Outlet DISS
Vacuum Outlets DISS
Vacuum Slide

Alarm and Valve Box Combo with 2 Gasses


Copper pipes and Fittings (ASTMB 819)
Copper pipes are seamless, vacuum
annealed internally and externally etched
and absolutely oil free. These are
degrease and cleaned from the inside so
that the residual grase on the interior
surface will not exceed 0.2 mg/dm2. Tube
eds are sealed and protected by plastic
caps . Copper tube, Hard drawm, Type L
inclusive of fittings and cleaning for
oxygen service
25mm*(6m)
22mm*(6m)
15mm*(6m)
12mm*(6m)
Fittings
2nd Floor
Isolation Valve
Isolation Valve (heavy duty) 22mm (Ball
Valve with extensions, pressure tested, cleaned
for medical gas service, blow out proof stem)
Isolation Valve (heavy duty) 12mm (Ball
Valve with extensions, pressure tested, cleaned
for medical gas service, blow out proof stem)
Medical Oxygen Outlets
Medical Oxygen Outlet DISS

Vacuum Outlets DISS

Vacuum Slide

Alarm and Valve Box Combo with 2 Gasses

Page 7 of 9 BOQ: Lot 1


Republic of the Philippines
Department of Health
WESTERN VISAYAS SANITARIUM
AND GENERAL HOSPITAL
Santa Barbara, Iloilo
Secondary Equipment
Oxygen Flowmeter with Humidifier Bottle

Vacuum Regulator with trap, tubings and bottle


Copper pipes and Fittings (ASTMB 819)
Copper pipes are seamless, vacuum
annealed internally and externally etched
and absolutely oil free. These are
degrease and cleaned from the inside so
that the residual grase on the interior
surface will not exceed 0.2 mg/dm2. Tube
eds are sealed and protected by plastic
caps . Copper tube, Hard drawm, Type L
inclusive of fittings and cleaning for
oxygen service
25mm*(6m)

22mm*(6m)

15mm*(6m)

12mm*(6m)

Fittings
Fire Protection System 1.00 lot
Roughing Ins./ Piping System
Black Iron Pipe, ASTM A‐53, ERW
Sched. 40., 6m (Supreme or Superior
Pipes)
25mm - 150mm
Fixtures & Accessories
Pendent Sprinkler heads,UL/FM Standard,
Globe Brand or Viking, 1/2" dia.,(Large
Orifice, 68deg. celsius)
Sidewall Sprinkler heads, UL/FM Standard,
Globe Brand or Viking 3/4" dia.,(Large Orfice,
68 deg. celsius)
Fire Hose Cabinet & Accessories UL/FM
Standard (Giacomini or BH Brand)
Valves & Accessories
Os & Y Gate Valve 6", Flange Connection
(hyflo, Viking, Lede, Mech, Globe) UL/FM
Standard.
Os & Y Gate Valve 4", Flange Connection
(hyflo, Viking, Lede, Mech, Globe) UL/FM
Standard.
Water Flow Switch 4", UL/FM Standard
(System Sensor)
Pressure Gaue 3"
Miscellaneous
Threaded Fittings UL/FM Standard ( Malleable
Iron, Class 150 or 300),"Mech Brand" Tee, Tee
Reducer, Bell Reducer & Elbow
Welded Fittings, sched. 40,Tee,Tee Reducer,
Elbow
Grooved Fittings UL/FM Standard (Rigid
Coupling, Flexible Coupling, Mechanical Tee,
Mechanical Tee Reducer) Brand: Mech, Lede,
Hyflor, Viking, Globe
Hanggers & Supports
Sway Braces,Angular Bars, Clevis Hangers,
Loop Hangers, Full thread Round Bars, Grip
Anchors, Bolts & Nuts Capscrews
Painting Works
Red Oxide Primer, International Red Paints,

Page 8 of 9 BOQ: Lot 1


Republic of the Philippines
Department of Health
WESTERN VISAYAS SANITARIUM
AND GENERAL HOSPITAL
Santa Barbara, Iloilo
Enamel, Paint Brush & Miscellaneous
Consumables
Welding Rods, Welding Mask, Cut off Wheels,
Grinding Disc, Cutting Disc, Teflon Tapes,
Oxygen & Acetylene
Negative Pressure System with HEPA 1.00 lot
Filtration and Magnehelic Pressure
Gauges
Centrifugal Exhaust Fans, SISW (Single Intake,
Single Width), Backward Curve, 5HP, 7200 CFM, 2
ESP (in H2O), 230 V, 3 Phase, 60HZ (1 unit)
Toilet and Bath Ceiling Mounted Exhaust, 80 Watts,
100 CMH, 230 V, 1 Phase, 60 HZ (14 units)
Forced Draft Fan, Clean Supply Intake with MERV
17-20 Filters, Axial Fan, 0.15 KW,500 CFM, 1 ESP
(In H2O), 230 V, 1 Phase, 60 HZ (1 unit)
Motorized Damper with Actuators (Belimo System)
700 x 700 in mm for EAF System 2 (1 unit)
Powder Coated Round Difussers with OBVD
(Multiple sizes) 150 to 350 mm EAG L2 (25 units)
Powder Coated Round Difussers with OBVD
(Multiple sizes) 150 to 350 mm FAG L2 (8 units)
Manual Inline Duct Damper Control VCD (150-
200mm) (26 units)
Magnehelic Pressure Gages (-30 to +30 Pascal)
Vertical Position Units (15 units)
Negative Pressurization Ducting System
Works, Installation and Leak Test
850 x 400 EAD MM Main Duct with SMACNA
Standard of Fabrication G22, with Insulation
700 x 400 EAD MM Main Duct with SMACNA
Standard of Fabrication G22,with Insulation
550 x 350 EAD MM Main Duct with SMACNA
Standard of Fabrication G24, with Insulation
400 x 350 EAD MM Main Duct with SMACNA
Standard of Fabrication G24, with Insulation
200 x 200 EAD MM Main Duct with SMACNA
Standard of Fabrication G24,with Insulation
300 x 200 EAD MM Main Duct with SMACNA
Standard of Fabrication G24, with Insulation
250 x 250 EAD MM Main Duct with SMACNA
Standard of Fabrication G25, with Insulation
750 x 750 EAD Exhaust Stack Duct with SMACNA
Standard of Fabrication G22,with Insulation
Other NPS Components
HEPA High Efficiency Particulate Absorbing
Filtrations, 99.95% H13, MERV 17-20
Ducting Support System Unitstruts SMACNA
Standards of 8-10 feet apart
Positive Forced Air System
550 x 400 FAL MM Main Duct SMACNA
Standard of Fabrication, G22, with Insulation
250 x 200 FAD MM Main Duct with
SMACNA Standard of Fabrication, G24, with
Insulation
150 x 150 FAD MM Sub Duct with SMACNA
Standard of Fabrication, G24, with Insulation

Total for Mechanical Works